DSEULTRA
®

STARTING
WITH SPECIFICATION

QUALITY. DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply

DSE704 & DSE4120 was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
AUTO MAINS FAILURE CONTROL MODULES need for internal batteries.

MAXIMUM OPERATING CURRENT


170mA(12V), 280mA(24V) (DSE4120)
50mA (DSE704)

TYPICAL CURRENT
35mA(12V and 24V)

ALTERNATOR INPUT RANGE


75V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY


50Hz – 60Hz at rated engine speed
(minimum:75V AC L-N) (Crank disconnect from
15V L-N @ 20Hz) Overspeed +14% (+24%
overshoot) Underspeed -20%

DSE704 DSE4120 START & FUEL OUTPUTS


1.2 Amp DC at supply voltage. Switches to
battery negative when active

AUXILIARY OUTPUTS
1.2 Amp DC at supply voltage. Switches to
battery negative when active

DSE704 DIMENSIONS
165mm x 125mm x 29mm
6.5” x 4.9” x 1.2”

DSE704 CUT OUT


149mm X 109mm
5.9” x 4.3”

DSE4120 DIMENSIONS
171mm x 115mm x 49mm
6.7” x 4.5” x 1.9”

DSE4120 PANEL CUT OUT


154mm x 98mm
6.1” x 3.9”

The DSE704 is an Auto Mains FEATURES OPERATION CHARGE FAIL


Failure Control Module that offers • Automatic mains (utility) supply The modules are operated using the 8 Volt Charge Fail at 12 Volts, 16 Volt Charge
monitoring three push buttons on the front: Fail at 24 Volts
an excellent range of engine
monitoring and protection features. • Automatic shutdown when fault
The module has been designed to conditions are detected MANUAL – This mode is
• Manual start used to manually start the ENVIRONMENTAL TESTING
monitor engine temperature, low oil STANDARDS
pressure, fail to start, charge failure, • Engine pre-heat engine.
over speed and under speed. • Engine monitoring and protection
features AUTO – This mode is used ELECTRO MAGNETIC CAPABILITY (EMC)
• Protected Solid State (PSS) to automatically start the BS EN 61000-6-4
When the module detects a fault EMC Generic Emission Standard for the Industrial
outputs engine. The module will be Environment
condition it automatically shuts • Front panel mounting started by the remote start BS EN 61000-6-2
down the engine. The module also • Front panel programming signal. EMC Generic Immunity Standard for the Industrial
includes two user configurable • Tamper proof engine hours Environment
auxiliary inputs. counter STOP – This button is used ELECTRICAL SAFETY
• Remote start to stop the engine when it is BS EN 60950
The DSE4120 module includes all • LED indicators running in either manual or Safety of Information Technology Equipment
the features of the DSE704 plus a • Configurable timers automatic mode. including Electrical Business Equipment

tamper proof engine hours counter, • Configurable outputs TEMPERATURE


engine exercise mode function and • Single/three phase mains sensing BS EN 60068-2-2
the enclosure has a closed back. Test Ab to 70oC
BENEFITS Test Ab to -30oC

Both modules have been designed • Transfers between mains (utility) VIBRATION
to automatically start the generator and generator power BS EN 60068-2-6
• On-site module configuration to Ten sweeps in each of the three major axes
when the mains (utility) power fails. 5Hz to 8Hz @ +/- 7.5mm
match user requirements
As soon as mains (utility) power is
• Hours counter provides accurate HUMIDITY
restored the modules have been information for monitoring BS EN 60068-2-30
designed to transfer the load back maintenance and warranty Test Db 95% RH @ 55oC for 12 hours
to the mains (utility) supply. The periods
modules then instruct the engine SHOCK
• Multiple engine parameters are BS EN 60068-2-27
to begin the cool down procedure monitored simultaneously Three shocks in each of three major axes
and stopping sequence (user 15gn in 11mS
configured).
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL


THAILAND +66 (0) 2678 3028 sales@dseplc.com
TPI Tower, Lobby 3
Floor 27, 26-56 Chan New Road FACSIMILE WEBSITE
Tungmahamek, Sathom +66 (0) 2670 6228 www.deepseaplc.com
Bangkok 10120, Thailand

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


USA +1 (815) 316 8706 sales@deepseausa.com
3230 Williams Avenue
Rockford FACSIMILE WEBSITE
IL 61101-2668 USA +1 (815) 316 8708 www.deepseausa.com

DSE704 & DSE4120


MECHANICAL INTERLOCK

LOAD

L1 L1

L2 L2

FROM L3 L3 FROM
GENERATOR MAINS

N L4

2 AMP 2 AMP
FUSES ELECTRICAL INTERLOCK FUSES

G M

NORMALLY OPEN NORMALLY CLOSED

+ * * +

20 21 14 13 16 17 18 19

L1 N L1 L2 L3 N
CLOSE MAINS
CLOSE GEN

GEN VOLTS MAINS VOLTS

MODULE 704/4120
COOLANT TEMP

REMOTE START
OIL PRESSURE
GEN RUNNING

CHRG ALT
OUTPUT 1

OUTPUT 2

BATTERY
INPUT 1

INPUT 2
CRANK
FUEL
+VE
-VE

1 2 3 4 5 6 7 8 9 10 11 12 15

* * * *

+ + + +

2 AMP FUSE
FUSE

FUEL CRANK CHOKE WL


BATTERY CHARGE
SOLENOID SOLENOID DEVICE
ALT

BATTERY NEGATIVE MUST BE GROUNDED

TERMINALS SUITABLE FOR 22-16 AWG (0.6MM - 1.3MM) FIELD WIRING


TIGHTENING TORQUE = 0.8Nm (7lb-in)

*NOTE. ALL THE OUTPUTS ARE SOLID STATE AND ARE NEGATIVE SWITCHING

CONFIGURATION RELATED MATERIALS


The modules can be configured to TITLE PART NO’S
match user’s individual parameter NORMAL DSE704 Installation Instructions 053-036
settings. Configuration mode is DSE704 Operators Manual 057-043
accessed via the switch at the rear DSE4120 Installation Instructions 053-021
of the module. Once in configuration DSE4120 Operators Manual 057-023
CONFIGURATION
mode the AUTO-LED
flashes rapidly.

Please refer to the installation instructions for the parameter settings and
configuration details.

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-042/05/07 (1)