Professional Documents
Culture Documents
SERVO 954-Manual
SERVO 954-Manual
Honeywell Enraf
Delftechpark 39, 2628 XJ Delft
PO Box 812, 2600 AV Delft
The Netherlands
E-mail: HFS-TAC-Support@Honeywell.com
Website: www.honeywellprocess.com
Introduction
The end user will typically use the 954 SmartServo FlexLine together
with a Terminal Inventory System for custody transfer operations, so
Weights and Measures legislation is applicable.
Revision History
References
Patents
Table of Contents
1 GENERAL ............................................................................................................................................. 1
1.1 Target Group for this Service Manual .................................................................................................... 1
1.2 Structure of this Manual ........................................................................................................................ 1
1.3 Trademarks............................................................................................................................................ 1
6 INSTALLATION ....................................................................................................................................49
7 COMMISSIONING................................................................................................................................50
7.1 Checks before starting the commissioning .......................................................................................... 50
7.2 Installation of measuring drum and displacer..................................................................................... 51
Tools................................................................................................................................................ 51
Installation of measuring drum ...................................................................................................... 53
Installation of displacer................................................................................................................... 54
Unlocking (locking) the motor block ............................................................................................... 55
1 GENERAL
2 – SAFETY & SECURITY This chapter provides all the essential and mandatory safety
instructions, precautions, and measures. It also describes
the safety conventions used, the labelling information, and
the compliance information.
3 – PRINCIPAL OF This chapter provides the basic principles of servo based
SERVO MEASUREMENT measuring system.
4 - SYSTEM This chapter provides an introductory impression of the 954
ARCHITECTURE SmartServo FlexLine’s modular-shaped hardware
architecture.
5 - SERVICE TOOLS This chapter provides the description of the SmartView and
the Engauge service tool.
6 - INSTALLATION This chapter provides a reference to the Installation Guide
for the 954 SmartServo FlexLine to make sure the relevant
module(s) are accurately installed, before starting the
commissioning.
7 - COMMISSIONING This chapter provides the information required for an
accurate commissioning of one or more 954 SmartServo
FlexConn modules.
8 - OPERATION This chapter describes the basic operation of the 954
SmartServo FlexLine.
1.3 Trademarks
2.1 General
For the correct and safe servicing of this product, it is essential that all
personnel follow the generally accepted safety procedures in addition to
the safety precautions specified in this manual.
WARNINGS
The following warning symbol is used in this manual to urge attention in
order to prevent personal injuries or dangerous situations, further
described in this manual.
Cautions
Safety Instructions
See the safety instructions shipped with the device for installation,
commissioning, operation, and maintenance.
Users
The mechanical and electrical installation must be carried out only by
trained personnel with knowledge of the requirements for installation of
explosion-proof equipment in hazardous areas.
Additional Information
Environmental Conditions
Observe the environmental conditions for the temperature and the
pressure.
2.4 Liability
The information in this installation guide is the copyright property of
Honeywell. Honeywell disclaims any responsibility for personal injury or
damage to equipment caused by:
WARNING! Only certified technicians are authorized to make changes on the 954
SmartServo FlexLine configuration. All modifications must be in
accordance to the guidelines as set forth by Honeywell. Modifications
not authorized by Honeywell will invalidate the approval certificates.
2.5 Labels
NOTE: This is a conceptual view of the type plate and therefore subject to change.
FIGURE 2-1 Identification label with Safety note on the SmartServo FlexLine
General
WARNING! Make sure that the power to the device is switched off before
you open the covers of the device. Failure to do so may cause
danger to persons or damage the equipment. All covers of the
device must be closed before switching the power on again.
WARNING! Treat the flange surface of the cover and the housing with care.
Keep the flange surface free of dirt. The O-ring must be present
and undamaged.
2.7.1.2 Tools
• All wiring entries must be closed such that the approvals are not
invalidated. See the see the Installation Guide for the 954 SmartServo
FlexLine, to make sure that the correct thread type is selected.
For installations using cable glands, use Ex d compound barrier
glands.
For installations using conduits, each conduit must be sealed within 18
inches of the enclosure.
• Make sure that the housing of the device is properly bonded to the
Protective Earth (PE).
Explosion Safety
• ATEX
o SmartServo FlexLine
II 1/2 G Ex d IIB T6 or Ex d [ia] IIB T6 according to KEMA 07ATEX0010 X
• IECEx
• FM
o SmartServo FlexLine
Class I, Division 1, Groups C and D, T6, according to 3030575
• CSA
o SmartServo FlexLine
Class I, Division 1, Groups C and D, T6, Enclosure 4X, Dual Seal Ex d [ia Ga]
IIB T6 IP66 / IP67 Ga/Gb, according to 1921040
NOTE: The radiated output power of the device is far below the
exposure limits. Nevertheless, use the device in such a manner that the
potential for human contact during normal operation is minimal.
Low-Voltage Directive
The device is suitable for the following:
• Pollution degree 2
• Overvoltage category II
• Class I equipment
Security note 1
For security and unintended changes by people that are not allowed
making changes the "Protect all configuration jumper" must be placed
on all boards after device commissioning and a physical seal shall be
applied to the outsight of the device.
Put the "Protect all configuration entities" jumper of all relevant boards
so no external resource can modify anything of the configuration
(operational settings) of the 954 SmartServo FlexLine.
Security note 2
During (at a last step of the) commissioning the hardware W&M write
protect jumper / switch should be placed so no unintended or accidental
metrology configuration changes will be possible.
Security note 3
Security note 4
By having the physical seals applied the boards are not directly
accessible to remove the hardware configuration protection jumpers.
https://honeywell.com/pages/vulnerabilityreporting.aspx
or
The shaft of the drum is connected to the stepper motor via a magnetic
coupling.
Level measurement
A level variation of product, in which the displacer is partially immersed,
causes a change in buoyancy, which will be detected by the force
transducer. The resulting difference between measured and desired
value will cause a variation in the position of the stepper motor and
consequently raise or lower the position of the displacer until the
measured value equals the desired value.
One revolution is divided into 200 steps, therefore one step is equivalent
to 0.05 mm. This resolution is direct consequence of the stepper motor
principle. The correct functioning of the stepper motor is continuously
checked. This is achieved by decoding the unique pattern of an encoder
disk mounted on the motor shaft.
Relative density
To measure the relative density, the displacer is positioned at specific
heights and the apparent weight of the displacer at each height is
measured. Knowing the volume of the displacer, its weight in air, and
the measured apparent weight, the relative density of the product at
each position of the displacer can be calculated. The software for the
density measurement is available as an option.
The original servo gauge does not look much like today's modern
version. The instruments have evolved into highly reliable mature
products, and are gradually replacing mechanical float gauges, cutting
down on maintenance and improving on inventory results. Modern
intelligent servo gauge shave very few moving parts, resulting in long
term reliability and accuracy. They also have a high degree of data
processing power. The instruments do not merely measure the liquid
level but are also capable measuring interface levels and product
density. Accurate, programmable level alarms are standard. Accuracy's
of better than 1 mm (1/16 inch) over a 40 m (125 ft) range can be
attained. The exceptional accuracy and reliability has resulted in the
acceptance of the measurements and remote transmission, by Weights
& Measures and Customs & Excise authorities in many countries.
4 SYSTEM ARCHITECTURE
Each FlexConn module has one or more function. In general, this can
be a sensor function, a communication function, or a digital-interface
function.
NOTE: Some FlexConn PCBs are also used in the SmartLink system.
Figure 4-3.
Jumpers:
With the jumpers, specific hardware settings can be made:
Jumper
Function
Number
1 All warning and monitoring-related commissioning entitiesa are
protected and cannot be changed
2 The password is protected from being read
3 All commissioning entities are protected and cannot be changed
4 Board-specific jumper
5 Board-specific jumper
Entities.
Health LED
The Health LED (= LE1, the blue circle) indicates the general health
status of the FlexConn module.
Good
Uncertain
Bad
2 function LEDs
These LEDS indicate module-specific activities, such as for instance
data being transmitted or received.
3 voltage monitors
The output of these monitors, being voltage levels from three different
FlexConn PCB locations, are used for diagnostics purposes.
See Figure 4-4
1 temperature sensor
For the operational PCB, this sensor acts as an input for environmental-
temperature diagnostics. The PCB’s environmental temperature is used
as a measure for the temperature inside the 954 SmartServo FlexLine.
4.3 Entities
Information exchange between the various FlexConn modules takes
place by means of the entities.
Status Entities
The “Health” and “Commissioned” entities provide information about the
general FlexConn module status and the functions implemented on this
module.
1. status
2. status category
3. status code
good
uncertain
bad
The following tables provides information about the status code and the
specific reason why the status is good, uncertain, or bad. This
information is presented as an information number coupled with a
textual description of this specific situation.
under range
over range
no data
cal fail
hw fail
sw fail
un-init
last
killed
actual manual stored instrument environment
valid
001 056 077 104 632 328 207 782 065 478 199 389 011 072 ........................................................
Generic Entity
The following command entities are implemented as generic functions.
“Reset device”
“Reset board”
A 1 0 0 0 0
internal preliminary
bug fixes
minor functionality
warning + measuring data related part
main functionality
hardware modifications
Function-specific Entities
General
The HART SmartView is used to set and control most of the FlexConn
module settings
H C I
FII-DO G N
FII-DO:>
board H C I
Relay 1 G N
Relay 2 G Y
Relay 3 U Y nnn
Relay 4 B Y
FII-DO:>
board H C I
Relay 1 GN
Relay 2 GY
Relay 3 U Y nnn
Relay 4 BY
For example, for the FII-DO module, the below listed specific tab pages
are present:
Relay 1
Relay 2
Relay 3
Relay 4
In case of complex functions, extra tab pages can exist, containing the
specific functions involved.
“Function identification”.
With this entity, you can change the function name, which is available
on the HART SmartView Primary Value screen and in Engauge.
5 SERVICE TOOLS
General
The HART SmartView is the basic tool in which you can communicate
with the SmartServo FlexLine modules.
Connections
Button Function
within menu ...
PV Go to next PV screen
Commissioning Move cursor 1 position to the right
PV Go to previous PV screen
Commissioning Leave current menu screen and go to higher-level
menu.
Important: Leaving an edit screen this way will undo all
Commands Leave current menu screen and go to higher-level
menu
Display contrast Decrease contrast
Button Function
within menu ...
Commissioning Within the menu screens, move cursor 1 line up
Within the edit screens, scroll characters as long as the
button is pressed
Commands Move cursor 1 line up
+ Show menu
Go to PV screen
<
<
<
MAI N
The [display settings] screen allows you to set the time-outs for the
buttons. The screen displays the following items:
When the [display test] screen is selected, the HART SmartView performs
a black/blank test. HART SmartView begins drawing a rectangle of 64 x
128 pixels, filled with black pixels for a period of 1 second. After that
period, the screen is cleared using a rectangle filled with white pixels for
a period of 1 second.
o customer ID
o HART SmartView
+ address
+ software version
+ software checksum
o board name
o board id
o instance
o software version
The [level & temperature] screen displays information about the measured
product level and temperature. In this menu mode, it is not possible to
change any settings.
NOTE: In case of an error situation, the level fields are filled with “#”
and the temperature fields with “9”.
Figure 5-6 The level & temperature screen (left), extra information screen (right)
Figure 5-7 PV-screen examples (left: level status, right: digital I/O status)
Max. Size
Data Field Description
[characters]
Primary Value 9 The measured value, for example,
+025.1277
PV identification 13 Quantity name, for example,
• Product level
• Product temperature
• P1 pressure
PV units 5 Quantity unit, for example
• m
• kg/m3
• kPa
PV type 3 Type can be:
• INN (innage)
• ULL (ullage)
• REL (relative)
• ABS (absolute)
PV health 9 Status of the Primary Value:
• UNCERTAIN
• BAD
Max. Size
Data Field Description
[characters]
PV representation 15 Representation of the PV:
• Manual
• Last valid
• Stored
• Instrument
• Environment
• Hardware
• Software
• Commission
• Calibration
• Operational
• No data
• No init.
• Killed
• Over range
• Under range
PV alarms 9 Alarm type that occurred:
• High High
• High
• Low
• Low Low
Tank identification 8 Tank name, for example, CRUDE 07
Alive indicator 1 Blinking cursor (bottom right) indicates
PV being updated
REMARKS:
When the password is entered correctly (only once for both menu
entries), you can change the values. 15 minutes after the last button is
pressed, the password needs to be re-entered.
You can navigate through the board list by using the up and down
buttons. A board can be selected by simultaneously pressing the left +
right button
The [function list] screen (see Figure 5-10) displays all the available
functions of the previously selected board. You can navigate through
the function list by using the up and down buttons. You can return to the
[board list] screen by pressing the left button. A function can be selected
by simultaneously pressing the left + right button. If a FlexConn module
does not contain any function commands, this is indicated in the list (<no
cmd>).
You can navigate through the board list by using the up or down button.
A board can be selected by simultaneously pressing the left + right
button.
The [function list] screen (see Figure 5-13) displays all configurable
entities of a function.
You can navigate through the board list by using the up or down
button. A function can be selected by simultaneously pressing the left
+ right button. You can return to the [board list] screen by pressing the left
button.
o You can return to the [entity list] screen by pressing the left
button.
NOTE: Use the left button to return to the [entity list] screen without
executing the modification(s). Press the left + right button
simultaneously to undo this (these) modification(s)!
The HART address screen allows you to change the address of the
HART SmartView. When the button left or right is pressed the new
address is immediately active. The address is stored in non-volatile
memory (see Figure 5-16).
< >
<
<
MAIN
MENU SELECT
< >
<
<
MAIN
MENU SELECT
Symbol Description
Checksum errors Number of received corrupt messages
Unknown msg's Number of unknown messages that the HSV received
Communication Activity:
Symbol Description
Tx Number of bytes transmitted after startup in Kb [1024 bytes]
Rx Number of bytes received after startup in Kb [1024 bytes]
5.2 Engauge
Using Engauge
After starting the Engauge application, first the specific transmission
address of the concerned 954 SmartServo FlexLine system must be set
correctly. Also, the transmission speed (baudrate) must be set.
6 INSTALLATION
7 COMMISSIONING
Caution
Keep screw thread from the compartment covers free from dirt. Grease them
lightly with an acid-free grease before closing the instrument. When closing, turn
the covers counter-clockwise until the thread clicks into place, then turn clockwise.
Tools
It is recommended to use a HART SmartViewto load the different
parameters. A tool set for commissioning and maintenance is available
from Honeywell Enraf (see
Figure 7-1)
Figure 7-1.
Item Description
1 Allen key 2 mm
2 Allen key 3 mm
3 Allen key 4 mm
4 Allen key 5 mm
5 Allen key 8 mm
7 Test magnet
10 Pipe wrench 27 mm
11 Tommy bar
Figure 7-1 Tool set for 954 SmartServo FlexLine (part no. A1854062)
Installation of displacer
If a density displacer is used, note the engraved displacer
weight and displacer volume on a piece of paper for later
use.
Remove the test weight and attach the displacer to the wire
through a mounting hatch.
Locate the transport bracket (see Figure 7-4) Loosen (do not
remove) the Allen key screw and turn the transport bracket
the opposite way. Use screwdriver for Allen key screws M4
(item 8 of the Honeywell Enraf tool set).
Fix the Allen key screw of the transport bracket. • Check the
span wire. It should always be under tension while both
ends are correctly positioned in the levers of the motor block
and force transducer.
Note: Use the same procedure for locking the motor block if the 954
SmartServo FlexLine needs to be removed.
Introduction
This chapter provides an overview of the commissioning information as
per the FlexConn module.
Commissioning a FlexConn module is performed by setting software parameters and the entities
(see 0
Text Conventions
7.3.3.1 Introduction
The Host Communication Instrument - Bi-Phase Mark (HCI-BPM) board
is a communication module for the instrument (gauge).
• The Enraf GPU protocol with its records and items (limited);
• 858 CIU
• 780 SmartLink
☛ After having checked/set all before listed entities, make sure you
check the following:
The [Board Health] and the [BPM slave Health] entities are
<GOOD>.
Element Description
Stepper motor Motor to control the drum position in order to be able to raise or
lower the displacer position in the storage tank.
Encoder Transmits unique patterns in order to read out the motor position
by the firmware.
Element Description
RTC Real Time Clock used for date and time stamping of
measurements and diagnostics.
Low power Signal generated by the CAN-SERVO board in case the power
drops below a certain threshold where the firmware needs stop
the servo stepper motor and store relevant operational data in
non-volatile memory e.g. motor position.
• Average density
• Density-Water dip
• Water-density dip
• Block
• Freeze
• Accept reference
• Unlock
• Test gauge
• Lock test
• Calibrate
• Test
• Lock to level
• Go down
• Go up
• Balance test
• Check bearings
• Unbalance compensation
It is done in 2 steps.
This is step 1.
[High alarm]
[Low alarm]
[Alarm hysteresis]
[High alarm]
[Low alarm]
[Alarm hysteresis]
[High alarm]
[Low alarm]
[Alarm hysteresis]
7.3.4.8 Density
Name Value Range Default Value Explanation
[Primary value] Shows the calculated
density value after a
density profile or tank
profile command.
Fields, see product
level
[Primary value gain] See product level
[Primary value offset] See product level
[Secondary value] N.A.
[High high alarm] See product level
[High alarm]
[Low alarm]
[Low low alarm]
[Alarm hysteresis]
[Alarm test enable] See product level
[Alarm test] See product level
[Kill measurement] See product level
[Manual overwrite] See product level
[Resurrect] See product level
[Manual overwrite status] See product level
7.3.4.11 Configuration
Name Value Range Default Value Explanation
[Displacer type] <no_displacer_type_selected> <No displacer During
<s0815345_cptfe_110mm> type selected> commissioning a
displacer type can be
<s0815344_cptfe_90mm> selected from a list.
<s0815343_cptfe_45mm>
<s0815360_cptfe_25mm>
<s0815350_aisi316_density_90mm>
<s0815355_aisi316_density_45mm>
<s0815316_stabigauge_90mm>
<s0815362_cptfe_spider_90mm>
<other_displacer_type>
[Measuring <no_measuring_range_selected> <No measuring During
range and wire <27m_88ft_aisi316> range commissioning the
material] selected> measuring range and
<27m_88ft_hastelloy_c22> wire material can be
<27m_88ft_tantalum> selected from a list.
<37m_121ft_aisi316>
<37m_121ft_invar>
<37m_121ft_tungsten>
<47m_154ft_aisi316>
<47m_154ft_tungsten>
<150m_492ft_aisi316>
<other_measuring_range_or
_wire_material>
[Drum <0.0> The drum
circumference] circumference.
[Set point 1] <0.208> This entity defines
the wire
weight/tension if it
reaches the interface
1 (product level)
transition.
[Set point 2] <0.208> This entity defines
the wire
weight/tension if it
reaches the interface
2 (2 different product
densities) transition.
[Set point 3] <0.208> This entity defines
the wire
weight/tension if it
reaches the interface
3 (water level)
transition.
7.3.4.14 Compensation
Name Value Range Default Value Explanation
[Setpoint compensation] <enable> <enable> Enable or disable the
following
<disable> <disable>
compensations for the
<disable> set point:
-Wire weight
Compensates for the
wire weight
-Unbalance
Compensates for the
unbalance of the drum
and bearings
-Density
Compensates for the
change in density over
time
[Compensation wire Shows the wire weight
weight] compensation.
[Compensation Shows the unbalance
unbalance] compensation.
[Compensation density] Shows the density
compensation.
[Level compensation] <enable> <enable> Enable or disable the
following
<disable> <enable>
compensations for the
<disable> level:
<disable> -Magnet coupling
7.3.4.15 Maintenance
Name Value Range Default Value Explanation
[Wire tension <enable> <enable> With this entity the possibility
protection] <disable> exists to enable or disable the
wire tension high and low check.
If enabled a high or low fail code
will be generated if the tension
exceeds the low or high
thresholds.
[Drum slip <enable> With this entity the possibility
detection] exists to enable or disable the
drum slip detection. If enabled a
drum slip fail code will be
generated if the measured
frequency is below a certain
limit.
[Drum slip Shows the number of drum slip
occurrence] occurrences
[Motor position Shows the number of observed
errors] slip detections of the reference
encoder
[Set to This command resets the Servo
Maintenance mode] board and after that enters the
maintenance mode. In this mode
there are no level
measurements. Now the 4
frequencies can be measured or
the find reference encoder can
be done. A limited number of
commands can be issued.
[Operational mode] Shows the mode the gauge is in:
Operational or Maintenance
[Find reference This command determines the
encoder position] reference encoder position and
synchronizes this with position.
Only available in Maintenance
mode.
[Frequency 0] <0.0> Frequency measured at resp.
[Frequency 1] <0.0> 25, 100, 175 and 250 g. load on
the wire.
[Frequency 2] <0.0>
[Frequency 3] <0.0>
[Measure This command will measure the
frequency] frequency with the actual
displacer/weight. The result is
placed in entity [Measured
frequency].
[Autonomous SAT enable] <SAT disable> <SAT enable up> Determines whether the
SAT is disabled, or
<SAT enable up>
enabled for upward
<SAT enable up and movements, or enabled
down> for upward and
downward movements.
No error
RIC configuration parameters not
commissioned
Product level below RIC minimum level
Error getting HART dynamic variables entity
device address 11
Error getting HART dynamic variables entity
device address 12
Error getting HART dynamic variables entity
device address 13
Wrong HART units device address 11
Wrong HART units device address 12
Wrong HART units device address 13
Bad HART status device address 11
Bad HART status device address 12
Bad HART status device address 13
[Compensation Shows the calculated compensation offset
factor] due to the roof immersion. This will be
applied to the L-record. Normally this will be
a negative number.
[Probes scan <0..255> <0> Determines the board id where the probes
board id] are connected. This can be:
6 : FCI-HT
7 : FII-VT
23: FCI-HRT
[Probes scan <0..7> <0> Determines the board instance of the above
board instance] mentioned board.
[Method] <Geometrical> <Geometrical> Two possible methods for doing the
calculations. They are recommended by the
<Roof weighing>
Polish Weight and Measures Institute called
the G.U.M.
[Total surface <0.0> Determines the total surface area of the
area product] product in the tank.
Miscellaneous
Note: only two relays, the low rated or high rated, are used not all 4
together.
With jumpers, the relays can individually be set to Normally Open (NO)
or Normally Closed (NC).
In addition to the board’s [Health] LED LE1, the LEDs LE2 and LE3 are
available (see Figure 7-7). They can be associated to a relay, by setting
the [LED Association] entity.
If the [Relay Mode] entity is set to <Energized>, the relay coil will be
energized when the relay state is <Deactivated>, and the relay coil will
be de-energized when the relay state is <Activated>.
If the [Relay Mode] entity is set to <De-Energized>, the relay coil will be
de-energized when the relay state is <Deactivated>, and the relay coil
will be energized when the relay state is <Activated>.
The <Energized> option is used for fail-safe operation whereas the <De-
Energized> option is used for non-fail-safe operation.
Physically
Relay Mode Relay State Physical Result
Configured
Normally Open De-Energized Activated Closed
(NO)
Deactivated Open
Energized Activated Open
Deactivated Closed
Normally Closed De-Energized Activated Open
(NC)
Deactivated Closed
Energized Activated Closed
Deactivated Open
7.3.6.4.1 PV Monitor
In [PV Monitor] mode, each individual FII-DO-relay unit can monitor the
Primary Value (PV) or Secondary Value (SV) of another board
connected to the CAN bus, and either activate or deactivate the
associated relay if a certain condition is <True> or <False>.
If the [Status Behavior] is set to <Not Used>, the respective relay will
not be activated if the scanned PV or SV health is Bad or Uncertain.
☛ For the FII-DO relays not used within the application, set the [Alarm
Mode] entities to <Not In Use>.
7.3.6.5 Commands
The following commands can be given to the FII-DO:
Activate
Deactivate
Acknowledge
7.3.6.5.1 Activate
The !Activate! command will cause the specified relay to become
<Activated>. This command is only available in [Remote Control] mode;
see 7.3.6.4.4.
If the [Time Setting] entity is set to a value other than zero, the relay will
be activated for a time in seconds equal to the value set in the [Time
Setting] entity, then deactivated. During the period the relay is activated,
the relay state will be !Time Setting Active!. This is useful for site
commissioning.
☛ For each relay, set the [Time Setting] entity to the desired value.
7.3.6.5.2 Deactivate
The !Deactivate! command will cause the specified relay to become
<Deactivated>. This command is only available in [Remote Control]
mode; see 7.3.6.4.4.
7.3.6.5.3 Acknowledge
The !Acknowledge! command will cause the specified relay to be
physically deactivated, but the relay status will be set to
!Acknowledged!. This command is only available in [PV Monitor] mode;
see 7.3.6.4.1. This command can only be given when the concerned
relay has already been activated.
The associated LED will be ON when the relay state is <Activated>, and
the LED will be OFF when the relay state is <Deactivated>.
NOTE: The LEDs do not indicate the physical relay state (coil state or
contacts state), as this depends on the software settings and the
physical settings (jumper), see Relay Configuration 7.3.6.3.
☛By using the table below, make sure all entities are commissioned.
The [Commissioned] entity will display either <True> if the function is
commissioned or <False> if the function is not commissioned. To
commission the function, the entities must be set in accordance with the
table below.
Remote
Operation Alarm
Control Parameters Commissioned
Mode Mode
Mode
Alarm Mode Remote Restricted [Control Board ID] >=1 and =255 <True>
Control [Control Board Instance] >=0 and <=7
[Control Function Instance] >=1 and <=15
[Time Setting] = 0
7.3.7.1 Introduction
The Field Communication Instrument - HART (FCI-HRT) board is a
module that communicates with HART SmartView.
The FCI-HRT board has a planar transformer for galvanic isolation from
the HART bus. See Figure 7-9.
LED LE1 is the board’s [Health] LED. LEDs LE2 and LE3 will be flashing
to indicate activity on the HART bus. LE2 indicates data is being
transmitted (Tx), LE3 indicates data is being received (Rx).
Figure 7-10 The analog and digital signals within the HART® communication
Moreover the FCI-HT module can calculate the HIMS1 product density.
The main function of the FCI-HT software is to measure HIMS product
pressure sensors, and via the FlexConn bus to a product level and a
water level sensor.
For tanks that are free venting to the atmosphere or floating-roof tanks,
P3 pressure is not required. The water level sensor is also optional.
In the multi-drop digital mode situation, one or two of the generic HART
sensors can be [P1 Pressure] or [P3 Pressure], providing product pressure
and Vapour pressure respectively, but no HIMS density calculation will
be available.
Example 1
Example 2
7.3.7.3.1 General
The main function of the FCI-HT software is to measure HIMS product
density, by connecting the FCI-HT board via the HART bus to 2
pressure sensors (P1 and P3), and via the FlexConn bus to a product
level sensor and an optional water level sensor.
The FCI-HT software only supports HART devices with the following
addresses.
7.3.7.3.2 P1 Pressure
The value is filtered, and the filtering factor depends on the value set in
the entity [P1 Integration time]. A higher value gives more filtering, and a
lower value gives less filtering.
The correction factor stored in the [P1 PV offset] entity is then subtracted
from the filtered value. If the [P1 PV offset] entity = 0 no offset is applied.
7.3.7.3.3 P3 Pressure
The value is filtered, and the filtering factor depends on the value set in
the entity [P3 Integration time]. A higher value gives more filtering, and a
lower value gives less filtering.
The correction factor stored in the [P3 PV offset] entity is then subtracted
from the filtered value. If the [P3 PV offset] entity = 0 no offset is applied.
• [Local Gravity]
P1 pressure
P3 pressure
Product level
The FII-VT board has a planar transformer for galvanic isolation from
the HART bus. See Figure 7-16.
LED LE1 is the board’s [Health] LED. LEDs LE2 and LE3 will be flashing
to indicate activity on the HART bus. LE2 indicates data is being
transmitted (Tx), LE3 indicates data is being received (Rx).
7.3.7.4.3 Commissioning
Commissioning Parameters for MTT/LT Probes
The following 9 configurations are possible:
Product Temperature
NOTE: Using Engauge, following entities are set within the Engauge
Product temperature tab.
Vapour Temperature
NOTE: Using Engauge, following entities are set within the Engauge
Vapour temperature tab. Some Vapour temperature settings are
shared with Product temperature settings.
Water Level (for 766/768 Combi probes and 765 Water probe only)
[Alarm test] Activates and selects at the [No Alarm] <No Alarm>
same time the Alarm test (if [High High alarm] [High
enabled with the [Alarm test Alarm]
enable] listed before, and the [Low Alarm]
4 alarm thresholds are [Low Low alarm]
properly set).
Product Temperature
NOTE: Using Engauge, following entities are set within the Engauge
Product temperature tab.
Vapour Temperature
NOTE: Using Engauge, following entities are set within the Engauge
Vapour temperature tab.
Some Vapour temperature settings are shared with Product
temperature settings.
For the entities to be set for the stand-alone 765 VITO water probe (see
Figure 7-21).
Water Level
7.3.8.1 Introduction
The Field Interface Instrument - Resistance Temperature Detector (FII-
RTD) board is a sensor module for the instrument (gauge) and
calculates average product, Vapour- and ambient temperatures.
Some important settings of the FII-RTD in Board Specific tab are listed
below.
Setting Remarks
[Measurement type] ″ MPT
″ MRT
″ Mtt
″ No measurement type
″ RTD 3-wire
″ RTD 4-wire
[Element type] ″ Cu100
″ Cu90 Beacon
″ Cu90 Enraf
″ Cu90 Nulectrohms
″ Ni191
″ No element type
″ Pt100 large
″ Pt100 small
″ PtCu100
″ Sangamo MRT
″ Sangamo spot
″ Thermocouple
[RTD configuration] • RTD1 in tank
• RTD1 + RTD2 in tank
• RTD1 in tank + RTD2 ambient
• RTD1 ambient
″ No RTD configuration
″ RTD1 in tank
″ RTD1 in tank + RTD2 ambient
[Gauge temperature scale] Can be:
• IPTS-68
• ITS-90
[Lowest element offset] This is the distance from tank bottom till lowest element
position
[Number of elements] Can be 1..6
[MPT sensor length] -
NO EXCLUSION
STATIC EXCLUSION DYNAMIC EXCLUSION
(default)
MPTs > = 2 elements MPTs > = 3 elements
RTDs and MPT
LAST VALID
LAST VALID
elements fail
USE T1
USE T2
USE T1
T1 T1 calculation
FAIL
FAIL
FAIL
T1 pos < Temperature element T2 pos < Smoothing level < T3 pos
7.3.8.4 Commissioning
7.3.8.4.1 Commissioning Parameters for 1 or 2 RTDs (3- and 4-wire) Temperature
Calculations
NOTE: Make sure the RTD/MPT jumper is set to RTD.
[Low element usage] See Figure 7-24 <No Exclusion> <No Exclusion>
<Static Exclusion>
<Dynamic Exclusion>
[Low element behaviour] See Figure 7-24 <Temp To Fail> <Temp To Fail>
<Temp To Last Valid>
<Temp Use First Element>
<Temp Use Second Element>
[Temperature element exclude See Figure 7-24 floating point number: <1.0>
zone] <-x.x .. +x.x>
[MPT element position mode] Determines whether the element <Automatically> <Automatically>
[Only for MPT] positions are automatically <Manually>
calculated (based on sensor
length) or manually entered.
[RTD element positions] If MPT element position mode floating point numbers: <0.0>
[Only for MPT] is MANUALLY then here the <-x.x .. +x.x>
positions can be filled in.
[Averaging constant] Value of how much of the old <0.0 .. 1.0> <0.9>
calculated value is used with
respect to the new calculated
value
[Temperature range check] Enables or disables the fact that <enable> <disable>
an element which is outside a <disable>
temperature range will lead to
temperature fail.
(See also Figure 7-23 )
[Alarm test enable] Enables (if activated, see next listed <enable> <disable>
entity) the simulation of one of the 4 <disable>
alarms for a minute, by simulating the
actual measured Primary Value is
below or above the alarm threshold.
[Alarm test] Activates and selects at the same time [No Alarm] <No Alarm>
the Alarm test (if enabled with the [High High
[Alarm test enable] listed before, and the alarm] [High
4 alarm thresholds are Alarm]
properly set). [Low Alarm]
[Low Low alarm]
[Function identification] The name of the current function of 13 characters <Ambient temp.>
this module. This name is visible on
the HART SmartView.
For viewing the software version, the Engauge Generic tab can be
viewed; also a Reset board command can be issued here.
7.3.9.1 Introduction
The Host Communication Interface – HART Analog Output (HCI-HAO)
is a HART® slave module which communicates with the associated
HART master over the HART bus.
The HCI-HAO board has a planar transformer for galvanic isolation from
the HART bus. See Figure 7-25.
LED LE1 is the board’s [Health] LED. LEDs LE2 and LE3 will be flashing
to indicate activity on the HART bus. LE2 indicates data is being
transmitted (Tx), LE3 indicates data is being received (Rx).
Figure 7-26 The analog and digital signals within the HART® communication
If any fatal errors occur during operation - which will run the
program into an undesired situation - then a software reset
(Warm Reset) is given to the HCI-HAO software. During this
situation, the output of the module remains at the desired
level till the software starts normal working. Handling of a
fatal error is a general FlexConn function. This will update
the appropriate entity as well.
HART Unit
Sensor Type Accepted HART Units Abbreviation
Code
Temperature Degrees Celsius °C 32
Degrees Fahrenheit °F 33
Pressure Pounds per square inch psi 6
Pascal Pa 11
Kilo Pascal kPa 12
Level Feet ft 44
Meters m 45
Inches in 47
Density Kilograms per cubic meter kg/m3 92
Pounds per cubic foot lb/ft3 94
Degrees API API 104
Status <BAD>
Status Category <GENERAL_HARDWARE_FAIL>
Status Code <DAC_READ-BACK_FAIL>
Until calibration has been carried out, the Health status of the PV and
the analog output function will be:
Status <BAD>
Status Category <STATUS_CATEGORY_BAD_GENERAL_CALIBRATION_FAIL>
Status Code <CALIBRATION_SET_POINTS_NOT_CALIBRATED>
7.3.9.6 Commissioning
Function
Name Explanation Default Function
Part
Value
[PV Link board ID] Board ID of Other FlexConn <0> Board Board Specific
to be linked as PV to HCI-
HAO
[PV Link board instance] Board Instance of the linked <0>
PV board
[PV Link function instance] Function Instance of the <0>
linked PV board
[PV Link Sensor Value]* Primary or secondary <PV_LINK>
variable of linked card can
be assigned to this
[HART PV unit code] Unit code for linked PV <UNIT_CODE_ Function 1 Communication
UNKNOWN> (HART
[HART Upper Transducer Upper transducer limit for <0> communication)
Limit] connected sensor of linked
PV board
[HART Lower Lower transducer limit for <0>
Transducer Limit] connected sensor of linked
PV board
[Polling Address] Polling address of the <0>
device, which is used for
poll-based addressing
[Transducer Serial Transducer serial number <123>
Number] of connected sensor of
linked PV board
[Upper Range Value] Upper range value for PV. <0> Function 2 Sensor
This value is used to (Analog Output)
calculate the analog output
current.
[Analog Output at 4mA] Calibration reading when <0>
[Calibrate at 4 mA] command
is given
[Analog Output at 18 Calibration reading when <0>
mA] [Calibrate at 18 mA] command
is given
[Lower Range Value] Lower range value for PV. <0>
This value is used to
calculate the analog output
current.
[Analog Burnout Value] Analog burnout value in <3.6mA>
case of malfunctioning
device
All the entities in the above table would be initialized to their default
values after [init novram] command is given. All the entities should have
their proper values so as to make the respective Function and Board
health to <GOOD> status.
The [Analog Output at 4 mA] and [Analog Output at 18 mA] fields should be
entered after giving proper calibration commands (for more details, see
7.3.9.4).
Function
Name Explanation Default Value Function
Part
[SV Link board ID] Board ID of Other FlexConn <0> Board Board
which is linked as SV to Specific
HCI-HAO
[SV Link board instance] Board Instance of the linked <0>
SV board
[SV Link function instance] Function Instance of the <0>
linked SV board
[TV Link board ID] Board ID of Other FlexConn <0>
which is linked as TV to
HCI-HAO
[TV Link board instance] Board Instance of the linked <0>
TV board
[TV Link function Function Instance of the <0>
instance] linked TV board
[QV Link board ID] Board ID of Other FlexConn <0>
which is linked as QV to
HCI-HAO
[QV Link board Board Instance of the linked <0>
instance] QV board
Function
Name Explanation Default Value Function
Part
[QV Link function Function Instance of the <0> Board Board Specific
instance] linked QV board
[Linked Primary Value] PV / SV value of linked PV <0>
board in the set unit code
[Linked Secondary PV value of linked SV <0>
Value] board in the set unit code
[Linked Tertiary Value] PV value of linked TV board <0>
in the set unit code
[Linked Quarternary PV value of linked QV <0>
Value] board in the set unit code
Function
Name Explanation Default Value Function
Part
[HART SV unit code] Unit code for linked SV <UNIT_CODE_ Function 1 Communica
UNKNOWN> tion (HART
[HART TV unit code] Unit code for linked TV <UNIT_CODE_ communica
UNKNOWN> tion)
[HART QV unit code] Unit code for linked QV <UNIT_CODE_
UNKNOWN>
[Configuration changed Increments every time the <0>
Counter] configuration is changed
[Device ID] Same as Enraf Serial
number. This is a unique
number to every board.
[Device Type] Device type registered with <127>
the HART Communication
Foundation
[Manufacturer ID Number] Manufacturer ID registered <148>
with the HART
Communication Foundation
[Number of Preambles] Number of preambles <7>
required for a request from
the HART master
[Number of Response Number of preambles in the <7>
Preambles] HCI-HAO response stream
[Fixed Current Value] Fixed analog output current <0> Function 2 Sensor
set by HART command 40 (Analog
Output)
[Loop Current Mode] If HART mode selected is <Enabled>
<Standard 4-20mA>, then it is
enabled.
If HART mode selected is
<Fixed 4-20mA>, then it is
disabled.
[Percentage of Range] Percentage of current PV <0>
with respect to the limits set
7.3.10.1 Introduction
The FlexLine 954 servo gauge is an
inventory and custody transfer level gauge
for storage tanks. It is a state of art
technology design with highest reliability
components and tested for the industrial
level performance across global locations.
This is designed to fit into existing
Emerson gauging system as an attractive
replacement with very minimal changes.
The replacement of FlexLine 954 gauge with the existing gauge is a
very smooth process and can be quickly done.
There will be no change in the existing measurement system network as
the replacement is designed to replicate the existing gauging system
with no changes in terms of measured parameters, number of sensors,
number of inputs/outputs, and relays.
The Figure 7-27 shows the Emerson system with Rex gauges, and one
of its gauge is replaced by FlexLine 954 gauge.
Figure 7-27 System Architecture - Rex Replaced with 954 SmartServo FlexLine
FCM-TRL/2
Open the Engauge tool from the PC where enguage is installed. Right
click on HCM-GPU card.Select Commissioning.
To read the current data of this TAB sheet, press the Read button.
Instead, you can also select to press the Read All button available when
extending the read function by the arrow at the right side of the read
button). Then the current data of all TAB sheets are read.
The TAB sheet Status gives information about the health of the HCM-
GPU module (Refer to "HCM-GPU Status").
Baud rate
38400. When required, the baud rate can be changed. The following
settings are possible:
115200
57600
38400
19200
9600
4800
2400
1200
To make the change effective, press the Send button. When the baud
rate is changed, also change the baud rate at the COM port icon (two
levels higher).
This setting is used for host systems that cannot switch directly from
sending to receiving. The delay time can be set between 0 and 2000
msec.
Identification:
The address of the SmartLink, ranging from 0 till 9 (similar as the CIU
address). Each SmartLink, connected to the same PC ComPort, must
have a unique address. If the GPU interface address is changed from
default, and the new address has been sent to the HCM-GPU module,
then also change the address at the SmartLink icon Properties TAB
sheet (one level higher).
The address for FlexConn communication, ranging from 1900 till 1999.
Each SmartLink, connected to the same PC ComPort, must have a
unique address. Similar as with the GPU interface address, if changed
from default, also alter this FlexConn address at the SmartLink icon
(one level higher).
Password:
Parity:
Can be set to: Odd, Even or None. Standard Enraf GPU protocol (and
ACK mechanism:
Function identification:
In the SmartLink, the HCM-GPU module has the function of: GPU-slave
(the host is the GPU-master).
Test LED’s button:The TxD and RxD led’s are switched on for 10
seconds. The selected FCM-TRL/2 Module is identified. This is useful
incase more than one FCM- TRL/2 Module is present.
Identification:
When one FCM- TRL/2 Module is used in the SmartLink, the default
start and stop addresses (0 and 99) can be used.
When one FCM- TRL/2 Module is used in the SmartLink, the default
start and stop addresses can be used.
When two or three FCM- TRL/2 Modules are used in the SmartLink, a
division must be made, like described above.
Password:
Function identification:
In the SmartLink, the FCM- TRL/2 module has the function of: TRL/2-
master (the instrument is the TRL/2- slave).
You must configure the gauge TRL/2 through engauge. Follow the steps
to configure the gauge TRL/2:
a) Enter the Rex Unit ID, DAU Unit ID, Rex Modbus
Address, DAU Modbus Address, GPU instrument
address, FlexConn instrument address.
NOTE: The basic configuration (Rex Unit ID, DAU Unit ID, Rex
Modbus Address, DAU Modbus Address, GPU instrument address,
FlexConn instrument address) of Gauge TRL/2 card must be done
using Engauge tool through SmartLink..
NOTE: The parameter for Rex Unit ID, DAU Unit ID, Rex Modbus
Address, DAU Modbus Address should be entered as per emerson
system, as in saved database (Refer "Saving configuration in
database").
a) Click Read.
b) Click Send.
8. Click Read.
9. Click Send.
19. Add the GPU and Flexconn address in the Engauge tool.
3. Add/Copy the bin format file to the card inside the Firmware
folder.
The health LED blinks indicating the health status. After few seconds
The Rex gauges are replaced with CAN TRL/2 FlexLine 954 gauges.
Follow the steps to replace Rex gauge:
d) Click on Browse.
Use the path where you saved the database.
Image: t.b.d
Image: t.b.d
Image: t.b.d
7.3.10.9 Troubleshooting
7.3.10.9.1 Gauge Scan Issue
Hardset the gauge and repeat all the steps from step 1.
3. If gauge scan Time out error appears then restart smart link
and try to scan again (check gauge address mentioned in
FCM-TRL/2).
2. Switch off the gauge and insert CAN-SD card with suitable
firmware inside gauge.
3. Switch on the gauge observe LED pattern of SD card and
HCI-TRL/2 card.
4. Remove SD card from CAN rail or from gauge after
firmware upgrade completed.
7.3.10.9.5 Firmware Upgrade issue/Gauge scan issue when smart link connected
to FCU host port
1. Check Time out, Retries options in Engauge. if Timeout is
less than 8000ms then Firmware upgrade will fail when it’s
done via FCU.
[LCD switch off time] <1 ..255> 3 digits <15> This is used to switch
off the LCD to increase
the life time of LCD.
LCD will be switched of
once time is elapsed
from the time of start-
up. Unit is
minutes(Min) for this
entity
1. Header as 954
3. Checksum of Firmware
Initial Screen
Initial screen will be displayed only if Show initial screen: entity is
configured as “Enable”
Level Value
Temperature Value
Operational Status
Displacer Status
Alarm Status
Refresh Indicator
Meter
Inches
Feet
Fraction
Alarm Screen
High Alarm
Low Alarm
Reached
Not Reached
Displacer Screen
Down
Up
No movement
SAT Active
No Status
General CAN-
SERVO board Fail
Balance Test
Block
Calibrate
Freeze
Go Down
Go Up
Interface Profile
Lock Test
Measure Frequency
Test Gauge
Tank Profile
Interface 1 Mode
Interface 2 Mode
Interface 3 Mode
Dip Mode
Test
Lock To Level
Check Bearings
Manual Process
Value
Innage
Ullage
Enable
Disable
GOOD
BAD
UNCERTAIN
No Servo Board
UNCERTAIN
UNCERTAIN
35 (default)
45
63
30
20
Backlight Screen
brightness
75(default)
100
25
Point
Comma
format numerical 0
Format letter O
DISPLAY_FORMAT_LEVEL_TEMPERAT
URE
DISPLAY_FORMAT_TEST
Display Record
Celcius
Fahrenheit
GOOD ACTUAL
GOOD MANUAL
BAD
UNCERTAIN
No Temperature
Board
7.3.12.1 Introduction
Field Interface Instrument - Safety Integrity Level (FII-SIL) is an optional
FlexConn board. The FII-SIL module provides overfill and underfill
protection functionality certified and suitable for use in Safety
Instrumented Systems at SIL 2 with systematic capability at SIL 3. It is
used with the 954 SmartServo FlexLine tank gauge system.
Errors
7.3.13.1 Safety Function Status
The Safety Function Status define possible reasons for activation of the
safe state for each output. Each is a condition monitored as part of the
safety categories outlined in section 7.3.12.1, above.
Board and function failures are hardware failures which are considered
to impact the integrity of the analog output current level. To assure a
safe state will always be signalled, these failures always result in a
latched burnout current level of 0 mA.
The safety function status error codes, user actions, and the default
latching behaviour and burnout action for each are defined below:
Safety Function This Safety Function selection is available on all three outputs. When
Not Used selected, the output is not functional. For the analog output, the output current
becomes fixed at 21 mA.
Analog Output The analog output is not functional, and the output current is fixed at 0 mA.
Mode Disabled
Analog Output An analog output current level above 20.5 mA is being requested. The actual
Over Range current level stays at the upper limit of 20.5 mA and the SIL function health
status becomes Uncertain.
Analog Output An analog output current level below 3.8 mA is requested. The actual current
Under Range level stays at the lower limit of 3.8 mA and the SIL function health status
becomes Uncertain.
Analog Output The Upper Range Value and Lower Range Value are equal, preventing a
Zero Span product level percent of range from being calculated. The output current stays
at the upper limit of 20.5 mA and the SIL function health status becomes
Uncertain.
Analog Output The analog output has not been calibrated. The output current which
Not Calibrated corresponds to the product level may not be accurate.
Commissioning
The FII-SIL module does not require the configuration of any entities for
commissioning. By default, the board and all three output functions are already in
the commissioned state. However, all outputs are in safe state, so configuration is
necessary for the FII-SIL module to be useful.
Proof Testing
The FII-SIL module requires periodic user operations to maintain its SIL
certification, which are described in the Safety Manual. One of these
activities is to perform proof tests on each of the outputs to assure the
safe state functionality will perform properly when necessary. A proof
test activates the safe state on each of the contacts and analog output
by simulating an overfill or underfill condition and exercising the
detection logic. A maximum interval can be configured for each output
to warn the user if the time from the last proof test (or from the factory
default state) has exceeded the interval time. A configurable timeout
assures that proof tests will not remain active.
Entities
The following entities are mostly specific to the FII-SIL module and are
readable or configurable using the Engauge and SmartView tools.
Contact 1
Status Category
GOOD, ACTUAL VALUE
GOOD, STORED VALUE
UNCERTAIN,
INSTRUMENT
BAD, HARDWARE
FAILURE
BAD, OPERATIONAL
FAILURE
Status Code
See section 7.3.13.1
“Safety Function Status” for
definitions.
[Contact 1 < Not Used > < Overfill > The condition of product level
safety relative to the threshold which
function] < Overfill > will determine the activation of
a contact 1 safe state, as an
< Underfill >
underfill or overfill condition.
[Contact 1 < 0 – 3.402823 × 1038 > <0> The product level limit value
threshold] for determining an overfill or
(meters)
underfill condition for contact
1.
[Contact 1 < 0 – 3.402823 × 1038 > < 0.010 > A value relative to the threshold
hysteresis] that will determine the point at
(meters)
which deactivation of a contact 1
safe state occurs after activation
by an overfill or underfill
condition.
[Contact 1 < 0 – 3.402823 × 1038 > <0> The number of contact 1 safe
safety state activations that have
shutdown occurred since commissioning.
counter]
(RO)
[Contact 1 Safety Function Status NO ERROR The safety function status code
safety Code identifies the reason for the last
shutdown time a contact 1 safe state
reason] activation occurred.
(RO)
[Contact 1 proof < 1 – 3650 > < 1825 > The maximum time interval
test interval] permitted between contact 1
(days)
proof tests. If exceed and when
a contact 1 safe state is not
active, the contact 1 safety
function status will change to W
to signal a warning that a proof
test is overdue. The status code
will remain as NO ERROR.
[Contact 1 proof < Auto timeout off > < 5 minutes > If not < Auto timeout off >, the
test timeout] maximum time duration a
< 5 minutes > contact 1 proof test will remain
active. If exceeded the proof
< 10 minutes >
test will automatically stop.
< 20 minutes >
[Contact 1 proof < 0 – 4,294,967,295 > <0> The elapsed time since the last
test elapsed contact 1 proof test or since
(days)
time] commissioning if no contact 2
output proof test has been
(RO)
executed.
Contact 2
Status Category
GOOD, ACTUAL VALUE
GOOD, STORED VALUE
UNCERTAIN,
INSTRUMENT
BAD, HARDWARE
FAILURE
BAD, OPERATIONAL
FAILURE
Status Code
See section 7.3.13.1
“Safety Function Status”
for definitions.
[Contact 2 < Not Used > < Overfill > The condition of product level
safety function] relative to the threshold which
< Underfill > will determine the activation of
a contact 2 safe state, as an
< Overfill >
underfill or overfill condition.
[Contact 2 < 0 – 3.402823 × 1038 > <0> The product level limit value
threshold] for determining an overfill or
(meters) underfill condition for contact
2.
[Contact 2 < 0 – 3.402823 × 1038 > < 0.010 > A value relative to the
hysteresis] threshold that will determine
(meters) the point at which
deactivation of a contact 2
safe state occurs after
activation by an overfill or
underfill condition.
[Contact 2 < 0 – 3.402823 × 1038 > <0> The number of contact 2 safe
safety shutdown state activations that have
counter] occurred since
commissioning.
(RO)
[Contact 2 Safety Function Status Code NO ERROR The safety function status
safety shutdown code identifying the reason
reason] for the last time a contact 2
safe state activation
(RO) occurred.
[Contact 2 < 0 – 3.402823 × 1038 > <0> The total number of contact 2
switch count] closures, or transitions from
safe state to normal state.
(RO)
[Contact 2 proof < 1 – 3650 > < 1825 > The maximum time interval
test interval] permitted between contact 2
(days) proof tests. If exceed and
when a contact 2 safe state
is not active, the contact 2
safety function status will
change to W to signal a
warning that a proof test is
overdue. The status code
will remain as NO ERROR.
[Contact 2 proof < 0 – 4,294,967,295 > <0> The elapsed time since the
test elapsed last contact 2 proof test or
time] (days) since commissioning if no
contact 2 output proof test
(RO) has been executed.
[Contact 2 proof < Auto timeout off > < 5 minutes > If not < Auto timeout off >,
test timeout] the maximum time duration a
< 5 minutes > contact 2 proof test will
remain active. If exceeded
< 10 minutes >
the proof test will
< 20 minutes > automatically stop.
Analog Output
Status Code
See section 7.3.13.1 “Safety
Function Status” for
definitions.
[Analog output < Disabled > < Disabled > Disabled: the analog output
mode] does not function and
< Enabled > remains at 0 mA current
value.
[Analog output < Not used > < Overfill and The condition of product level
safety function] underfill > relative to the threshold which
< Overfill > will determine the activation of
an analog output safe state, as
< Underfill >
an underfill or overfill condition.
< Overfill and underfill >
Overfill: activation occurs when
the product level is above the
Overfill Threshold.
[Analog output < 0 – 3.402823 × 1038 > <0> The product level limit value
overfill for determining an overfill
threshold] (meters) condition for the analog output.
[Analog output < 0 – 3.402823 × 1038 > <0> The product level limit value
underfill for determining an underfill
threshold] (meters) condition for the analog output.
[Analog output < 0 – 3.402823 × 1038 > < 0.010 > A value relative to the threshold
hysteresis] that will determine the point at
(meters) which deactivation of an analog
output safe state occurs after
activation by an overfill or
underfill condition.
[Analog output < High >, < Low > < High > The burnout action or safe state
burnout action of the analog output for each of
the possible reasons for
activating a safe state.
[Analog output < 21 – 25 > < 21 The safe state current level of
high burnout the analog output for a condition
value] (mA) configured for high burnout.
[Analog output < 0.5 – 3.6 > < 3.6 > The safe state current level of
low burnout the analog output for a condition
value] (mA) configured for low burnout.
[Analog output < 0 – 3.402823 × 1038 > <0> Product level value
upper range corresponding to a 20 mA or
value] (meters) 100% current level.
[Analog output < 0 – 3.402823 × 1038 > <0> Product level value
lower range corresponding to a 4 mA or 0%
value] (meters) current level.
[Analog output < 0 – 3.402823 × 1038 > <0> The number of safe state
safety activations that have occurred
shutdown for the analog output.
counter]
(RO)
[Analog output Safety Function Status NO ERROR The safety function status code
safety Code identifying the reason for the last
shutdown time an analog output safe state
reason] activation occurred.
(RO)
[Analog output < 1 – 3650 > < 1825 > The maximum time interval
proof test permitted between analog
interval] (days) output proof tests. If exceed
and when an analog output safe
state is not active, the analog
output safety function status will
change to W to signal a warning
that a proof test is overdue. The
status code will remain as NO
ERROR.
[Analog output < Auto timeout off > < 5 minutes > If not < Auto timeout off >, the
proof test maximum time duration an
timeout] < 5 minutes > analog output proof test will
remain active. If exceeded the
< 10 minutes >
proof test will automatically stop.
< 20 minutes >
[Analog output < 0 – 4,294,967,295 > <0> The elapsed time since the last
proof test analog output proof test or since
elapsed time] (days) commissioning if no analog
output proof test has been
(RO) executed.
All Outputs
[Safe state < Enabled > Defined in Behavior of a safe state when
latching section 7.3.13.1 the reason for activation no
behavior] < Disabled > “Safety Function longer applies, to either
Status”. deactivate when Disabled, or
to remain active (latch) until
power is cycled when Enabled.
It is important to know that 854 alarms, via B and L records are based
on the displacer level. The 954 SmartServo FlexLine also follows this
principle, so choose the right HART SmartView function and the right
Engauge tab when setting the alarm levels.
This is also important when relays of the FII-DO are configured to switch
on alarms. To prevent high alarm tripping when e.g. a lock test is
issued, one can link a relay to the product level, which will have then a
status “good actual stored” when the displacer leaves the product level
interface.
Note: Make two or three manual dips and compare each reading to
ensure the manual dip value is correct.
Do not perform this procedure with a “S0815316 stabigauge 90 mm” or the “S0815360
cptfe 25 mm” displacer, because this will cause damage to the drum.
Make sure the servo auto test downwards is disabled, else the servo gauge will end
up in a SAT failure and will stop measuring level. Refer to section 8.7
Proceed as follows:
Entity name Entity name Description
(SmartView)
[Calibrate] [Calibrate] The displacer will be raised until it stops against the
(Product level) flange of the level gauge.
Caution
If a 45 mm displacer is used, immediately stop the
Calibrate command as soon as the displacer is above
the ball valve, followed by a freeze command.
Make sure the displacer is positioned above the ball
valve. Close the ball valve.
[Unlock] [Unlock] Unlock the gauge and wait the displacer reaches the top
(Product level) of the ball valve.
Calculate the immersion depth of the displacer at the
product interface (for a 90 mm displacer use 3 mm; for a
45 mm displacer use 12 mm).
[Reference level] [Reference level] Enter the position of the top of the ball valve with respect
(Product level) to the tank zero adding the immersion depth of the
displacer at the product level.
[Accept reference] [Accept reference] By giving this command, the level value entered in entity
(Product level) [Reference level] is accepted as level value and will be
shown on the display after the automatic reset.
[Calibrate] [Calibrate] The displacer will now raise from the ball valve. Let it
(Product level) stop against the flange or give a freeze command.
Open the ball valve.
[Unlock] [Unlock] (Product Unlock the gauge. The displacer will now move down till
level) it reaches the level
Interface measurement
Interface 3 is used as product / water interface measurement (with
interface 2 another interface can be measured). The set point must be
set to such a value that half of the displacer volume is immersed in the
water and the other half of the displacer volume is immersed in the
product. That can be calculated as follows (refer to Figure 7-41 and to
Appendix B for detailed displacer information):
(
Setpoint3 = 0.001* [Displacer weight] - [Displacer volume] ( 1
2
ρ product + 12 ρ water ) ) [ kg ]
where:
Example:
When <No measuring range selected> or <Other measuring range or wire type> is
selected the wire weight needs to be set manually:
7.7.1.2 Unbalance
The unbalance compensation needs a table with the measured
unbalance. This table is automatically generated when performing a
balance test.
Note: Whenever the drum has been (temporarily) removed from the
gauge or the drum is replaced by another one, a new balance test must
be performed to update the unbalance table.
Level compensations
Level compensations directly affect the accuracy of the level
measurement.
When <No measuring range selected> or <Other measuring range or wire type> is
selected the wire temperature coefficient needs to be set manually:
When <No measuring range selected> or <Other measuring range or wire type> is
selected the elasticity coefficient (Young’s modulus) and the wire cross
sectional area need to be set manually:
[Wire cross sectional area] < 3.1416x10-9 [m2] > Wire cross sectional area (0.25 * π * diameter2)
For the tank shell compensation, the following entities should be
set:
[Tank shell ambient temperature < TII-SRV board Select the board temperature, magnet
selection] temperature> temperature, the ambient temperature provided by
a local RTD board or the ambient temperature
distributed by a CIU.
[Tank shell vapour ambient ratio] < 0.5 > Ratio of vapour and ambient temperatures for
calculation of the dry part of the tank shell
temperature. Refer to table 4 for more information
on the settings in a particular situation.
[Tank shell product ambient < 0.875 > Ratio of product and ambient temperatures for
ratio] calculation of the wet part of the tank shell
temperature. Refer to table 4 for more information
on the settings in a particular situation.
The gauge reference height is compensated for both the wet and dry
part of the tank shell. The compensated gauge reference height
[Compensated tank top] is available as a reference for hand
measurements.
Note: For proper reference a hand measurement must use the compensated
gauge reference height and subtract a temperature compensated tape value!
For the hydrostatic deformation compensation, the following
entities should be set:
First, the upper reference movement must be found. Then with linear
regression, a best fit line can be found as compensation. The outcome
of that calculation is used for the [Hydrostatic deformation factor] and
[Hydrostatic deformation minimum innage] values.
where
δh : tank shell deformation [m]
D : tank diameter [m]
ρ : product density [kg/m3]
g : local gravity constant [m/s2]
μ : Poisson’s constant (for steel μ=3.3)
E : modulus of elasticity (for steel E=206.1 x 109)
t : tank shell (ring) thickness [m]
h : distance of the liquid surface with respect to a level
below the liquid surface
a and b are e.g. the distances of the liquid surface with respect to the
top and bottom of the shell segment under investigation.
If the tank shell thickness and internal diameter remains constant over
the total height, a=0 and b equals the innage level.
The above calculation is for a full tank (level 21.945 m). The tank shell
deformation for the same tank, but then with a level of 21 metres is:
The same procedure must be followed for all different levels, with for
instance an interval of 1 meter. Then the following table is obtained:
Example of hydrostatic deformation figures
Level Deformation Level Deformation Level Deformation
[m] [mm] [m] [mm] [m] [mm]
0 0 8 0.54 16 2.64
1 0.01 9 0.69 17 3.08
2 0.03 10 0.88 18 3.57
3 0.07 11 1.09 19 4.17
4 0.13 12 1.32 20 4.71
5 0.20 13 1.59 21 5.36
6 0.29 14 1.90 21.945 6.04
7 0.40 15 2.25
The values in this table are the basis for the graph in Figure 7-43
Calculate a regression line from the level where the tank shell
deviation is approximately 0.5 mm. In this example, the regression line
is calculated from 8 meters level till the maximum level.
Then, the [Hydrostatic deformation factor] becomes: 0.3869 mm/m.
The [Hydrostatic deformation level] is the point where the regression
line crosses the X-axis; in this example at 8.1435 m.
8 OPERATION
With the freeze command, the displacer remains in its position even
when the level reaches the displacer position. Hence, the level cannot
be followed and the high, low, high high and low low level alarms cannot
be generated.
The block command stops the displacer and, depending on how the
block mode (item BM) is set, the displacer will only move up with an
increasing level, or the block is cancelled when the level reaches the
displacer position.
8.4 Unlock
The Unlock command cancels any operational command.
The default setting is on interface 1 (I1). If one of the other two interface
measurements is selected, the gauge will remain on that interface
measurement till the default measurement (I1) is selected.
8.6 Dip mode
When the gauge is in dip mode the displacer will be set at some
distance [Dip height] above interface 1 (product surface). After a certain
time [Dip interval time] a single product measurement is executed. After
the interface has been measured, the displacer will be raised over the
dip height.
The level, shown on the display and transmitted to the host, will be the
dipped level and not the actual displacer position.
For the dip mode, entities [Dip height] and [Dip interval time] must be
set (checked) during commissioning (or at a later stage):
The SAT will not only be executed immediately after tank loading has
apparently stopped, but also at regular configurable intervals.
< SAT status > Shows the status of the SAT (idle, 1st attempt, 2nd attempt, 3rd
attempt, denied, fail, success).
< SAT level last fail > Level at which a SAT last failed.
< SAT last level executed > Level at which the most recent SAT was performed.
< SAT minimum level Lowest level at which a SAT has been performed since NOVRAM
executed > initialization.
< SAT maximum level Highest level at which a SAT has been performed since NOVRAM
executed > initialization
< SAT highest number of Highest number of retries observed during a SAT since NOVRAM
retries > initialization.
< SAT number of executed Total number of SATs performed since NOVRAM initialization.
tests >
< SAT time elapsed since Number of minutes elapsed since the most recent SAT
last SAT > successfully completed.
< SAT RTC last fail > Date and time of the last SAT fail.
Note: for useful information the Real Time Clock (RTC) needs to be
set correctly (refer to section 7.3.4
If the tank top value and the gauge reading differs more than the
specified value, the calibration procedure as described in section 7.6.2
should be repeated.
Make sure the servo auto test downwards is disabled, else the servo gauge will end
up in a SAT failure and will stop measuring level. Refer to section Error! Reference
source not found..
Proceed as follows:
Entity name Entity name Description
(SmartView)
[Calibrate] [Calibrate] The displacer will be raised until it stops against the flange
(Product level) of the level gauge.
Caution
If a 45 mm displacer is used, immediately stop the
Calibrate command as soon as the displacer is above the
ball valve, followed by a freeze command.
Make sure the displacer is positioned above the ball valve.
Close the ball valve.
[Unlock] [Unlock] Unlock the gauge and wait the displacer reaches the top
(Product level) of the ball valve.
[Reference level] [Reference level] Request for the reference level value, which was
(Product level) established during calibration. The level reading from the
gauge should not differ more than ±2 mm (±1/16") with the
value in entity [Reference level].
[Calibrate] [Calibrate] The displacer will now raise from the ball valve. Let it stop
(Product level) against the flange or give a freeze command.
Open the ball valve.
[Unlock] [Unlock] Unlock the gauge. The displacer will now move down till it
(Product level) reaches the level
If the reference level value and the gauge reading differ more than the
specified value, the calibration procedure as described in section 7.6.3
should be repeated.
9 MAINTENANCE
• Check bearings
• Balance test
• Run-down test
• Repeatability test
[Check bearings raise height] Raise height of the displacer before performing the actual test.
Note: This value is automatically set at start-up if a specific
displacer is selected (entity [Displacer type]) but can be manually
adjusted before the command is issued. Make sure the displacer is
raised above the product level.
[Check bearings] Raises the displacer and measures the hysteresis of the system
[Measured bearing status] Contains the last 10 measurements of the bearings with the latest
on top. The entity contains the status (GOOD, UNCERTAIN or
BAD), the measured hysteresis caused by the bearings and the
date of the measurement.
Clean the displacer when the displacer’s weight differs more than 3 g
from the value in entity [Displacer weight] or recalibrate the force
transducer with the test weights (refer to section 9.49.5. For
replacement of the printed circuit boards, motor block or force
transducer (refer to section 9.4). After replacement of force transducer
or motor block the force transducer requires re-calibration (refer to
section 9.5).
The 954 SmartServo FlexLine is an explosion proof instrument with intrinsically safe
output/input circuits. Modification to the instrument may only be carried out by trained
personnel which is authorized by Honeywell Enraf. Failure to adhere to this will
invalidate the approval certificate.
Balance test
The balance test measures the unbalance and quality of the bearings
over one drum rotation over a configurable number of points. The
resulting unbalance data is used for the unbalance compensation for
both level and density when enabled (refer to sections 7.7.1 and 10.2.3
).
The balance test results in several quality indicators that can be viewed
in Engauge and partly on the SmartView.
[Balance test result [Drum unbalance [kg]] The drum unbalance should be within 3
unbalance] (Product level) grams. When the drum unbalance is more,
check for contamination of the drum. If the
unbalance is still more than 3 grams replace
the drum bearings (refer to section 9.1.2).
[Balance test result [Avg meas weight [kg]] Refer to section 9.1.2 when the displacer’s
average weight] (Product level) weight differs more than 3 g from the value in
entity [Displacer weight].
[Balance test result [Max unbal weight [kg]]
maximum weight] (Product level)
[Balance test result [Min unbal weight [kg]]
minimum weight] (Product level)
[Balance test result [Avg meas freq [kg]]
average frequency] (Product level)
[Measured bearing - Refer to section 9.1.1
status]
The result of the balance test can also be viewed graphically by the
diagram viewer in Engauge (Servo Unbalance Diagram).
The red lines are only available after a balance test until the next reset.
After a reset, only the blue line is still available (see Figure 9-2).
Figure 9-3 Example of a less smooth servo unbalance diagram (16 points)
Run-down test
With the run-down test one can estimate the state of the bearings and
the presence of obstructions over a certain range. The command will fill
data arrays containing maximum and minimum measured frequency
over 140 segments. Those segments are equally distributed between
the start and stop position of the test. So, the segment size will be
smaller when the range is smaller (with a minimum of 2 cm). By
decreasing the range, one can zoom in on a certain part of the range.
Figure 9-5 Example of a smooth run-down diagram (segment size ~26 cm)
The joints between each cover and the housing are waterproof IP65.
For this purpose, the covers of the servo, drum compartment and
terminal compartment are fitted with O-rings (refer to Figure 9-7). Use a
metal rod (like a Tommy bar) for opening the covers.
Keep screw threads free from dirt. Grease them lightly with an acid-free grease before
closing the instrument. When closing, turn the covers counter-clockwise until the
thread clicks into place, then turn clockwise.
The drum shaft bushing is kept in position by a circlip. The drum shaft
bushing is provided with an internal thread which facilitates removal
from the magnet cap.
7. Pull out the drum and fix the wire to the drum with a
rubber band.
15. Pull out the drum and fix the wire to the drum with a
rubber band.
Do not grease the carbon PTFE bearings. The drum bearings do not require any
lubricant at all.
Detailed description
The electronic part of the 954 SmartServo FlexLine requires no special
maintenance.
Never remove the electronic boards when the mains power is connected to
the gauge. It may damage the electronic circuits.
1. Mounting bracket
1. Switch off the mains and remove the cover from the electronic
compartment.
Figure 9-10 Position of CAN-LCD screws, clamping bracket, and FlexConn board connectors
If the motor block needs to be removed, first remove the measuring drum
(refer to section 9.3.1)
8. Gently remove the motor from its shaft and remove the key.
1. Cut the tie-wraps on the bracket carefully for non-I.S. and I.S
(blue) wires.
3. Unscrew and remove the three screws (G,H and I) securing the
mounting bracket, then remove the mounting bracket carefully
without damaging any wires. (refer to Figure 9-5)
Use the following procedure for calibration. It is assumed that the 954
SmartServo FlexLine is fully operational. Calibration of an incompletely
checked and reprogrammed gauge is not advisable.
Switch off the wire protection before calibrating the force transducer:
Remove the displacer from the measuring wire and attach the smallest
test weight of 25 grams.
Do not yet reprogram this value in the gauge. Reprogram all values
after completion of all the four calibration measurements. Repeat this
calibration from for the other 3 test weight combinations:
Remove the test weights from the measuring wire and attach the
displacer. Program the measured frequencies:
10.1 Introduction
Functional description
A special software package for density measurement is available for the
954 SmartServo FlexLine gauge. This optional package offers the
possibility to measure tank density profiles and interface density
profiles.
Notes:
Absolute inaccuracies of less than 5 kg/m3 (0.31 lbs/ft3) for the Tank
Profile density measurement, and
Principle of operation
The 954 can be used for density measurement if the servo level gauge
is equipped with the optional software. In addition to the software a
density displacer with an increased volume (200 cm3) must be used.
10.2 Commissioning
Check the stability of the mounting of the 954. As all position changes of
the 954 perpendicular on the shaft axes will introduce a density
deviation, the horizontal angle should not exceed ± 0.5 °.
Note:
Calibrate the force transducer. This is required for the most accurate
density measurement result. Refer to section 9.5.
Check the displacer weight after the calibration of the force transducer.
Refer to sections 9.1.2 and 9.1.3.
It is recommended to weigh the displacer with the balance test and then
check the average unbalanced weight.
Note: The measured displacer weight should not differ more than 0.1
grams from the engraved displacer weight (0.1 gram measuring error by
the displacer weight results in a density error of 0.5 kg/m3).
If it is more than 0.1 grams, re-calibrate the force transducer and/or
check the drum unbalance.
[Tank profile start Refer to Figure 10-1. The distance from the liquid surface till the
distance] middle point of the highest density measuring point. For a good
density measuring result, the value must be at least 0.3 m (1 ft).
[Default tank profile stop Refer to Figure 10-1. The middle point of the lowest density
level] measuring point. For a good density measuring result, the value
must be at least 0.2 m (8") above the motor limit switch low.
[Density scan direction] Determines the direction in which a tank profile (or interface profile)
is measured.
Scan direction down: from product surface downwards
Scan direction up: from bottom upwards
Note: When also water bottom is measured first via the water dip
command, it is advised to set the scan direction upwards. Then the
combined dip command directs the displacer downwards for water
measurement, and on the way back, density is measured.
[Number of tank profile The number of measurement points for one density measurement
drum balance points] equally distributed over one drum rotation.
[Tank profile method] Determines the measurement method:
• Multi over drum: measures at multiple points of one drum
rotation to get an accurate density measurement. This
method is the most accurate.
• One drum position: measures only at one drum position.
For an accurate density measurement, the unbalance
compensation must be enabled. This requires a valid
unbalance table (refer to section 9.1.3).
[Reset board] Reset the TII-SRV to activate the settings.
[Interface profile start Refer to Figure 10-1. An interface profile density start level
level] measurement can be performed at any location in the tank.
[Interface profile start level] specifies the highest interface level (so
that is independent of the density scan direction).
[Interface profile stop Refer to Error! Reference source not found. An interface profile
level] density start level measurement can be performed at any location in
the tank. [Interface profile stop level] specifies the lowest interface
level (so that is independent of the density scan direction).
[Density scan direction] Determines the direction in which an interface profile (or tank
profile) is measured.
Scan direction down: from [Interface profile start level]
downwards
Scan direction up: from [Interface profile stop level] upwards
Corrections
Entity [Air density] contains the ambient air density and is used to
present the measured observed density as density in vacuum. If the
density value is required as density in air, then entity [Air density] must
be set to 0.
10.3 Operation
Manual input
For the tank profile measurement, the default density stop distance can
be changed by entity [Tank profile stop level]. After a power down, or
reset of the level gauge, the manual input data is lost.
[Tank profile stop level] If the level value for this entity is higher than [Default tank profile
stop level], this value is used as stop level instead.
Maintenance
With the density option it is recommended to check (once or twice a
year) the level gauge regularly by means of a balance test (refer to
section 9.1.3).
Trouble shooting
Besides the primary value status code, data items from the density
measurement contain one or two status bytes, which also gives
valuable information. These bytes are readable ASCII characters.
However, most of them are bit coded. Appendix C contains an ASCII
table for conversion of the status bits into the actual status.
Bit 7 is always a ‘0’ and bit 6 is always a ‘1’ to avoid ‘control’ characters.
Bit Description
0 general fail / default setting
1 measurement not completed
2 0 = Tank Profile, 1 = Interface Profile
3 no measuring point or measuring point out of range
4 level / trajectory exceeds motor limit level
5 0
6 1
7 0
11 TROUBLE SHOOTING
The primary value status shows the actual status. Additionally, each
function has a [Status history uncertain] and [Status history bad] list
that contains the last 10 warnings and errors that have occurred since
the last reset.
Warnings
Numbers in the range 6272-6335 are warning codes. Warnings will set
the status of the Primary value to UNCERTAIN.
Status code Description Remarks
(SmartView) (Engauge)
6273 No valid product level for E.g. because the displacer is not
compensation measuring product level. Please check
the Primary value of the Product level.
6274 No valid temperature for tank shell One of the temperatures needed for
compensation the tank shell compensation is not
available (refer to section 7.7.2.3).
Please check the vapour and product
temperatures on the FCI-HRT or
FII-RTD.
6275 Balance test number of valid test The unbalance table has too few valid
points too low entries. Can appear when the
unbalance compensation for set point
or density is enabled. Perform a
balance test to provide a new table
(refer to sections 7.7.1 and 9.3.1).
6276 Balance test number of valid test The unbalance table has too many
points too high valid entries. Can appear when the
unbalance compensation for set point
or density is enabled. Perform a
balance test to provide a new table.
(refer to sections 7.7.1 and 9.3.1)
6277 No valid vapour temp. for wire Please check the vapour temperature
temp. compensation on the FCI-HRT.
6278 No valid magnet temp. for magnet Please check the magnet temperature
temp. compensation status (Board Specific).
6279 No valid product level for E.g. because the displacer is not
hydrostatic deformation comp. measuring product level. Please check
the Primary value of the Product level.
6280 No valid displacer temp. for Please check the product temperature
volume compensation on the FCI-HRT.
6283 No valid product level or magnet Please check the magnet temperature
temp. for drum temp. status (Board Specific) or the Primary
compensation value of the Product level.
6285 RIC configuration parameters not
commissioned
6286 Product level below RIC minimum
level
6287 Error getting HART dynamic RIC warning
variables entity device address 11
6288 Error getting HART dynamic RIC warning
variables entity device address 12
6289 Error getting HART dynamic RIC warning
variables entity device address 13
6290 Wrong HART units device address RIC warning
11
6291 Wrong HART units device address RIC warning
12
Errors
Codes in the range 6130-6271 are error codes. Errors will set the
status of the Primary value to BAD.
Status code Description Remarks
(SmartView) (Engauge)
6130 Frequencies F0..F3 not Commissioning error (refer to section
commissioned 7.4).
6131 Drum circumference not Commissioning error (refer to section
commissioned 7.4).
6132 Motor limits high or low not Commissioning error (refer to section
commissioned 7.4).
6133 Tank top level not commissioned Commissioning error (refer to section
7.4).
6134 Reference level not Commissioning error (refer to section
commissioned 7.4).
6144 Frequency sensor failed to start Hardware error of the frequency sensor.
up
6146 Find positions failed encoder Hardware error of the reference
problem encoder.
6148-6154 Sensor frequencies out of range Calibration of the frequency sensor
failed. Please check [Frequency 0] -
[Frequency 3].
6156 Frequency coefficients out of Calibration of the frequency sensor
range failed.
6158 Find positions failed offset to big The displacer level is unreliable. The
reference encoder needs to be
calibrated in maintenance mode (refer to
section 9.6)
6159 Find positions failed wire tension The reference encoder could not be
error checked because the wire tension is too
low or too high. Please check the wire
and displacer.
6160 Find positions failed no space The motor limits are too close to each
other. Find positions needs 10mm up or
downwards.
Displacer type Part number Displacer area Displacer volume Displacer weight
[m2] [cm3] [kg]
Carbon filled PTFE
ø 25 mm S0815360 0.00049 105 0.223
ø 45 mm S0815343 0.0016 105 0.223
ø 90 mm S0815344 0.0064 105 0.223
ø 110 mm S0815345 0.0095 105 0.223
Density displacer approximately 200; approximately
(stainless steel) exact value is 265; exact value
ø 90 mm S0815350 0.0064 engraved on is engraved on
ø 43 mm S0815355 0.0016 displacer displacer
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, USA, TX 77042