Professional Documents
Culture Documents
E-Band Trouble Shooting Guide v.07C PDF
E-Band Trouble Shooting Guide v.07C PDF
E-Band Trouble Shooting Guide v.07C PDF
1.2 Purpose
Assisting Technicians and approved contacted vendors to properly install, align and
maintain the E-Link 1000 and E-Link 1000 EXR.
1.3 Objective
Adherence to this document is intended to reduce the time and expensive of
installation, and shorten any outages.
1.4 Audience
This document is intended for the use by E-Band certified installation, alignment and
maintenance personnel.
GUI
To install the radio in the Horizontal plane position install the radio with the handle
mounted on the top or bottom of the radio (see Figure 4). Preferred position is the
handle mounts such that the connections are orientated „down”.
O-Ring
Waveguide
Remove the dust cover from the waveguide on the antenna after silicone grease has
been applied to “O Ring” in section 2.4. This will be a small piece of tape that keeps
dust and debris from getting inside the waveguide. (see Figure 11)
Drain Hole
Before pulling cat 5 or fiber cable it is best practice to label the cables. Many times
there are multiple radios being installed at one locations and cable can often times
get mixed up.
Insure when using non penetrating roof mounts that there are the proper amount of
weights to keep the sled from moving in a heavy wind storm. If the mast moves this
will cause the radio to loss signal.
During installation the installer will want to identify as many lobes as possible. In
most cases there will be 2 lobes on each side of the main lobe, align to the highest
lobe or peak RSSI. (see Figure 19 & Figure 20)
Main Lobe
Side Lobes
Figure 19 Lobes
Main Lobe
Side Lobes
Occasionally there are paths that are more difficult to align than others. This is
sometimes caused by not seeing the main lobe, but seeing two side lobes with one
slightly better. If this happens or if you see two almost identical lobes follow this
procedure.
1) Align to the valley between the two lobes
2) On one end of the link, adjust the elevation to the valley between the two side
lobes.
3) Now adjust the azimuth and you should see three lobes like in the figure below.
(see Figure 21)
Main Lobe
Side Lobes
The voltage on the GUI in the RSSI Aid or Detailed Status page is correct and reads
the voltage at the receiver. The BNC port requires a ground reference and if the radio
is not grounded properly it may read incorrectly.
We recommend using T-568A on both sides of the Cat5E/Cat6 cable. It really does
not matter which standard you use, just as long as you use the same at both ends of
the cable.
If the pinouts are correct, you either have too long of a Cat5E/Cat6 drop or you have
a faulty connection somewhere in the cable. 1000BaseT and 10/100BaseT both have
a 328ft (100m) limit. Any cable longer than 328ft may have intermittent
communications with the radio. You are required in this case to use a MM Fiber
Tributary radio and an Ethernet Booster on the management port. Please see you E-
Band Representative for more information on the MM Fiber option.
If you still have the issue, double check to make sure the Ethernet Boot is properly
assembled. The cable may not be extending far enough out to make contact with the
internal RJ45 port.
Note: Pasternack recommends that the center pin be soldered not crimped.
This same problem can occur at the N-Connector at the radio. E-Band suggests that
you do the same twist/move test on the N-Connector and replace if the radio resets.
If there is no continuity, double check the polyphaser ports to insure no wires are
shorting out or falling out of the screw terminals.
-48VDC
Site Boss
Rtn
Rtn
Rtn
P -48V Pasternack
-48V
R Rtn Pasternack
-48V
O S -48V Color Code
T U Issue RG58
-48VDC
E R Power
C Polyphaser G Cable
T AAR-107-1105T E
E
D
E-Band Radio
To restart the traffic, go to the Unit Control screen and select “Fault Recovery”
You may also need to reset the traffic manual on the remote radio, by logging into
the remote radio.
When there appears to be no weather related reason for the low RSSI, follow these
steps to determine the source of the problem:
1) First check to see if you have communication to the other radio on the link.
a) If there is no communication, then roll a truck to that link and determine why
the radio is not in service. Most likely reason being a power outage or surge
protector failure.
b) If there is communication, check to see if that unit also has a low RSSI level.
i) If this unit also has a low RSSI, then the most probable cause is an
alignment issue or ice buildup on the radome. Have someone check for
ice buildup or re-align the antenna.
c) If there is communication, but the RSSI is good, then either the transmitter
has failed or the receiver of the unit with the low RSSI has failed.
i) First check the radio with the good RSSI to see if the transmitter is
muted.
ii) If so, un-Mute the transmitter.
iii) If not, check to see if any other alarms are present on this unit. If so, use
that alarm to debug the failure situation.
iv) If no other alarms, then replace the unit with the good RSSI (possible
transmitter failure).
v) If that does not fix the problem, then return the old unit to service and
replace the unit with the low RSSI (possible receiver failure).
To do this, go to the Unit Control screen under the Fault Recovery button, there is a
Tributary/SFP Parameter button.
This needs to be enabled to communicate properly with Fiber radios and disabled to
communicate properly with Copper radios.
To disable the tributary, go to the Unit Control screen and select “Test Mode”
If the BER cleans up after disabling the tributary, then the problem is with the
fiber or copper GigE cable or surge protector. In the case of fiber, clean all fiber
connectors. In the case of copper, check for non-shielded or not properly
connected shielded RJ45connectors at the Polyphaser GigE surge protector or
faulty Cat6 cable. Please see section 5.4 CRC errors reported by switch for
details on how to test the Cat6 cable and its connectors.
4) Local Interference
We have found that the placement of high band vs. low band sometimes causes a
BER issue. If the GigE ports are disabled or the cables not connected and the
BER problem does not go away, swapping the high and low band sides can
resolve the problem.
7) Reflection
Look for possible reflection sources
8) 80GHz Interference
Turn off or mute the transmitter and see if the other end still has power being
received
Try increasing the transmit power to see if the radio is beginning to fail.
One way to detect this fault is to watch the TX Monitor voltage in the Detailed
Status screen. This value should be relatively stable. If this value is changing
often, the radio should be replaced.
Another way to detect this fault is to mute the radio. Go to the Unit Control and
select Mute and submit.
If the other radio does not drop in RSL at all, then the transmitter may have
failed, the radio should be replaced.
1) Identify Ethernet cable from E-Band E-Link 1000 EXR, locate the Polyphaser
107-1105 T. On the protection side of the Polyphaser 107-1105 T trace Ethernet
cable back to switch.
(1) Cable will be routed and terminated into a 10/100 port (Port XX). This
will be the management cable.
(1) Cable will be routed and terminated into a Gig E port on the same layer
2 switch (Port XX).
NOTE: This link must be disconnected from the switches at both ends of the link
before you proceed. Ethernet loop backs can cause packet storms.
2) Log into E-Link 1000 EXR radio with Installer access level (admin or Installer
user id). On the left side menus click on <Unit Control>, on the right side click
on <Test Mode>.
3) Terminate cable that was disconnected from the switch into a GigE port on Gig E
tester. Run the Layer 2 BERT test. If no Bit Errors are present test the other end
of the link. If Bit Errors are present continue to step 4.
4) Unplug cable on the protect side of the Polyphaser 107-1105 T. Using a known
good Ethernet jumper, terminate one end of cable into Gig E tester, and the other
end into the Polyphaser 107-1105 T. Run the Layer 2 BERT test. If no Bit Errors
are present, change Ethernet cable between switch port and Polyphaser 107-1105
T. If Bit Errors are present proceed to step 5
The Cable can be tested by itself, if you have a dual port GigE tester. Connect
just the cable into the two ports to test. Run the same Layer 2 BERT test.
The Polyphaser 107-1105 T can be tested by itself, if you have a dual port GigE
tester. Connect one known good Ethernet cable into the two ports on the
Polyphaser 107-1105 T and the two ports on the GigE Tester. Run the same
Layer 2 BERT test.
Note a shielded RJ45 connector must be used at the Polyphaser 107-1105 T and
non-shielded RJ45 connector at radio.
Remove loopback feature, <Unit Control>, <Test Mode>, <Disable Loopback>.
7) Replace radio. Then terminate all cables at radio, Polyphaser 107-1105 T and
switch. Using Gig E tester repeat process to insure that CRC errors are gone.
NOTE: This link must be disconnected from the switches at both ends of the link
before you proceed. Ethernet loop backs can cause packet storms.
2) Log into E-Link 1000 EXR radio with Installer access level (admin or Installer
user id). On the left side menus click on <Unit Control>, on the right side click
on <Test Mode>.
Under the <test mode option> type in <desired minutes> then click <tributary>.
Suggest that you run for 60 minutes and double check before and after each test.
4) Locate the Fiber Termination box near the radio. Unplug cable on the switch side
of the patch panel in the fiber termination box. Using a known good fiber
jumper, loop back the fiber towards the GigE test set. Run the Layer 2 BERT
test. If no Bit Errors are present, clean the fiber on both ends of the fiber cable
and re-run step 3. If Bit Errors are present proceed to step 5
5) On the radio side of the patch panel in the fiber termination box, unplug tributary
cable. Terminate cable into GigE tester. Run the Layer 2 BERT test. If no Bit
Errors are present, double check the seating of the fiber into the fiber patch panel
and clean the fiber. If Bit Errors are present, proceed to step 6
6) Clean the E-Band supplied fiber jumper at the both ends and Run the Layer 2
BERT test. If no Bit Errors are present, reconnect all fibers and proceed to step 3
to retest. If Bit Errors are present, proceed to step 7
7) Replace the E-band supplied fiber jumper to the radio and Run the Layer 2
BERT test. If no Bit Errors are present, reconnect all fibers and proceed to step 3
to retest. If Bit Errors are present, proceed to step 8