Explosion relief
This Technical Measures Document refers to the explosion relief measures that can be adopted
in plant design to ensure safe operation.

The relevant Level 2 Criteria are:

5.2.1.3(29)b,g [1]

5.2.1.6(38)e [2]

5.2.1.10(53) [3]

Related Technical Measures Documents include:

Inerting [4]

Earthing [5]

Plant layout [6]

Design Codes ­ plant [7]

Design Codes ­ pipework [8]

Plant modification / change procedures [9]

Maintenance procedures [10]

General principles
Operators should demonstrate that appropriate measures are in place either to prevent
explosions from taking place, or to protect against/minimise the effects of explosions.

Explosion prevention is always preferable to explosion protection, particularly where an explosion
is likely to result in emission of toxic material.

Operators need to draw a clear distinction between pressure relief designed to protect against an
explosion, and relief designed to protect plant from some other cause of overpressure. Explosions
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 1/11
6/20/2015 Explosive relief

are rapid events and consequently:

Protective devices have to work very rapidly;

Much larger sizes of vent panels or doors are needed in order to work successfully and

Duct work downstream from the relief panel needs careful design to avoid throttling the
flow and preventing the relief acting fast enough;

Historically, explosion relief has been used as a mitigation measure in three main types of plant:
large­scale gas fired combustion plant, solvent evaporating processes/ovens and plants handling
explosible dusts. It may also be provided on buildings, which contain plant that gives rise to risk of
a rapid and substantial release of gas inside the building. Compressor houses are an example.
The reports on the Manro and Chemstar incidents show the possibilities with distillation plant, but
inadequate explosion relief was not the prime problem in this case.

The advent of improved gas control systems means that in many cases explosion relief is not now
fitted to combustion plant. A European harmonised standard for solvent evaporating ovens
prefers alternative precautions for many applications, but in the dust handling industries explosion
relief remains a widely used mitigation measure. This is because it is often impossible to prevent
the formation of dense dust clouds inside the process. The dust itself, or mechanical moving parts
in contact with the dust often create ignition risks that cannot be eliminated completely.

The COMAH Regulations do not apply to a material if the only risk created is that of a dust
explosion. However, many toxic materials are handled in fine powder form, and a serious dust
explosion could cause a major accident. A dust explosion involving a non­toxic dust like
polyethylene would not result in a major accident as defined in the regulations, unless it also led
to loss of containment of a COMAH substance. A dust explosion could then be an initiator of a
major accident. Measures to prevent major accidents should address all potential initiators.

The material released from an explosion relief vent typically includes quantities of the
original, unburnt substance in addition to combustion products. Alternative mitigation
measures are available, including explosion suppression, or building the plant strong
enough to withstand the anticipated explosion pressures. The adoption of measures
such as these is likely to be necessary where the process of venting could itself lead to
the release of sufficient toxic material to create a major accident. However, it is worth
noting that even finely powdered solids are significantly less easily dispersed than are
gases and volatile liquids ­ with shorter hazard ranges as a result.

http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 2/11
6/20/2015 Explosive relief

In assessing the risks from an explosion, Operators should consider flame propagation,
pressure effects, recoil forces and the materials that would be released. An explosion of
gas or vapour will release hot combustion products, but continuing burning is only likely if
there is a continuing source of release, perhaps because nearby pipework has been
damaged. A dust explosion, however, will usually release burning and unburnt dust, and
may well disturb dust deposits in the area. A secondary explosion or continuing fire is
much more likely. These factors will have a significant impact on plant layout, design of
plant and supporting structures and explosion relief routes. Relief points from explosion
protection devices should normally be located outside the building containing the plant,
but certainly not in the vicinity of regularly occupied areas or plant that would be easily
damaged.

The ACOPs and Guidance to DSEAR discuss the alternatives for explosion prevention and
mitigation measures. In particular they provide a hierarchy of controls. This hierarchy relates to
intentional or unintentional releases, but the precautions to prevent an explosion inside the
process plant are not the same. Normally the following options should be considered to prevent
an explosion inside the plant:

Substitution of combustible materials;

Control of concentration, e.g. by excluding air, or purging with air before start up of
combustion plant

Inerting, exclusion of oxygen by use of inert gases

Monitoring and detection of smouldering particles with automatic quench systems
(specific to dust explosions);

Elimination of ignition sources;

Having implemented these precautions, risks may remain in the ALARP region. The ALARP
demonstration should then include an assessment of the following options for mitigation:

Containment (explosion­resistant construction);

High speed isolation;

Segregation (keeping catalysts or pyrophoric materials apart from other products);

Explosion pressure relief (venting);

Explosion suppression.
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 3/11
6/20/2015 Explosive relief

Explosion vent panels and doors are considered as autonomous protective systems within the
meaning of the ATEX equipment regulations. As such, new panels or doors must comply fully with
the essential health and safety requirements, and be tested and certified by a Notified Body.
Existing panels do not need to be replaced, but they should be suitable for the purpose.

A harmonised standard for the design and testing of explosion vent panels and doors is under
preparation within CEN TC 305, as EN 14491.

General principles that relate to sizing methods for events that are slower than an explosion are
covered in the Technical Measures Document Relief Systems / Vent Systems [11].

Sizing of explosion panelsk
Explosion panels for gases and vapours
The size of vent area required for effective control depends upon a number of factors including:

The explosion properties of the gas or vapour;

The size of the vessel to be vented;

The geometry of the hazardous region;

The strength of the plant;

The opening pressure of the vent panel/door and its inertia;

Any initial or induced turbulence in the system;

The location of the ignition source;

The influence of any vent ducts needed.

In particular the possibility of pressure piling needs to be considered. If an explosion that starts at
one location inside a plant causes the explosive mixture ahead of the flame front to be
compressed, much higher ultimate pressures can result. In extreme cases, explosion flames can
accelerate to detonation, generating very high pressures and explosion relief is unlikely to be a
suitable method of protection in this case. See TD5/039, Detonations.

Recent work by HSL has extended our knowledge of the pressures likely to be developed by
gas/vapour explosions in a variety of circumstances. This work is summarised in Paper 18 by
Lunn and Pritchard from the IChemE's Hazards XVII conference held in March 2003. Operators
are unlikely to present safety cases drawing on this work in the immediate future, but it can be
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 4/11
6/20/2015 Explosive relief

used to check predictions, and if they vary sharply from the content of a safety report, Operators
could be asked to reconsider the implications.

BS EN 1539 2000 1 recognises the need for explosion relief for some designs of ovens, and
recommends using NFPA 68 as no European standard was available at the time the standard
was approved. This remains the case.

Explosion vent relief sizing panels for dusts and powders
A considerable amount of experimental data has been used to develop empirical design
equations. Many different equations have been published, each with a restricted range of
applicability, and plants will be found which have used all these design equations. More recently,
work within CEN has produced a rationalisation and simplification of the design equations
recommended, and this standard should be adopted when it becomes available. Checking of
calculations is best done by the computer expert system DUST EXPERT, developed by HSE, and
available to relevant process safety specialists. Basic input data required is the strength of the
process equipment, the equipment volume, KST and P max figures for the dust itself, and the
opening pressure of the vent panel or door.

Some equipment suppliers use the German VDI 3673 guide as a basis for the design of explosion
relief vents. This is acceptable, and much of the advice is contained in the other sources quoted.

Alternatively, the IChemE Dust Explosion book should be consulted.

Explosion relief from buildings
HSE's traditional advice for buildings storing flammable liquids has been to ask for a lightweight
roof, which will act as explosion relief if a vapour cloud ignited within the building, and this has not
changed as a result of DSEAR. Stores designed for storage of petroleum liquids under earlier
legislation normally had heavy concrete structures, to provide maximum protection for the stored
product from a fire in the vicinity. COMAH removed licensing for petroleum stores at COMAH
sites, and DSEAR removed licensing for all drum stores. There is insufficient justification to seek
structural alterations to buildings, if any petroleum­type stores are found on COMAH sites.

A vent sizing routine for buildings is given in the NFPA 68 code, and repeated in the IChemE Dust
Explosion book, but without the explosibility constant for organic vapours; the missing value of C 1
= 0.045 is given in the NFPA code.

http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 5/11
6/20/2015 Explosive relief

Dust explosions (especially in powder transfer and dryers)
A dust explosion can take place only if a number of conditions are simultaneously satisfied:

The dust must be explosible (refer to table on dust explosion classes);

The dust must have a particle size distribution that will allow the propagation of flame

The atmosphere into which the dust is dispersed as a cloud or suspension must contain
sufficient oxidant to support combustion;

The dust cloud must have a concentration within the explosible range;

The dust cloud must be in contact with an ignition source of sufficient energy to cause an
ignition.

Dust may be grouped into dust explosion classes as determined using standard test apparatus.
K ST is defined as the maximum rate of pressure rise measured in a 1m3 vessel, it is usually
calculated from measurements in smaller test apparatus. These groupings are as follows:

Grouping Description

ST0 Not explosible

ST1 K ST less Slow explosion, but these can still be very destructive ­ 80% of explosible


than 200 dusts fall in this group

ST2 200<K ST= Medium speed explosion


<300

ST3 K ST>300 Very high speed explosion, this group includes mainly metal dusts

Exothermic reactions
Overpressurisation of reactors is addressed in the Technical Measures Documents Relief
Systems / Vent Systems [12] and Reaction / Product Testing [13].

Hazards from exothermic reactions occur in the event of thermal runaway of the reaction mixture
in which the rate of generation of heat is greater than the available cooling capacity of the system.
Pressure relief needs to take into account the nature of the reaction mixture involved, (e.g.
viscosity, boiling gas/liquid mixtures) and sizing routines for gas and dust explosions are not
appropriate.

http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 6/11
6/20/2015 Explosive relief

Various testing strategies and experimental methods are commonly available for determination of
thermal decomposition hazards. The operator should have shown due consideration of these
hazards and taken appropriate measures to provide pressure relief. Measures for provision of
pressure relief in these cases are addressed in the Technical Measures Document on Relief
Systems / Vent Systems [14].

Unstable substances
When unstable substances are in use, the operator should demonstrate that at the research stage
of the product a systematic approach to the identification of hazards relating to the nature of the
materials has been followed. These hazards should be identified and documented, with
subsequent evidence of implementation of control measures. Hazards that merit consideration
include:

Explosibility;

Thermal and pressure conditions;

Flammability;

Toxicity;

Environmental problems.

If products show properties that indicate they can explode in the solid phase (i.e. the energy
release comes from decomposition not combustion), explosion relief is an inappropriate mitigation
measure.

The assessment is specifically concerned with the physical properties of the products, and
possible by­products.

Guidance and Codes of Practice relating to explosion relief
HS(G)103 2 Safe handling of combustible dusts: precautions against explosions, Health
and Safety Executive, 2nd Edition, 2003.
A guide to the prevention, control and mitigation of dust explosions, aimed at operators
of such plant, not designers. Paragraphs 60 to 87 discuss explosion relief and plant
design and layout.

HS(G)51 2 Storage of Flammable Liquids in Containers, Health and Safety Executive,
1998.
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 7/11
6/20/2015 Explosive relief

This asks for a lightweight roof for HFL stores.

Approved Codes of Practice and Guidance to the Dangerous Substances and Explosive
Atmospheres Regulations 2002 (DSEAR)

Discipline Information Note, DIN TD5 039 Detonations, Helen James, Oct 2001, HSE
Intranet.

Dust Explosion Prevention and Protection: A Practical Guide, IChemE, 2002 Edition, J
Barton (Editor) ISBN 085295 410 7
This should be the basic design reference for new plant.

CIA Guidance for the location and design of occupied buildings on chemical
manufacturing sites, (version 2) CIA/CISHEC, 2003.

BS EN 1127­1: 1998 1: Explosive atmospheres. Explosion prevention and protection.
Part 1. Basic concepts and methodology, British Standards Institution, 1998.
Good general introduction to the subject, but not detailed enough for design purposes.
Comments that 'explosion relief into the workrooms shall not be permitted unless there is
proven evidence that persons cannot be endangered'.

BS 5908: 1990 1: Code of practice for fire precautions in the chemical and allied
industries, British Standards Institution.
This provides many cross­references to other sources of information, but some of these
are obsolete, and the whole document is about to be rewritten. Section 5, Paragraph
27.1 provides guidance on minimising explosion risks from processes by location of plant
in the open air or in open­sided structures, excluding personnel while the plant is
operating and the provision of explosion relief vents. Section 10, Paragraph 58.5
provides guidance on ignition energy of powder atmospheres and methods of handling
powders to reduce risks.

BS EN 1539 2000 1: Dryers and ovens in which flammable substances are released.
Safety requirements, British Standards Institution.

VDI 3673, Pressure relief of dust explosions, Verein Deutscher Ingenieure ­ Kommission
Reinhaltung der Luft, Germany, 1995. Influential and widely used. Gives specific advice,
but with a tendency to ignore all non German sources of research data and guidance.

NFPA 68, Guide for venting of deflagrations, National Fire Protection Association,
Quincy, USA, 1988.

http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 8/11
6/20/2015 Explosive relief

Useful while there is little European guidance on venting for gas explosions.

Gas Explosion Handbook (in English)  [15], produced by the Norwegian research
organisation, Gexcon.
This requires you to sign in, but needs no password. It has much information about
explosions presented simply with good graphs and diagrams. Useful for understanding
the factors that influence an event. Also some brief video clips of explosion experiments.

Further reading material
The Fire and Explosion at Chemstar Ltd September 1981, HMSO

The Fire and Explosion at Manro Products Ltd December 1982, HMSO

Dust Explosions in the Process Industries, 2 nd Edition 1997, R K Eckhoff
ISBN 07506 3270 4
A comprehensive survey of the topic, with a critical discussion of a large range of
research work.

Prevention of fires and explosions in dryers, Abbott, J. A. Institute of Chemical Engineers
ISBN 0 85295 257 0, 1990

Hazards from pressure: exothermic reactions, unstable substances, pressure relief and
atmospheric discharge, European Federation of Chemical Engineering, EFCE
Publication Series No. 59, Institution of Chemical Engineers, 1987.

Flammable liquids and gases: Explosion hazards, FS6011, Fire Protection Agency.
The section on explosion prevention provides guidance on the reduction of the likelihood
of explosions of gas or vapour/air mixtures by:

Provision of ventilation, where plant is within buildings, to reduce the concentration of
gas or vapour to a safe value;

Construction of plant so as to prevent gas or vapour escaping, forming explosive
mixtures with air and reaching ignition sources;

Removal or protection of ignition sources, especially electrical sources

References
1.  For further information on the relevant British Standards  [16], please access the British
Standards web site and use the search facility.
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 9/11
6/20/2015 Explosive relief

Link URLs in this page

1.  5.2.1.3(29)b,g
http://www.hse.gov.uk/comah/sram/index.htm
2.  5.2.1.6(38)e
http://www.hse.gov.uk/comah/sram/index.htm
3.  5.2.1.10(53)
http://www.hse.gov.uk/comah/sram/index.htm
4.  Inerting
http://www.hse.gov.uk/comah/sragtech/techmeasinerting.htm
5.  Earthing
http://www.hse.gov.uk/comah/sragtech/techmeasearthing.htm
6.  Plant layout
http://www.hse.gov.uk/comah/sragtech/techmeasplantlay.htm
7.  Design Codes ­ plant
http://www.hse.gov.uk/comah/sragtech/techmeasplant.htm
8.  Design Codes ­ pipework
http://www.hse.gov.uk/comah/sragtech/techmeaspipework.htm
9.  Plant modification / change procedures
http://www.hse.gov.uk/comah/sragtech/techmeasplantmod.htm
10.  Maintenance procedures
http://www.hse.gov.uk/comah/sragtech/techmeasmaintena.htm
11.  Relief Systems / Vent Systems
http://www.hse.gov.uk/comah/sragtech/techmeasventsyst.htm
12.  Relief Systems / Vent Systems
http://www.hse.gov.uk/comah/sragtech/techmeasventsyst.htm
13.  Reaction / Product Testing
http://www.hse.gov.uk/comah/sragtech/techmeasreaction.htm
14.  Relief Systems / Vent Systems
http://www.hse.gov.uk/comah/sragtech/techmeasventsyst.htm
15.  Gas Explosion Handbook (in English)
http://www.gexcon.com/index.php?src=/handbook/GEXHBcontents.htm
http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 10/11
6/20/2015 Explosive relief

16.  British Standards
http://www.bsi­global.com/index.xalter

http://www.hse.gov.uk/comah/sragtech/techmeasexplosio.htm 11/11