Electrical Load Calculation

Design Assumption
AC area 80 W/m2
MV area 20 W/m2
NV area 10 W/m2

Common Area
Floor Level Usage Units AC Area (m2)
(m2)
Level 14 Roof Top 1117
Level 14 Apartment 9 1040 138
Level 13 Apartment 9 912 138
Level 12 Apartment 9 1040 138
Level 11 Apartment 9 912 138
Level 10 Apartment 9 1040 138
Level 9 Apartment 9 912 138
Level 8 Apartment 9 1040 138
Level 7 Apartment 9 912 138
Level 6 Apartment 9 1040 138
Level 5 Apartment 9 912 138
Level 4 Apartment 9 1331 138
Level 3 Car Park 1469
Level 2 Car Park 1469
Level 1 Car Park & Admin services 1571
Semi Basement Car Park 2139

Common Services
No Electrical Load
Pumps
Horse reel pump 1 3
Sprinkler pump 1 21.5
Wet riser pump 1 3

Lifts
Passenger Lifts 2 25
Service Lifts 2 30
Cold room 1 7.5

EV chargers 113.5

Outdoor lighting 20

Fire command center 21.62

# John Keells Group - Confidential


Sum of Apartment Levels, Carparks & Common services
For Additional Provisions (10%)

MSB Diversity (0.7)

VA rating (0.8PF)

Transformer Size

# John Keells Group - Confidential


Diversity Electrical Demand (W)

0.8 8,936
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 86,288
0.8 11,752
0.8 11,752
0.8 25,136
0.8 34,224

Diversity Electrical Demand (W)

0.8 2,400
0.8 17,200
0.8 2,400

0.8 40,000
0.8 48,000
0.8 6,000

0.5 56,750

0.5 10,000

1 21,620

# John Keells Group - Confidential


arparks & Common services 1,018,138 W
Additional Provisions (10%) 1,119,952 W

MSB Diversity (0.7) 783,966 W

VA rating (0.8PF) 979,958 VA


Total Demand 979.96 kVA

Transformer Size 1000 kVA