Professional Documents
Culture Documents
Electrical Load Calculation: Design Assumption
Electrical Load Calculation: Design Assumption
Electrical Load Calculation: Design Assumption
Design Assumption
AC area 80 W/m2
MV area 20 W/m2
NV area 10 W/m2
Common Area
Floor Level Usage Units AC Area (m2)
(m2)
Level 14 Roof Top 1117
Level 14 Apartment 9 1040 138
Level 13 Apartment 9 912 138
Level 12 Apartment 9 1040 138
Level 11 Apartment 9 912 138
Level 10 Apartment 9 1040 138
Level 9 Apartment 9 912 138
Level 8 Apartment 9 1040 138
Level 7 Apartment 9 912 138
Level 6 Apartment 9 1040 138
Level 5 Apartment 9 912 138
Level 4 Apartment 9 1331 138
Level 3 Car Park 1469
Level 2 Car Park 1469
Level 1 Car Park & Admin services 1571
Semi Basement Car Park 2139
Common Services
No Electrical Load
Pumps
Horse reel pump 1 3
Sprinkler pump 1 21.5
Wet riser pump 1 3
Lifts
Passenger Lifts 2 25
Service Lifts 2 30
Cold room 1 7.5
EV chargers 113.5
Outdoor lighting 20
VA rating (0.8PF)
Transformer Size
0.8 8,936
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 67,664
0.8 59,472
0.8 86,288
0.8 11,752
0.8 11,752
0.8 25,136
0.8 34,224
0.8 2,400
0.8 17,200
0.8 2,400
0.8 40,000
0.8 48,000
0.8 6,000
0.5 56,750
0.5 10,000
1 21,620