o While some companies are maintaining a cautious approach and continuing to use

the gel seal grid systems with 100% filtration coverage there has been a surge in the

use of heavy duty gasket grid systems using a mixed flow design.

o The traditional gel grid approach, which is usually associated with a pressurized

plenum system or fan filter modules minimizes design change and is therefore a

relatively low risk solution. The cost however is prohibiting due to the extensive air

delivery system (full coverage filters, AHU’s, chilled water, etc.).

o The gasket grid approach to air flow utilizes less filter coverage (25-30%) with a

concentration of filtration in some of the more critical areas. By introducing turbulence

inducing devices down stream of the filter media you can improve the classification

by mixing the air to create a “Turbulent Flow”.

o The ceiling should be pinhole airtight seal around the filters. Sealants are used to

seal HEPA filters into ceiling grids. Plastic, silicone, and gel sealant are commonly

used.

5) Vacuum Systems (House Keeping)

o A comprehensive clean room design shall include a vacuum system for routine house

keeping. Sealed convenience receptacles for hose attachments can be placed on the

raised floor walls to achieve full accessibility and coverage. PVC piping is used to

direct particulate to the vacuum collection system. Canister, motor and filter can be

located in a less sensitive area outside the clean rooms to prevent contamination.

6) Procedural Considerations (Air Showers, Gowning etc.)

It is important to adapt a proper procedure for personnel entering and exiting from the clean

room.