Download as pdf or txt
Download as pdf or txt
You are on page 1of 172

1- Introduction.

2- Grilles & Registers.


3- Linear Bar Grille.
4- Diffusers.
5- Linear Slot Diffuser.
6- Flow Bar Diffuser.
7- Circular & Jet Diffusers.
8- Louvers.
9- Air Filters.
10- Gypsum Access Panel.
Introduction

Cooling Industries Company Was Found In 1978, It Rapidly Became One Of The Leading
Manufactures Of Aluminium Air Outlets (Grilles, Diffusers, Linear Slots ...).

CIC is a Jordan Based Company With Its Office In Amman, Superior Quality & High
Performance Are Some Features Of Our Product, Those Features Helped Us Establish Good
Reputation & Gain Major Market Share In Our Region.

An Expanded Product Range & More Than 30 Years Of Experience Helped Our Grilles &
Diffusers Cover Major Part Of Jordan Market & Many International Markets Such As Yeman,
Qatar, Kuwait, Lebanon, Algeria, Iraq, Negeria and Many Others.

CIC Products are will known for their Clean finish and Perfect Paint, This Is Achieved Through
Our Policy Of In House Painting By Using Supervised 6 Stages Of Treatment, Before Powder
Coating, This Is Done Using The Highest Quality Paints.

The Product Catalogue Contains Detailed Information About Our Full Product Range, Such
As Applications, Drawings, Dimensions Selection Tables Project Reference List, It Will Help
You Select The Most Suitable Product For Your Application.

Cooling Industries Company www.cic-jo.com 1


GRILLES & REGISTERS

Page Contents

2 Air Supply Grille


4 Air Supply Registers
6 Engineering - Selection Data
12 Grilles & Registers - Selection Table
32 Grilles & Registers - Drop Chart
33 Air Return Grilles
34 Air Return Registers
35 Air Return Grilles - Selection Table
36 Egg Crate Style Return Air Grille
41 Access Doors
43 Door Grilles
Air Supply Grille
Horizontal or Vertical Face Vanes
Single Deflection

Model: CI - Air SG - VS
Model: CI - Air SG - HS

CI - Air SG - VS CI - Air SG - HS

Features:

Provide maximum air pattern flexibility in a single


vane, available in horizontal face vanes (used for air
drop correction) or vertical face vanes (used for lateral
air pattern adjustments).

Heavy gauge, extruded aluminium, anodized finish


construction frame, with rigid corner clips fasteners
to assure greater strength and tighter rigid smooth
fitting corners. CI - Air SG - VS

Streamline extruded aluminium vanes of 18mm deep 19mm Centers allow for smooth and uniform air
distribution.
Nylon self lubricating bushing in frame holes to eliminate rattling and vibration.
White the standard color, other colors are available upon request.

2 www.cic-jo.com Cooling Industries Company


Air Supply Grille
Horizontal or Vertical Face Vanes
Double Deflection

Model: CI - Air SG - VD
Model: CI - Air SG - HD

CI - Air SG - VD CI - Air SG - HD

Features:

Provides maximum air pattern flexibility in any


direction by means of two sets of individually
adjustable vanes with either horizontal face vanes
and vertical rear vanes or vertical face vanes and
horizontal rear vanes (horizontal vanes used for
air drop correction and vertical vanes used for
lateral air pattern adjustments).
CI - Air SG - HD

Heavy gauge, extruded aluminium, anodized finish construction frame with rigid corner clips fasteners to
assure greater strength and tighter rigid smooth fitting corners.

Streamline extruded aluminium vanes of 18mm deep 19mm Centers allow for smooth and uniform air
distribution.

Nylon self lubricating bushing in frame holes to eliminate rattling and vibration.
White the standard color, other colors are available upon request.

Cooling Industries Company www.cic-jo.com 3


Air Supply Registers
Horizontal or Vertical Face Vanes
Single Deflection

Model: CI - Air SR - VS

CI - Air SR - VS

CI - Air SR - VS

Features:

Is a combination of single deflection supply grille and opposed blades dampers (the standard volume
controllers) which also provide even distribution of air over the whole face of the grille.

The operating mechanism provides positive setting in any position from fully open to fully close and is not
affected by the air velocity.

Heavy gauge, extruded aluminium, anodized finish construction frame, with rigid corner clips fasteners to
assure greater strength and tighter rigid smooth fitting corners.

Streamline extruded aluminium vanes of 18mm deep 19mm Centers allow for smooth and uniform air
distribution.
Nylon self lubricating bushing in frame holes to eliminate rattling and vibration. White the standard color,
other colors are available upon request.

4 www.cic-jo.com Cooling Industries Company


Air Supply Registers
Horizontal or Vertical Face Vanes
Double Deflection

Model: CI - Air SR - VD

CI - Air SR - VD

CI - Air SR - VD

Features:

Is a combination of double deflection supply grille and opposed blades dampers (the standard
volume controllers) which provide even distribution of air over the whole face of the grille.
The operating mechanism provides positive setting in any position from fully open to fully close and is not
affected by the air velocity.

Heavy gauge, Extruded aluminium, anodized finish construction frame with rigid corner clips fasteners to
assure greater strength and tighter rigid smooth fitting corners.

Streamline extruded aluminium vanes of 18mm deep 19mm Centers allow for smooth and uniform air
distribution.

Nylon self lubricating bushing in frame holes to eliminate rattling and vibration. White the standard color,
other colors are available upon request.

Cooling Industries Company www.cic-jo.com 5


Grille & Registers
Engineering Selection Data

Ordering System:
* Note: When ordering specify as follows:

CI Cooling Industries Company.


Air S - Air R Air Supply - Air Return or Exhaust
G or R Grille or Register
H or V Horizontal Face vanes or Vertical Face vanes
S or D Single Deflection or Double Deflection

Please specify the horizontal dimension first.

Example:

CI-Air SG-HS
Means Cooling Industries Supply Grille with Horizontal Face Vanes Single Deflection.

Definitions:

Satisfactory air distribution and flow is one of the major ultimates of an engineer working in the design of
the air conditioning, heating, of ventilation systems of any project.
To assure a proper air flow rate without undesirable noise or drafts, the engineer has to select the right
supply and return air grilles and registers.
Let us first look into some important terms used throughout.

Damper:

A unit when used in conjunction with a grille, will allow for air flow rate regulation.

Register:

A grille equipped with a damper.

Outlet velocity:

The average velocity on the grille surface as measured by ALNOR with tip number 2220 (Measured in FPM).

Total Pressure: Pt = Ps + Pv
The pressure required to move air through a register and is equal to the sum of static pressure and velocity
pressure (measured in inches of water).
The Pressure drop across a grille increases with the increase of grille outlet velocity. To find static
pressure drop; calculate the core area (nominal width - ¾) x (nominal height - ¾) divide the CFM by area to
determine the core Velocity, and apply it to the following formula.

[ ]
2
Total pressure - Corevelocity
4005

6 www.cic-jo.com Cooling Industries Company


Drop:

The vertical distance between the oulet and the point at which the terminal velocity is measured. Normally
it is designed to be 6 feet above floor level (See fig. Below) The total drop of an air stream is the sum of
drop due to throw and drop due to temperature difference of the air in the room and the air at the grille.
Drop (D) = D (throw) + D (Temperature)

Terminal Velocity:

The point at which the velocity of the air stream drops to 50 FPM.
(50 feet per minute being the maximum velocity that an occupant should be subjected to for long
periods).

Throw:

The horizontal distance between the outlet and the


point at which the velocity of the air stream is equal
to the terminal velocity. (Measured in feet and M)

Definitions:
Long dimension of the grille
ASPECT RATIO =
Short dimension of the grille.

The aspect ratio of a grille has little effect on the distance of throw.
ASHRAE GUIDE dictates that there is less than 14% difference in throw at an aspect ratio of 4.

The figures to the Below show the air patterns for different blade settings, It is noted that the throw and
drop will decrease as the angle of deflection increased.
Other observations can be read from the selection tables on following pages.
These variable deflection settings to satisfy air distribution requirements are obtained by individual
adjustment of the blades.
To obtain long throw and narrow air pattern use 0° to 22° deflection, For shorter throw and wide air
patterns use 45° deflection or more.

Deflection Settings:

Cooling Industries Company www.cic-jo.com 7


Sound level:

Sound level at a grille is directly proportional to the grille outlet velocity.


It also depends on the turbulence of the air stream, blower noise, A/C machinery or high pressure drop
across the damper unit.

In selecting grilles, one is mainly concerned with sound due to outlet velocity and this is why emphasis is
put on proper outlets selection.
The table below gives the outlet velocities recommended for different applications.

Recommended
Application N.C. Level Velometer Velocities

Broadcasting studios Below 25 500 FPM


Residences Below 25 750 FPM
Apartments Below 25 500 to 750 FPM
Mosques or Churches NC 25 - 30 500 to 750 FPM
Hotel Bedrooms NC 25 - 30 500 to 750 FPM
Legitimate Theaters 500 to 1000 FPM
Private offices, acoustically treated 500 to 1000 FPM
Motion Picture Theaters 1000 to 1250 FPM
Private offices, NC 30 - 35 1000 to 1250 FPM
General offices NC 35 - 40 1250 to 1500 FPM
Stores, upper floors NC 40 - 45 1500 FPM
Stores, main floors 1500 FPM
Industrial buildings NC 45 - 50 & Over 1500 to 2000 FPM

8 www.cic-jo.com Cooling Industries Company


Table:

When opposed blades damper is partially closed for balancing purposes, pressure drop and sound are
affected and following correction factors should apply.

Damper closed 1/4 1/3 1/2

Pressure addition 0.05 0.15 0.25

NC addition 5 10 15

Effective Free Area


Ak Factors (Sq. Ft.)
Listed Height Deflection
4 5 6 8 10 12 14 16 18 20 24 0° 22 1/2° 45°
6 5 0.08 0.07 0.058
8 6 0.11 0.10 0.082
10 8 6 0.15 0.14 0.11
12 10 8 0.18 0.17 0.14
14 12 10 8 0.23 0.22 0.18
18 14 12 0.30 0.28 0.22
20 16 14 10 0.32 0.30 0.235
24 20 16 12 10 0.42 0.38 0.31
30 24 20 14 12 0.52 0.48 0.39
38 30 24 18 14 12 0.65 0.59 0.48
Listed Width

40 32 26 20 16 14 0.78 0.75 0.58


44 36 30 24 18 16 14 0.98 0.90 0.75
44 36 26 22 18 16 1.14 1.04 0.85
48 40 30 24 20 18 16 1.25 1.12 0.90
48 38 30 24 22 18 1.49 1.36 1.07
40 32 28 24 20 18 1.61 1.45 1.17
42 36 30 26 24 22 20 2.07 1.86 1.50
46 42 36 30 26 24 22 2.48 2.17 1.82
44 38 34 30 28 24 2.94 2.65 2.10
48 42 36 34 28 3.25 2.84 2.47
44 40 36 30 3.97 3.57 3.27
48 42 36 4.58 4.08 3.68
48 40 5.08 4.58 4.18
42 5.69 5.09 4.59
48 6.08 5.60 4.79

Cooling Industries Company www.cic-jo.com 9


Effective Free Area
A. K. Area In sq. Ft. For supply Grilles and Registers

6x5 6x6 8x6 10x6


Size 8x4 8x5 10x5 12x5
10x4 12x4 16x4
Deflection 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45°
A.K. 0.11 0.10 0.082 0.15 0.14 0.11 0.18 0.17 0.14 0.24 0.22 0.18
12x6 10x8 10x10 12x10
14x5 14x6 12x8 14x8
Size
18x4 16x5 16x6 20x6
22x4 20x5 24x5
Deflection 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45°
A.K. 0.30 0.28 0.22 0.34 0.32 0.25 0.42 0.38 0.31 0.53 0.48 0.39
12x12 20x8 14x12 10x8
18x8 28x6 22x8 14x6
Size
30x5 34x6 30x6 16x5
24x6 44x4 36x5 22x4
Deflection 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45°
A.K. 0.65 0.59 0.48 0.76 0.70 0.56 0.80 0.74 0.59 0.34 0.32 0.25
12x8 14x8 12x12 20x8
16x6 20x6 18x8 28x6
Size
20x5 24x5 24x6 34x5
24x6 32x4 30x5 44x4
Deflection 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45°
A.K. 0.42 0.38 0.31 0.53 0.48 0.39 0.65 0.59 0.48 0.76 0.70 0.36
22x8 14x14 20x12 20x14
30x6 20x10 24x10 24x12
Size
36x5 24x8 30x8 28x10
48x4 34x6 42x6 36x8
Deflection 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45° 0° 221/2° 45°
A.K. 0.80 0.74 0.59 0.94 0.86 0.69 1.16 1.05 0.85 1.40 1.27 1.02
18x18 24x24
28x12 36x16
Size
32x10 48x12
40x8 74x8
Deflection 0° 221/2° 45° 0° 221/2° 45°
A.K. 1.61 1.45 1.17 3.0 2.7 2.15

10 www.cic-jo.com Cooling Industries Company


Balancing Procedure
For Sidewall Supply Outlets.

Fig. 1 Fig. 2

With a 2220A ALNOR Voltmeter jet is positioned as shown in Fig. 1, take readings across the face of the
outlet as indicated by dots in Fig. 2 Use 4 readings for small grilles; 6 for medium size and 8 for large grilles.

Make certain that grille pattern has been set for deflection required as Ak factors are given for 3 Settings.

After determining average jet velocity multiply by Ak factors to determine C.F.M. Volume being delivered.

CFM = V X Ak
V : Velocity fpm
Ak : Effective free Area.

Cooling Industries Company www.cic-jo.com 11


Grilles & Registers
Selection Table

8x8 10x8
(20x20) (25x20)
6x6 8x6 10x6 12x6 14x6
(15x15) (20x15) (25x15) (30x15) (36x15)
8x5 10x5 12x5 14x5 16x5
Air Size (20x13) (25x13) (30x13) (36x13) (41x13)
Quant. Inches 8x4 10x4 12x4 16x4 18x4 20x4

CFM (Cms) (20x10) (25x10) (30x10) (40x10) (46x10) (51x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 350 400 460

Tot. Press 0.008 0.010 0.013

50 Throw Ft. 8 7 6

(M) (2.4) (2.1) (1.8)

N.C <20 <20 <20

Velocity 530 605 680 420 480 540 340 390 435

Tot. Press 0.017 0.023 0.029 0.011 0.014 0.018 0.008 0.010 0.014

75 Throw Ft. 12 10 9 11 9 8 10 8 7

(M) (3.7) (3.0) (2.7) (3.4) (2.7) (2.4) (3.0) (2.4) (2.1)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 705 800 900 560 640 715 450 510 575 370 420 475 306 350 390

Tot. Press 0.032 0.040 0.051 0.019 0.026 0.032 0.013 0.016 0.020 0.009 0.011 0.014 0.006 0.008 0.010

100 Throw Ft. 16 13 12 14 12 10 13 11 9 12 10 9 11 9 8

(M) (4.9) (4.0) (3.7) (4.3) (3.7) (3.0) (4.0) (3.4) (2.7) (3.7) (3.0) (2.7) (3.4) (2.7) (2.4)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

12 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

8x8 10x8
(20x20) (25x20)
6x6 8x6 10x6 12x6 14x6
(15x15) (20x15) (25x15) (30x15) (36x15)
8x5 10x5 12x5 14x5 16x5
Air Size (20x13) (25x13) (30x13) (36x13) (41x13)
Quant. Inches 8x4 10x4 12x4 16x4 18x4 20x4

CFM (Cms) (20x10) (25x10) (30x10) (40x10) (46x10) (51x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 880 1000 1125 700 800 1025 565 640 720 465 530 595 380 430 485 325 370 415

Tot. Press 0.049 0.062 0.079 0.032 0.040 0.065 0.020 0.026 0.033 0.013 0.017 0.022 0.009 0.012 0.019 0.007 0.009 0.011

125 Throw Ft. 20 17 14 18 15 13 16 14 12 15 13 11 13 11 9 12 10 9

(M) (6.1) (5.2) (4.3) (5.5) (4.6) (4.0) (4.9) (4.3) (3.7) (4.6) (4.0) (3.4) (4.0) (3.4) (2.7) (3.7) (3.0) (2.7)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 1060 1210 1355 840 960 1075 680 775 870 555 630 710 455 520 580 390 445 500

Tot. Press 0.070 0.091 0.002 0.044 0.058 0.072 0.029 0.038 0.049 0.019 0.025 0.032 0.013 0.017 0.021 0.010 0.013 0.015

150 Throw Ft. 24 20 17 22 19 16 19 16 14 18 15 13 16 14 12 15 13 11

(M) (7.3) (6.1) (5.2) (6.7) (5.8) (4.9) (5.8) (4.9) (4.3) (5.5) (4.6) (4.0) (4.9) (4.3) (3.7) (4.6) (4.0) (3.4)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 1230 1400 1575 980 1130 1255 790 900 1010 650 740 830 535 610 680 455 520 580

Tot. Press 0.094 0.122 0.155 0.060 0.080 0.099 0.039 0.051 0.063 0.027 0.035 0.043 0.017 0.023 0.029 0.013 0.017 0.021

175 Throw Ft. 28 24 20 25 21 18 23 20 17 20 17 14 19 16 14 17 14 12

(M) (8.5) (7.3) (6.1) (7.6) (6.4) (5.5) (7.0) (6.1) (5.2) (6.1) (5.2) (4.3) (5.8) (4.9) (4.3) (5.2) (4.3) (3.7)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 1410 1600 1800 1220 1390 1560 905 1030 1160 740 840 945 610 659 780 520 580 665

Tot. Press 0.123 0.160 0.202 0.093 0.120 0.152 0.051 0.066 0.084 0.035 0.044 0.056 0.023 0.031 0.038 0.017 0.021 0.028

200 Throw Ft. 32 27 23 31 26 22 26 22 19 23 20 17 21 18 15 20 17 14

(M) (9.8) (8.2) (7.0) (9.4) (7.9) (6.7) (7.9) (6.7) (5.8) (7.0) (6.1) (5.2) (6.4) (5.5) (4.6) (6.1) (5.2) (4.3)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 1580 1800 2000 1265 1440 1620 1020 1160 1300 835 950 1065 685 780 875 585 665 750

Tot. Press 0.156 0.202 0.249 0.100 0.129 0.164 0.065 0.084 0.105 0.044 0.057 0.070 0.29 0.038 0.49 0.021 0.028 0.036

225 Throw Ft. 36 31 26 33 28 24 29 25 21 26 22 19 24 20 17 22 19 16

(M) (11.0) (9.4) (7.9) (10.0) (8.5) (7.3) (8.8) (7.6) (6.4) (7.9) (6.7) (5.8) (7.3) (6.1) (5.2) (6.7) (5.8) (4.9)

N.C <20 <20 <20 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 13


Grilles & Registers
Selection Table

8x8 10x8
(20x20) (25x20)
6x6 8x6 10x6 12x6 14x6
(15x15) (20x15) (25x15) (30x15) (36x15)
8x5 10x5 12x5 14x5 16x5
Air Size (20x13) (25x13) (30x13) (36x13) (41x13)
Quant. Inches 8x4 10x4 12x4 16x4 18x4 20x4
CFM (Cms) (20x10) (25x10) (30x10) (41x10) (46x10) (51x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1760 2000 1400 1580 1820 1125 1270 1460 925 1045 1200 760 865 995 650 735 840

Tot. Press 0.193 0.249 0.122 0.156 0.206 0.079 0.010 0.132 0.054 0.068 0.090 0.037 0.047 0.062 0.027 0.035 0.044

250 Throw Ft. 40 34 36 31 26 32 27 23 29 25 21 26 22 19 25 21 18

(M) (12.2) (10.4) (11.0) (9.4) (7.9) (9.8) (8.2) (7.0) (8.8) (7.6) (6.4) (7.9) (6.7) (5.8) (7.6) (6.4) (5.5)

N.C <30 <30 <25 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1940 1545 1760 1240 1410 1585 1020 1160 1300 835 950 1065 720 820 920

Tot. Press 0.134 0.149 0.193 0.096 0.123 0.156 0.065 0.084 0.105 0.044 0.057 0.070 0.033 0.042 0.053

275 Throw Ft. 44 40 34 35 30 25 32 27 23 29 25 21 27 23 19

(M) (13.4) (12.2) (10.4) (10.7) (9.1) (7.6) (9.8) (8.2) (7.0) (8.8) (7.6) (6.4) (8.2) (7.0) (5.8)

N.C <30 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1685 1900 1360 1550 1740 1110 1265 1410 915 1040 1170 775 880 990

Tot. Press 0.178 0.225 0.115 0.150 0.189 0.076 0.100 0.123 0.053 0.067 0.085 0.038 0.049 0.061

300 Throw Ft. 43 37 39 33 28 35 30 25 32 27 23 29 25 21

(M) (13.1) (11.3) (11.9) (10.0) (8.5) (10.7) (9.1) (7.6) (9.8) (8.2) (7.0) (8.8) (7.6) (6.4)

N.C <30 <30 <25 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1825 1470 1680 1880 1200 1270 1540 990 1130 1265 840 955 1075

Tot. Press 0.207 0.134 0.176 0.223 0.090 0.101 0.148 0.061 0.080 0.100 0.044 0.057 0.076

325 Throw Ft. 47 42 36 30 38 32 27 34 29 24 32 27 23

(M) (14.3) (12.8) (11.0) (9.1) (11.6) (9.8) (8.2) (10.4) (8.8) (7.3) (9.8) (8.2) (7.0)

N.C <30 <30 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

14 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

8x8 10x8
(20x20) (25x20)
6x6 8x6 10x6 12x6 14x6
(15x15) (20x15) (25x15) (30x15) (36x15)
8x5 10x5 12x5 14x5 16x5
Air Size (20x13) (25x13) (30x13) (36x13) (41x13)
Quant. Inches 8x4 10x4 12x4 16x4 18x4 20x4

CFM (Cms) (20x10) (25x10) (30x10) (41x10) (46x10) (51x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1790 1580 1800 2000 1300 1480 1660 1065 1220 1360 950 1030 1160

Tot. Press 0.241 0.156 0.202 0.249 0.105 0.136 0.172 0.070 0.093 0.115 0.51 0.066 0.084

350 Throw Ft. 50 45 38 32 41 35 30 37 31 27 34 29 24

(M) (15.2) (13.7) (11.6) (9.8) (12.5) (10.7) (9.1) (11.3) (9.4) (8.2) (10.4) (8.8) (7.3)

N.C <30 <30 <30 <30 <25 <25 <30 <25 <25 <25 <25 <25 <25

Velocity 1700 1940 1390 1580 1780 1140 1300 1460 970 1105 1240

Tot. Press 0.180 0.234 0.120 0.156 0.197 0.081 0.105 0.132 0.058 0.076 0.096

375 Throw Ft. 48 41 44 37 32 40 34 29 37 31 27

(M) (14.6) (12.5) (13.4) (11.3) (9.8) (12.2) (10.4) (8.8) (11.3) (9.4) (8.2)

N.C <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1810 1480 1685 1900 1215 1380 1555 1035 1180 1320

Tot. Press 0.204 0.136 0.178 0.225 0.092 0.118 0.151 0.067 0.087 0.106

400 Throw Ft. 52 47 40 34 42 36 30 39 33 28

(M) (15.8) (14.3) (12.2) (10.4) (12.8) (11.0) (9.1) (11.9) (10.0) (8.5)

N.C <30 <30 <30 <30 <25 <25 <25 <25 <25 <25

Velocity 1920 1580 1800 2000 1290 1470 1650 1100 1250 1405

Tot. Press 0.225 0.156 0.202 0.249 0.104 0.134 1.170 0.075 0.098 0.121

425 Throw Ft. 55 50 43 36 45 38 32 41 35 30

(M) (16.8) (15.2) (13.1) (11.0) (13.7) (11.6) (9.8) (12.5) (10.7) (9.1)

N.C <30 <30 <30 <30 <30 <30 <30 <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 15


Grilles & Registers
Selection Table

20x4
(51x10)
8x8 10x8
(20x20) (25x20)
6x6 8x6 10x6 12x6 14x6
(15x15) (20x15) (25x15) (30x15) (36x15)
8x5 10x5 12x5 14x5 16x5
Air Size (20x13) (25x13) (30x13) (36x13) (36x13)
Quant. Inches 8x4 10x4 12x4 16x4 18x4 20x4
CFM (Cms) (20x10) (25x10) (30x10) (41x10) (46x10) (51x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1670 1900 1370 1530 1750 1165 1325 1485

Tot. Press 0.176 0.225 0.117 0.146 0.191 0.085 0.109 0.140

450 Throw Ft. 53 45 48 41 35 44 37 32

(M) (16.2) (13.7) (14.6) (12.5) (10.7) (13.4) (11.3) (9.8)

N.C <30 <30 <25 <25 <25 <25 <25 <25

Velocity 1760 2000 1445 1645 1850 1230 1400 1580

Tot. Press 0.195 0.249 0.130 0.169 0.215 0.094 0.122 0.156

475 Throw Ft. 55 47 50 43 36 46 39 33

(M) (16.8) (14.3) (15.7) (13.1) (11.0) (14.0) (11.9) (10.0)

N.C <30 <30 <25 <25 <25 <25 <25 <25

Velocity 1850 1520 1730 1940 1295 1475 1660

Tot. Press 0.215 0.145 0.187 0.234 0.104 0.135 0.175

500 Throw Ft. 58 53 45 38 49 42 35

(M) (17.7) (16.2) (13.7) (11.6) (14.9) (12.8) (10.7)

N.C <30 <30 <30 <30 <25 <25 <30

Velocity 1680 1920 1420 1620 1820

Tot. Press 0.176 0.225 0.114 0.164 0.206

550 Throw Ft. 58 49 53 45 38

(M) (17.7) (14.9) (16.2) (13.7) (11.6)

N.C <30 <30 <25 <30 <30

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

16 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 32x4 14x12 32x5 14x14 26x8 16x16 30x8
(25x25) (30x25) (61x13) (30x30) (81x10) (36x30) (81x13) (36x36) (66x20) (41x41) (76x20)
12x8 14x8 28x4 14x10 34x4 16x10 34x5 16x12 32x6 18x14 32x8
(30x20) (36x20) (71x10) (36x25) (86x10) (41x25) (86x13) (41x30) (81x15) (46x36) (81x20)
16x6 18x6 30x4 18x8 36x4 20x8 18x12 34x6 20x12 48x5
(41x15) (46x15) (76x10) (46x20) (91x10) (51x20) (46x30) (86x15) (51x30) (122x13)
20x5 20x6 24x6 26x6 20x10 36x6 24x10
Air Size (51x13) (51x15) (61x15) (66x15) (51x25) (91x15) (61x25)
Quant. Inches 26x4 22x5 26x5 28x6 24x8 48x4 26x10
CFM (Cms) (66x10) (56x13) (66x13) (71x15) (61x20) (122x10) (66x25)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 325 440 495

Tot. Press 0.009 0.012 0.015

175 Throw Ft. 16 14 12

(M) (4.9) (4.3) (3.7)

N.C <20 <20 <20

Velocity 440 500 560 405 460 520

Tot. Press 0.012 0.015 0.019 0.010 0.013 0.016

200 Throw Ft. 18 15 13 17 14 12

(M) (5.5) (4.6) (4.0) (5.2) (4.3) (3.7)

N.C <20 <20 <20 <20 <20 <20

Velocity 495 565 635 455 520 580 350 400 450

Tot. Press 0.015 0.020 0.025 0.013 0.016 0.021 0.008 0.010 0.013

225 Throw Ft. 20 17 14 19 16 14 17 14 12

(M) (6.1) (5.2) (4.3) (5.8) (4.9) (4.3) (5.2) (4.3) (3.7)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 17


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 32x4 14x12 32x5 14x14 26x8 16x16 30x8
(25x25) (30x25) (61x13) (30x30) (81x10) (36x30) (81x13) (36x36) (66x20) (41x41) (76x20)
12x8 14x8 28x4 14x10 34x4 16x10 34x5 16x12 32x6 18x14 32x8
(30x20) (36x20) (71x10) (36x25) (86x10) (41x25) (86x13) (41x30) (81x15) (46x36) (81x20)
16x6 18x6 30x4 18x8 36x4 20x8 18x12 34x6 20x12 48x6
(41x15) (46x15) (76x10) (46x20) (91x10) (51x20) (46x30) (86x15) (51x30) (122x13)
20x5 20x6 24x6 26x6 20x10 36x6 24x10
Air Size (51x13) (51x13) (61x15) (66x15) (51x25) (91x15) (61x25)
Quant. Inches 26x4 22x5 26x5 28x6 24x8 48x4 26x10
CFM (Cms) (66x10) (56x13) (66x13) (71x15) (61x20) (122x10) (66x25)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 550 625 705 500 570 640 390 445 500 415

Tot. Press 0.19 0.024 0.032 0.015 0.020 0.026 0.010 0.012 0.015 0.011

250 Throw Ft. 23 20 17 21 18 14 19 16 14 11

(M) (7.0) (6.1) (5.2) (6.4) (5.5) (4.3) (5.8) (4.9) (4.3) (3.4)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 605 690 775 555 360 710 430 490 550 410 460

Tot. Press 0.023 0.030 0.038 0.019 0.025 0.032 0.012 0.015 0.019 0.011 0.013

275 Throw Ft. 25 21 18 24 20 17 20 17 14 16 13

(M) (7.6) (6.4) (5.5) (7.3) (6.1) (5.2) (6.1) (5.2) (4.3) (4.9) (4.0)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 660 760 845 605 690 775 470 535 600 395 450 505

Tot. Press 0.027 0.036 0.045 0.023 0.030 0.038 0.014 0.018 0.022 0.010 0.013 0.015

300 Throw Ft. 27 23 19 26 22 19 22 19 16 21 18 15

(M) (8.2) (7.0) (5.8) (7.9) (6.7) (5.8) (6.7) (5.8) (4.9) (6.4) (5.5) (4.6)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 715 815 915 655 745 840 510 560 600 425 485 545 380 430

Tot. Press 0.032 0.042 0.053 0.027 0.035 0.044 0.016 0.019 0.026 0.011 0.014 0.018 0.009 0.012

325 Throw Ft. 29 25 21 28 24 20 24 20 17 23 20 17 16 14

(M) (8.8) (7.6) (6.4) (8.5) (7.3) (6.1) (7.3) (6.1) (5.2) (7.0) (6.1) (5.2) (4.9) (4.3)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

18 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 32x4 14x12 32x5 14x14 26x8 16x16 30x8
(25x25) (30x25) (61x13) (30x30) (81x10) (36x30) (81x13) (36x36) (66x20) (41x41) (76x20)
12x8 14x8 28x4 14x10 34x4 16x10 34x5 16x12 32x6 18x14 32x8
(30x20) (36x20) (71x10) (36x25) (86x10) (41x25) (86x13) (41x30) (81x15) (46x36) (81x20)
16x6 18x6 30x4 18x8 36x4 20x8 18x12 34x6 20x12 48x6
(41x15) (46x15) (76x10) (46x20) (91x10) (51x20) (46x30) (86x15) (51x30) (122x13)
20x5 20x6 24x6 26x6 20x10 36x6 24x10
Air Size (51x13) (51x13) (61x15) (66x15) (51x25) (91x15) (61x25)
Quant. Inches 26x4 22x5 26x5 28x6 24x8 48x4 26x10
CFM (Cms) (66x10) (56x13) (66x13) (71x15) (61x20) (122x10) (66x25)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 770 875 985 705 800 900 550 625 705 455 520 580 360 410 460

Tot. Press 0.037 0.049 0.061 0.032 0.040 0.051 0.019 0.024 0.032 0.013 0.016 0.021 0.009 0.011 0.013

350 Throw Ft. 32 27 23 30 26 22 26 22 19 24 20 17 21 18 15

(M) (9.8) (8.2) (7.0) (9.1) (7.9) (6.7) (7.9) (6.7) (5.8) (7.3) (6.1) (5.2) (6.4) (5.5) (4.6)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 852 990 1055 755 860 965 585 665 750 490 560 625 385 440 485 420

Tot. Press 0.043 0.055 0.069 0.036 0.047 0.058 0.021 0.028 0.036 0.015 0.019 0.024 0.010 0.012 0.014 0.011

375 Throw Ft. 34 29 25 32 27 23 28 24 20 26 22 19 23 20 17 15

(M) (10.4) (8.8) (7.6) (9.8) (8.2) (7.0) (8.5) (7.3) (6.1) (7.9) (6.7) (5.8) (7.0) (6.1) (5.2) (4.6)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 880 1000 1125 805 915 1030 625 710 800 525 600 670 410 465 525 350 440 450

Tot. Press 0.049 0.062 0.080 0.41 0.053 0.066 0.024 0.032 0.040 0.019 0.022 0.028 0.011 0.013 0.017 0.008 0.010 0.013

400 Throw Ft. 36 31 26 34 29 25 30 26 22 28 24 20 24 20 17 23 20 17

(M) (11.0) (9.4) (7.9) (10.4) (8.8) (7.6) (9.1) (7.9) (6.7) (8.5) (7.3) (6.1) (7.3) (6.1) (5.2) (7.0) (6.1) (5.2)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 935 1065 1200 855 970 1095 665 760 850 555 630 710 440 500 565 375 425 480

Tot. Press 0.055 0.071 0.090 0.046 0.059 0.074 0.028 0.036 0.046 0.019 0.025 0.032 0.012 0.015 0.020 0.009 0.011 0.014

425 Throw Ft. 38 32 27 36 31 26 32 27 23 29 25 21 26 22 19 24 20 17

(M) (11.6) (9.8) (8.2) (11.0) (9.4) (7.9) (9.8) (8.2) (7.0) (8.8) (7.6) (6.4) (7.4) (6.7) (5.8) (7.3) (6.1) (5.2)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 19


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 32x4 14x12 32x5 14x14 26x8 16x16 30x8
(25x25) (30x25) (61x13) (30x30) (81x10) (36x30) (81x15) (36x36) (66x20) (41x41) (76x20)
12x8 14x8 28x4 14x10 34x4 16x10 34x5 16x12 32x6 18x14 32x8
(30x20) (36x20) (71x10) (36x25) (86x10) (41x25) (86x13) (41x30) (81x15) (46x36) (81x20)
16x6 18x6 30x4 18x8 36x4 20x8 18x12 34x6 20x12 48x5
(41x15) (46x15) (76x10) (46x20) (91x10) (51x20) (46x30) (86x15) (51x30) (122x13)
20x5 20x6 24x6 26x6 20x10 36x6 24x10
Air Size (51x13) (51x15) (61x15) (66x15) (51x25) (91x15) (61x25)
Quant. Inches 26x4 22x5 26x5 28x6 24x8 48x4 26x10
CFM (Cms) (66x10) (56x13) (66x13) (71x15) (61x20) (122x10) (66x25)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 990 1130 1270 910 1030 1165 705 800 900 590 665 755 465 530 680 395 450 505

Tot. Press 0.061 0.080 0.101 0.052 0.066 0.085 0.032 0.040 0.051 0.021 0.028 0.036 0.013 0.017 0.029 0.010 0.013 0.015

450 Throw Ft. 41 35 30 39 33 28 34 29 25 31 26 22 28 24 20 26 22 19

(M) (12.5) (10.7) (9.1) (11.9) (10.0) (8.5) (10.4) (8.8) (7.6) (9.4) (7.9) (6.7) (8.5) (7.3) (6.1) (7.9) (6.7) (5.8)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 1040 1185 1330 960 1090 1230 740 845 945 640 730 820 490 560 715 415 470 530

Tot. Press 0.067 0.088 0.110 0.058 0.074 0.095 0.035 0.045 0.056 0.026 0.034 0.042 0.015 0.019 0.032 0.011 0.014 0.017

475 Throw Ft. 43 37 31 41 35 30 35 30 25 34 29 25 29 25 21 27 23 19

(M) (13.1) (11.3) (9.4) (12.5) (10.6) (9.1) (10.7) (9.1) (7.6) (10.4) (8.8) (7.6) (8.8) (7.6) (6.4) (8.2) (7.0) (5.8)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 1110 1250 1410 1050 1200 1345 780 890 1000 655 755 840 515 585 750 440 500 560

Tot. Press 0.075 0.098 0.123 0.069 0.090 0.122 0.038 0.050 0.062 0.027 0.036 0.044 0.016 0.021 0.036 0.021 0.015 0.019

500 Throw Ft. 45 38 32 43 37 31 37 32 27 35 30 25 31 26 22 29 25 21

(M) (13.7) (11.6) (9.8) (13.1) (11.3) (9.4) (11.3) (9.8) (8.2) (10.7) (9.1) (7.6) (9.4) (7.9) (6.7) (8.8) (7.6) (6.4)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 1220 1390 1560 1205 1380 1540 860 980 1100 720 820 920 570 650 830 480 550 615

Tot. Press 0.093 0.120 0.152 0.091 0.119 0.148 0.047 0.60 0.075 0.033 0.042 0.053 0.020 0.027 0.043 0.014 0.018 0.023

550 Throw Ft. 52 44 37 50 43 34 41 35 30 38 32 27 34 29 25 31 26 22

(M) (15.8) (13.4) (11.3) (15.2) (13.1) (10.4) (12.5) (10.7) (9.1) (11.6) (9.8) (8.2) (10.2) (8.8) (7.6) (9.4) (7.9) (6.7)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

20 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 26x5 14x12 32x5 14x14 26x8


(25x25) (30x25) (61x13) (30x30) (66x13) (36x30) (81x13) (36x36) (66x20)
10x8 12x8 14x8 28x4 14x10 32x4 16x10 34x5 16x12 32x6
(25x20) (30x20) (36x20) (71x10) (36x25) (81x10) (41x25) (86x13) (41x30) (81x15)
14x6 16x6 18x6 30x4 18x8 34x4 20x8 18x12 36x6
(36x15) (41x15) (46x15) (76x10) (46x20) (86x10) (51x20) (46x30) (91x15)
16x5 20x5 20x6 22x6 36x4 26x6 20x10 48x4
Air Size (41x13) (51x13) (51x15) (56x15) (91x10) (66x15) (51x25) (122x10)
Quant. Inches 20x4 26x4 22x5 24x6 28x6 24x8
CFM (Cms) (51x10) (66x10) (56x13) (61x15) (71x15) (61x20)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1555 1775 1980 1320 1500 1680 1210 1380 1550 990 1130 1270 785 895 1000 630 720 805

Tot. Press 0.151 0.198 0.246 0.108 0.139 0.179 0.092 0.119 0.150 0.061 0.080 0.101 0.039 0.051 0.062 0.025 0.033 0.041

600 Throw Ft. 28 49 42 54 46 39 52 44 37 47 40 34 42 36 30 37 31 27

(M) (17.7) (14.9) (12.8) (16.5) (14.0) (11.9) (15.8) (13.4) (11.3) (14.3) (12.2) (10.4) (12.8) (11.0) (9.1) (11.3) (9.4) (8.2)

N.C <30 <30 <30 <25 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1680 1915 1430 1630 1830 1310 1495 1675 1070 1220 1370 850 965 1085 685 780 880

Tot. Press 0.178 0.231 0.126 0.166 0.210 0.107 0.138 0.177 0.071 0.093 0.117 0.046 0.058 0.073 0.030 0.038 0.049

650 Throw Ft. 63 53 59 50 42 56 48 40 51 43 47 45 38 32 41 35 30

(M) (19.2) (16.2) (18.0) (15.2) (12.8) (17.1) (14.6) (12.2) (15.5) (13.1) (11.3) (13.7) (11.6) (9.8) (12.5) (10.7) (9.1)

N.C <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1810 1540 1760 1970 1410 1610 1800 1150 1310 1470 915 1040 1170 735 835 940

Tot. Press 0.205 0.148 0.195 0.244 0.123 0.162 0.203 0.083 0.107 0.134 0.053 0.067 0.086 0.034 0.044 0.055

700 Throw Ft. 38 63 54 45 60 51 43 55 47 40 48 41 35 44 37 32

(M) (20.7) (19.2) (16.5) (13.7) (18.3) (15.5) (13.1) (16.7) (14.3) (12.2) (14.6) (12.5) (10.7) (13.4) (11.3) (9.8)

N.C <30 <30 <30 <30 <30 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1940 1650 1880 1510 1720 1930 1235 1405 1580 980 1120 1235 790 900 1010

Tot. Press 0.237 0.172 0.222 0.142 0.185 0.234 0.095 0.122 0.156 0.060 0.078 0.099 0.039 0.051 0.063

750 Throw Ft. 73 68 58 65 55 47 59 50 42 52 44 37 47 40 34

(M) (22.2) (20.7) (17.7) (19.8) (16.7) (14.3) (18.0) (15.2) (12.8) (15.8) (13.4) (11.3) (14.3) (12.2) (10.4)

N.C <30 <30 <30 <30 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 21


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 26x5 14x12 32x5 14x14 26x8


(25x25) (30x25) (61x13) (30x30) (66x13) (36x30) (81x13) (36x36) (66x20)
10x8 12x8 14x8 28x4 14x10 32x4 16x10 34x5 16x12 32x6
(25x20) (30x20) (36x20) (71x10) (36x25) (81x10) (41x25) (86x13) (41x30) (81x15)
14x6 16x6 18x6 30x4 18x8 34x4 20x8 18x12 36x6
(36x15) (41x15) (46x15) (76x10) (46x20) (86x10) (51x20) (46x30) (91x15)
16x5 20x5 20x6 22x6 36x4 26x6 20x10 48x4
Air Size (41x13) (51x13) (51x15) (56x15) (91x10) (66x15) (51x25) (122x10)
Quant. Inches 20x4 26x4 22x5 24x6 28x6 24x8
CFM (Cms) (51x10) (66x10) (56x13) (61x15) (71x15) (61x20)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1760 2000 1610 1830 1320 1500 1685 1045 1190 1340 840 960 1075

Tot. Press 0.195 0.250 0.162 0.210 0.108 0.139 0.179 0.068 0.089 0.112 0.044 0.058 0.072

800 Throw Ft. 72 61 69 29 63 54 45 55 47 40 50 42 36

(M) (21.9) (18.6) (21.1) (18.0) (19.2) (16.5) (13.7) (16.8) (14.3) (12.2) (15.2) (12.8) (11.0)

N.C <30 <30 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1980 1810 1485 1690 1900 1175 1340 1500 950 1080 1220

Tot. Press 0.246 0.205 0.136 0.180 0.227 0.086 0.112 0.139 0.057 0.072 0.093

900 Throw Ft. 81 77 71 60 51 57 48 41 56 48 40

(M) (24.7) (23.5) (21.6) (18.3) (15.5) (17.4) (14.6) (12.5) (17.1) (14.6) (12.2)

N.C <30 <30 <30 <30 <30 <25 <25 <25 <25 <25 <25

Velocity 1650 1880 1300 1480 1660 1050 1200 1340

Tot. Press 0.172 0.222 0.105 0.135 0.174 0.069 0.090 0.112

1000 Throw Ft. 78 66 69 59 50 62 53 45

(M) (23.8) (20.1) (21.1) (18.0) (19.2) (18.9) (16.2) (13.7)

N.C <30 <30 <25 <25 <25 <25 <25 <25

Velocity 1815 1435 1635 1835 1155 1320 1480

Tot. Press 0.206 0.127 0.167 0.211 0.083 0.108 0.135

1100 Throw Ft. 86 76 65 56 68 58 49

(M) (26.2) (23.2) (19.8) (17.1) (20.7) (17.7) (14.9)

N.C <30 <30 <30

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

22 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

10x10 12x10 24x5 12x12 26x6 14x12 32x5 14x14 26x8


(25x25) (30x25) (61x13) (30x30) (66x13) (36x30) (81x13) (36x36) (66x20)
10x8 12x8 14x8 28x4 14x10 32x4 16x10 34x5 16x12 32x6
(25x20) (30x20) (36x20) (71x10) (36x25) (81x10) (41x25) (86x13) (41x30) (81x15)
14x6 16x6 18x6 30x4 18x8 34x4 20x8 18x12 34x8
(36x15) (41x15) (46x15) (76x10) (46x20) (86x10) (51x20) (46x30) (86x20)
16x5 20x5 20x6 22x6 36x4 26x6 20x10 36x6
Air Size (41x13) (51x13) (51x15) (56x15) (91x10) (66x15) (51x25) (91x15)
Quant. Inches 20x4 26x4 22x5 24x6 28x6 24x8 48x4
CFM (Cms) (51x15) (66x10) (56x13) (61x15) (71x15) (61x20) (122x10)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1570 1785 2000 1260 1435 1610

Tot. Press 0.154 0.200 0.250 0.100 0.127 0.162

1200 Throw Ft. 83 71 60 74 63 53

(M) (25.3) (21.6) (18.3) (22.6) (19.2) (16.2)

N.C <30 <30 <30 <30 <30 <30

Velocity 1700 1940 1370 1560 1755

Tot. Press 0.181 0.237 0.117 0.152 0.194

1300 Throw Ft. 90 76 81 69 58

(M) (27.4) (23.2) (24.7) (21.1) (17.7)

N.C <30 <30 <30 <30 <30

Velocity 1470 1675 1880

Tot. Press 0.134 0.177 0.222

1400 Throw Ft. 87 74 63

(M) (25.6) (22.6) (19.2)

N.C <30 <30 <30

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 23


Grilles & Registers
Selection Table

16x16 26x10 18x16 30x10 18x18 34x10 20x18 36x10 20x20 34x12 22x20 31x12
(41x41) (66x25) (46x41) (76x25) (46x46) (86x25) (51x46) (91x25) (51x51) (86x30) (86x30) (91x30)
18x14 30x8 20x14 36x8 20x16 22x16 22x18 40x10 24x18
(46x36) (76x20) (51x36) (91x20) (51x41) (56x41) (56x46) (102x25) (61x46)
20x12 32x8 24x12 48x6 24x14 26x14 26x16 28x16
Air Size (51x30) (81x20) (61x30) (122x15) (61x36) (66x36) (66x41) (71x41)
Quant. Inches 24x10 36x15 28x10 32x10 30x10 28x14 32x14
CFM (Cms) (61x25) (122x13) (71x25) (81x25) (76x30) (71x36) (81x36)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 530 605 680 430 490 550 365 415 465 345 395 440

Tot. Press 0.017 0.023 0.029 0.012 0.015 0.019 0.009 0.011 0.013 0.008 0.010 0.012

600 Throw Ft. 34 29 25 31 26 22 23 24 20 28 24 20

(M) (10.4) (8.8) (7.6) (9.4) (7.9) (6.7) (8.56) (7.3) (6.1) (3.5) (7.3) (6.1)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 570 650 730 465 530 595 400 455 510 375 425 480 340 390 435

Tot. Press 0.020 0.26 0.034 0.013 0.017 0.022 0.010 0.013 0.010 0.009 0.011 0.014 0.008 0.010 0.012

650 Throw Ft. 37 31 27 33 28 24 31 26 22 30 26 22 28 24 20

(M) (11.3) (9.4) (8.2) (10.0) (8.5) (7.3) (9.4) (7.9) (6.7) (9.1) (7.9) (6.7) (8.5) (7.3) (6.1)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 615 700 785 500 570 640 430 490 550 405 460 520 365 415 465

Tot. Press 0.023 0.031 0.039 0.015 0.020 0.026 0.012 0.015 0.19 0.010 0.013 0.016 0.009 0.011 0.013

700 Throw Ft. 40 34 29 36 31 26 33 28 24 32 27 23 31 26 22

(M) (12.2) (10.4) (8.8) (11.0) (9.4) (7.9) (10.0) (8.5) (7.3) (9.8) (8.2) (7.0) (9.4) (7.9) (6.7)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 660 750 845 540 615 690 460 525 590 435 495 560 390 445 500 355 405 455

Tot. Press 0.027 0.036 0.045 0.018 0.023 0.030 0.013 0.017 0.021 0.012 0.015 0.019 0.010 0.012 0.015 0.008 0.010 0.013

750 Throw Ft. 43 37 31 39 33 28 36 31 26 35 30 25 33 28 24 31 26 22

(M) (13.1) (11.3) (9.4) (11.9) (10.0) (8.5) (11.0) (9.4) (7.9) (10.7) (9.1) (7.6) (10.0) (8.5) (7.3) (9.4) (7.9) (6.7)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

24 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

16x16 26x10 18x16 30x10 18x18 34x10 20x18 36x10 20x20 34x12 22x20 31x12
(41x41) (66x25) (46x41) (76x25) (46x46) (86x25) (51x46) (91x25) (51x51) (86x30) (86x30) (91x30)
18x14 30x8 20x14 36x8 20x16 22x16 22x18 40x10 24x18
(46x36) (76x20) (51x36) (91x20) (51x41) (56x41) (56x46) (102x25) (61x46)
20x12 32x8 24x12 48x6 24x14 26x14 26x16 28x16
Air Size (51x30) (81x20) (61x30) (122x15) (61x36) (66x36) (66x41) (71x41)
Quant. Inches 24x10 36x15 28x10 32x10 30x10 28x14 32x14

CFM (Cms) (61x25) (122x13) (71x25) (81x25) (76x30) (71x36) (81x36)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 700 795 895 575 655 735 490 560 630 460 525 590 415 475 530 380 435 485

Tot. Press 0.031 0.040 0.051 0.020 0.027 0.034 0.015 0.019 0.025 0.013 0.017 0.021 0.011 0.014 0.017 0.009 0.012 0.014

800 Throw Ft. 45 38 32 41 31 30 38 32 27 37 31 27 35 30 25 33 28 24

(M) (13.7) (11.6) (9.8) (12.5) (10.7) (9.1) (11.6) (9.8) (8.2) (11.2) (9.4) (8.2) (10.7) (9.1) (7.6) (10.0) (8.5) (7.3)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 790 900 1010 650 740 830 550 625 700 520 590 665 445 510 570 430 490 550

Tot. Press 0.039 0.051 0.063 0.026 0.035 0.043 0.019 0.024 0.031 0.016 0.021 0.023 0.012 0.016 0.020 0.012 0.015 0.019

900 Throw Ft. 51 43 37 46 39 33 43 37 31 42 36 30 37 31 27 38 32 27

(M) (15.5) (13.1) (11.3) (14.0) (11.9) (10.0) (13.1) (11.3) (9.4) (12.8) (11.0) (9.1) (11.3) (9.4) (8.2) (11.6) (9.8) (8.2)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 880 1000 1125 720 820 920 615 700 785 575 655 735 520 590 665 475 540 610

Tot. Press 0.049 0.062 0.079 0.033 0.042 0.053 0.023 0.031 0.039 0.020 0.027 0.034 0.016 0.021 0.023 0.014 0.018 0.023

1000 Throw Ft. 57 48 41 51 43 37 48 41 35 46 39 33 44 47 32 42 46 30

(M) (17.4) (14.6) (12.5) (15.5) (13.1) (11.3) (14.6) (12.5) (10.7) (14.0) (11.9) (10.0) (13.4) (11.3) (9.8) (12.8) (11.0) (9.1)

N.C <25 <25 <25 <25 <25 <25 <20 <25 <25 <20 <20 <25 <20 <20 <20 <20 <20 <20

Velocity 970 1105 1240 790 900 1010 675 770 860 635 720 810 570 650 730 525 600 670

Tot. Press 0.059 0.076 0.096 0.039 0.051 0.063 0.029 0.037 0.047 0.025 0.033 0.041 0.020 0.026 0.034 0.017 0.022 0.028

1100 Throw Ft. 63 54 45 56 48 40 57 44 37 51 43 37 48 41 35 46 39 33

(M) (19.2) (16.5) (13.7) (17.1) (14.6) (12.2) (15.8) (13.4) (11.3) (15.5) (13.1) (11.3) (14.6) (12.5) (10.7) (14.0) (11.9) (10.0)

N.C <25 <25 <25 <25 <25 <25 <20 <25 <25 <20 <20 <25 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 25


Grilles & Registers
Selection Table

16x16 26x10 18x16 30x10 18x18 34x10 20x18 36x10 20x20 34x12 22x20 31x12
(41x41) (66x25) (46x41) (76x25) (46x46) (86x25) (51x46) (91x25) (51x51) (86x30) (56x51) (91x30)
18x14 30x8 20x16 36x8 20x16 22x16 22x18 40x10 24x18
(46x36) (76x20) (51x41) (91x20) (51x41) (56x41) (56x46) (102x25) (61x46)
20x12 32x8 24x12 48x6 24x14 26x14 26x16 28x16
Air Size (51x30) (81x20) (61x30) (122x15) (61x36) (66x36) (66x41) (71x41)
Quant. Inches 24x10 48x5 28x10 32x10 30x12 28x14 32x14

CFM (Cms) (61x25) (122x13) (71x25) (81x25) (76x30) (71x36) (81x36)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1055 1200 1350 865 985 1105 735 835 940 690 785 885 625 710 800 570 650 730

Tot. Press 0.069 0.090 0.113 0.046 0.061 0.76 0.034 0.044 0.055 0.030 0.039 0.050 0.025 0.032 0.040 0.020 0.026 0.034

1200 Throw Ft. 68 58 49 62 53 45 57 48 41 55 47 40 53 45 38 50 43 36

(M) (20.7) (17.7) (14.9) (18.9) (16.2) (13.7) (17.4) (14.6) (12.5) (16.7) (14.3) (12.2) (16.2) (13.7) (11.6) (15.2) (13.1) (11.0)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1140 1300 1460 935 1065 1200 800 910 1025 750 855 960 675 770 860 620 705 790

Tot. Press 0.081 0.105 0.132 0.055 0.071 0.090 0.040 0.052 0.066 0.036 0.046 0.058 0.029 0.037 0.047 0.024 0.031 0.039

1300 Throw Ft. 74 63 53 67 57 48 63 53 45 60 51 43 57 48 41 55 47 40

(M) (22.6) (19.2) (16.2) (20.4) (17.4) (14.6) (18.9) (16.2) (13.7) (18.3) (15.5) (13.1) (17.4) (14.6) (12.5) (16.7) (14.3) (12.2)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1230 1400 1580 1005 1145 1285 860 980 1100 810 920 1035 730 830 935 670 760 855

Tot. Press 0.095 0.121 0.156 0.063 0.082 0.103 0.047 0.060 0.075 0.041 0.053 0.067 0.034 0.043 0.055 0.028 0.036 0.046

1400 Throw Ft. 80 68 58 72 61 52 66 56 48 65 55 47 61 52 44 59 50 43

(M) (24.4) (20.7) (17.7) (21.9) (18.6) (15.8) (20.1) (17.1) (14.6) (19.8) (16.7) (14.3) (18.8) (15.8) (13.4) (18.0) (15.2) (13.1)

N.C <25 <25 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

26 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

16x16 26x10 18x16 30x10 18x18 34x10 20x18 36x10 20x20 34x12 22x20 31x12
(41x41) (66x25) (46x41) (76x25) (46x46) (86x25) (51x46) (91x25) (51x51) (86x30) (56x51) (91x30)
18x14 30x8 20x16 36x8 20x16 22x16 22x18 40x10 24x18
(46x36) (76x20) (51x41) (91x20) (51x41) (56x41) (56x46) (102x25) (61x46)
20x12 32x8 24x12 48x6 24x14 26x14 26x16 28x16
Air Size (51x30) (81x20) (61x30) (122x15) (61x36) (66x36) (66x41) (71x41)
Quant. Inches 24x10 48x5 28x10 32x10 30x12 28x14 32x14

CFM (Cms) (61x25) (122x13) (71x25) (81x25) (76x30) (71x36) (81x36)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 1400 1600 1790 1150 1310 1470 980 1120 1255 920 1050 1180 835 950 1070 760 865 970

Tot. Press 0.121 0.160 0.201 0.083 0.107 0.134 0.060 0.078 0.099 0.053 0.069 0.087 0.044 0.057 0.071 0.036 0.047 0.059

1600 Throw Ft. 90 76 65 82 70 59 76 65 56 74 63 53 70 59 50 67 57 48

(M) (27.4) (23.2) (19.8) (25.0) (21.3) (18.0) (23.2) (19.8) (17.1) (22.6) (19.2) (16.2) (21.3) (16.0) (15.2) (20.4) (17.4) (14.6)

N.C <25 <30 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1290 1470 1650 1100 1250 1280 1040 1180 1330 935 1065 1200 855 975 1100

Tot. Press 0.104 0.134 0.172 0.075 0.098 0.102 0.067 0.087 0.110 0.055 0.071 0.090 0.046 0.059 0.075

1800 Throw Ft. 92 78 66 85 72 61 83 71 60 78 66 56 75 74 54

(M) (28.1) (23.8) (20.1) (25.9) (20.9) (18.6) (25.3) (21.6) (16.3) (23.8) (20.1) (17.1) (22.9) (19.5) (16.5)

N.C <25 <25 <30 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1225 1420 1565 1150 1310 1470 1040 1185 1330 955 1085 1220

Tot. Press 0.094 0.125 0.153 0.083 0.107 0.134 0.067 0.088 0.110 0.057 0.073 0.093

2000 Throw Ft. 95 81 68 91 77 65 87 74 63 84 71 60

(M) (28.9) (24.7) (20.7) (27.7) (23.5) (19.8) (25.5) (22.6) (19.2) (25.6) (21.6) (18.3)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25 <25

Velocity 1050 1200 1345

Tot. Press 0.069 0.090 0.112

2200 Throw Ft. 92 78 66

(M) (28.1) (23.8) (20.1)

N.C <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 27


Grilles & Registers
Selection Table

22x22 36x14 24x24 48x12 8x26 40x18 30x30 32x32 34x34


(56x56) (91x36) (61x61) (122x30) (71x66) (102x46) (76x76) (81x81) (86x86)
24x20 40x12 26x22 30x24 32x28 34x30 36x32
(61x51) (102x30) (66x56) (76x61) (81x71) (86x76) (91x81)
28x18 42x12 32x18 32x22 34x26 36x28 42x28
Air Size (71x46) (107x30) (81x46) (81x56) (86x66) (91x71) (107x71)
Quant. Inches 30x16 48x10 36x16 36x20 40x22 42x24 48x24

CFM (Cms) (76x41) (122x25) (91x41) (91x51) (102x56) (107x61) (122x61)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 340 390 435

Tot. Press 0.008 0.010 0.012

800 Throw Ft. 32 27 23

(M) (9.8) (8.2) (7.0)

N.C <20 <20 <20

Velocity 380 485 500

Tot. Press 0.009 0.014 0.015

900 Throw Ft. 36 31 26

(M) (11.0) (9.4) (7.9)

N.C <20 <20 <20

Velocity 425 490 540 355 405 455

Tot. Press 0.011 0.015 0.018 0.008 0.010 0.013

1000 Throw Ft. 40 34 29 36 31 26

(M) (12.2) (10.4) (8.8) (11.0) (9.4) (7.9)

N.C <20 <20 <20 <20 <20 <20

Velocity 465 530 590 390 445 500

Tot. Press 0.013 0.017 0.021 0.010 0.012 0.015

1100 Throw Ft. 44 37 32 40 34 29

(M) (13.4) (11.3) (9.8) (12.2) (10.4) (8.8)

N.C <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

28 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

22x22 36x14 24x24 48x12 8x26 40x18 30x30 32x32 34x34


(56x56) (91x36) (61x61) (122x30) (71x66) (102x46) (76x76) (81x81) (86x86)
24x20 40x12 26x22 30x24 32x28 34x30 36x32
(61x51) (102x30) (66x56) (76x61) (81x71) (86x76) (91x81)
28x18 42x12 32x18 32x22 34x26 36x28 42x28
Air Size (71x46) (107x30) (81x46) (81x56) (86x66) (91x71) (107x71)
Quant. Inches 30x16 48x10 36x16 36x20 40x22 42x24 48x24

CFM (Cms) (76x41) (122x25) (91x41) (91x51) (102x56) (107x61) (122x61)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 510 580 650 425 485 454

Tot. Press 0.016 0.021 0.026 0.011 0.014 0.08

1200 Throw Ft. 48 41 35 43 37 31

(M) (14.6) (12.5) (10.7) (13.1) (11.3) (9.4)

N.C <20 <20 <20 <20 <20 <20

Velocity 550 630 700 460 520 590 355 405 455

Tot. Press 0.019 0.025 0.031 0.013 0.016 0.021 0.008 0.010 0.013
1300
Throw Ft. 52 44 37 47 40 34 41 35 30

(M) (15.8) (13.4) (11.3) (14.3) (12.2) (10.4) (12.5) (10.2) (9.1)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 590 670 755 500 570 640 385 440 495

Tot. Press 0.021 0.028 0.036 0.015 0.020 0.026 0.009 0.012 0.015

1400 Throw Ft. 56 48 40 51 43 37 45 38 32

(M) (17.1) (14.6) (12.2) (15.5) (13.1) (11.3) (13.7) (11.6) (9.8)

N.C <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 680 775 870 570 650 730 440 500 560 370 420 475

Tot. Press 0.029 0.038 0.048 0.020 0.026 0.034 0.021 0.015 0.019 0.009 0.011 0.014

1600 Throw Ft. 64 55 47 58 49 42 51 43 37 47 40 34

(M) (19.8) (16.8) (14.3) (17.7) (14.9) (12.8) (15.5) (13.1) (11.3) (14.3) (12.2) (10.4)

N.C <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 29


Grilles & Registers
Selection Table

22x22 36x14 24x24 48x12 8x26 40x18 30x30 32x32 34x34


(56x56) (91x36) (61x61) (122x30) (71x66) (102x46) (76x76) (81x81) (86x86)
24x20 40x12 26x22 30x24 32x28 34x30 36x32
(61x51) (102x30) (66x56) (76x61) (81x71) (86x76) (91x81)
28x18 42x12 32x18 32x22 34x26 36x28 42x28
Air Size (71x46) (107x30) (81x46) (81x56) (86x66) (91x71) (107x71)
Quant. Inches 30x16 48x10 36x16 36x20 40x22 42x24 48x24

CFM (Cms) (76x41) (122x25) (91x41) (91x51) (102x56) (107x61) (122x61)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 760 865 970 640 730 820 495 656 630 415 475 530 360 410 460

Tot. Press 0.036 0.047 0.059 0.026 0.034 0.042 0.015 0.020 0.025 0.011 0.014 0.017 0.009 0.011 0.013

1800 Throw Ft. 72 61 52 65 55 47 57 48 41 52 44 37 48 41 35

(M) (21.9) (18.6) (15.8) (19.8) (16.8) (14.3) (17.4) (14.6) (12.5) (15.8) (13.4) (11.3) (14.6) (12.5) (10.7)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 850 970 1085 710 810 910 550 625 705 460 525 590 400 445 510 350 400 445

Tot. Press 0.046 0.059 0.073 0.032 0.041 0.052 0.019 0.024 0.032 0.013 0.017 0.021 0.010 0.013 0.016 0.008 0.010 0.012

2000 Throw Ft. 81 69 58 72 61 52 64 54 46 58 49 42 54 46 39 51 43 37

(M) (24.9) (21.1) (17.7) (21.9) (18.6) (15.8) (19.5) (16.5) (14.0) (17.7) (14.9) (12.8) (16.5) (14.0) (11.9) (15.5) (13.1) (11.3)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 930 1060 1190 780 890 1000 600 685 770 505 575 645 440 500 560 385 440 495

Tot. Press 0.054 0.070 0.089 0.038 0.060 0.062 0.022 0.030 0.037 0.015 0.020 0.026 0.012 0.016 0.019 0.009 0.012 0.015

2200 Throw Ft. 88 75 63 80 68 58 70 60 50 64 54 46 59 50 42 56 48 40

(M) (26.8) (22.9) (19.2) (24.4) (20.7) (17.7) (21.3) (18.3) (15.2) (19.5) (16.5) (14.0) (18.0) (15.2) (12.8) (17.1) (14.6) (12.2)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 855 960 1095 660 760 840 550 625 705 480 550 615 420 480 540

Tot. Press 0.046 0.058 0.074 0.027 0.036 0.044 0.019 0.024 0.032 0.014 0.019 0.028 0.011 0.014 0.018

2400 Throw Ft. 87 74 74 76 65 56 70 60 50 65 55 47 61 52 44

(M) (26.5) (22.6) (22.6) (23.2) (19.8) (17.1) (21.3) (18.3) (15.2) (19.8) (16.8) (14.3) (18.6) (15.8) (13.4)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20 <20 <20 <20

Velocity 925 1060 1185 710 810 910 600 680 770 520 590 665 455 520 580

Tot. Press 0.054 0.070 0.088 0.032 0.041 0.052 0.022 0.029 0.037 0.016 0.021 0.023 0.013 0.016 0.021

2600 Throw Ft. 94 80 68 82 70 59 76 65 55 70 60 50 66 56 48

(M) (28.7) (24.4) (20.7) (25.0) (21.3) (18.0) (23.2) (19.8) (16.8) (21.3) (18.3) (15.2) (20.1) (17.1) (14.6)

N.C <25 <25 <25 <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

30 www.cic-jo.com Cooling Industries Company


Grilles & Registers
Selection Table

22x22 36x14 24x24 48x12 8x26 40x18 30x30 32x32 34x34


(56x56) (91x36) (61x61) (122x30) (71x66) (102x46) (76x76) (81x81) (86x86)
24x20 40x12 26x22 30x24 32x28 34x30 36x32
(61x51) (102x30) (66x56) (76x61) (81x71) (86x76) (91x81)
28x18 42x12 32x18 32x22 34x26 36x28 42x28
Air Size (71x46) (107x30) (81x46) (81x56) (86x66) (91x71) (107x71)
Quant. Inches 30x16 48x10 36x16 36x20 40x22 42x24 48x24

CFM (Cms) (76x41) (122x25) (91x41) (91x51) (102x56) (107x61) (122x61)

Deflection
0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45° 0° 22° 45°
Angle

Velocity 765 870 980 645 735 825 560 640 715 490 560 625

Tot. Press 0.037 0.048 0.060 0.026 0.034 0.043 0.019 0.026 0.032 0.015 0.019 0.024

2800 Throw Ft. 88 75 63 82 70 59 75 74 54 71 60 51

(M) (26.8) (22.9) (19.2) (25.0) (21.3) (18.0) (22.9) (19.5) (16.5) (21.6) (18.3) (15.5)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 820 930 1050 690 785 880 600 680 765 525 600 670

Tot. Press 0.042 0.054 0.069 0.030 0.039 0.049 0.022 0.029 0.037 0.017 0.022 0.028

3000 Throw Ft. 95 81 68 87 74 63 81 69 58 76 75 55

(M) (28.9) (24.7) (20.7) (25.6) (22.6) (19.2) (24.7) (21.1) (17.7) (23.2) (19.8) (16.8)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20 <20 <20 <20

Velocity 735 840 940 640 730 820 560 640 715

Tot. Press 0.034 0.044 0.055 0.026 0.034 0.042 0.019 0.026 0.032

3200 Throw Ft. 93 79 67 86 73 62 81 69 59

(M) (28.3) (24.1) (20.4) (26.2) (22.2) (18.9) (24.7) (21.1) (18.0)

N.C <25 <25 <25 <25 <25 <25 <20 <20 <20

Velocity 680 775 870 595 680 760

Tot. Press 0.029 0.038 0.048 0.022 0.029 0.036

3400 Throw Ft. 91 77 65 86 73 62

(M) (27.2) (23.5) (19.8) (26.2) (22.2) (18.9)

N.C <25 <25 <25 <20 <20 <25

Velocity 630 700 805

Tot. Press 0.025 0.31 0.041

3600 Throw Ft. 91 77 65

(M) (27.7) (23.5) (19.8)

N.C <25 <25 <25

*Note: Velocity Measured: FPM Tot. Press. Measured: inches of water

Cooling Industries Company www.cic-jo.com 31


Grilles & Registers
Drop Chart

How to use the drop chart. A 32x8” grille is to discharge 700 CFM with a throw of 40 ft, (Note that
this selection complies with the grille vanes set at 0 degrees).

From selection tables read the velocity of 615 FPM (Page 24).
To determine the drop at 15° DT and 20° DT lay a straight line connecting the values of velocity and throw
to intersect the drop line as shown.

As discussed before under Engineering Data, the drop of an air stream below the discharge Grille depends
on the distance of the throw and the difference between the temperature of the air on grille, and the room
temperature.
The drop chart below should be used in conjunction with the performance tables to calculate the drop of
an air stream for given velocity and throw and for either 15° F or 20° F DT.

Velocity (fpm) Drop Due to Throw Throw


(ft)
2000 6

Drop due to throw = DT = 4.95ft Drop (ft) 8 1


Drop at 15° DT = Ddt = 9.8 ft 1500 at 15° at 20°
Drop 20° DT = Ddt = 13.4 ft 1400 1 10
Total drop at 15° Dt = 9.8 + 4.95 = 14.75 1300
1 2
Total Drop at 20° Dt = 13.4 + 4.95 = 18.35 1200 12
1100 2 3 14
1000
900 16 2
3 4
18
800 4 5 20

700 5 6
3
6 10 30
600 12 4
10
14 40 5
12
500 14
16 50 6
7
400 60

32 www.cic-jo.com Cooling Industries Company


Air Return Grilles
Horizontal or Vertical Face Vanes

Model: CI - AIR RG - H

CI - Air RG - H
CI - Air RG - H

Features:

Supplied with either horizontal or vertical face vane which is spaced on 19 mm centers and set at 45° angle
to restrict vision.
Heavy gauge, extruded aluminum, anodized finish construction frame, with rigid corner clips fasteners to
assure greater strength and tighter rigid smooth fitting corners.

Stream line extruded aluminum vanes which allow for smooth air flow and less noise Nylon self
lubricating bushing in frame holes to eliminate rattling and vibration.
White the standard color, other colors are available upon request.

Cooling Industries Company www.cic-jo.com 33


Air Return Registers
Horizontal or Vertical Face Vanes

Model: CI - Air RR - H
Model: CI - Air RR - V

CI - Air RR - V
CI - Air RR - H

Features:

Combination of return grilles and opposed blades dampers (The standard volume controllers).
The operating mechanism gives positive setting in any position from fully open to fully close and is not
affected by the air velocity.

Heavy gauge, extruded aluminum, anodized finish construction frame, with rigid corner clips fasteners to
assure greater strength and tighter rigid smooth fitting corners.

Stream line extruded aluminum vanes which allow for smooth air flow and less noise Nylon self
lubricating bushing in frame holes to eliminate rattling and vibration.
White is the standard color, other colors are available upon request.

34 www.cic-jo.com Cooling Industries Company


Air Return Grilles
Selection Table

Face Velocity fpm 300 400 500 600 700 800 900 1000
Size
Inch Negative Static Press, inches WG 0.016 0.025 0.040 0.056 0.075 0.100 0.120 0.150
(CM)
Free Area sq. Ft CFM Rating
10x6
0.23 70 90 115 140 160 185 205 230
(25x15)
12x6
0.28 85 110 140 170 195 225 250 280
(30x15)
14x6
0.33 100 130 165 200 230 265 295 330
(36x15)
12x8
0.40 120 160 200 240 280 320 360 400
(30x20)
18x6
0.43 130 170 215 260 300 345 385 430
(46x15)
12x12
0.61 185 245 305 365 425 485 550 610
(30x30)
18x12
0.80 240 320 400 480 560 640 720 800
(46x30)
24x12
1.31 395 525 655 785 915 1045 1180 1310
(61x30)
18x18
1.55 465 640 775 930 1080 1240 1400 1550
(46x46)
30x12
1.64 490 660 820 985 1150 1310 1475 1640
(76x30)
24x18
2.05 615 820 1020 1230 1430 1640 1840 2050
(61x46)
30x18
2.56 770 1020 1280 1540 1790 2050 2300 2560
(76x46)
24x24
2.64 790 1060 1320 1580 1840 2100 2370 2640
(61x61)
36x18
3.08 930 1235 1540 1850 2160 2460 2780 3080
(91x46)
30x24
3.38 1010 1355 1700 2030 2370 2700 3050 3380
(76x61)
36x24
4.07 1220 1630 2030 2440 2850 3250 3670 4070
(91x61)
36x30
5.18 1550 2070 2580 3100 3620 4140 4650 5180
(91x76)
48x24
5.48 1640 2190 2740 3280 3840 4380 4930 5480
(122x61)
48x30
6.93 2080 2780 3470 4160 4850 5540 6260 6930
(122x76)
48x36
8.25 2480 3300 4130 4950 5780 6600 7420 8250
(122x91)

Cooling Industries Company www.cic-jo.com 35


Egg Crate Style Return Air Grille
( ½’’ x ½’’ x ½’’)

Model: CI - Air EG - H

CI - Air EG - H

Features: CI - Air EG - H

• Egg crate return grilles for use in ceiling or sidewall where a variety of bold crisp lines are desired with a
Free area of 90% .

• The aluminium egg crate style core has an opening of ½’’ x ½’’
• Frame is extruded aluminium alloy and are polyester powder coated with a white finish
• The frame has atypical wall thickness of 1/21”and thickness of aluminium grid is 1/32”.
The frame mounting holes are dimpled allowing for a counter - sunk fastener head appearance .

• Standard finish is white painted under electrostatic polyester powder coating system other colors
Available on request the polyester powder of highest quality are used to enhance the appearance
Of the units .

36 www.cic-jo.com Cooling Industries Company


EGG Crate Style Return Air Grille
Performance Data
Core Velocity (FPM) 300 400 500 600 700 800 1000 1200 1400
Nominal
Core Area
Duct Size Velocity Pressure (in. w.g.) 0.066 0.010 0.016 0.022 0.031 0.040 0.062 0.090 0.122
(Sq. Ft.)
(inches)
Negative SP (in. w.g.) 0.016 0.026 0.042 0.059 0.082 0.106 0.165 0.238 0.323

CFM 52 69 86 103 120 138 172 206 241


6x6 0.172
NC 25 28 30 32 33 34 36 38 40
CFM 74 99 124 149 174 198 248 298 347
8x6 0.248
NC 24 27 29 31 32 34 36 38 39
CFM 93 125 156 187 218 250 312 374 437
10x6 0.312
NC 23 26 28 30 32 33 35 37 38
CFM 116 155 194 232 271 310 387 464 542
12x6 0.387
NC 23 26 28 30 31 33 35 37 38
CFM 135 181 226 271 316 361 452 542 633
14x6 0.452
NC 23 26 28 30 31 32 35 36 38
CFM 155 207 259 310 362 414 517 620 724
16x6 0.517
NC 23 25 28 29 31 32 34 36 38
CFM 178 237 296 355 414 474 592 710 829
18x6 0.592
NC 22 25 27 29 31 32 34 36 37
CFM 197 263 329 394 460 526 657 788 920
20x6 0.657
NC 22 25 27 29 30 32 34 36 37
CFM 239 319 298 478 558 638 797 956 1116
24x6 0.797
NC 22 24 27 28 30 31 33 35 37
CFM 281 374 468 562 655 749 936 1123 1310
28x6 0.936
NC 21 24 26 28 30 31 33 35 36
CFM 320 426 533 640 746 853 1066 1279 1492
32x6 1.066
NC 21 24 26 28 29 31 33 35 36
CFM 361 482 603 723 844 964 1205 1446 1687
36x6 1.205
NC 21 24 26 28 29 30 33 34 36
CFM 404 538 673 807 942 1076 1345 1614 1883
40x6 1.345
NC 21 23 26 27 29 30 32 34 36
CFM 487 650 813 975 1137 1300 1625 1950 2275
48x6 1.625
NC 20 23 25 27 29 30 32 34 35
CFM 103 138 172 206 241 275 344 413 482
8x8 0.344
NC 23 26 28 30 31 33 35 37 38
CFM 132 176 220 267 309 353 441 529 617
10x8 0.441
NC 23 26 28 30 31 32 35 36 38
CFM 158 211 264 316 369 422 527 632 738
12x8 0.527
NC 22 25 27 29 31 32 34 36 37
CFM 187 250 312 374 437 499 624 749 874
14x8 0.624
NC 22 25 27 29 30 32 34 36 37
CFM 216 288 360 433 505 577 721 865 1009
16x8 0.721
NC 22 24 27 28 30 31 33 35 37
CFM 245 327 409 491 573 654 818 982 1145
18x8 0.818
NC 21 24 26 28 30 31 33 35 36
CFM 274 366 457 549 640 732 915 1098 2081
20x8 0.915
NC 21 24 26 28 29 31 33 35 36
CFM 330 444 555 665 776 887 1109 1331 1557
24x8 1.109
NC 21 24 26 28 29 30 33 34 36
CFM 391 521 651 781 911 1042 1302 1562 1823
28x8 1.302
NC 21 23 26 27 29 30 32 34 36
CFM 445 594 743 891 1039 1188 1485 1782 2079
32x8 1.485
NC 70 23 25 27 29 30 32 34 35
CFM 504 672 840 1007 1175 1343 1679 2015 2351
36x8 1.679
NC 20 23 25 27 28 30 32 34 35
CFM 562 749 936 1123 1311 1498 1873 2248 2622
40x8 1.873
NC 20 23 25 27 28 29 32 33 35

Cooling Industries Company www.cic-jo.com 37


EGG Crate Style Return Air Grille
Performance Data
Core Velocity (FPM) 300 400 500 600 700 800 1000 1200 1400
Nominal
Core Area
Duct Size Velocity Pressure (in. w.g.) 0.066 0.010 0.016 0.022 0.031 0.040 0.062 0.090 0.122
(Sq. Ft.)
(inches)
Negative SP (in. w.g.) 0.016 0.026 0.042 0.059 0.082 0.106 0.165 0.238 0.323

CFM 675 900 1125 1360 1575 1800 2250 2700 3150
48x8 2.250
NC 19 22 24 26 28 29 31 33 34
CFM 168 224 280 336 392 448 560 672 784
10x10 0.560
NC 22 25 27 29 31 32 34 36 37
CFM 200 267 333 400 467 534 667 800 934
12x10 0.667
NC 22 25 27 29 30 32 34 36 37
CFM 242 323 403 484 565 646 807 968 1130
14x10 0.807
NC 22 24 27 28 30 31 33 35 37
CFM 278 370 643 556 648 740 926 1111 1296
16x10 0.926
NC 21 24 26 28 30 31 33 35 36
CFM 316 422 527 632 438 843 1054 1265 1467
18x10 1.054
NC 21 24 26 28 29 31 33 35 36
CFM 355 474 592 710 829 947 1184 1221 1658
20x10 1.184
NC 21 24 26 28 29 30 33 34 36
CFM 426 568 710 853 995 1137 1421 1705 1989
24x10 1.421
NC 20 23 25 27 29 30 32 34 35
CFM 497 663 829 995 1161 1326 1658 1990 2321
28x10 1.658
NC 20 23 25 27 28 30 32 34 35
CFM 571 762 952 1143 1333 1524 1905 2286 2667
32x10 1.905
NC 20 23 25 27 28 30 32 34 35
CFM 646 861 1076 1292 1507 1722 2153 2584 3014
36x10 2.153
NC 20 23 25 27 28 29 32 33 35
CFM 720 960 1200 1440 1680 1920 2400 2880 3360
40x10 2.400
NC <20 22 24 26 28 29 31 33 34
CFM 865 1154 1442 1731 2019 2308 2885 3462 4039
48x10 2.885
NC <20 22 24 26 27 29 31 32 34
CFM 249 332 414 497 580 663 829 995 1161
12x12 0.829
NC 21 24 26 28 30 31 33 35 36
CFM 294 392 489 587 685 783 979 1175 1371
14x12 0.979
NC 21 24 26 28 29 31 33 35 36
CFM 339 452 565 678 791 904 1130 1356 1582
16x12 1.130
NC 21 24 26 28 29 30 33 34 36
CFM 384 512 640 767 897 1025 1281 1537 1793
18x12 1.280
NC 21 24 26 27 29 30 32 34 36
CFM 430 573 716 859 1002 1146 1432 1718 2005
20x12 1.432
NC 20 23 25 27 29 30 32 34 35
CFM 520 693 866 1039 1213 1386 1733 2080 2426
24x12 1.733
NC 20 23 25 27 28 30 32 34 35
CFM 610 814 1017 1220 1424 1627 2034 2440 2848
28x12 2.034
NC 20 23 25 27 28 29 32 33 35
CFM 697 930 1162 1395 1627 1860 2325 2790 3255
32x12 2.325
NC <20 22 24 26 28 29 31 33 34
CFM 788 1050 1313 1575 1838 2100 2626 3151 3676
36x12 2.626
NC <20 22 24 26 27 29 31 33 34
CFM 878 1171 1464 1757 2050 2342 2928 3514 4088
40x12 2.928
NC <20 22 24 26 27 29 31 32 34
CFM 1056 1408 1760 2112 2464 2816 3520 4224 4928
48x12 3.520
NC <20 21 24 25 27 28 30 32 34
CFM 349 465 581 697 813 930 11620 1394 1627
14x14 1.162
NC 21 24 26 28 29 30 33 34 36
CFM 400 534 667 801 934 1068 1335 1602 1869
16x14 1.335
NC 21 23 26 27 29 30 32 34 36

38 www.cic-jo.com Cooling Industries Company


EGG Crate Style Return Air Grille
Performance Data
Core Velocity (FPM) 300 400 500 600 700 800 1000 1200 1400
Nominal
Core Area
Duct Size Velocity Pressure (in. w.g.) 0.066 0.010 0.016 0.022 0.031 0.040 0.062 0.090 0.122
(Sq. Ft.)
(inches)
Negative SP (in. w.g.) 0.016 0.026 0.042 0.059 0.082 0.106 0.165 0.238 0.323

CFM 452 603 753 904 1055 1206 1507 1808 2110
18x14 1.507
NC 20 23 25 27 29 30 32 34 35
CFM 504 672 839 1007 1175 1343 1679 2015 2351
20x14 1.679
NC 20 23 25 27 28 30 32 34 35
CFM 610 814 1017 1220 1424 1627 2034 2441 2848
24x14 2.034
NC 20 23 25 27 28 29 32 33 35
CFM 717 956 1195 1434 1673 1912 2390 2868 3346
28x14 2.390
NC <20 22 24 26 28 29 31 33 34
CFM 823 1098 1372 1647 1921 2196 2745 3294 3843
32x14 2.745
NC <20 22 24 26 27 29 31 33 34
CFM 930 1240 1550 1860 2170 2480 3100 3720 4340
36x14 3.100
NC <20 22 24 26 27 29 31 32 34
CFM 1036 1382 1727 2073 2418 2764 3455 4146 4837
40x14 3.455
NC <20 21 24 25 27 28 30 32 34
CFM 1246 1662 2077 2493 2908 3324 4155 4986 5817
48x14 4.155
NC <20 21 23 25 27 28 30 32 33
CFM 462 616 769 923 1077 1231 1539 1847 2155
16x16 1.539
NC 20 23 25 27 29 30 32 34 35
CFM 520 693 866 1040 1213 1386 1733 2080 2426
18x16 1.733
NC 20 23 25 27 28 30 32 34 35
CFM 584 779 974 1169 1364 1558 1948 2338 2727
20x16 1.948
NC 20 23 25 27 28 29 32 33 35
CFM 704 938 1173 1408 1624 1877 2346 2815 3284
24x16 2.346
NC <20 22 24 26 28 29 31 33 34
CFM 826 1102 1377 1653 1928 2204 2755 3306 3857
28x16 2.755
NC <20 22 24 26 27 29 31 33 34
CFM 945 1266 1582 1899 2215 2532 3165 3798 4431
32x16 3.165
NC <20 22 24 26 27 29 31 32 34
CFM 1072 1430 1787 2144 2502 2859 3574 4259 5004
36x16 3.574
NC <20 21 24 25 27 28 30 32 34
CFM 1192 1589 1986 2383 2780 3178 3972 4766 5561
40x16 3.972
NC <20 21 23 25 27 28 30 32 33
CFM 1437 1916 2395 2874 3353 3832 4790 5748 6706
48x16 4.790
NC <20 21 23 25 26 28 30 32 33
CFM 591 788 985 1182 1379 1576 1970 2364 2758
18x18 1.970
NC <20 23 25 27 28 29 32 33 35
CFM 591 878 1098 1318 1537 1757 2196 2635 3074
20x18 2.196
NC <20 22 24 26 28 29 31 33 34
CFM 498 1064 1330 1595 1861 2127 2659 3190 3723
24x18 2.659
NC <20 22 24 26 27 29 31 33 34
CFM 936 1248 1560 1873 2185 2497 3121 3745 4369
28x18 3.121
NC <20 22 24 26 27 29 31 32 34
CFM 1075 1434 1792 2150 2509 2867 3584 4301 5018
32x18 3.584
NC <20 21 24 25 27 28 30 32 34
CFM 1214 1619 2028 2428 2833 3238 4047 4856 5666
36x18 4.047
NC <20 21 23 25 27 28 30 32 33
CFM 1350 1800 2250 2700 3150 3600 3500 5400 6300
40x18 4.499
NC <20 21 23 25 26 28 30 32 33
CFM 1627 2170 2712 3255 3797 4340 5425 6510 7595
48x18 5.425
NC <20 21 23 24 25 27 29 31 33
CFM 736 982 1227 1472 1718 1963 2454 2945 3436
20x20 2.454
NC <20 22 24 26 28 29 31 33 34

Cooling Industries Company www.cic-jo.com 39


EGG Crate Style Return Air Grille
Performance Data
Core Velocity (FPM) 300 400 500 600 700 800 1000 1200 1400
Nominal
Core Area
Duct Size Velocity Pressure (in. w.g.) 0.066 0.010 0.016 0.022 0.031 0.040 0.062 0.090 0.122
(Sq. Ft.)
(inches)
Negative SP (in. w.g.) 0.016 0.026 0.042 0.059 0.082 0.106 0.165 0.238 0.323

CFM 891 1188 1485 1783 2078 2377 2971 3565 4159
24x20 2.971
NC <20 22 24 26 27 29 31 32 34
CFM 1046 1395 1743 2092 2441 2790 3487 4181 4882
28x20 3.487
NC <20 21 23 25 27 80 30 32 33
CFM 1201 1602 2002 2402 2803 3203 4004 4805 5605
32x20 4.004
NC <20 21 23 25 27 28 30 32 33
CFM 1353 1804 2255 2706 3157 3608 4510 5412 6314
36x20 4.510
NC <20 21 23 25 26 28 30 32 33
CFM 1508 2011 2513 3016 3519 4022 5027 6032 7038
40x20 5.027
NC <20 21 23 24 26 27 29 31 33
CFM 1818 2424 3030 3616 4242 4848 6060 7272 8484
48x20 6.060
NC <20 20 22 24 26 27 29 31 33
CFM 1078 1438 1797 2157 2516 2876 3595 4314 5033
24x24 3.595
NC <20 21 24 25 27 28 30 32 34
CFM 1266 1688 2109 2531 2953 3375 4219 5063 5907
28x24 4.219
NC <20 21 23 25 27 28 30 32 33
CFM 1450 1933 2416 2899 3383 3866 4833 5800 6766
32x24 4.833
NC <20 21 23 25 26 28 30 32 33
CFM 1637 2183 2728 3274 3820 4365 5457 6548 7640
36x24 5.457
NC <20 21 23 24 26 27 29 31 33
CFM 1824 2432 3040 3649 4257 4865 6081 7297 8513
40x24 6.081
NC <20 20 22 24 26 27 29 31 33
CFM 2199 2932 3665 4398 5131 5864 7330 8796 10.262
48x28 7.330
NC <20 20 22 24 26 27 29 31 33
CFM 1482 1976 2470 2965 3459 3953 4941 5929 6917
28x28 4.940
NC <20 21 23 25 26 28 30 32 33
CFM 1702 2269 2836 3403 3970 4538 5672 6806 7941
32x28 5.672
NC <20 21 23 24 26 27 29 31 33
CFM 1921 2562 3202 3842 4483 5123 6404 7685 8966
36x28 6.404
NC <20 20 22 24 26 27 29 31 33
CFM 2141 2854 3568 4282 4995 5709 7136 8563 9990
40x28 7.136
NC <20 20 22 24 26 27 29 31 32
CFM 2577 3436 4294 5153 6012 6871 8589 10.307 12.052
48x28 8.589
NC <20 <20 21 23 25 27 29 31 32
CFM 1954 2605 3256 3907 4558 5210 6512 7814 9117
32x32 6.512
NC <20 20 22 24 26 27 29 31 32
CFM 2206 2941 3676 4411 5146 5882 7352 8822 10.293
36x32 7.352
NC <20 20 22 24 26 27 29 31 32
CFM 2457 3276 4095 4914 5734 6553 8191 9829 11.467
40x32 8.191
NC <20 <20 22 24 26 27 29 30 31
CFM 2958 3943 4929 5915 6901 7887 9859 11.831 13.803
48x32 9.859
NC <20 <20 22 24 26 27 29 30 31
CFM 2490 3320 4150 4980 5810 6640 8300 9960 11.620
36x36 8.299
NC <20 <20 21 23 25 27 29 31 32
CFM 2770 3694 4918 5541 6464 7388 9235 11.802 12.929
40x36 9.235
NC <20 <20 22 24 26 27 29 30 31
CFM 3339 4452 5565 6678 7791 8904 11.130 13.356 15.582
48x36 11.130
NC <20 <20 22 24 26 27 28 30 31
CFM 3087 4116 5145 6174 7203 8232 10.290 12.348 14.406
40x40 10.290
NC <20 <20 22 24 26 27 29 30 31
CFM 3720 4960 6200 7440 8680 9920 12.400 14.880 17.350
48x40 12.400
NC <20 <20 22 24 26 27 28 30 32
CFM 4479 5672 7464 8957 10.450 11.943 14.929 17.915 20.900
48x48 14.929
NC <20 <20 21 23 25 27 28 30 32

40 www.cic-jo.com Cooling Industries Company


Access Doors
Access door with fixed horizontal blades

Model: CI - Air ACC - D

Features:

The frame and blades are extruded aluminium anodized or powder coated with a white finish.
Other colors available on request. The frame has a typical wall thickness of (1/21)” and is separated from
the blades by an extruded rigid PVC track which becomes an integral part of the frame.

This method of assembly helps to eliminate corrosion and vibration.


All blades are air foil in design, are set in a fixed position at an angle of 35 and are spaced 3/4” on center.
The blade/frame section is secured to an extruded aluminium frame with two hinges and a locking
nut arrangement. This allows the frame/blade assembly to swing away for access to the area behind
as desired. Air filters for use with access doors are available.

As an option to provide for 1” thick air filter, the model is assembled in a two part system: one is the
mounting frame that serves as a retainer for the filter and the other is the core which provides access to
the filter.

Dimensions

Size Horizontal Vertical CFM

in. (mm) in. (mm) Range


10x6 10 (254.0) 6 (152.4) 60-100
10x8 10 (254.0) 8 (203.2) 90-130
12x6 12 (304.8) 6 (152.4) 80-120
12x8 12 (304.8) 8 (203.2) 120-80
12x12 12 (304.8) 12 (304.8) 180-270
18x6 18 (457.2) 6 (152.4) 100-200 CI - Air ACC - D
18x12 18 (457.2) 12 (304.8) 120-180
18x18 18 (457.2) 18 (457.2) 270-400
24x12 24 (609.6) 12 (304.8) 410-620

Dimensions

Size Horizontal Vertical CFM

in. (mm) in. (mm) Range


24x18 24 (609.6) 18 (457.2) 360-540
24x24 24 (609.6) 24 (609.6) 600-1000
30x12 30 (762.0) 12 (304.8) 550-830
30x18 30 (762.0) 18 (457.2) 410-620
30x24 30 (762.0) 24 (609.6) 700-1080
36x18 36 (914.4) 18 (457.2) 850-1280
36x24 36 (914.4) 24 (609.6) 1110-1670
36x30 36 (914.4) 30 (762) 1440-2160
48x24 48 (1219.2) 24 (609.6) 1600-2500

Cooling Industries Company www.cic-jo.com 41


Access Doors
Performance Data

45° Blade Angle


Face Velocity (FPM)
Listed 200 300 400 500 600 700 800 900
Area
Sizes
Factor Static Pressure Drop (in. w.g.)
(inches)
0.003 0.007 0.012 0.019 0.028 0.038 0.049 0.062
Air Capacity (CFM)
10x6 0.143 57 72 86 100
10x8 0.20 80 100 120 140
12x6 0.17 68 85 102 119
12x8 0.25 100 125 150 175 200
12x12 0.37 185 222 259 296
18x6 0.6 104 130 156 182 208
18x12 0.54 108 162 216
18x18 0.83 249 332 415 498
24x12 0.74 370 444 518 592 666
24x18 1.13 339 452 565
24x24 1.52 456 608 760 912 1064
30x12 0.94 470 564 658 752 846
30x18 1.40 280 420 560 700
30x24 1.93 579 772 965 1158
36x18 1.71 855 1026 1197 1368
36x24 2.29 916 1145 1374 1603 1832
36x30 2.88 1440 1728 2016 2304
48x24 3.06 1530 1836 2142 2448 2754

* Note:

Determine CFM by the following equation.


CFM = Area Factor x Face Velocity.

Access Door with 0° blades will have a lower static pressure with the same face velocity.

To calculate the approximate area factor of sizes not shown, use the following formula.
Length {0.375 + (N x 0.3125)}
Area Factor =
144
Where:
Length = Nominal Width - 0.875 - (*number of dividers x 0.625)

Height - 1.5
N=
0.75
* Based upon dividers spaced every 12 inches.

42 www.cic-jo.com Cooling Industries Company


Door Grilles
Horizontal Bars

Model: CI - Air DG - H

CI - Air DG - H

Features:

Absolute privacy , good looks and impact resistance, Suitable for doors,
walls and partitions.
Non-vision transfer grilles produced from heavy gauge inverted V shape,
extruded anodised finish aluminium bars with Vinyl bar spacers to assure
rattle-free performance which also lower the noise and vibration.
Corner clips construction prevents open miters and provides increased
rigidity.

Also can be supplied with auxiliary movable frame can be adjusted for CI - Air DG - H
different thicknesses from 26.5mm to 54.7mm.

Selection Table:

The table on the next page gives the static pressure differential in inches water and the CFM holding
capacity of the door louvers at different anemometer velocities.
Velocities up to 500 FPM are acceptable for applications allowing for a sound level up to 50 NC.

If the selection falls on a size which does not appear in the table, direct interpolation from the table gives
reasonable results.

Cooling Industries Company www.cic-jo.com 43


Door Grilles
Horizontal Bars

Velocity FPM. 100 200 300 400 500 600 700 800
Size
Inches Static Press. Inches W.G 0.008 0.027 0.065 0.092 0.140 0.190 0.250 0.310
(CMS)
Net Area (Ft2) CFM Rating
12x6
0.270 27 54 81 108 135 162 189 216
(30x15)
12x8
0.390 39 78 117 156 195 234 273 312
(30x20)
18x6
0.424 42 84 126 168 210 252 294 336
(46x15)
12x10
0.518 52 104 156 208 260 312 364 416
(30x25)
12x12
0.610 61 122 183 244 305 366 427 488
(30x30)
24x6
0.610 61 122 183 244 305 366 427 488
(61x20)
24x8
0.840 84 168 252 336 420 504 588 672
(61x20)
18x12
0.940 94 188 282 376 470 564 685 752
(46x30)
24x10
1.090 109 218 327 436 545 654 763 872
(61x25)
24x12
1.280 128 256 384 512 640 768 896 1024
(61x30)
30x12
1.640 164 328 492 656 820 984 1148 1812
(76x30)
36x12
1.980 198 396 594 792 990 1188 1386 1584
(91x30)
30x16
2.200 220 440 660 880 1100 1320 1540 1760
(76x41)
36x16
2.72 272 544 816 1088 1360 1632 1908 2176
(91x41)
30x24
3.450 345 690 1035 1380 1725 2070 2415 2760
(76x61)
36x24
4.200 420 840 1260 1680 2100 2520 2940 3380
(91x61)
48x20
4.700 470 940 1410 1880 2350 2820 3290 3760
(122x51)
48x24
5.640 564 1128 1692 2256 2820 3384 3948 4512
(122x61)
36x36
6.400 640 1280 1920 2560 3200 3840 4480 5120
(91x91)
48x36
8.500 850 1700 2550 3400 4250 5100 5950 6800
(122x91)

44 www.cic-jo.com Cooling Industries Company


LINEAR BAR GRILLE

Page Contents

2 Single Deflection Linear Bar Grilles


5 Double Deflection Linear Bar Grilles
8 Accessories
10 Performance Data
20 Floor Grilles & Register
Linear Grilles and Registers
Single Deflection
Linear Bar Grilles

Model: CI-SBG-SD
Model: CI-SBR-SD

CI-SBG-SD CI-SBR-SD

CI-SBG-SD CI-SBR-SD

Features:

The single deflection linear grille is a wall mounted grille, used as an exhaust or return grille in cooling,
heating or air ventilation applications.

The single deflection linear grille is composed of a set of fixed horizontal Straight bars attached to a frame,
both are manufactured from extruded aluminium sections.

White are the standard colors. Other colors are available upon request.

2 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Single Deflection
Linear Bar Grilles

(Standard) Deflection bars 0° Deflection one way 15° Deflection two way 15°

Front bars have one of the following basic designs:


• 0° deflection bars (Standard)
• 15° deflection, one way -15° deflection, two way Front bars are assembled in horizontal straight lines with
a center to center spacing of 16 mm.
Available with easily removable opposed blades damper, attached to the frame by means of (S) clips to
ensure tight attachment and maximum flexibility. The damper is made of extruded aluminium bars and
the damper opening is easily adjusted by means of control lever that is
Driven by screw driver from the front face of the bar grille.

Available types of finishing:


Powder coated (painted to RAL 9016 standard color)

Types of Fixing:
1- Concealed type fixing (wall only) 2- Screw Fixing

Concealed fixing Clips Screw Fixing

Length Width
Standard Sizes: A B
Use any combination of length and width. (mm) (mm)
100
1000 150
To convert into Imperial units use (1 inch = 25 mm) 200
Non standard sizes are available upon request. 2000 250
300

Cooling Industries Company www.cic-jo.com 3


Linear Grilles and Registers
Single Deflection
Linear Bar Grilles Types & Models

Ordering System:

Type Size Finish

RAL : Powder coated finish as per RAL codes.


Anodized : Anodized aluminium finish.

Size: Length A x Width B

CI-SBR-SD: Single deflection linear grille with damper.


CI-SBG-SD: Single deflection linear grille without damper.

4 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Double Deflection
Linear Bar Grilles

Model: CI-SBG-DD
Model: CI-SBR-DD

CI-SBG-DD CI-SBR-DD

CI-SBG-DD CI-SBR-DD

Features:

The double deflection linear grille is a wall mounted supply grille used in cooling heating or air ventilation
Applications.

The double deflection linear grille is composed of a set of fixed horizontal straight bars in the front face and
individual adjustable vertical deflectors on the rear to control air flow pattern, both are manufactured from
extruded Aluminium sections.

Cooling Industries Company www.cic-jo.com 5


Linear Grilles and Registers
Double Deflection
Linear Bar Grilles

(Standard) Deflection bars 0° Deflection one way 15° Deflection two way 15°

Front bars have one of the following basic designs:


• 0° deflection bars (Standard)
• 15° deflection, one way 15° deflection, two way Front bars are assembled in horizontal straight lines with
a center to center spacing of 16 mm.
Available with easily removable opposed blades damper, attached to the frame by means of (S) clips to
ensure tight attachment and maximum flexibility. The damper is made of extruded aluminium bars and
the damper opening is easily adjusted by means of control lever that is
Driven by screw driver from the front face of the bar grille.

Available types of finishing:


Powder coated (painted to RAL 9016 standard color)

Types of Fixing:
1- Concealed type fixing (wall only) 2- Screw Fixing

Concealed fixing Clips Screw Fixing

Length Width
Standard Sizes: A B
Use any combination of length and width. (mm) (mm)
100
1000 150
To convert into Imperial units use (1 inch = 25mm) 200
Non standard sizes are available upon request. 2000 250
300

6 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Double Deflection
Linear Bar Grilles Types & Models

Ordering System:

Type Size Finish

RAL : Powder coated finish as per RAL codes.


Anodized : Anodized aluminium finish.

Size: Length A x Width B

CI-SBR-DD: Double deflection linear grille with damper.


CI-SBG-DD: Double deflection linear grille without damper.

Example: CI-SBG-DD 1000 x 150 Anodized.

Cooling Industries Company www.cic-jo.com 7


Linear Grilles and Registers
Accessories

1- One end linear Grille / Register (D1) 2- Intermediate Linear Grille / Register (D2)
Available in any standard size Available in any standard size

D1 D2

3- Corner pieces (D3, D4, D5)


Available in any combination of B, X, Y &.

D3
B (mm) X (mm) Y (mm) (degree)
100 300 300 45°

150 600 600 90°

200 800 800 135°

250 1000 1000

300 1200 1200

D4
D5

8 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Accessories

4- Curved shape linear grilles

Minimum radius = 1000 mm


Used as supply / Return linear grilles

Cooling Industries Company www.cic-jo.com 9


Linear Grilles and Registers
Performance Data
S.I.Units
Type:
CI-SBG-DD
CI-SBR-DD 0 Degree
Unit Vk Ps. Pt.
(L/Sec.) Per 1000 mm Th. (M) N.C.
Width (m/Sec.) (mm.wg) (mm.wg)
47 0.76 3.7-1.5-0.9 0.04 0.05 <15
94 1.52 4.9-3.0-2.1 0.12 0.18 <15
142 2.31 6.1-4.0-3.0 0.30 0.43 <15
189 3.07 7.0-4.9-3.7 0.50 0.74 <15

100 mm 236 3.86 7.9-5.5-4.3 0.80 1.17 15


Ak = 0.061 283 4.62 8.8-6.1-4.6 1.14 1.68 22
330 5.38 9.8-6.7-5.2 1.56 2.29 27
378 6.15 10.7-7.6-5.8 2.03 2.97 30
472 7.70 11.9-9.1-7.3 3.17 4.65 38
566 9.25 13.1-10.4-8.5 4.60 6.73 46
47 0.58 4.0-1.5-0.6 0.02 0.03 <15
71 0.86 4.6-1.8-0.9 0.04 0.05 <15
118 1.45 5.8-3.7-2.4 0.09 0.13 <15
165 2.03 6.7-4.6-3.4 0.15 0.23 <15
212 2.59 7.6-5.5-4.3 0.25 0.38 <15

150 mm 260 3.18 8.5-6.1-4.9 0.37 0.56 <15


Ak = 0.082 307 3.76 9.4-6.7-5.5 0.52 0.79 15
378 4.62 10.7-7.6-6.1 0.79 1.19 20
472 5.77 11.9-8.8-6.7 1.25 1.88 24
566 6.93 12.8-10.1-7.6 1.79 2.69 30
661 8.08 14.0-11.6-9.1 2.48 3.71 35
755 9.25 14.9-12.8-10.4 3.27 4.88 40
47 0.43 3.7-1.5-0.9 0.02 0.03 <15
94 0.89 4.9-2.1-1.2 0.04 0.05 <15
142 1.32 6.1-4.0-2.4 0.07 0.10 <15
189 1.78 7.0-4.9-3.7 0.15 0.20 <15
236 2.21 7.9-5.8-4.6 0.22 0.30 <15
283 2.67 8.8-6.4-5.2 0.31 0.43 <15
200 mm
330 3.10 9.8-7.0-5.8 0.41 0.58 <15
Ak = 0.107
378 3.53 10.4-7.6-6.1 0.54 0.76 <15
472 4.42 11.6-8.5-6.7 0.85 1.19 21
566 5.31 12.5-9.4-7.3 1.20 1.70 25
708 6.63 13.7-11.0-8.5 1.91 2.69 31
850 7.95 14.9-12.2-10.1 2.71 3.84 37
944 8.84 15.8-13.1-11.0 3.34 4.72 41

Symbols: Conditions:
L/Sec : Air volume in litres per second. -Supply
Ak : Area factor in meters square per 1000 mm. -Vertical blades deflection : 0 degree
Vk : Face velocity in meters per second -Noise Criteria values are based on (10 dB) room attenuation
Ps. : Static pressure in millimeters water gauge -Damper is fully open
Pt. : Total pressure in millimeters water gauge -Data is based on 1000 mm length.
Th. : Throw in meters
N.C. : Noise Criteria

10 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Performance Data
S.I.Units
Type:
CI-SBG-DD
CI-SBR-DD 0 Degree
Unit Vk Ps. Pt.
(L/Sec.) Per 1000 mm Th. (M) N.C.
Width (m/Sec.) (mm.wg) (mm.wg)
47 0.33 3.0-1.5-0.6 0.02 0.03 <15
94 0.66 4.6-1.8-0.9 0.02 0.03 <15
118 0.81 5.8-2.4-1.2 0.04 0.05 <15
165 1.12 6.7-4.0-2.4 0.05 0.08 <15
212 1.45 7.6-5.2-3.7 0.08 0.13 <15
260 1.78 8.5-6.1-4.6 0.14 0.20 <15
307 2.08 9.4-6.7-5.2 0.19 0.28 <15
250 mm
354 2.41 10.4-7.3-5.8 0.26 0.38 <15
Ak = 0.147
425 2.90 11.3-8.2-6.7 0.41 0.58 <15
566 3.86 12.5-9.7-7.9 0.73 1.04 17
708 4.83 14.0-10.7-8.8 1.13 1.63 21
850 5.79 14.9-11.6-9.8 1.60 2.31 26
991 6.76 15.8-12.5-10.7 2.18 3.15 33
1133 7.72 17.1-13.4-11.3 2.83 4.09 37
1227 8.36 18.0-13.4-12.2 3.30 4.78 40
47 0.28 2.4-1.2-0.3 0.02 0.03 <15
94 0.56 4.3-1.8-0.9 0.02 0.03 <15
142 0.81 6.1-2.7-1.5 0.04 0.05 <15
189 1.09 7.0-4.3-2.7 0.05 0.08 <15
236 1.37 7.9-5.5-4.0 0.09 0.13 <15
283 1.65 8.8-6.4-4.9 0.12 0.18 <15
330 1.93 9.8-7.0-5.5 0.15 0.23 <15

300 mm 378 2.18 10.7-7.6-6.1 0.21 0.30 <15


Ak = 0.172 472 2.74 11.6-8.5-7.0 0.31 0.46 <15
566 3.30 12.8-9.1-7.6 0.47 0.69 15
708 4.11 13.7-10.4-8.5 0.70 1.04 20
850 4.95 14.6-11.6-9.8 1.06 1.55 25
991 5.77 15.8-12.5-10.4 1.39 2.06 29
1133 6.60 16.8-13.7-11.6 1.82 2.69 33
1322 7.70 17.7-14.9-12.5 2.48 3.66 38
1510 8.79 18.9-16.5-13.7 3.23 4.78 43

* Notes Corrections on Noise Criteria for other lengths.


• The large throw values are based on the minimum terminal velocity of 0.25 m/Sec.
Length 1000 mm 2000 mm 3000 mm
• The middle throw values are based on the middle terminal velocity of 0.50 m/Sec.
• The small throw values are based on the maximum terminal velocity of 0.75 m/Sec. N.C. (+0) (+3) (+5)

Cooling Industries Company www.cic-jo.com 11


Linear Grilles and Registers
Performance Data
S.I.Units
Type:
CI-SBG-DD
CI-SBR-DD 15 Degrees
Unit Vk Ps. Pt.
(L/Sec.) Per 1000 mm Th. (M) N.C.
Width (m/Sec.) (mm.wg) (mm.wg)
47 0.8 2.4-1.5-0.6 0.14 0.15 <15
94 1.7 3.0-1.8-0.9 0.50 0.56 <15
142 2.5 4.0-2.4-1.5 1.14 1.27 <15
189 3.4 5.2-3.7-2.7 2.00 2.24 15

100 mm 236 4.2 6.1-4.6-3.0 3.19 3.56 22


Ak = 0.061 283 5.1 7.0-5.5-3.7 4.55 5.08 29
330 5.9 7.9-6.1-4.0 6.13 6.86 34
378 6.8 8.5-6.4-4.6 7.94 8.89 39
472 8.5 9.4-7.3-5.5 12.49 13.97 44
566 10.2 10.1-7.9-6.1 17.94 20.07 49
142 1.9 2.7-1.8-1.5 0.38 0.43 <15
189 2.5 4.0-2.4-1.8 0.66 0.76 <15
236 3.1 4.6-3.7-1.8 1.04 1.19 19
283 3.8 5.5-4.3-2.4 1.50 1.73 24

150 mm 330 4.4 6.4-4.9-3.0 1.98 2.29 30


Ak = 0.082 378 5.0 7.3-5.8-4.0 2.62 3.02 34
472 6.3 7.9-6.1-4.6 4.10 4.72 40
566 7.5 8.8-6.7-4.9 5.95 6.86 46
661 8.8 9.8-7.6-5.5 8.04 9.27 52
755 10.0 10.4-8.2-6.4 11.18 12.07 58
142 1.5 3.4-2.1-1.2 0.10 0.15 <15
189 2.0 5.8-3.7-1.8 0.20 0.25 <15
236 2.5 6.7-4.3-2.1 0.25 0.41 <15
283 3.0 13-5.2-2.1 0.43 0.56 <15

200 mm 330 3.5 8.2-6.1-4.0 0.48 0.79 18


Ak = 0.107 378 4.0 8.8-6.78-4.6 0.79 1.02 25
472 5.0 9.4-7.3-5.2 0.97 1.60 32
566 6.0 10.1-7.9-5.8 1.79 2.29 37
755 8.1 11.0-8.8-6.7 2.45 4.06 42
944 10.1 12.2-10.1-7.9 4.97 6.35 47

Symbols: Conditions:
L/Sec : Air volume in litres per second. -Supply
Ak : Area factor in meters square per 1000 mm. -Vertical blades deflection : 45 degree
Vk : Face velocity in meters per second -Noise Criteria values are based on (10 dB) room attenuation
Ps. : Static pressure in millimeters water gauge -Damper is fully open
Pt. : Total pressure in millimeters water gauge -Data is based on 1000 mm length.
Th. : Throw in meters
N.C. : Noise Criteria

12 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Performance Data
S.I.Units
Type:
CI-SBG-DD
CI-SBR-DD 15 Degrees
Unit Vk Ps. Pt.
(L/Sec.) Per 1000 mm Th. (M) N.C.
Width (m/Sec.) (mm.wg) (mm.wg)
142 1.1 3.0-1.5-0.9 0.06 0.08 <15
189 1.5 4.3-2.4-1.5 0.09 0.13 <15
236 1.9 5.2-2.7-1.8 0.15 0.20 <15
283 2.3 6.1-3.4-2.4 0.23 0.30 <15

250 mm 330 2.7 6.7-4.0-3.0 0.30 0.41 <15


Ak = 0.124 378 3.0 7.6-4.9-4.0 0.39 0.53 <15
472 3.8 8.2-5.5-4.6 0.62 0.84 18
566 4.6 8.8-6.1-5.2 0.90 1.22 24
755 6.1 9.8-7.3-6.1 1.60 2.16 34
944 7.6 10.7-8.8-7.3 2.43 3.30 44
142 1.0 2.4-12-0.6 0.04 0.05 <15
189 1.3 3.4-2.4-1.5 0.08 0.10 <15
236 1.6 4.0-3.0-1.8 0.11 0.15 <15
283 1.9 4.9-3.4-2.4 0.17 0.23 <15

300 mm 330 2.2 6.1-4.0-3.0 0.23 0.30 <15


Ak = 0.149 378 2.5 7.0-4.6-3.4 0.28 0.38 15
566 3.8 7.9-5.5-4.3 0.62 0.84 27
755 5.1 8.8-6.7-5.2 1.11 1.50 37
944 6.4 9.8-7.6-6.4 1.73 2.34 43
1133 7.6 11.0-8.8-7.3 2.43 3.30 49

* Notes Corrections on Noise Criteria for other lengths.


• The large throw values are based on the minimum terminal velocity of 0.25 m/Sec.
Length 1000 mm 2000 mm 3000 mm
• The middle throw values are based on the middle terminal velocity of 0.50 m/Sec.
• The small throw values are based on the maximum terminal velocity of 0.75 m/Sec. N.C. (+0) (+3) (+5)

Cooling Industries Company www.cic-jo.com 13


Linear Grilles and Registers
Performance Data
Return S.I.Units
Type:
CI-RBG-SD
CI-RBR-SD
Unit (L/Sec.) Per 1000 mm Neg. Ps. (mm.wg) N.C.
Width
94 0.25 16
142 0.51 21
189 1.02 25
100 mm 236 1.78 28
283 2.29 30
330 3.05 32
378 3.81 34
189 0.25 <15
236 0.51 20
283 0.76 26
150 mm 330 1.02 30
378 1.52 35
425 1.78 39
472 2.29 45
189 0.25 18
283 0.51 24
378 1.02 28
200 mm 472 1.78 30
566 2.29 33
661 3.05 34
755 3.81 37
283 0.25 <15
378 0.76 17
472 1.02 22
250 mm 566 1.52 28
661 2.03 31
802 3.05 34
944 4.06 37
283 0.25 <15
378 0.25 18
472 0.51 23
300 mm 566 0.76 35
661 1.02 37
755 1.52 43
944 2.29 53

Symbols: Conditions:
L/Sec : Air volume in litres per second. -Return
Negative Ps. : Negative Static pressure in millimeters -Noise Criteria is based on (10 dB) room attenuation
water gauge -Data is based on 1000 mm length.
N.C. : Noise Criteria

14 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Performance Data
Imperial Units
Type:
CI-SBG-DD
CI-SBR-DD 0 Degree
Unit Vk Ps. Pt.
CFM per foot Th. (ft) N.C.
Width (fpm.) (in.wg) (in.wg)
30 150 12-5-3 0.001 0.002 <15
60 300 16-10-7 0.005 0.007 <15
90 455 20-13-10 0.012 0.017 <15
120 605 23-16-12 0.020 0.029 <15

4 inch 150 760 26-18-14 0.031 0.046 <15


Ak = 0.20 180 910 29-20-15 0.045 0.066 18
210 1060 32-22-17 0.061 0.090 23
240 1210 35-25-19 0.080 0.117 26
300 1515 39-30-24 0.125 0.183 30
360 1820 43-34-28 0.181 0.265 34
30 115 +13-5-2 0.001 0.001 <15
45 170 15-6-3 0.001 0.002 <15
75 285 19-12-8 0.003 0.005 <15
105 400 22-15-11 0.006 0.009 <15
135 510 25-18-14 0.010 0.015 <15

6 inch 165 625 28-20-16 0.015 0.022 <15


Ak = 0.26 195 740 31-22-18 0.021 0.031 <15
240 910 35-25-20 0.031 0.047 16
300 1135 39-29-22 0.049 0.074 20
360 1365 42-33-25 0.070 0.106 26
420 1590 46-38-30 0.097 0.146 31
480 1820 49-42-34 0.129 0.192 36
30 85 12-5-3 0.001 0.001 <15
60 175 16-7-4 0.001 0.002 <15
90 260 20-13-8 0.003 0.004 <15
120 350 23-16-12 0.006 0.008 <15
150 435 26-19-15 0.009 0.012 <15
180 525 29-21-17 0.012 0.017 <15
8 inch
210 610 32-23-19 0.016 0.023 <15
Ak = 0.35
240 695 34-25-20 0.021 0.030 <15
300 870 38-28-22 0.033 0.047 17
360 1045 41-31-24 0.047 0.067 21
450 1305 45-36-28 0.075 0.106 26
540 1565 49-40-33 0.107 0.151 33
600 1740 52-43-36 0.131 0.186 37

Symbols: Conditions:
CFM : Air volume is cubic feet per minute -Supply
Ak : Area factor in meters square per 1000 mm. -Vertical blades deflection: 0 degree
Vk : Face velocity in meters per second -Noise Criteria values are based on (10 dB) room attenuation
Ps. : Static pressure in millimeters water gauge -Damper is fully open
Pt. : Total pressure in millimeters water gauge -Data is based on 1 Ft length.
Th. : Throw in feet
N.C. : Noise Criteria

Cooling Industries Company www.cic-jo.com 15


Linear Grilles and Registers
Performance Data
Imperial Units
Type:
CI-SBG-DD
CI-SBR-DD 0 Degree
Unit Vk Ps. Pt.
CFM per foot Th. (ft) N.C.
Width (fpm.) (in.wg) (in.wg)
30 65 10-5-2 0.001 0.001 <15
60 130 15-6-3 0.001 0.001 <15
75 160 19-8-4 0.001 0.002 <15
105 220 22-13-8 0.002 0.003 <15
135 285 25-17-12 0.003 0.005 <15
165 350 28-20-15 0.005 0.008 <15
195 410 31-22-17 0.007 0.011 <15
10 inch
225 475 34-24-19 0.010 0.015 <15
Ak = 0.47
270 570 37-27-22 0.016 0.023 <15
360 760 41-31-26 0.029 0.041 <15
450 950 46-35-29 0.045 0.064 16
540 1140 49-38-32 0.063 0.091 22
630 1330 52-41-35 0.086 0.124 27
750 1520 56-44-37 0.111 0.161 33
780 1645 59-49-40 0.130 0.188 36
30 55 8-4-1 0.001 0.001 <15
60 110 14-6-3 0.001 0.001 <15
90 160 20-9-5 0.001 0.002 <15
120 215 23-14-9 0.002 0.003 <15
150 270 26-18-13 0.004 0.005 <15
180 325 29-21-16 0.005 0.007 <15
210 380 32-23-18 0.006 0.009 <15

12 inch 240 430 35-25-20 0.008 0.012 <15


Ak = 0.56 300 540 38-28-23 0.012 0.018 <15
360 650 42-30-25 0.018 0.027 <15
450 810 45-34-28 0.028 0.041 17
540 975 48-38-32 0.042 0.061 22
630 1135 52-41-34 0.055 0.081 25
720 1300 55-45-38 0.072 0.106 29
840 1515 58-49-41 0.098 0.144 34
960 1730 62-54-45 0.127 0.188 39

* Notes Corrections on Noise Criteria for other lengths.


• The large throw values are based on the minimum terminal velocity of 50 fpm.
Length 3 ft 6 ft 10 ft
• The middle throw values are based on the middle terminal velocity of 100 fpm.
• The small throw values are based on the maximum terminal velocity of 50 fpm. N.C. (+4) (+7) (+9)

16 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Performance Data
Imperial Units
Type:
CI-SBG-DD
CI-SBR-DD 15 Degree
Unit Vk Ps. Pt.
CFM per foot Th. (ft) N.C.
Width (fpm.) (in.wg) (in.wg)
30 165 8-5-2 0.006 0.006 <15
60 335 10-6-3 0.020 0.022 <15
90 500 13-8-5 0.045 0.050 <15
120 665 17-12-9 0.079 0.088 <15

4 inch 150 835 20-15-10 0.126 0.140 18


Ak = 0.18 180 1000 23-18-12 0.179 0.200 25
210 1165 26-20-13 0.241 0.270 30
240 1335 28-21-15 0.313 0.350 35
300 1665 31-24-18 0.492 0.550 40
360 2000 33-26-20 0.706 0.790 45
90 370 9-6-5 0.015 0.017 <15
120 490 13-8-6 0.026 0.030 <15
150 615 15-12-6 0.041 0.047 15
180 740 18-14-8 0.059 0.068 20

6 inch 210 860 21-16-10 0.078 0.090 26


Ak = 0.24 240 985 24-19-13 0.103 0.119 30
300 1235 26-20-15 0.161 0.186 36
360 1480 29-22-16 0.234 0.270 40
420 1730 32-25-18 0.317 0.365 46
480 1975 34-27-21 0.440 0.478 50
90 295 11-7-4 0.004 0.006 <15
120 395 19-12-6 0.008 0.010 <15
150 495 22-14-7 0.010 0.016 <15
180 595 24-17-9 0.017 0.022 <15

8 inch 210 695 27-20-13 0.019 0.031 <15


Ak = 0.30 240 790 29-22-15 0.031 0.040 <15
300 990 31-24-17 0.038 0.063 21
360 1190 33-26-19 0.070 0.090 28
480 1585 36-29-22 0.096 0.160 38
600 1980 40-33-26 0.196 0.250 48

Symbols: Conditions:
CFM : Air volume is cubic feet per minute -Supply
Ak : Area factor in meters square per 1000 mm. -Vertical blades deflection: 45 degree
Vk : Face velocity in meters per second -Noise Criteria values are based on (10 dB) room attenuation
Ps. : Static pressure in millimeters water gauge -Damper is fully open
Pt. : Total pressure in millimeters water gauge -Data is based on 1 Ft length.
Th. : Throw in feet
N.C. : Noise Criteria

Cooling Industries Company www.cic-jo.com 17


Linear Grilles and Registers
Performance Data
Imperial Units
Type:
CI-SBG-DD
CI-SBR-DD 15 Degree
Unit Vk Ps. Pt.
CFM per foot Th. (ft) N.C.
Width (fpm.) (in.wg) (in.wg)
90 225 10-5-3 0.002 0.003 <15
120 300 14-8-5 0.004 0.005 <15
150 375 17-9-6 0.006 0.008 <15
180 450 20-11-8 0.009 0.012 <15

10 inch 210 525 22-13-10 0.012 0.016 <15


Ak = 0.47 240 600 25-16-13 0.015 0.021 <15
300 750 27-18-15 0.024 0.033 <15
360 900 29-20-17 0.035 0.048 20
480 1200 32-24-20 0.063 0.085 30
600 1500 35-29-24 0.096 0.130 40
90 190 8-4-2 0.002 0.002 <15
120 250 11-8-5 0.003 0.004 <15
150 315 13-10-6 0.004 0.006 <15
180 375 16-11-8 0.007 0.009 <15

12 inch 210 440 20-13-10 0.009 0.012 <15


Ak = 0.56 240 500 23-15-11 0.011 0.015 <15
360 750 26-18-14 0.024 0.033 23
480 1000 29-22-17 0.044 0.059 33
600 1250 32-25-21 0.068 0.092 39
720 1500 36-29-24 0.096 0.130 45

* Notes Corrections on Noise Criteria for other lengths.


• The large throw values are based on the minimum terminal velocity of 50 fpm.
Length 3 ft 6 ft 10 ft
• The middle throw values are based on the middle terminal velocity of 100 fpm.
• The small throw values are based on the maximum terminal velocity of 50 fpm. N.C. (+4) (+7) (+9)

18 www.cic-jo.com Cooling Industries Company


Linear Grilles and Registers
Performance Data
Return Imperial Units
Type:
CI-RBG-SD
CI-RBR-SD
Unit CFM Per foot Neg. Ps. (in.wg) N.C.
Width
60 0.01 <15
90 0.02 17
120 0.04 22
4 inch 150 0.07 25
180 0.09 27
210 0.12 29
240 0.15 30
120 0.01 <15
150 0.02 16
180 0.03 20
6 inch 210 0.04 25
240 0.06 30
270 0.07 35
300 0.09 41
120 0.01 <15
180 0.02 20
240 0.04 25
8 inch 300 0.07 27
360 0.09 29
420 0.12 30
480 0.15 33
180 0.01 <15
240 0.03 <15
300 0.04 18
10 inch 360 0.06 24
420 0.08 27
510 0.12 30
600 0.16 33
180 0.01 <15
240 0.01 <15
300 0.02 19
12 inch 360 0.03 31
420 0.04 33
480 0.06 39
600 0.09 49

Symbols: Conditions:
CFM : Air volume in cubic feet per minute. -Return
Negative Ps. : Negative Static pressure in millimeters -Noise Criteria is based on (10 dB) room attenuation
water gauge -Data is based on 1 Ft length.
N.C. : Noise Criteria

Cooling Industries Company www.cic-jo.com 19


Floor Grilles & Register

General :

CIC Floor Grilles & Register ( (F.B.G) & (F.B.R) ) are designed to be installed on floors where air-ducts are
required to be underneath the floor level, such as for computer rooms.
They are designed to withstand 450kg. point load for heavy duty applications.

Floor Grille F.B.G - With Frame Floor Grille F.B.G - Framless

Description :

F.B.G are multiparallel horizontal or vertical fixed Bars in continuous modular sections. They are available in
fixed pattern of air flow (Zero Deflection) for supplying vertical air flow. Bars are of heavy duty type 6mm
wide, and are equally spaced (1/4") distance.
Mullion bars across the blades provide additional strength and extra reinforcement in the structure of the
grille to withstand loads up to 450kg. Bars are fixed by a standard frame (1.5mm thickness). special type
heavy duty frames with 7mm thickness are also available forming an extra special type of floor grilles.
Both horizontal and vertical bar models can supplied with opposed blade dampers and are called registers
F.B.R.

LISTED WIDTH + 58mm LISTED SIZE + 6mm


6mm 12.5mm(½") 32mm

7mm 6mm
51.5mm

62mm

62mm

3mm(1⁄₈")

52mm
LISTED WIDTH

F.B.G - With Frame - (Floor Grille) F.B.G - Framless - (Floor Grille)

20 www.cic-jo.com Cooling Industries Company


Floor Grilles & Register
Performance Data

Model: CI - FBG
Velocity
Size Area 400 500 600 700 800 1000 1200 1400 1600
(FPM)
WxH Factor
(Inch) (Ft²) St. Pressure
0.01 0.016 0.025 0.039 0.052 0.093 0.134 0.178 0.218
(Inch W.G)
CFM 126 162 180 216 252 306 360 414 468
12x6 0.26
NC <20 <20 <20 <20 20 23 26 29 32

12x8 CFM 168 216 240 288 335 408 481 554 627
0.35
16x6 NC <20 <20 <20 <20 21 24 27 30 33

12x10 CFM 210 270 300 358 417 508 599 690 781
0.44
20x6 NC <20 <20 <20 <20 22 26 30 34 37
12x12 CFM 252 296 340 428 498 610 722 834 946
18x8 0.53
24x6 NC <20 <20 <20 20 23 27 31 35 38
16x12 CFM 351 442 510 590 686 840 994 1148 1302
20x10 0.75
24x8 NC <20 <20 <20 21 24 28 32 36 40
16x12 CFM 378 477 540 635 738 905 1072 1239 1406
20x10 0.86
36x6 NC <20 <20 <20 22 25 29 33 37 41

12x12 CFM 420 530 600 704 818 1005 1192 1379 1566
0.93
24x10 NC <20 <20 <20 23 26 30 34 38 42

24x12 CFM 504 630 720 840 979 1210 1441 1672 1903
1.12
36x6 NC <20 <20 20 24 28 32 36 39 43
20x18 CFM 630 766 900 1040 1213 1494 1774 2056 2337
30x12 1.48
36x10 NC <20 <20 21 25 29 33 37 40 45
CFM 1010 1203 1440 1654 1925 2385 2845 3305 3765
24x24 2.41
NC <20 <20 22 26 30 34 38 41 46
CFM 1283 1490 1800 2060 2384 2966 3548 4130 4712
30x24 3.25
NC <20 <20 23 27 31 35 39 42 47
CFM 1502 1773 2160 2462 2852 3550 4248 4946 5644
36x24 4.09
NC <20 <20 24 28 32 36 40 44 48

Cooling Industries Company www.cic-jo.com 21


DIFFUSERS

Page Contents

2 Supply Air Diffusers 1, 2 , 3 , 4 Way


6 Ordering System
7 Pattern
8 Ceiling Diffusers - Engineering Selection Data
13 Supply Air Diffusers - Performance Data
25 Return Air Diffusers - Performance Data
27 Diffuser Accessories
29 Perforated Diffuser
Supply Air Diffusers
Square, One Way Flow Pattern
Rectangular, One Way Flow Pattern

Model: Cl - Air SD - R1
Model: Cl - Air SD - S1

Features:

Ceiling diffusers available in square or rectangular shape, one way


flow pattern to meet the design air distribution requirement.

Constructed of anodized finish extruded aluminium blades fixed


together by rigid fasteners to prevent open miters and provide
increased rigidity.
Cl - Air SD - R1
The horizontal lip on all sides of the inner core blades provides
a horizontal air pattern that is tight to the ceiling and maybe used for
any ceiling height.

Easily removable core gives simple installation and better damper


adjustment also interchangeable in the same size of diffuser to give
flexibility in the air conditioned area repartitioning by changing air
supply pattern ie. Two, three, or four way flow.
(Fixed core available on request).

Fitted with opposite blade damper air volume controller.


Cl - Air SD - S1
White and anodized aluminium are the standard color, other colors
are available upon request.

2 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers
Square, Two Way Flow Pattern
Rectangular, Two Way Flow Pattern

Model: Cl - Air SD - S 02
Model: Cl - Air SD - R 02L

Features:

Ceiling diffusers available in square or rectangular shape, opposite


or comer two way flow pattern to meet the design air distribution
requirement.

Constructed of anodized finish extruded aluminium blades fixed


together by rigid fasteners to prevent open miters and provides
increased rigidity, The horizontal lip on all sides of the inner core
blades provides a horizontal air pattern that is tight to the ceiling and Cl - Air SD - S 02
maybe used for any ceiling height. (Opposite Pattern)

Easily removable core gives simple installation and better damper


adjustment also interchangeable in the same size of diffuser to give
flexibility in the air conditioned area repartitioning by changing air
supply pattern ie. One, three, or four way flow.
(Fixed core available on request).

Fitted with opposite blade damper air volume controller.


White and anodized aluminium are the standard color, other colors
are available upon request.
Cl - Air SD - R 02L
(Opposite Pattern)

Cooling Industries Company www.cic-jo.com 3


Supply Air Diffusers
Square, Three Way Flow Pattern
Rectangular, Three Way Flow Pattern

Model: Cl - Air SD - R3
Model: Cl - Air SD - S3

Features:

Ceiling diffusers available in square or rectangular three way flow


pattern to meet the design air Distribution requirement.

Constructed of anodized finish extruded aluminium blades fixed


together by rigid fasteners to prevent open miters and provides
increased rigidity.
Cl - Air SD - R3
The horizontal lip on all sides of the inner core blades provides a
horizontal air pattern that is tight to the ceiling and may be used for
any ceiling height.

Easily removable core gives simple installation and better damper


adjustment also interchangeable in the Same size of diffuser to give
flexibility in the air conditioned area repartitioning by changing air
supply pattern ie. One, two, or four way flow.
(Fixed core available on request).

Fitted with opposite blade damper air volume controller. White


and anodized aluminium are the standard color, other colors are
CI- Air SD - S3
available upon request.

4 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers
Square, Four Way Flow Pattern
Rectangular, Four Way Flow Pattern

Model: CI - Air SD - S4
Model: CI - Air SD - R4
Model: CI - Air FSD - S4

Features:

Ceiling diffusers available in square or rectangular shape, four way


flow pattern to meet the design air distribution requirement.

Constructed of anodized finish extruded aluminium blades fixed


together by rigid fasteners to prevent open miters and provides
increased rigidity.
Cl - Air SD - S4
The horizontal lip on all sides of the inner core blades provides
a horizontal air pattern that is tight to the ceiling and may be used for
any ceiling height.

Easily removable core gives simple installation and better damper


adjustment also interchangeable in the same size of diffuser to give
flexibility in the air conditioned area repartitioning by changing air
supply pattern ie, one, two or three, way flow.
(Fixed core available on request).

Fitted with opposite blade damper air volume controller. Cl - Air SD - R4


White and anodized aluminium are the standard color, other colors
are available upon request.

CI - Air FSD S4
Note:
Flat Diffuser available in two sizes 4 way only
* Nick Size 30x30 cm - Face size 60x60 cm
* Nick Size 38x38 cm - Face size 60x60 cm

Cooling Industries Company www.cic-jo.com 5


Ordering System

Note:
When Ordering Specify as follows:

CI Air SD S O I L

L. For Flow Pattern Paralled to Long Side Dimension.


R. For Flow Pattern Parallel to short Side Dimension.

1,2,3,4 For Identification of Flow Pattern.

O. For 2 - way Opposite Pattern.


C. For 2 - way Corner Pattern.

S. For Square Diffusers.


R. For Rectangular Diffusers.

SD. For Air Supply Diffusers.


RD. For Air Return Diffusers.

CI. For Cooling Industries Co.

6 www.cic-jo.com Cooling Industries Company


Pattern:

Pattern Pattern
Description Description
Designator Designator

One - way flow. Two-way flow


Square diffuser. Rectangular diffuser.
Air SD - SI Comer pattern.
Major portion of air flow to right
(as illustrated).
Air SD - RC 2 R
One-way flow
Rectangular diffuser.
Blades parallel to the short dimension. Two-way flow
Air flow perpendicular to short dimension Rectangular diffuser.
AirSD-R I W Comer pattern.
Major portion of air flow to left
(as illustrated).
Air SD - RC 2L
One-way flow
Rectangular diffuser. Three-way flow.
Blades parallel to the long dimension. Square diffuser.
Air flow perpendicular to long dimension. Air SD - S 3
AirSD-R I L

Two-way flow. Three-way flow


Square diffuser. Rectangular diffuser.
Air SD - SO2 Single segment in direction
of short dimension.
AirSD-R 3 S
Two-way flow
Rectangular diffuser. Three-way flow
Blades parallel to the short dimension. Rectangular diffuser.
Air flow perpendicular to short dimension. Single segment indirection of
Air SD - RO 2 W long dimentsion.
Single segment dimension is
twice the double segment
dimension.
Two-way flow Air SD-R 3 L
Rectangular diffuser.
Blades parallel to the long dimension.
Air flow perpendicular to long dimension. Four-way flow.
Air SD - RO 2 L Square diffuser.
Air SD - S 4
Two-way flow.
Square diffuser.
Comer pattern. Four-way flow.
Air flow two streams 90° apart. Rectangular diffuser.
Air SD-SC 2 AirSD-R 4

* View shown are Reflected Ceiling Plan.

Cooling Industries Company www.cic-jo.com 7


Ceiling Diffusers
Engineering Selection Data

Selection Procedure:

In order to make quick, easy and accurate selection of a ceiling air distribution terminals, the following
performance data should be considered:
1- The air quantity (CFM) which is given by the air conditioning system design, to be distributed by each
ceiling Diffuser.
2- The sound (NC) level according to the air conditioned space application and the architect demands
(table 1).
3- The ceiling diffuser pattern which depends on the size and shape of the space to be air conditioned,
the layout of air distribution duct work and the type and location of the lighting fixtures or other devices
mounted on the ceiling of that area.
4- The required ceiling diffusers air throw which is determined from the building plan after the ceiling
diffuser location has been decided, then the throw is considered as the distance from center line of
diffuser to the nearest enclosing wall, or to the point of the intersection of its air stream with the air
stream being delivered from another adjacent diffuser.

For high ceiling application, throw may be measured as the horizontal distance described above, plus the
vertical distance from the diffuser location to a point of 1.5 meters above ground level.
In general rule, the throw should not be more than 1.5 times the ceiling height.

The minimum and maximum throw values shown in the diffusers performance tables are based on the
following:

Minimum Throw: is the horizontal distance between the diffuser center line and the point at which the
residual velocity reaches 75 FPM.
Maximum Throw: is the horizontal distance between the diffuser center line and the point at which the
residual velocity is not more than 35 FPM.

In general an average throw can be considered for an application (such as restaurants offices etc.)
Allowing for a residual velocity of 55 FPM.

8 www.cic-jo.com Cooling Industries Company


Ceiling Diffusers
Engineering Selection Data

Sizing Procedure:

After selecting pattern of ceiling diffuser (from page “7”) according to the size and shape of the space to be
air Conditioned, and layout of the air distribution duct work.

1- Check recommended limit of Max. CFM (per each direction) and temperature differential relationship
with mounting Height (table 2).
2- Check the limit of sound (NC) level (table 1) with type of Occupancy and application.
3- Using the performance tables on the following pages, with The total CFM for each diffuser to select the
most suitable size Of diffuser and the best throw which will meet the application, The neck velocity and
the total pressure drop through the Diffuser (which is equal to neck velocity pressure drop plus Static
pressure drop).
4- Use the sound (NC) level curve to check the NC level which should match with the required sound level
as per step 2.

Table 1
Application NC

Concert halls, studios, opera halls. 22

Offices, board room, private relaxation room. 25

Theaters. 27

Conference rooms, private room, houses, villas. 30

Lecture halls, reception rooms, planetarium, study halls. 32

Libraries,hotels individual rooms, courtroom. 35

Post offices, restaurants, night clubs, recreation halls. 40

Kitchens and toilets, halls and corridors, cafeterias, supermarkets. 45

Accounting offices, coliseums. 50

Foundries, factories, heavy machinery rooms. 60-65

Note:
Selection of all diffusers supplied by the same branch duct should be made at approximately the same neck velocities in order
to facilitate balancing after installation.

Cooling Industries Company www.cic-jo.com 9


Ceiling Diffusers
Engineering Selection Data

Table 2 Table 3
Maximum Dimen. Ratio of long Reduced short side
Ceiling Height Maximum CFM
Temperature to short side throw factor
ft (M) per side
Differential
1.25 0.940
8 (2.44) 20° F 200
1.33 0.890
10 (3.05) 26° F 500
0.50 0.870
12 (3.66) 30° F 850
1.66 0.850
14 (4.27) 30° F 1300
1.75 0.835
16 (4.88) 30° F 1600
2.00 0.790
Gives the maximum CFM per side of the diffuser as a function of
ceiling height. 2.25 0.755
2.33 0.745
Diffuser Short Side Correction Factor
2.50 0.730
Having the diffuser dimensional ratio of long side to short
2.66 0.720
side, enter table 3 and multiply the reduced short side
throw factor by the long side throw value obtained from the 2.75 0.700
performance table. 3.00 0.685
3.50 0.640
Sound Level Curves:
Sound Level In Nc From Sound Power Data 4.00 0.610
Lw - 8 Re 10-12 Watt Damper Fully Open.
Neck Area in Sq. Ft.

CFM
Table is based on 4-way for 3 way add 3, for 2 way add 2, for 1 way add 1

10 www.cic-jo.com Cooling Industries Company


Ceiling Diffusers
Engineering Selection Data

Balancing Of Supply Air Diffusers: Balancing Of Return Air Diffusers:

Using an ALNOR Velometer (instrument for Using a rotating vane anemometer, take a
measuring air velocity in FPM manufactured by one minute average reading by holding the
Illinois Testing Laboratory) equipped with a 2200 A anemometer flush with the diffuser face and
jet sensing tip, take readings around the centers of moving it continuously to sample the entire face
all active outer passages. area.
To determine delivered CFM average the readings With the average anemometer reading and the
and multiply by the supply air area factor as shown diffuser neck size, enter the performance table of
in. return air Diffuser page 25-26 and determine the
CFM being returned.
Table 4 - Free Area For Supply Air Diffuser (ft2)
One Way Flow Pattern (With O. B. Damper)
Neck
6 9 12 15 18 21 24 27 30 33 36
Size
6 0.14
9 0.20 0.27
12 0.25 0.38 0.50
15 0.32 0.48 0.63 0.79
18 0.38 0.57 0.75 0.94 1.03
21 0.44 0.70 0.87 1.02 1.23 1.39
24 0.50 0.75 1.00 1.21 1.43 1.59 1.81
27 0.56 0.84 1.10 1.40 1.54 1.80 2.02 1.45
30 0.62 0.93 1.20 1.50 1.74 2.06 2.24 2.75 3.05
33 0.68 1.01 1.40 1.70 1.95 2.37 2.53 2.95 3.30 3.65
36 0.75 1.10 1.50 1.80 2.15 2.55 2.79 3.25 3.65 3.86 4.0

Two Way Flow Pattern (With O. B. Damper)


Neck
6 19 12 15 18 21 24 27 30 33 36 39 42 45 48
Size
6 0.13
9 0.20 0.29
12 0.25 0.37 0.49
15 0.33 0.47 0.60 0.74
18 0.39 0.54 0.72 0.92 1.05
21 0.46 0.63 0.84 1.11 1.35 1.42
24 0.53 0.73 0.94 1.32 1.52 1.62 1.85
27 0.60 0.84 1.08 1.41 1.71 1.93 2.18 2.48
30 0.66 0.94 1.17 1.61 1.92 2.13 2.39 2.78 3.08
33 0.73 1.02 1.24 1.83 2.10 2.35 2.68 3.09 3.35 3.67
36 0.79 1.11 1.45 1.91 2.31 2.54 2.98 3.36 3.69 3.87 4.02
39 0.86 1.21 1.62 2.23 2.49 2.72 3.198 3.69 4.18 4.46 4.77 5.07
42 0.92 1.30 1.80 2.43 2.70 2.96 3.58 3.96 4.57 4.89 5.18 5.47 5.89
45 0.98 1.30 2.03 2.72 2.89 3.15 3.92 4.30 4.96 5.31 5.67 5.92 6.77 7.01
48 1.05 1.48 2.26 2.96 3.21 3.47 4.25 4.62 5.42 5.70 6.12 6.29 7.01 7.32 7.47

Cooling Industries Company www.cic-jo.com 11


Ceiling Diffusers
Engineering Selection Data

Three Way Flow Pattern (With O. B. Damper)


Neck
6 19 12 15 18 21 24 27 30 33 36 39 42 45 48
Size
6
9 0.16 0.33
12 0.24 0.43 0.57
15 0.30 0.53 0.70 0.68
18 0.37 0.64 0.83 0.94 1.23
21 0.44 0.74 0.97 1.19 1.40 1.60
24 0.50 0.83 1.10 1.40 1.60 1.80 2.17
27 0.57 0.95 1.20 1.50 1.90 2.10 2.46 2.75
30 0.62 1.02 1.40 1.70 2.10 2.30 2.57 2.98 3.16
33 0.71 1.10 1.50 1.90 2.30 2.50 3.06 3.29 3.45 3.07
36 0.84 1.18 .1.60 2.10 2.50 2.76 3.32 3.57 3.76 3.68 4.08
39 0.91 1.26 .1.70 2.30 2.70 2.87 3.58 3.89 4.29 4.62 4.80 5.20
42 0.96 1.34 1.86 2.50 2.90 3.09 3.87 4.17 4.68 4.96 5.20 5.56 6.17
45 1.05 1.52 2.07 2.78 3.12 3.36 4.17 4.48 5.08 5.37 2.75 6.08 6.88 7.57
48 1.12 1.60 2.34 3.01 3.301 3.62 4.52 4.89 5.48 5.82 6.16 6.34 7.10 7.50 7.60

Four Way Flow Pattern (With O. B. Damper)


Neck
6 19 12 15 18 21 24 27 30 33 36 39 42 45 48
Size
6 0.20
9 0.27 0.36
12 0.32 0.46 0.58
15 0.39 0.55 0.71 0.87
18 0.42 0.65 0.84 1.03 1.22
21 0.48 0.74 0.96 1.25 1.40 1.63
24 0.57 0.85 1.16 1.36 1.60 1.84 2.10
27 0.64 0.94 1.25 1.55 1.80 2.16 2.36 2.54
30 0.72 1.06 1.36 1.75 2.10 2.33 2.50 2.80 3.15
33 0.78 1.15 1.55 1.95 2.29 2.65 2.75 3.13 3.40 3.70
36 0.84 1.25 1.65 2.13 2.40 2.95 3.10 3.42 3.70 3.93 4.08
39 0.91 1.36 1.76 2.29 2.57 3.09 3.26 3.73 4.25 4.50 4.81 5.15
42 1.02 1.45 1.86 2.52 2.80 3.20 3.65 4.04 4.64 4.95 5.25 5.50 6.02
45 1.06 1.56 2.09 2.78 2.97 3.32 4.06 4.35 5.02 5.40 5.75 6.02 3.96 7.30
48 1.15 1.67 2.40 3.02 3.29 3.58 4.30 4.70 5.58 5.75 6.20 6.35 7.15 7.48 7.60

12 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Square
One Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
(CMS) Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033

CFM 100 115 125 135 150 160 170


6x6 Throw Ft. 4-12 6-14 8-16 10-20 20-22 12-24 12-26
(15x15) (Mt.) (1.2-3.7) (1.8-4.3) (2.4-6.1) (3.0-6.1) (3.0-6.7) (3.7-7.3) (3.7-7.9)
Tot. Press IN.W.G 0.046 0.057 0.070 0.084 0.101 0.116 0.135
CFM 225 250 280 300 335 365 390
9x9 Throw Ft. (10-20) (16-22) 16-24 18-26 18-28 18-30 20-32
(23x23) (Mt.) (3.0-6.1) (4.9-6.7) (4.9-7.3) (5.5-7.9) (5.5-8.5) (5.5-9.1) (6.1-9.5)
Tot. Press IN.W.G 0.055 0.068 0.084 0.101 0.119 0.141 0.162
CFM 400 450 500 550 600 650 700
12x12 Throw Ft. 20-30 20-32 22-36 22-38 24-40 24-42 26-44
(30x30) (Mt.) (6.1-9.1) (6.1-9.5) (6.7-11.0) (6.7-11.6) (7.3-12.2) (7.3-12.8) (7.9-13.4)
Tot. Press IN.W.G 0.052 0.066 0.080 0.097 0.115 0.137 0.157
CFM 625 700 770 850 930 1010 1090
15x15 Throw Ft. 22-34 24-36 24-38 24-40 26-44 26-46 28-48
(38x38) (Mt.) (6.7-10.4) (7.3-11.0) (7.3-11.6) (7.3-12.2) (7.9-13.4) (7.9-14.6) (8.5-14.6)
Tot. Press IN.W.G 0.052 0.070 0.083 0.0696 0.117 0.135 0.160

Cooling Industries Company www.cic-jo.com 13


Supply Air Diffusers, Rectangular
One Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 150 170 185 205 225 245 260
6x9 Throw Ft. 10-18 10-20 10-22 12-24 14-26 16-28 16-30
(15x23) (Mt.) (3.0-5.5) (3.0-6.1) (3.0-6.7) (3.7-7.3) (4.3-7.9) (4.9-8.5) (4.9-9.1)
Tot. Press IN.W.G 0.055 0.068 0.083 0.099 0.118 0.138 0.161
CFM 200 225 250 275 300 325 350
6x12 Throw Ft. 12-20 12-22 14-26 16-28 16-32 16-34 18-26
(15x30) (Mt.) (3.7-6.1) (3.7-6.7) (4.3-7.9) (4.9-8.5) (4.9-9.8) (4.9-10.7) (5.5-7.9)
Tot. Press IN.W.G 0.053 0.066 0.081 0.098 0.117 0.131 0.160
CFM 250 280 310 340 375 400 430
6x15 Throw Ft. 14-20 16-24 18-28 18-30 18-32 18-34 20-38
(15x38) (Mt.) (4.3-6.1) (4.9-7.3) (5.5-8.5) (5.5-9.1) (5.5-9.5) (5.5-10.4) (6.1-11.6)
Tot. Press IN.W.G 0.052 0.064 0.076 0.094 0.112 0.129 0.151
CFM 300 330 370 410 450 480 425
6x18 Throw Ft. 14-24 16-28 18-30 18-32 20-36 20-38 22-40
(15x46) (Mt.) (4.3-7.3) (4.9-8.5) (5.5-9.1) (5.5-9.5) (6.1-11.0) (6.1-11.6) (6.7-12.2)
Tot. Press IN.W.G 0.054 0.068 0.082 0.098 0.119 0.135 0.157
CFM 350 390 430 480 520 600 620
6x21 Throw Ft. 16-24 18-26 20-32 20-34 20-36 20-38 24-44
(15x53) (Mt.) (4.9-7.3) (5.5-7.8) (6.1-9.5) (6.1-10.4) (6.1-11.0) (6.1-11.6) (7.3-13.4)
Tot. Press IN.W.G 0.053 0.066 0.080 0.096 0.116 0.134 0.156
CFM 400 450 500 550 600 650 700
6x24 Throw Ft. 18-26 18-28 20-30 20-32 20-36 24-40 26-44
(15x61) (Mt.) (5.5-7.9) (5.5-8.5) (6.1-9.1) (6.1-9.5) (6.1-11.0) (7.3-12.2) (7.9-13.4)
Tot. Press IN.W.G 0.057 0.065 0.079 0.096 0.114 0.136 0.156
CFM 300 330 380 410 450 530 550
9x12 Throw Ft. 18-24 18-26 18-28 18-32 20-36 20-38 22-42
(23x30) (Mt.) (5.5-7.3) (5.5-7.9) (5.5-8.5) (5.5-9.8) (6.1-11.0) (6.1-11.6) (6.7-12.8)
Tot. Press IN.W.G 0.054 0.068 0.082 0.098 0.119 0.135 0.157

14 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Rectangular
One Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
(CMS) Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033

CFM 375 420 470 510 560 610 655


9x15 Throw Ft. 18-24 18-26 20-30 20-32 24-36 24-38 24-40
(23x38) (Mt.) (5.5-7.3) (5.5-7.9) (6.1-9.1) (6.1-9.8) (7.3-11.0) (7.3-11.6) (7.3-12.2)
Tot. Press IN.W.G 0.050 0.062 0.075 0.092 0.107 0.130 0.150
CFM 450 500 570 610 675 730 785
9x18 Throw Ft. 18-30 20-30 22-32 24-34 26-36 26-38 28-40
(23x46) (Mt.) (5.5-9.1) (6.1-9.1) (6.7-9.5) (7.3-10.4) (7.9-11.0) (7.9-11.6) (8.5-12.2)
Tot. Press IN.W.G 0.054 0.067 0.082 0.094 0.115 0.137 0.157
CFM 520 590 650 720 780 850 910
9x21 Throw Ft. 20-32 20-34 22-36 24-38 24-40 27-46 30-50
(23x53) (Mt.) (6.1-9.8) (6.1-10.4) (6.7-11.0) (7.3-11.6) (7.3-12.2) (8.5-14.0) (9.1-15.2)
Tot. Press IN.W.G 0.054 0.069 0.082 0.111 0.121 0.146 0.160
CFM 600 680 750 820 900 960 1050
9x24 Throw Ft. 24-34 24-36 26-38 28-44 28-46 30-48 32-50
(23x61) (Mt.) (7.3-10.4) (7.3-11.0) (7.9-11.6) (8.5-13.4) (8.5-14.0) (9.1-14.6) (9.5-15.2)
Tot. Press IN.W.G 0.055 0.070 0.085 0.104 0.124 0.146 0.166
CFM 620 680 750 810 875
12x15 Throw Ft. 20-30 22-32 24-34 26-36 26-38 26-40 28-40
(30x38) (Mt.) (6.1-9.1) (6.7-9.8) (7.3-10.4) (7.9-11.0) (7.9-11.6) (7.9-12.2) (8.5-12.2)
Tot. Press IN.W.G 0.053 0.066 0.081 0.100 0.119 0.137 0.158
CFM 600 660 750 820 900 970 1050
12x18 Throw Ft. 24-34 24-36 26-38 28-40 28-42 32-46 32-48
(30x46) (Mt.) (7.3-10.4) (7.3-11.0) (7.9-11.6) (8.5-12-2) (8.5-12.8) (9.8-14.0) (9.8-14.6)
Tot. Press IN.W.G 0.056 0.071 0.080 0.106 0.125 0.147 0.167
CFM 800 900 1000 1100 1200 1300 1400
12x24 Throw Ft. 24-38 26-40 30-48 32-50 34-50 34-52 36-54
30x61 (Mt.) (11.0-11.6) (11.0-12.2) (9.1-14.6) (9.5.15.2) (10.4-15.2) (10.4-15.8) (10.0-16.5)
Tot. Press IN.W.G 0.056 0.070 0.087 0.105 0.125 0.141 0.171

Cooling Industries Company www.cic-jo.com 15


Supply Air Diffusers, Square,
Two Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 100 110 120 130 150 160 170
6x6 Throw Ft. 10-12 10-14 10-16 10-18 10-20 10-22 10-24
(15x15) (Mt.) (3.0-3.7) (3.0-4.3) (3.0-4.9) (3.0-5.5) (3.7-6.1) (3.7-6.7) (4.7-7.3)
Tot. Press IN.W.G 0.025 0.063 0.072 0.093 0.111 0.125 0.145
CFM 225 250 275 300 330 360 390
9x9 Throw Ft. 12-20 14-22 16-24 18-26 18-28 18-30 18-34
(23x23) (Mt.) (3.7-6.1) (4.3-6.7) (4.9-7.3) (5.5-7.9) (5.5-8.5) (5.5-9.1) (5.5-10.4)
Tot. Press IN.W.G 0.042 0.051 0.064 0.073 0.086 0.099 0.114
CFM 400 450 500 550 600 650 700
12x12 Throw Ft. 14-24 18-30 20-36 22-38 24-40 26-46 26-48
(30x30) (Mt.) (4.3-7.3) (5.5-9.1) (6.1-11.0) (6.7-11.6) (7.3-12.2) (7.9-14.0) (7.9-14.6)
Tot. Press IN.W.G 0.062 0.076 0.092 0.109 0.129 0.149 0.172
CFM 620 700 780 850 930 1010 1100
15x15 Throw Ft. 24-34 24-36 24-38 28-42 30-46 30-48 30-50
(38x38) (Mt.) (7.3-10.4) (7.3-11.0) (7.3-11.6) (8.5-12.8) (9.1-14.0) (9.1-14.6) (9.1-15.2)
Tot. Press IN.W.G 0.059 0.068 0.088 0.093 0.122 0.144 0.163
CFM 900 1000 1120 1240 1350 1460 1550
18x18 Throw Ft. 24-36 24-38 26-40 28-46 30-48 32-50 32-52
(46x46) (Mt.) (7.3-11.0) (7.3-11.6) (7.9-12.2) (8.5-14.6) (9.1-14.6) (9.5-15.2) (9.5-15.8)
Tot. Press IN.W.G 0.070 0.085 0.101 0.118 0.143 0.166 0.191
CFM 1220 1300 1530 1680 1830 1990 2140
21x21 Throw Ft. 32-36 36-50 36-54 38-56 42-60 42-68 42-70
(53x53) (Mt.) (9.5-14.6) (11.0-15.2) (11.0-16.5) (11.6-17.1) (12.8-18.3) (12.8-20.7) (12.8-21.3)
Tot. Press IN.W.G 0.070 0.086 0.102 0.120 0.144 0.167 0.192
CFM 1600 1800 2000 2200 2400 2600 2800
24x24 Throw Ft. 36-50 40-58 42-62 46-66 46-68 48-70 50-78
(61x61) (Mt.) (11.0-15.2) (12.2-17.7) (12.8-18.9) (14.6-20.1) (14.6-20.7) (14.6-21.3) (15.2-23.8)
Tot. Press IN.W.G 0.072 0.087 0.102 0.121 0.145 0.167 0.195

16 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Rectangular
Two Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 150 170 190 200 225 245 260
6x9 Throw Ft. 10-14 10-18 12-20 14-22 14-26 14-28 14-30
(15x23) (Mt.) (3.0-4.3) (3.0-5.5) (3.7-6.1) (4.3-6.7) (4.3-7.9) (4.3-8.5) (4.3-9.1)
Tot. Press IN.W.G 0.063 0.078 0.094 0.109 0.131 0.152 0.172
CFM 200 225 250 275 300 325 350
6x12 Throw Ft. 16-24 18-26 20-28 20-30 20-36 24-40 24-42
(15x30) (Mt.) (4.9-7.3) (5.5-7.9) (6.1-8.5) (6.1-9.1) (6.1-11.0) (7.3-12.2) (7.3-12.8)
Tot. Press IN.W.G 0.056 0.069 0.090 0.107 0.129 0.144 0.167
CFM 300 330 375 410 450 480 530
9x12 Throw Ft. 16-24 18-26 20-28 20-32 20-36 24-40 21-42
(23x30) (Mt.) (4.9-7.3) (5.5-7.9) (6.1-8.5) (6.1-9.5) (6.1-11.0) (7.3-12.2) (7.3-12.8)
Tot. Press IN.W.G 0.050 0.074 0.089 0.107 0.125 0.143 0.161
CFM 375 422 470 510 560 610 650
9x15 Throw Ft. 18-28 20-30 20-32 20-36 22-38 24-42 24-44
(23x38) (Mt.) (5.5-8.5) (6.1-9.1) (6.1-9.5) (6.1-11.0) (6.7-11.6) (7.3-12.8) (7.3-13.4)
Tot. Press IN.W.G 0.054 0.075 0.095 0.112 0.123 0.156 0.176
CFM 450 500 560 600 675 731 780
9x18 Throw Ft. 18-30 20-32 24-34 24-36 24-38 26-42 26-46
(23x46) (Mt.) (5.5-9.1) (6.1-9.5) (7.3-10.4) (7.3-11.0) (7.3-11.6) (11.0-12.8) (11.0-14.0)
Tot. Press IN.W.G 0.065 0.079 0.096 0.113 0.137 0.152 0.180

Cooling Industries Company www.cic-jo.com 17


Supply Air Diffusers, Rectangular
Two Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 250 600 650 720 780 850 910
9x21 Throw Ft. 22-30 22-34 22-36 24-38 24-40 28-44 28-48
(23x53) (Mt.) (6.7-9.1) (6.7-10.4) (7.3-11.0) (7.3-11.6) (7.3-12.3) (8.5-13.4) (8.5-14.6)
Tot. Press IN.W.G 0.054 0.066 0.080 0.093 0.110 0.126 0.145
CFM 500 560 625 680 750 820 870
12x15 Throw Ft. 20-30 22-36 24-38 24-40 24-42 26-46 28-48
(30x38) (Mt.) (6.1-9.1) (6.7-11.0) (7.3-11.6) (7.3-12.2) (7.9-12.8) (7.9-14.0) (8.5-14.6)
Tot. Press IN.W.G 0.064 0.080 0.095 0.114 0.136 0.156 0.185
CFM 600 675 750 825 900 975 1050
12x18 Throw Ft. 22-32 24-34 24-36 24-38 28-42 30-46 30-50
(30x46) (Mt.) (6.7-9.5) (7.3-10.4) (7.3-11.0) (7.3-11.6) (8.5-12.8) (9.1-14.0) (9.1-15.2)
Tot. Press IN.W.G 0.067 0.081 0.098 0.116 0.136 0.157 0.182
CFM 700 780 875 960 1050 1140 1250
12x21 Throw Ft. 24-36 24-38 26-42 26-44 26-46 26-50 30-52
(30x53) (Mt.) (7.3-11.0) (7.3-11.6) (7.9-12.9) (7.9-13.9) (7.9-14.0) (7.9-15.2) (9.1-15.8)
Tot. Press IN.W.G 0.062 0.080 0.096 0.117 0.137 0.160 0.187
CFM 720 800 1000 1100 1200 1300 1400
12x24 Throw Ft. 26-38 28-42 30-46 30-48 32-50 34-54 34-56
(30x61) (Mt.) (7.9-11.6) (8.5-12.8) (9.1-14.0) (9.1-14.6) (9.5-15.2) (10.4-16.5) (10.4-17.1)
Tot. Press IN.W.G 0.065 0.082 0.099 0.118 0.138 0.161 0.188

18 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Square,
Three Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 100 110 125 135 150 160 175
6x6 Throw Ft. 4-10 4-12 6-14 6-16 8-18 10-20 12-22
(15x15) (Mt.) (1.2-3.0) (1.2-3.7) (1.8-4.3) (1.8-4.9) (2.4-5.5) (3.0-6.1) (3.7-6.7)
Tot. Press IN.W.G 0.043 0.052 0.064 0.075 0.088 0.100 0.117
CFM 225 250 280 310 335 365 390
9x9 Throw Ft. 8-12 10-16 10-18 12-18 12-20 12-22 12-24
(23x23) (Mt.) (2.4-3.7) (3.0-4.9) (3.0-5.5) (3.7-5.5) (3.7-6.1) (3.7-6.7) (3.7-7.3)
Tot. Press IN.W.G 0.047 0.059 0.070 0.083 0.098 0.111 0.129
CFM 400 450 500 550 600 650 700
12x12 Throw Ft. 12-18 14-18 14-20 14-26 14-28 16-30 16-24
(30x30) (Mt.) (3.7-5.5) (3.7-5.5) (4.3-6.1) (4.3-7.9) (4.3-8.5) (4.9-9.1) (4.9-7.3)
Tot. Press IN.W.G 0.050 0.060 0.074 0.088 0.104 0.120 0.140
CFM 624 700 780 860 935 1015 1090
15x15 Throw Ft. 14-20 14-24 14-26 14-28 16-30 16-32 16-34
(38x38) (Mt.) (4.3-6.1) (4.3-7.3) (4.3-7.9) (4.3-8.5) (4.9-9.1) (4.9-9.5) (4.9-10.4)
Tot. Press IN.W.G 0.049 0.062 0.075 0.088 0.104 0.120 0.140
CFM 900 1010 1125 1240 1350 1460 1575
18x18 Throw Ft. 16-24 18-28 20-30 20-36 20-28 22-40 24-40
(46x46) (Mt.) (4.9-7.3) (5.5-8.5) (6.1-9.1) (6.1-11.0) (6.1-11.6) (6.7-12.2) (7.3-12.2)
Tot. Press IN.W.G 0.061 0.076 0.093 0.112 0.130 0.151 0.173
CFM 1600 1800 2000 2200 2400 2600 2800
24x24 Throw Ft. 22-36 24-30 24-40 26-46 30-48 30-50 32-56
(61x61) (Mt.) (6.7-11.0) (7.3-9.1) (7.3-12.2) (7.9-14.6) (9.1-14.6) (9.1-15.2) (9.5-17.1)
Tot. Press IN.W.G 0.064 0.083 0.102 0.119 0.139 0.158 0.182

Cooling Industries Company www.cic-jo.com 19


Supply Air Diffusers, Rectangular
Three Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 150 170 190 205 225 245 260
6x9 Throw Ft. 6-12 8-14 8-16 8-18 8-20 10-24 10-26
(15x23) (Mt.) (1.7-3.7) (2.4-4.3) (4.2-4.9) (2.4-5.5) (2.4-6.1) (3.0-7.3) (3.0-7.9)
Tot. Press IN.W.G 0.045 0.056 0.067 0.081 0.095 0.109 0.126
CFM 200 225 250 275 300 325 350
6x12 Throw Ft. 8-14 8-16 10-18 10-20 10-22 10-26 10-28
(15x30) (Mt.) (2.4-4.3) (2.4-4.9) (3.0-5.5) (3.0-6.1) (3.0-6.7) (3.0-7.9) (3.0-8.5)
Tot. Press IN.W.G 0.042 0.051 0.064 0.074 0.088 0.101 0.118
CFM 250 280 310 345 375 405 440
6x15 Throw Ft. 10-16 10-18 10-20 10-22 12-24 12-28 14-30
(15x38) (Mt.) (3.0-4.9) (3.0-5.5) (3.0-6.1) (3.0-6.7) (3.7-7.3) (3.7-8.5) (4.3-9.1)
Tot. Press IN.W.G 0.049 0.061 0.072 0.086 0.101 0.115 0.133
CFM 300 340 375 415 450 490 525
9x12 Throw Ft. 10-16 10-18 12-20 12-24 12-26 12-28 14-30
(23x30) (Mt.) (3.0-4.9) (3.0-5.5) (3.7-6.1) (3.7-7.3) (3.7-7.9) (3.7-8.5) (4.3-9.1)
Tot. Press IN.W.G 0.052 0.064 0.078 0.093 0.109 0.114 0.136
CFM 375 420 470 515 565 610 655
9x15 Throw Ft. 12-18 12-20 12-24 14-26 14-28 16-30 16-32
(23x38) (Mt.) (3.7-5.5) (3.7-6.1) (3.7-7.3) (4.3-7.9) (4.3-8.5) (4.9-9.1) (4.9-9.8)
Tot. Press IN.W.G 0.050 0.063 0.076 0.090 0.106 0.124 0.137

20 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Rectangular
Three Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 450 505 565 620 675 730 790
9x18 Throw Ft. 12-20 14-22 14-26 14-28 16-30 16-32 16-34
(23x46) (Mt.) (3.7-6.1) (4.3-6.7) (4.3-7.9) (4.3-8.5) (4.9-9.1) (4.9-9.8) (4.9-10.4)
Tot. Press IN.W.G 0.051 0.064 0.073 0.087 0.103 0.117 0.133
CFM 525 590 655 720 785 850 915
9x21 Throw Ft. 14-22 14-24 14-28 16-30 16-34 18-36 18-38
(23x53) (Mt.) (4.3-6.7) (4.3-7.3) (4.3-8.5) (4.9-9.1) (4.9-10.4) (5.5-11.0) (5.5-11.6)
Tot. Press IN.W.G 0.048 0.063 0.072 0.085 0.102 0.116 0.134
CFM 600 675 750 825 900 975 1050
9x24 Throw Ft. 14-24 14-26 16-28 18-30 18-34 18-38 18-40
(23x61) (Mt.) (4.3-7.3) (4.3-7.9) (4.9-8.5) (5.5-9.1) (5.5-10.4) (5.5-11.6) (5.5-12-2)
Tot. Press IN.W.G 0.051 0.062 0.076 0.090 0.108 0.121 0.141
CFM 500 560 625 690 750 815 875
12x15 Throw Ft. 14-24 14-26 16-28 18-30 18-32 18-34 18-36
(30x38) (Mt.) (4.3-7.3) (4.3-7.9) (4.9-8.5) (5.5-9.1) (5.5-9.5) (5.5-10.4) (5.5-11.0)
Tot. Press IN.W.G 0.051 0.065 0.074 0.088 0.103 0.118 0.136
CFM 600 675 750 825 900 975 1050
12x18 Throw Ft. 16-26 16-30 16-34 18-36 18-38 18-40 20-42
(30x46) (Mt.) (4.9-7.9) (4.9-9.1) (4.9-10.4) (4.9-11.0) (4.9-11.6) (4.9-12.2) (6.1-12.8)
Tot. Press IN.W.G 0.050 0.061 0.075 0.089 0.107 0.120 0.140

Cooling Industries Company www.cic-jo.com 21


Supply Air Diffusers, Square
Four Way Flow Pattern
Performance Data

Size
Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 100 110 120 130 150 160 175
6x6 Throw Ft. 4-10 4-12 6-14 6-16 6-18 8-20 8-22
(15x15) (Mt.) (1.2-3.0) (1.2-3.7) (1.8-4.3) (1.8-4.9) (1.8-5.5) (2.4-6.1) (2.4-6.7)
Tot. Press IN.W.G 0.035 0.042 0.054 0.060 0.072 0.081 0.095
CFM 220 250 280 300 330 360 390
9x9 Throw Ft. 6-12 6-14 8-16 10-18 10-20 10-22 10-24
(23x23) (Mt.) (1.8-3.7) (1.8-4.3) (2.4-4.9) (3.0-5.5) (3.0-6.1) (3.0-6.7) (3.0-7.3)
Tot. Press IN.W.G 0.043 0.056 0.063 0.074 0.087 0.090 0.115
CFM 400 450 500 550 600 650 700
12x12 Throw Ft. 8-14 10-16 12-18 14-22 14-24 16-26 16-28
(30x30) (Mt.) (2.4-4.3) (3.0-4.9) (3.7-5.5) (4.3-6.7) (4.3-7.3) (4.9-7.9) (4.9-8.5)
Tot. Press IN.W.G 0.046 0.055 0.069 0.082 0.095 0.098 0.127
CFM 624 700 780 850 930 1010 1100
15x15 Throw Ft. 12-20 14-22 16-24 16-26 18-28 20-30 20-32
(38x38) (Mt.) (3.1-6.1) (4.3-6.7) (4.9-7.3) (4.9-7.9) (6.1-8.5) (6.1-9.1) (6.1-9.8)
Tot. Press IN.W.G 0.048 0.064 0.077 0.087 0.101 0.116 0.135
CFM 900 1010 1120 1240 1350 1460 1550
18x18 Throw Ft. 16-24 18-26 20-30 20-32 20-34 20-36 20-30
(46x46) (Mt.) (4.9-7.3) (5.5-7.9) (6.1-9.1) (6.1-9.8) (6.1-10.4) (6.1-11.0) (6.1-11.6)
Tot. Press IN.W.G 0.053 0.065 0.079 0.102 0.105 0.123 0.141
CFM 1220 1380 1530 1680 1830 1990 2160
21x21 Throw Ft. 18-30 20-32 24-34 24-36 24-38 26-40 26-42
(53x53) (Mt.) (5.5-9.1) (6.1-9.8) (7.3-10.4) (7.3-11.0) (7.3-11.6) (7.9-12.2) (7.9-12.8)
Tot. Press IN.W.G 0.055 0.067 0.080 0.110 0.111 0.126 0.144
CFM 1600 1800 2000 2200 2400 2700 2900
24x24 Throw Ft. 22-34 24-36 24-38 26-40 28-46 30-48 30-50
(61x61) (Mt.) (6.7-10.4) (7.3-11.0) (7.3-11.6) (7.9-12.2) (8.5-14.0) (9.1-14.6) (9.1-15.2)
Tot. Press IN.W.G 0.059 0.070 0.082 0.111 0.112 0.128 0.147
CFM 3600 4000 4500 5000 5500 6000 6500
36x36 Throw Ft. 30-50 34-54 36-56 40-60 42-64 46-68 48-70
(91x91) (Mt.) (9.1-15.2) (10.4-16.5) (11.0-17.1) (12.2-18.3) (12.8-19.5) (14.0-20.7) (14.6-21.3)
Tot. Press IN.W.G 0.064 0.082 0.096 0.129 0.134 0.163 0.182
CFM 6500 7300 8000 9000 9500 10500 11500
48x48 Throw Ft. 46-66 50-72 52-76 56-78 58-83 60-85 60-90
(122x122) (Mt.) (14.0-20.1) (15.2-21.9) (15.8-23.2) (17.1-23.8) (17.7-25.3) (18.3-25.9) (18.3-27.4)
Tot. Press IN.W.G 0.064 0.089 0.097 0.115 0.140 0.152 0.186

22 www.cic-jo.com Cooling Industries Company


Supply Air Diffusers, Rectangular
Four Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 150 160 170 200 220 240 260
6x9 Throw Ft. 4-10 6-12 8-14 8-16 8-18 8-20 8-22
(15x23) (Mt.) (1.2-3.0) (1.8-3.7) (2.4-4.3) (2.4-4.9) (2.4-5.5) (2.4-6.1) (2.4-6.7)
Tot. Press IN.W.G 0.034 0.041 0.050 0.058 0.067 0.079 0.090
CFM 200 225 250 275 300 325 350
6x12 Throw Ft. 6-12 8-14 8-16 10-18 10-20 10-22 12-24
(15x30) (Mt.) (1.8-3.7) (2.4-4.3) (2.4-4.9) (3.0-5.5) (3.0-6.1) (3.0-6.7) (3.7-7.3)
Tot. Press IN.W.G 0.040 0.049 0.059 0.069 0.082 0.092 0.108
CFM 300 325 375 410 450 480 510
9x12 Throw Ft. 8-14 10-16 12-18 12-20 14-22 14-24 14-26
(23x30) (Mt.) (2.4-4.3) (3.0-4.9) (3.7-5.5) (3.7-6.1) (4.3-6.7) (4.3-7.3) (4.3-7.9)
Tot. Press IN.W.G 0.043 0.053 0.063 0.074 0.086 0.099 0.113
CFM 375 420 470 510 560 610 650
9x15 Throw Ft. 10-16 12-18 14-20 14-22 14-24 14-26 14-28
(23x38) (Mt.) (3.0-4.9) (3.7-5.5) (4.3-6.1) (4.3-6.7) (4.3-7.3) (4.3-7.9) (4.3-8.5)
Tot. Press IN.W.G 0.043 0.053 0.061 0.066 0.089 0.104 0.117
CFM 450 500 560 610 675 780 800
9x18 Throw Ft. 12-18 14-20 14-22 14-24 14-26 14-28 14-30
(23x46) (Mt.) (3.1-5.5) (4.3-6.1) (4.3-6.7) (4.3-7.3) (4.3-7.9) (4.3-8.5) (4.3-9.1)
Tot. Press IN.W.G 0.079 0.061 0.075 0.086 0.111 0.115 0.134
CFM 510 600 650 730 780 850 900
9x21 Throw Ft. 12-20 14-22 14-24 16-26 16-28 16-30 17-36
(23x53) (Mt.) (3.7-6.1) (4.3-6.7) (4.3-7.3) (4.9-7.9) (4.9-8.5) (4.9-9.1) (5.5-11.0)
Tot. Press IN.W.G 0.051 0.063 0.076 0.089 0.114 0.118 0.136

Cooling Industries Company www.cic-jo.com 23


Supply Air Diffusers, Rectangular
Four Way Flow Pattern
Performance Data

Size Neck Velocity FPM. 400 450 500 550 600 650 700
In
Inches
Vel. Pressure (IN. W. G) 0.012 0.015 0.019 0.022 0.024 0.029 0.033
(CMS)
CFM 500 650 600 680 750 800 870
12x15 Throw Ft. 12-22 14-24 14-26 14-28 16-30 16-32 16-38
(30x38) (Mt.) (3.7-6.7) (4.3-7.3) (4.3-7.9) (4.3-8.5) (4.9-9.1) (4.9-9.8) (4.9-11.6)
Tot. Press IN.W.G 0.049 0.063 0.076 0.087 0.111 0.116 0.135
CFM 600 675 750 825 900 975 1080
12x18 Throw Ft. 14-22 14-26 16-28 16-30 18-34 18-36 18-38
(30x46) (Mt.) (4.3-6.7) (4.3-7.9) (4.9-8.5) (4.9-9.1) (5.5-10.4) (5.5-11.0) (5.5-11.6)
Tot. Press IN.W.G 0.050 0.061 0.075 0.088 0.110 0.117 0.136
CFM 800 900 1000 1100 1200 1300 1400
12x24 Throw Ft. 16-26 18-28 18-36 20-38 20-40 20-42 20-44
(30x61) (Mt.) (4.9-7.9) (5.5-8.5) (5.5-11.0) (6.1-11.6) (6.1-12.2) (6.1-12.8) (6.1-13.7)
Tot. Press IN.W.G 0.053 0.065 0.078 0.091 0.107 0.122 0.141
CFM 750 800 900 1000 1100 1200 1310
15x18 Throw Ft. 16-28 16-30 18-38 18-40 20-42 20-44 20-46
(38x46) (Mt.) (4.5-8.5) (4.9-9.1) (5.5-11.6) (5.5-12.2) (6.1-12.8) (6.1-13.7) (6.1-14.0)
Tot. Press IN.W.G 0.049 0.065 0.077 0.091 0.105 0.121 0.137
CFM 1200 1300 1500 1600 1800 2000 2100
18x24 Throw Ft. 20-36 24-40 24-42 26-44 26-46 26-48 26-50
(46x61) (Mt.) (6.1-11.0) (7.3-12.3) (7.3-12.8) (7.9-13.7) (7.9-14.0) (7.9-14.6) (7.9-15.2)
Tot. Press IN.W.G 0.055 0.069 0.081 0.094 0.112 0.125 0.143

24 www.cic-jo.com Cooling Industries Company


Return Air Diffusers
Performance Data

Model: CI - Air RD - S4

Anemometer Velocity
100 150 200 250 300 350 400 450 500 550
FPM

Negative Static Pressure


0.008 0.016 0.030 0.050 0.070 0.090 0.120 0.160 0.200 0.280
(Inches of Water)

Size
Inch. C.F.M. Range
(Cms)
6x6
40 50 65 80 100 105 120 145 165 170
(15x15)
6x9
50 70 95 120 140 165 190 215 240 260
(15x23)
6x12
60 90 120 150 185 215 245 275 305 335
(15x30)
9x9
70 100 135 170 205 240 275 310 345 375
(23x23)
9x12
85 130 170 215 260 300 345 385 430 470
(23x30)
9x15
105 155 205 255 310 360 410 460 510 565
(23x38)
12x12
110 160 215 270 325 380 435 485 540 595
(30x30
12x15
125 195 255 325 400 455 520 565 650 710
(30x38)
12x18
155 230 305 385 460 535 610 690 765 840
(30x46)
12x21
175 265 355 440 430 620 710 795 880 970
(30x53)

Cooling Industries Company www.cic-jo.com 25


Return Air Diffusers
Performance Data
Model: CI - Air RD - S4

Anemometer Velocity
100 150 200 250 300 350 400 450 500 550
FPM

Negative Static Pressure


0.008 0.016 0.030 0.050 0.070 0.090 0.120 0.160 0.200 0.280
(Inches of Water)

Size
Inch. C.F.M. Range
(Cms)
15x15
160 240 320 400 475 555 640 715 795 870
(38x38)
15x18
185 280 375 465 560 655 750 840 935 1030
(38x46)
15x21
215 325 435 540 650 755 865 970 1080 1190
(38x53)
15x24
245 365 490 610 730 680 975 1100 1220 1340
(38x61)
18x18
220 335 445 555 670 780 890 990 1110 1225
(46x46)
18x21
255 380 510 640 770 895 1030 1160 1260 1415
(46x53)
18x24
300 440 580 730 880 1025 1165 1320 1460 1610
(46x61)
21x21
300 450 590 750 920 1040 1200 1330 1500 1650
(53x53)
21x24
335 500 675 840 1015 1180 1340 1520 1700 1860
(53x61)
24x24
380 580 780 970 1150 1360 1560 1740 1940 2120
(61x61)

26 www.cic-jo.com Cooling Industries Company


Diffuser Accessories

· Opposed Blade Dampers


Application :

O.B.D. For Volume Control.

Features and Installation :

Opposed Blade assures precision control of air volume with a


minimum of noise.
The opposed blade damper section connects to the frame
with a screw and is operated by either a lever from the side or
hidden screw.

Material and Finish :

Extruded aluminium construction, with powder coated black


finish.

· Equalizing Grid
Application :

Equalizing grid for equalization of air flow, directional control and minor adjustments of air flow.

Features and Installation :

The Equalizing grid is available as an accessory above the diffuser to provide uniform air flow over the
surface of the diffuser face.
The blades are individually adjustable to allow additional control when needed.
The blades spaced on 3/4" centres, help to control the air flow in a linear manner, reducing pressure losses
enabling the over all system to run more efficiently.

Material and Finish :

Extruded aluminium construction, with powder


coated black finish.

Cooling Industries Company www.cic-jo.com 27


Diffuser Accessories
Installation Details

28 www.cic-jo.com Cooling Industries Company


Perforated Diffuser
Perforated Ceiling Diffusers

Model: CI - Air - PD

Features:

1- Perforated face plate is made of mild steel (removable type)


of thickness 1mm includes powder coated.
2- 4-3-2 or 1 Way air pattern controller and external frame are
made of extruded aluminium, in powder coated finish same
as that of perforated face plate.

CI - Air - PD
· Construtional Details & Dimensions
Perforated Diffusers Engineering and Performance data. The tabulated performance Data includes Area
factor, Throw pattern, Discharge velocity and Sound power level.

Air Flow Rate: Air volumes are given in CFM

Throw T: The throw values given in the tables are related to the perforated diffuser placed
nearer to the ceiling. Two throw values are given for each qv to the corresponding
terminal velocities Vt.
Minimum throw 50 FPM Vt
Maximum Throw 100 FPM Vt

Neck Velocity Vk: The effective discharge velocities given are related to the corresponding effective
free area Ak.

NC Values: Noise data is given in terms of NC levels. These have been derived from sound
power level data ( dB 10-12 watts ) by subtracting 10 dB ( Room effect ) from the
sound power levels.

Neck Size: Outlet sizes are mentioned on the left side of each row within a tolerance of ±10%.

Cooling Industries Company www.cic-jo.com 29


Perforated Ceiling Diffusers
Performance Data

Neck Size Neck Area Neck Velocity, FPM 300 400 500 600 700 800 1000 1200 1400
(Inches) (Sq. ft.) Velocity Pressure, in. W.G. 0.006 0.010 0.016 0.023 0.031 0.040 0.063 0.090 0.123
Total Pressure, in. W.G 0.013 0.023 0.037 0.053 0.072 0.094 0.147 0.211 0.287
Flow Rate, CFM 75 100 125 150 175 200 250 300 350
NC <20 <20 <20 23 26 29 37 43 48
6x6 0.25 4 - way 1-1 1-2 1-3 1-4 1-5 2-6 3-8 4-9 5-11
3 - way 1-3 1-5 2-6 3-8 4-9 5-10 6-13 8-16 9-17
Throw, Feet
2 - way 1-4 2-7 3-9 4-10 6-12 7-14 9-18 10-19 12-21
1 - way 1-6 2-8 4-11 6-13 7-15 8-17 11-20 13-22 15-24
Total Pressure, in. W.G 0.018 0.031 0.049 0.071 0.096 0.126 0.196 0.283 0.385
Flow Rate, CFM 133 177 222 266 310 355 444 532 621
NC <20 <20 23 27 31 35 43 49 >50
8x8 0.44 4 - way 1-2 1-4 1-6 2-7 3-8 4-9 6-12 7-14 8-17
3 - way 1-5 2-8 4-10 5-12 7-14 8-16 10-20 12-24 14-26
Throw, Feet
2 - way 2-8 4-10 6-13 8-16 9-19 10-21 13-26 16-29 19-31
1 - way 3-9 5-13 8-16 9-19 11-23 13-26 16-30 19-33 23-35
Total Pressure, in. W.G 0.022 0.039 0.061 0.088 0.119 0.156 0.243 0.350 0.477
Flow Rate, CFM 208 277 347 416 485 555 694 832 971
NC <20 22 27 31 35 40 47 >50 >50
10x10 0.69 4 - way 1-4 2-6 3-8 4-10 5-11 6-13 8-16 10-20 11-23
3 - way 2-8 4-11 6-13 8-16 9-19 11-22 13-27 16-32 19-35
Throw, Feet
2 - way 3-11 6-14 9-18 11-22 13-26 14-29 18-36 22-39 26-43
1 - way 5-13 9-18 11-22 13-27 16-32 18-36 22-41 27-45 32-49
Total Pressure, in. W.G 0.026 0.047 0.073 0.105 0.144 0.188 0.293 0.422 0.574
Flow Rate, CFM 300 400 500 600 700 800 1000 1200 1400
NC <20 25 30 34 39 43 >50 >50 >50
12x12 1.00 4 - way 1-6 3-8 4-11 6-13 7-15 8-17 11-22 13-26 15-30
3 - way 3-10 6-14 9-18 10-21 12-25 14-28 18-36 21-42 25-45
Throw, Feet
2 - way 5-14 9-19 12-24 14-29 17-34 19-39 24-46 29-51 34-55
1 - way 8-17 11-23 14-29 17-35 20-41 23-47 29-53 35-58 41-63

30 www.cic-jo.com Cooling Industries Company


Perforated Ceiling Diffusers
Performance Data

Neck Size Neck Area Neck Velocity, FPM 300 400 500 600 700 800 1000 1200 1400
(Inches) (Sq. ft.) Velocity Pressure, in. W.G. 0.006 0.010 0.016 0.023 0.031 0.040 0.063 0.090 0.123
Total Pressure, in. W.G 0.030 0.055 0.085 0.122 0.169 0.220 0.343 0.494 0.671
Flow Rate, CFM 408 544 680 816 952 1088 1360 1632 1904
NC <20 27 32 36 41 46 >50 >50 >50
14x14 1.36 4 - way 1-8 4-10 5-13 8-16 9-19 10-22 14-28 16-32 19-37
3 - way 4-12 8-17 12-23 13-26 15-31 17-34 23-45 26-52 31-55
Throw, Feet
2 - way 7-17 12-24 15-30 17-36 22-42 24-49 30-56 36-62 42-67
1 - way 11-21 14-28 17-36 21-43 24-50 28-58 36-65 44-67 50-77
Total Pressure, in. W.G 0.034 0.063 0.097 0.139 0.194 0.252 0.393 0.566 0.768
Flow Rate, CFM 534 712 890 1068 1246 1424 1780 2136 2492
NC 22 29 34 39 44 >50 >50 >50 >50
16x16 1.78 4 - way 1-10 5-12 6-15 10-19 11-23 12-27 17-34 19-38 23-43
3 - way 5-14 10-20 14-28 16-31 18-37 20-40 28-54 31-62 37-65
Throw, Feet
2 - way 9-20 15-29 18-36 20-43 27-50 29-59 36-66 43-73 50-79
1 - way 17-25 17-33 20-43 25-51 28-59 33-69 43-77 53-84 59-94
Total Pressure, in. W.G 0.036 0.071 0.109 0.156 0.209 0.284 0.443 0.638 0.865
Flow Rate, CFM 675 900 1125 1350 1575 1800 2250 2700 3150
NC 23 31 36 42 >50 >50 >50 >50 >50
18x18 2.25 4 - way 1-12 6-14 7-17 12-22 13-27 14-32 20-40 22-44 27-50
3 - way 6-16 12-23 16-32 18-36 21-43 23-46 33-63 36-72 43-75
Throw, Feet
2 - way 11-23 18-34 21-42 23-50 32-58 34-69 42-77 50-84 58-91
1 - way 17-29 20-38 23-50 29-59 32-68 38-50 50-89 62-97 68-108
Negative SP, in. W.G 0.024 0.043 0.068 0.098 0.133 0.174 0.271 0.391 0.532
Return
3.36 Flow Rate, CFM 1008 1344 1680 2016 2352 2688 3360 4032 4704
22x22
NC <20 <20 <20 <20 22 26 34 40 46

Cooling Industries Company www.cic-jo.com 31


LINEAR SLOT DIFFUSER

Page Contents

2 Linear Slot Supply Air Diffuser 3/4"


3 Linear Slot Return Air Diffuser 3/4"
4 Linear Slot Supply Air Diffuser 1"
5 Linear Slot Return Air Diffuser 1"
6 Linear Slot Supply Air Diffuser - Adjustable Blade Configurations
7 Linear Slot Diffuser - Mounting Methods
8 Linear Slot Diffuser - Engineering Data
9 Linear Slot Supply Air Diffuser - Performance Data
12 Linear Slot Return Air Diffuser - Performance Data
13 Curved Linear Slot Diffuser
Linear Slot Supply Air Diffuser
Linear With Deflection Blades and Volume Control Damper

Model: CILS - AD 3/4"

Features:

The linear slot diffuser with deflection blades and control


damper is constructed of extruded anodized aluminum as
standard, painted, for powder coated are available on
request, the damper has black finish, The fully adjustable
defection blades allow for the air pattern to be controlled
along the ceiling straight down or at some intermediate
setting.
The deflecting blades are designed so that when in the CILS - AD 3/4"
closed position the air pressure tends to form a tight seal.

The air flow rate can be varied without changing the air pattern by the use of the vo ume control damper
attached to the rear side of the diffuser.
The volume control damper consists of two strips of extruded aluminum, one fixed and one movable.
They both have 5/8” x 7/8” rectangular holes on 1-3/4” center.
By offsetting the holes the air flow rate can be redused.

CILS - AD 3/4"

Listed Sizes (cm)

No of Slots 1 2 3 4 5 6 7 8
A (cm) 4.5 8 11.7 15.3 19 22.5 26.2 29.8
B (cm) 4.2 7.3 11 14.6 18.3 21.8 25.5 29.1
C (cm) 8 11.1 14.8 18.4 22.1 25.6 29.3 32.9

2 www.cic-jo.com Cooling Industries Company


Linear Slot Return Air Diffuser
Linear Slot Diffuser With Deflection Blades and Without Volume
Control Damper

Model: CILR - D 3/4"

Features:

The linear slot diffuser with deflection blades is constructed


of extruded anodized aluminum as standards, painted,
powder coated are available on request.

The fully adjustable deflection blades allow for the air


pattern to be controlled along the ceiling, straight down
or at some intermediate setting.
CILR - D 3/4"

The deflection blades are designed so that when in the closed position the air pressure tends to form a
tight seal.

CILR - D 3/4"

Listed Sizes (cm)

No of Slots 1 2 3 4 5 6 7 8
A (cm) 4.5 8 11.7 15.3 19 22.5 26.2 29.8
B (cm) 4.2 7.3 11 14.6 18.3 21.8 25.5 29.1
C (cm) 8 11.1 14.8 18.4 22.1 25.6 29.3 32.9

Cooling Industries Company www.cic-jo.com 3


Linear Slot Supply Air Diffuser
Linear Slot Diffuser With Deflection Blades and With Volume
Control Damper

Model: CILS - AD1"

Features:

The linear slot diffuser with deflection blades is constructed


of extruded anodized aluminum as standards, painted,
powder coated are available on request.

The fully adjustable deflection blades allow for the air


pattern to be controlled along the ceiling, straight down or
at some intermediate setting.
CILS - AD1"

The deflection blades are designed so that when in the closed position the air pressure tends to form
a tight seal.

CILS - AD1"

Listed Sizes (cm)

No of Slots 1 2 3 4 5 6 7 8
A (cm) 5.2 9.5 13.6 17.8 22.1 26.2 30.4 34.6
B (cm) 4.3 8.5 12.7 16.9 21.1 25.2 29.4 33.6
C (cm) 8.2 12.4 16.6 20.9 25 29.2 33.4 37.6

4 www.cic-jo.com Cooling Industries Company


Linear Slot Return Air Diffuser
Linear Slot Diffuser With Deflection Blades and Without Volume
Control Damper

Model: CILR - D1"

Features:

The linear slot diffuser with deflection blades is constructed


of extruded anodized aluminum as standards, painted,
powder coated are available on request.

The fully adjustable deflection blades allow for the air


pattern to be controlled along the ceiling, straight down or
at some intermediate setting.
CILR - D1"

The deflection blades are designed so that when in the closed position the air pressure tends to form
a tight seal.

CILR - D1"

Listed Sizes (cm)

No of Slots 1 2 3 4 5 6 7 8
A (cm) 5.4 9.9 14.4 18.9 23.4 27.6 32.3 36.8
B (cm) 4.7 9.2 13.7 18.2 22.7 27.2 31.7 36.2
C (cm) 8.4 12.8 17.3 21.8 26.3 30.8 35.3 39.8

Cooling Industries Company www.cic-jo.com 5


Linear Slot Supply Air Diffuser Adjustable Blade Configurations
The Deflection Blades Provide Combination Air-Pattern, Flow Rate
Control and Blank-Off

Single Slot Adjustments:

Multiple Slot Adjustments, Up to 8 Slots Wide:

6 www.cic-jo.com Cooling Industries Company


Linear Slot Diffuser
Mounting Methods

Universal Bracket Mounting Method:

Suspension Mounted:

Cooling Industries Company www.cic-jo.com 7


Linear Slot Diffuser
Engineering Data

Blade Settings:

The deflection blades of the supply slot linear diffuser


can be adjusted to give either a horizontal or vertical air
pattern.
The horizontal air flow adjustment may be set for either
left or right hand throw.

Throw Data:

All throw data is based on the results of tests of 4-foot


Changing the blade setting also changes the noise and
length diffusers. To determine throws for other diffuser total pressure
lengths, use correction factors as follows:

Selection Procedure
Diffuser Active Length (ft) 1 2 3 4 6-8
The horizontal throw data is presented in
Throw Correction Factor 0.6 0.8 0.9 1.0 1.3 the performance data pages with all slots
supplying air in a given direction.
Sound Data: To determine two-way throw, use the catalog
throw data for the desired quantity of air from
Sound data (NC values) shown in the Performance the number of slots in each direction and
Tables are based on a room absorption of 10dB, reduce the throw by twenty percent.
10-12 watts and a 4-foot unit test length.
Example:
To determine NC Values for other lengths, add NC val-
ue to catalog data as follows: Determine the throw for a 4 ft long, 3-slot
diffuser with 240 CFM in one direction, and
Diffuser Active Length (ft) 2 3 4 5 6-8 120 CFM in the other.
Add NC Value -3.0 -1.5 0 1.0 2.0
A) 240 CFM, 4’ ,2-slots = 60 CFM/ft
Catalog throws = 17-24
Throws x 0.80 = 14-19

B) 120 CFM, 4’ ,1-slot = 30 CFM/ft


Catalog throws = 12-17
Throws x 0.80 = 10-14

8 www.cic-jo.com Cooling Industries Company


Linear Slot Supply Air Diffuser
Performance Data
Ak = Free Area Ft2

Model: CILS - AD 1/2"


Ak= 0.005 Ak= 0.037 Ak= 0.028 Ak= 0.031
No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
10 0.033 4-8 <20 0.018 <20 50 0.045 9-18 <20 0.028 <20
20 0.134 8-14 22 0.072 <20 100 0.180 18-30 22 0.110 <20
1 5
30 0.300 12-17 25 0.158 22 150 0.405 25-34 25 0.248 22
40 0.535 14-20 30 0.284 25 200 0.720 29-41 30 0.440 25

Ak= 0.011 Ak= 0.016 Ak= 0.033 Ak= 0.036


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
20 0.038 5-12 <20 0.022 <20 60 0.047 11-20 <20 0.029 <20
40 0.153 12-19 22 0.086 <20 120 0.188 20-33 22 0.116 <20
2 6
60 0.344 17-24 25 0.193 22 180 0.423 29-40 25 0.261 22
80 0.610 19-28 30 0.344 25 240 0.750 33-47 30 0.465 25

Ak= 0.016 Ak= 0.021 Ak= 0.039 Ak= 0.041


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
30 0.041 7-14 <20 0.024 <20 70 0.048 11-22 <20 0.030 <20
60 0.164 14-24 22 0.095 <20 140 0.192 22-36 22 0.122 <20
3 7
90 0.370 20-29 25 0.213 22 210 0.434 31-42 25 0.273 22
120 0.660 24-35 30 0.382 25 280 0.770 36-51 30 0.489 25

Ak= 0.022 Ak= 0.025 Ak= 0.045 Ak= 0.046


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
40 0.043 8-16 <20 0.026 <20 80 0.049 12-23 <20 0.031 <20
80 0.172 16-27 22 0.104 <20 160 0.198 24-38 22 0.124 <20
4 8
120 0.388 24-33 25 0.235 22 240 0.444 33-45 25 0.281 22
160 0.690 27-39 30 0..417 25 320 0.790 36-54 30 0.500 25

Note:
NC Data based on 10 dB room attenuation, 4ft. Lenght.
Throw data based on isothermal air at 100 and 50 fpm
terminal velocity.
Horizontal throw is 1 way pattern.
Static Pressure (Ps) in inches w.g.

Cooling Industries Company www.cic-jo.com 9


Linear Slot Supply Air Diffuser
Performance Data
Ak = Free Area Ft2

Model: CILS - AD 3/4"


Ak= 0.073 Ak= 0.121 Ak= 0.330 Ak= 0.355
No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
16 0.051 6-15 <20 0.028 <20 52 0.023 11-28 <20 0.014 <20
26 0.141 11-19 21 0.076 <20 104 0.09 22-39 21 0.054 <20
1 5
36 0.277 13-23 24 0.0149 21 156 0.203 28-48 24 0.124 21
47 0.458 15-26 29 0.246 24 208 0.361 32-55 29 0.220 24

Ak= 0.135 Ak= 0.182 Ak= 0.395 Ak= 0.413


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
21 0.023 5-17 <20 0.013 <20 62 0.023 12-30 <20 0.014 <20
52 0.141 16-28 21 0.079 <20 125 0.09 24-43 21 0.055 <20
2 6
73 0.277 19-33 24 0.155 21 187 0.203 30-52 24 0.125 21
94 0.458 21-37 29 0.256 24 250 0.361 35-60 29 0.223 24

Ak= 0.201 Ak= 0.237 Ak= 0.455 Ak= 0.470


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
31 0.023 7-21 <20 0.024 <20 73 0.023 13-33 <20 0.014 <20
62 0.09 17-30 21 0.095 <20 146 0.09 25-46 21 0.057 <20
3 7
94 0.203 21-37 24 0.213 21 218 0.203 33-56 24 0.127 21
140 0.458 26-45 29 0.382 24 291 0.361 38-65 29 0.229 24

Ak= 0.265 Ak= 0.295 Ak= 0.520 Ak= 0.530


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
42 0.023 10-25 <20 0.013 <20 83 0.023 14-23 <20 0.014 <20
83 0.09 19-35 21 0.054 <20 166 0.09 27-49 21 0.056 <20
4 8
104 0.141 22-39 24 0.085 21 250 0.203 35-60 24 0.128 21
166 0.361 28-49 29 0.218 24 333 0.361 40-70 29 0.228 24

Note:
NC Data based on 10 dB room attenuation, 4ft. Lenght.
Throw data based on isothermal air at 100 and 50 fpm
terminal velocity.
Horizontal throw is 1 way pattern.
Static Pressure (Ps) in inches w.g.

10 www.cic-jo.com Cooling Industries Company


Linear Slot Supply Air Diffuser
Performance Data
Ak = Free Area Ft2 / m

Model: CILS - AD 1"


Ak= 0.073 Ak= 0.109 Ak= 0.574 Ak= 0.455
No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
20 0.032 8-12 <20 0.019 <20 100 0.023 17-29 26 0.010 26
30 0.100 11-17 27 0.060 27 150 0.100 24-34 34 0.060 34
1 5
40 0.130 14-20 33 0.070 33 200 0.180 28-42 40 0.108 40
50 0.210 16-24 39 0.170 39 250 0.250 34-49 48 0.210 48

Ak= 0.149 Ak= 0.208 Ak= 0.436 Ak= 0.554


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
40 0.032 9-19 21 0.019 21 120 0.032 19-32 27 0.019 27
60 0.10 14-23 29 0.069 29 180 0.100 27-39 35 0.060 35
2 6
80 0.150 18-28 35 0.090 35 240 0.017 31-46 41 0.109 41
100 0.250 24-32 41 0.150 41 300 0.260 36-53 50 0.220 50

Ak= 0.224 Ak= 0.297 Ak= 0.489 Ak= 0.660


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
60 0.032 13-23 23 0.014 23 140 0.032 21-34 28 0.019 28
90 0.105 18-28 30 0.028 30 210 0.105 30-40 36 0.063 36
3 7
120 0.150 23-34 37 0.090 37 280 0.15 34-50 43 0.090 43
150 0.240 29-39 44 0.150 44 350 0.30 38-56 52 0.20 52

Ak= 0.297 Ak= 0.419 Ak= 0.617 Ak= 0.746


No. of CFM/ No. of CFM/
Slots Ft. Hor. Throw Vert. Slots Ft. Hor. Throw Vert.
NC NC NC NC
Ps (ft) Ps Ps (ft) Ps
80 0.033 15-26 25 0.024 25 160 0.032 23-36 30 0.019 30
120 0.106 23-32 32 0.060 32 240 0.106 32-44 37 0.064 37
4 8
160 0.140 25-38 39 0.072 39 320 0.16 36-52 45 0.096 45
200 0.250 27-43 46 0.150 46 400 0.31 39-60 54 0.210 54

Note:
NC Data based on 10 dB room attenuation, 4ft. Lenght.
Throw data based on isothermal air at 100 and 50 fpm
terminal velocity.
Horizontal throw is 1 way pattern.
Static Pressure (Ps) in inches w.g.

Cooling Industries Company www.cic-jo.com 11


Linear Slot Return Air Diffuser
Performance Data

Model: CILR - D 3/4" Model: CILR - AD 3/4"


Linear slot diffuser with deflection blades & Linear slot diffuser without deflection blades &
without volume control damper. without volume control damper.

No . Of Slot No . Of Slot

CFM/ft. 10 20 30 40 CFM/ft. 10 20 30 40
1 Neg. Ps 0.005 0.018 0.042 0.074 1 Neg. Ps 0.011 0.044 0.098 0.176
NC <20 <20 <20 <20 NC <20 <20 <20 22
CFM/ft. 20 40 60 80 CFM/ft. 20 40 60 80
2 Neg. Ps 0.005 0.019 0.044 0.078 2 Neg. Ps 0.013 0.050 0.114 0.202
NC <20 <20 <20 23 NC <20 <20 24 32
CFM/ft. 30 60 90 120 CFM/ft. 30 60 90 120
3 Neg. Ps 0.005 0.020 0.045 0.080 3 Neg. Ps 0.014 0.055 0.124 0.220
NC <20 <20 23 29 NC <20 <20 30 35
CFM/ft. 40 80 120 160 CFM/ft. 40 80 120 160
4 Neg. Ps 0.005 0.021 0.047 0.083 4 Neg. Ps 0.014 0.057 0.130 0.230
NC <20 <20 26 32 NC <20 23 30 35
CFM/ft. 50 100 150 200 CFM/ft. 50 100 150 200
5 Neg. Ps 0.005 0.021 0.047 0.083 5 Neg. Ps 0.015 0.060 0.134 0.240
NC <20 <20 28 34 NC <20 26 30 35
CFM/ft. 60 120 180 240 CFM/ft. 60 120 180 240
6 Neg. Ps 0.005 0.021 0.047 0.084 6 Neg. Ps 0.015 0.062 0.141 0.250
NC <20 23 31 35 NC <20 29 32 35
CFM/ft. 70 140 210 280 CFM/ft. 70 140 210 280
7 Neg. Ps 0.005 0.021 0.048 0.085 7 Neg. Ps 0.016 0.065 0.146 0.260
NC <20 23 31 35 NC <20 31 32 35
CFM/ft. 80 160 240 320 CFM/ft. 80 160 240 320
8 Neg. Ps 0.005 0.022 0.048 0.086 8 Neg. Ps 0.017 0.066 0.149 0.265
NC <20 24 32 35 NC <20 30 32 35

Note:
NC Data based on 10 dB room attenuation, 4ft. Lenght.
Throw data based on isothermal air at 100 and 50 fpm
terminal velocity.
Horizontal throw is 1 way pattern.
Static Pressure (Ps) in inches w.g.

12 www.cic-jo.com Cooling Industries Company


Curved Linear Slot Diffuser

Curved shape slot diffusers

Corner Trim Piece

Minimum radius = 1000 mm


Used as supply / Return slot diffusers

Corner Trim Piece

Available in one through eight slots

Cooling Industries Company www.cic-jo.com 13


FLOW BAR DIFFUSER

Page Contents

2 High Throw Pattern


3 Jet Throw Pattern
4 Flow Bar Architectural Ceiling Diffusers
5 Optional Mitered Corner & Flow Cross
6 Installation Instruction
7 High Throw Pattern - Performance Data
8 Jet Throw Pattern - Performance Data
Flow Bar Diffuser
High Throw Pattern

Model NO. LFBD-10-HT / 1" SLOT


Model NO. LFBD-15-HT / 1.5" SLOT
Model NO. LFBD-20-HT / 2" SLOT
Model NO. LFBD-25-HT / 2.5" SLOT
Model NO. LFBD-30-HT / 3" SLOT

Features:

The High Throw Pattern controller allows air to be directed the Left or right as well as downward when
installed in a ceiling system.
As air is horizontally directed, a surface effect is maintained, even at reduced volumes to provide room air
motion without draft.
Along with its high induction characteristics, make the high Throw an excellent choice for variable volume
Systems.

The CIC Flow Bar linear system is a continuous slot system which allows the air distrubution to become
inconspicuous while fully integrating and complementing the ceiling system and other ceiling
components.

Standerd slot sizes are 1, 1½" , 2" , 2½" , 3".


Section lengths up to 12 ft are standerd to minimize joints in long runs. Flow Bar is manufactured using
only heavy wall extruded aluminium.

Integral pattern controllers are on standards 24" center, allowing the airstream to be directed left or right
for horizontal and vertical airflow.

The Flow Bar System allows supply, return and exhaust air, all from one diffuser .
Standard finish is flat black for interior surfaces exposed to view and white for exposed flanges. Anodized
finishes and custom colors are available.
Flow Bar Systems satisfy both the architect's and engineer's requirements for designing an air distribution
system that will maintain optimum room air conditions while being inconspicuous to the viewer.

2 www.cic-jo.com Cooling Industries Company


Flow Bar Diffuser
Jet Throw Pattern

Model NO. LFBD-10-JT / 1" SLOT


Model NO. LFBD-15-JT / 1.5" SLOT
Model NO. LFBD-20-JT / 2" SLOT
Model NO. LFBD-25-JT / 2.5" SLOT
Model NO. LFBD-30-JT / 3" SLOT

Features:

The Jet Throw Pattern controller allows air to be directed to meet required comfort conditions.
Jet Throw is an excellent choice for high bay application perimeter zones requiring vertical projection, and
for side wall applications requiring extended throw for heating and cooling air, when used in side wall
application where heated air can be directed downward, terminating at the floor at a comfortable velocity.

The CIC Flow Bar linear system is a continuous slot system which allows the air distrubution to become
inconspicuous while fully integrating and complementing the ceiling system and other ceiling
components.

Standerd slot sizes are 1, 1½" , 2" , 2½" , 3".


Section lengths up to 12 ft are standerd to minimize joints in long runs. Flow Bar is manufactured using
only heavy wall extruded aluminium.

The optional Jet Throw pattern controllers allow the airstream to be jetted in a vertical direction when
installed in a ceiling and hroizontal when installed in a wall, the throw is directed left or right when installed
in a ceiling application, and up or down when installed in a side wall application.

Integral pattern controllers are on standards 22" center, allowing the airstream to be directed left or right
for horizontal and vertical airflow.

Jet Throw pattern controllers can be alternated with the standard high Throw pattern controllers, where
heated air can be directed to the floor while cooled air is directed horizontally across the ceiling, all from
the same Flow Bar.

The Flow Bar System allows supply, return and exhaust air, all from one diffuser .
Standards finish is flat black for interior surfaces exposed to view and white for exposed flanges. Anodized
finishes and custom colors are available.

Flow Bar Systems satisfies both the architect's and engineer's requirements for designing an air
distribution system that will maintain optimum room air conditions while being inconspicuous to the
viewer.

Cooling Industries Company www.cic-jo.com 3


Flow Bar Architectural Ceiling Diffusers
Dimensions & Borders

Pattern Controllers
LFBD-10 1" SLOT
LFBD-15 1.5" SLOT
LFBD-20 2" SLOT
LFBD-25 2.5" SLOT
LFBD-30 3" SLOT

Slot W A D H H
Number of Slots
Width Width Border Border HT Series HT Series
1 2¾ 7⁄8 1 ³⁄8 1 11⁄16 1 11⁄16
1½ 3¾ 1 1⁄8 1 5⁄8 1 11⁄16 1 11⁄16
1 2 4¾ 1 ³⁄8 1 7⁄8 1 11⁄16 1 11⁄16
½ 5¾ 1 5⁄8 2 1⁄8 1 11⁄16 2 5⁄16
3 6¾ 1 7⁄8 2 ³⁄8 1 11⁄16 2 5⁄16
1 5 ³⁄5 7⁄8 1 ³⁄8 1 11⁄16 1 11⁄16
1½ 7 ³⁄5 1 1⁄8 1 5⁄8 1 11⁄16 1 11⁄16
2 2 9 ³⁄5 1 ³⁄8 1 7⁄8 1 11⁄16 1 11⁄16
2½ 11 ³⁄5 1 5⁄8 2 1⁄8 1 11⁄16 2 5⁄16
3 13 ³⁄5 1 7⁄8 2 ³⁄8 1 11⁄16 2 5⁄16
Dimensions are in inches.

4 www.cic-jo.com Cooling Industries Company


Optional Mitered Corner & Flow Cross

Top View Face View


LFBD-10 1" SLOT
LFBD-15 1.5" SLOT
LFBD-20 2" SLOT
LFBD-25 2.5" SLOT
LFBD-30 3" SLOT

Number Slot Without Border With Border Number Slot Without Border With Border
of Slots Width L W A L W A of Slots Width L W A W A
1 12 3⁄4 2 3⁄4 10 13 1⁄4 3 3⁄4 9½ 1 14 3⁄4 2 3⁄4 6 3 3⁄4 5½
1 1⁄₂ 13 3⁄4 3 3⁄4 10 14 1⁄4 4 3⁄4 9½ 1 1⁄₂ 15 3⁄4 3 3⁄4 6 4 3⁄4 5½
1 2 14 3⁄4 4 3⁄4 10 15 1⁄4 5 3⁄4 9½ 1 2 16 3⁄4 4 3⁄4 6 5 3⁄4 5½
2 1⁄₂ 15 3⁄4 5 3⁄4 10 16 1⁄4 6 3⁄4 9½ 2 1⁄₂ 17 3⁄4 5 3⁄4 6 6 3⁄4 5½
3 16 3⁄4 6 3⁄4 10 17 1⁄4 7 3⁄4 9½ 3 18 3⁄4 6 3⁄4 6 7 3⁄4 5½
All Dimensions are in inches. All Dimensions are in inches.

Top View
XLFBD-10 1" SLOT
XLFBD-15 1.5" SLOT
Face View XLFBD-20 2" SLOT
XLFBD-25 2.5" SLOT
XLFBD-30 3" SLOT

End caps, End Boarder to be specified upon


ordering, Mitered Corners, and Blank Offs are End Cap and Mitered Corner Installation
optional.

FlowBar Diffusers can be joined together end-


to-end to form long continuous run.

End Boarders and End Caps close off ends of


the diffusers and simplify installations ending
at walls and other stopping points.

Mitered Corners are rendered inactive with


factory installed blank-offs.
Alignment Strips maintain tight joints
between sections & provide Alignment for
long continuous run.

Cooling Industries Company www.cic-jo.com 5


Flow Bar Architectural Ceiling Diffusers
Installation Instruction

Supply Jet Throw


Wall Installation
Supply High & Jet Throw
Ceiling Installation

Return Jet Throw


Wall Installation

Return High & Jet Throw


Ceiling Installation
Area Factor
Flow Bar Diffusers Air Flow Factors
Air Flow Measurements :
Slot Opening Ak / Foot
1. Determine the area weighted average using the ALNOR
1 inch 0.063
Velometer.
1.5 Inches 0.075
Hold probe against the diffuser, facing the air stream,
2 Inches 0.093
opposite to throw direction.
2.5 Inches 0.125
See the foloowing figure.
3 Inches 0.134

2. Calculate the flow rate using the following equation.


Flow Rate:
CFM = Ak/Foot X FT X Average Velocity (FPM)
Where:
CFM = Unit flow rate
Ak/Foot = Factor presented in the following airflow
Factor table.
Ft = Active feet of linear diffuser Average
Velocity (FPM) = Average of several velocity readings

6 www.cic-jo.com Cooling Industries Company


Flow Bar Diffusers
High Throw Pattern - Performance Data

Airflow, CFM/ft. 25 40 55 70 85 100 115

1- Static Pressure 0.028 0.072 0.136 0.221 0.325 0.450 0.596


Slot NC (Noise Criteria) <10 16 26 33 39 44 49
1.0" Throw 5-8-14 9-13-18 12-15-21 14-17-24 15-19-27 17-20-29 18-22-31
Slot
Width Airflow, CFM/ft. 50 75 100 125 150 175 200

2- Static Pressure 0.028 0.063 0.113 0.176 0.253 0.345 0.450


Slot NC (Noise Criteria) <10 17 26 33 39 44 48
Throw 7-11-20 11-17-25 15-20-29 19-23-32 20-25-35 22-27-38 23-29-41
Airflow, CFM/ft. 30 45 60 75 90 105 120

1- Static Pressure 0.032 0.073 0.130 0.203 0.292 0.398 0.520


Slot NC (Noise Criteria) <10 14 24 31 37 42 48
1.5" Throw 6-10-16 10-14-19 13-16-22 14-18-25 16-19-27 17-21-29 18-22-32
Slot
Width Airflow, CFM/ft. 60 85 110 135 160 185 210

2- Static Pressure 0.032 0.065 0.109 0.164 0.231 0.309 0.398


Slot NC (Noise Criteria) <10 16 24 31 36 41 45
Throw 9-14-22 13-19-27 17-21-30 19-24-33 21-26-36 23-28-39 24-29-42
Airflow, CFM/ft. 30 50 70 90 110 130 150

1- Static Pressure 0.020 0.057 0.111 0.184 0.274 0.383 0.510


Slot NC (Noise Criteria) <10 11 22 30 36 41 46
2.0" Throw 5-9-16 9-14-20 13-17-24 16-19-27 17-21-30 19-23-33 20-25-35
Slot
Width Airflow, CFM/ft. 60 95 130 165 200 235 270

2- Static Pressure 0.020 0.051 0.096 0.154 0.227 0.313 0.413


Slot NC (Noise Criteria) <10 12 22 30 36 41 46
Throw 7-12-22 13-19-28 17-23-33 21-26-37 23-29-41 25-31-44 27-33-47
Airflow, CFM/ft. 30 55 80 105 130 155 180

1- Static Pressure 0.012 0.041 0.088 0.151 0.232 0.329 0.444


Slot NC (Noise Criteria) <10 11 23 31 38 43 48
2.5" Throw 4-8-16 10-15-21 14-18-26 17-21-29 19-23-33 21-25-36 22-27-39
Slot
Width Airflow, CFM/ft. 60 105 150 195 240 285 330

2- Static Pressure 0.012 0.038 0.077 0.130 0.197 0.278 0.373


Slot NC (Noise Criteria) <10 13 24 32 38 44 48
Throw 6-11-22 13-20-29 19-25-35 23-28-40 26-32-45 28-34-49 30-37-52
Airflow, CFM/ft. 30 60 90 120 150 180 210

1- Static Pressure 0.011 0.044 0.100 0.177 0.277 0.399 0.543


Slot NC (Noise Criteria) <10 <10 18 27 34 40 45
3.0" Throw 3-7-15 10-15-22 15-19-27 18-22-32 20-25-35 22-27-39 24-29-42
Slot
Width Airflow, CFM/ft. 60 120 180 240 300 360 420

2- Static Pressure 0.011 0.044 0.100 0.177 0.277 0.399 0.543


Slot NC (Noise Criteria) <10 <10 21 30 37 43 48
Throw 5-10-21 14-21-32 21-27-39 26-32-45 29-35-50 32-39-55 34-42-59

* All Pressure are in inches of water.


* Isothermal throw values given are for terminal velocities of 150, 100 and 50 FPM. Table A Throw Correction Multiplier for length
* Throw data based on active sections 4 feet long. For other length refer to table A.
* data obtained from tests conducted in accordance with ASHRAE Standard 70-2006 Length, Feet 2 4 8 10 12
"Method of Testing for Rating the Performance of Air Outlets and Inlets."
* Throw values for HighThrow units are based on a one-way discharge from the slot. Throw Correction 0.72 1 1.5 1.7 1.8

Cooling Industries Company www.cic-jo.com 7


Flow Bar Diffusers
Jet Throw Pattern - Performance Data

Airflow, CFM/ft. 20 40 60 80 100 120 140

1- Static Pressure 0.007 0.027 0.061 0.109 0.170 0.245 0.334


Slot NC (Noise Criteria) <10 <10 17 24 28 32 36
1.0" Throw 2-3-7 4-7-13 7-10-19 9-13-22 11-17-24 13-19-26 15-20-29
Slot
Width Airflow, CFM/ft. 40 85 130 175 220 265 310

2- Static Pressure 0.007 0.031 0.072 0.130 0.206 0.299 0.409


Slot NC (Noise Criteria) <10 11 22 29 34 38 42
Throw 3-5-9 7-10-20 10-15-27 14-20-32 17-25-36 21-25-36 24-30-42
Airflow, CFM/ft. 30 60 90 120 150 180 210

1- Static Pressure 0.008 0.031 0.070 0.125 0.196 0.282 0.384


Slot NC (Noise Criteria) <10 <10 17 22 28 33 37
1.5" Throw 2-4-7 5-7-15 7-11-22 10-15-26 12-18-30 15-22-32 17-25-35
Slot
Width Airflow, CFM/ft. 60 120 180 240 300 360 420

2- Static Pressure 0.008 0.031 0.070 0.125 0.196 0.282 0.384


Slot NC (Noise Criteria) <10 <10 19 27 32 37 40
Throw 2-5-10 7-10-21 10-15-31 14-21-37 17-26-42 21-31-46 24-35-49
Airflow, CFM/ft. 35 75 115 155 195 235 275

1- Static Pressure 0.006 0.026 0.062 0.112 0.178 0.258 0.353


Slot NC (Noise Criteria) <10 <10 17 24 29 33 37
2.0" Throw 1-3-7 5-8-15 8-12-23 10-16-30 13-20-34 16-24-37 18-28-40
Slot
Width Airflow, CFM/ft. 70 150 230 310 390 470 550

2- Static Pressure 0.006 0.026 0.062 0.112 0.178 0.258 0.353


Slot NC (Noise Criteria) <10 <10 19 26 32 36 40
Throw 2-4-10 7-11-21 11-16-33 15-22-42 18-28-48 22-33-52 26-39-57
Airflow, CFM/ft. 40 95 150 205 260 315 370

1- Static Pressure 0.005 0.027 0.068 0.126 0.203 0.298 0.412


Slot NC (Noise Criteria) <10 <10 18 25 30 35 39
2.5" Throw 1-3-7 6-8-17 9-13-26 12-18-35 15-23-39 18-28-43 22-33-46
Slot
Width Airflow, CFM/ft. 80 190 300 410 520 630 740

2- Static Pressure 0.005 0.027 0.068 0.126 0.203 0.298 0.412


Slot NC (Noise Criteria) <10 11 22 28 34 38 42
Throw 2-4-10 8-12-24 12-19-37 17-26-49 22-32-55 26-39-60 31-46-66
Airflow, CFM/ft. 50 115 180 245 310 375 440

1- Static Pressure 0.005 0.028 0.067 0.125 0.200 0.293 0.403


Slot NC (Noise Criteria) <10 <10 17 24 30 34 38
3.0" Throw 1-3-8 6-9-18 9-14-28 13-19-38 16-24-42 20-29-47 23-34-51
Slot
Width Airflow, CFM/ft. 100 230 360 490 620 750 880

2- Static Pressure 0.005 0.028 0.067 0.125 0.200 0.293 0.403


Slot NC (Noise Criteria) <10 <10 21 27 34 39 43
Throw 2-4-11 8-13-25 13-20-40 18-27-53 23-34-60 28-42-66 33-49-71

* All Pressure are in inches of water.


* Isothermal throw values given are for terminal velocities of 150, 100 and 50 FPM.
* Throw data based on active sections 4 feet long. For other length refer to table A. Table A Throw Correction Multiplier for length
* data obtained from tests conducted in accordance with ASHRAE Standard 70-2006
Length, Feet 2 4 8 10 12
"Method of Testing for Rating the Performance of Air Outlets and Inlets."
* Throw values for JetThrow units are based on the pattern controller at 0° discharge Throw Correction 0.72 1 1.5 1.7 1.8
(vertical blow).

8 www.cic-jo.com Cooling Industries Company


CIRCULAR & JET DIFFUSERS

Page Contents

2 Circular Ceiling Diffusers


5 Jet Flow Diffusers
7 Jet Nozzles
10 Drum Shaped Diffusers
23 Exhaust Air Valves
Circular Ceiling Diffusers

Model: CI - Air CCD

CI - Air SCCD

CI - Air RCCD

Features:

CIC round ceiling diffusers are designed for application in air conditioning. Ventilation and forced air
heating systems, in both civil and industrial plats.
The construction is made of Aluminium sheets. The are employed to both diffuse and exhaust air form the
ambient.

CIC round ceiling diffusers offer valuable with a competitive price. Therefore they represent the most
suitable choice in all applications where a major concern is to limit the first cost of system without
however reducing overall efficiency.

CIC round ceiling diffusers, in fact, do ensure acceptable sound level, low pressure drop and high induction
rate with ambient air.

Mounting:
CIC ceiling diffusers are easily and quickly installed, thanks to its removable core.

Size:
CIC ceiling diffusers are manufactured in four different sizes with nominal diameters ranging from 150mm
to 450mm.

Butterfly damper:
It is made from GI.Steel It permits front adjustment through the diffuser, with screwdriver.

2 www.cic-jo.com Cooling Industries Company


Supply Circular Ceiling Diffusers
Performance Data

Model: CI - Air SCCD

Neck Neck Velocity


Neck Area 300 400 500 600 700 800 1000 1200 1400 1600
Size (FPM)
Area Factor
Inches Velocity Pressure
(Ft°) (Ft°) 0.007 0.011 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(cm) (Inches W.G.)

Air Flow rate (CFM) 60 80 100 120 135 155 195 235 275 315

Total Press. Drop 0.025 0.041 0.061 0.082 0.106 0.132 0.201 0.282 0.380 0.480
6"
0.196 0.13
(15)
Throw (Ft) 3-5 3-6 3-6 4-6 4-6 4-6 5-7 5-7 6-8 7-10

NC <20 <20 <20 <20 <20 25 30 35 39 45

Air Flow rate (CFM) 105 140 175 210 245 280 350 420 490 560

Total Press. Drop 0.021 0.032 0.052 0.071 0.100 0.122 0.183 0.271 0.370 0.480
8"
0.349 0.22
(20)
Throw (Ft) 4-6 4-6 5-7 6-8 6-8 6-8 7-10 7-11 8-13 9-14

NC <20 <20 <20 20 25 29 33 38 42 46

Air Flow rate (CFM) 165 220 275 325 380 435 545 655 765 870

Total Press. Drop 0.040 0.061 0.092 0.122 0.181 0.242 0.361 0.500 0.710 0.950
10"
0.545 0.25
(25)
Throw (Ft) 4-6 6-9 7-10 7-10 7-11 8-13 9-14 10-16 12-18 15-22

NC <20 <20 <20 21 26 30 34 39 43 47

Air Flow rate (CFM) 225 315 395 470 550 630 785 940 1100 1255

Total Press. Drop 0.026 0.041 0.072 0.101 0.152 0.201 0.313 0.490 0.670 0.870
12"
0.785 0.38
(30)
Throw (Ft) 6-8 7-10 7-11 7-11 8-13 9-14 10-16 14-21 15-23 19-27

NC <20 <20 <20 22 28 32 36 41 45 48

Air Flow rate (CFM) 320 430 535 640 750 855 1070 1285 1500 1710

Total Press. Drop 0.034 0.051 0.080 0.112 0.156 0.201 0.313 0.460 0.600 0.800
14"
1.07 0.50
(35)
Throw (Ft) 6-8 8-13 9-15 10-16 11-17 12-18 15-23 19-2 19-27 21-31

NC <20 <20 <20 24 29 33 37 42 46 49

Air Flow rate (CFM) 420 560 700 840 980 1120 1400 1680 1960 2240

15" Total Press. Drop 0.043 0.075 0.106 0.140 0.202 0.262 0.413 0.593 0.800 0.980
1.40 0.59
(38)
Throw (Ft) 7-11 9-14 9-15 11-17 12-18 15-23 16-25 19-27 21-31 25-36

NC <20 <20 20 25 30 34 38 43 47 50

Air Flow rate (CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830

18" Total Press. Drop 0.033 0.052 0.082 0.113 0.166 0.220 0.350 0.530 0.710 0.950
1.77 0.75
(45)
Throw (Ft) 8-13 9-14 10-16 12-18 14-12 17-24 19-27 21-31 22-33 26-38

NC <20 <20 21 26 31 35 39 44 48 51

Cooling Industries Company www.cic-jo.com 3


Return Circular Ceiling Diffusers
Performance Data

Model: CI - Air RCCD

Neck Neck Velocity


Neck 300 400 500 600 700 800 1000 1200 1400 1600
Size (FPM)
Area
Inches Velocity Pressure
(Ft°) 0.007 0.011 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(cm) (Inches W.G.)

Air Flow (CFM) 60 80 100 120 135 155 195 235 275 315
6"
0.196 Total Press. Drop 0.029 0.048 0.076 0.108 0.146 0.188 0.294 0.421 0.569 0.749
(15)
NC <20 <20 <20 <20 21 26 32 37 41 46

Air Flow (CFM) 105 140 175 210 245 280 350 420 490 560
8"
0.349 Total Press. Drop 0.020 0.034 0.053 0.077 0.100 0.123 0.207 0.293 0.394 0.519
(20)
NC <20 <20 <20 21 26 30 34 39 43 47

Air Flow (CFM) 165 220 275 325 380 435 545 655 765 870
10"
0.545 Total Press. Drop 0.019 0.033 0.050 0.071 0.096 0.120 0.196 0.281 0.379 0.477
(25)
NC <20 <20 <20 22 27 31 36 41 45 48

Air Flow (CFM) 225 315 395 470 550 630 785 940 1100 1255
12"
0.785 Total Press. Drop 0.018 0.029 0.045 0.064 0.086 0.112 0.176 0.249 0.339 0.443
(30)
NC <20 <20 <20 23 29 33 37 42 46 49

Air Flow (CFM) 320 430 535 640 750 855 1070 1285 1500 1710
14"
1.07 Total Press. Drop 0.017 0.028 0.042 0.061 0.083 0.108 0.170 0.242 0.328 0.430
(35)
NC <20 <20 20 25 30 34 38 43 47 50

Air Flow (CFM) 420 560 700 840 980 1120 1400 1680 1960 2240
15"
1.40 Total Press. Drop 0.016 0.025 0.041 0.059 0.079 0.103 0.162 0.231 0.314 0.411
(38)
NC <20 <20 21 26 31 35 39 44 48 51

Air Flow (CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830
18"
1.77 Total Press. Drop 0.015 0.025 0.040 0.057 0.077 0.099 0.156 0.224 0.303 0.397
(45)
NC <20 <20 22 27 32 36 40 45 49 52

4 www.cic-jo.com Cooling Industries Company


Jet Flow Diffusers

Model: CI - Air JET - R

Nominal
200 250 300 350 400
Dimensions (mm)
Description:

CIC Jet Flow Diffuser Model JET-R are used in applications where large quantity of supply air from the
diffuser has to travel a long distance to the required air conditioned area. Such as sport halls, airports, large
rooms, Mosques, Churches, arcades, etc.
Many factors could effect the direction and length of this air stream such as air velocity from the
Jet Flow Diffuser, the temperature difference between the supply air and the room, and local convection
effects or draughts within the room.

CIC Jet Flow Diffuser type JET-R are designed to be manually adjusted up to 35° upwards, and up to 35°
downwards in order to minimize these factors, and direct the supply air to the desired location.
Normally the Jet Flow Diffuser should be adjusted upwards (for cooling), and downwards (for heating).

Noise level:

The well-designed, aerodynamically efficient shape of CIC Jet Flow Diffuser Model, results a low noise
character istics. Which allow the utilization of these jet nozzles in critical areas such as concert halls,
theaters, museums etc.
Construction and finish:

CIC Jet Flow Diffuser Model JET-R consists of square plate 1, with several centric cylinders 2.
All are made of G.I. Steel, and colored Powder Coated RAL9016.
Other colors are available on request.

Installation:

CIC Jet Flow Diffuser Model JET-R could be installed in the side walls, or in the ceiling.
Easily by screwing or riveting the plate on plenum box, or directly onto the duct.

Cooling Industries Company www.cic-jo.com 5


Jet Flow Diffusers

Heating
Model: CI - Air JET - R

Cooling

Selection Table For Vertical Throw: Selection Table For Horizantal Throw:
Air Nozzle Air Pressure Noise Air Nozzle Air Horizantal Pressure Noise
Drop
Flow Diam. Throw Drop Level Flow Diam. Throw Drop Level
m3/h (mm) (m) (Pa) (dB) m3/h (mm) (m) (m) (Pa) (dB)
350 200 4 18 15-20 350 200 7 4 18 15-20
500 200 6 34 25-30 500 200 8 5 34 25-30
650 200 8 55 35-40 650 200 9.5 7 55 35-40
200 10 100 40-45 200 14 9 100 40-45
850 850
250 7.5 35 25-30 250 11 9 35 25-30
200 11 125 45-50 200 16 10.5 125 45-50
1000 250 8.5 43 30-35 1000 250 14 10 43 30-35
300 6 25 20-25 300 12 10 25 20-25
200 13 180 50-55 200 19 12.5 180 50-55
250 10 65 35-40 250 15 10.5 35 35-40
1200 1200
300 6.5 38 25-30 300 13 11 38 25-30
350 5 15 15-20 350 11 9 15 15-20
200 15 230 55-60 200 22 14.5 230 55-60
250 11 85 40-45 250 16.5 11.5 85 40-45
1400 1400
300 8.5 50 35-40 300 15 12 50 35-40
350 6.5 20 20-25 350 12 10 20 20-25
250 15 150 45-50 250 22 14 150 45-50
1800 300 11 80 40-45 1800 300 19 15 80 40-45
350 9 38 25-30 350 16 12 38 25-30
250 16 165 50-55 250 24 15 165 50-55
300 11.5 90 40-45 300 20 17 90 40-45
2000 2000
350 10 45 30-35 350 17 14 45 30-35
400 8 15 15-20 400 13 11 15 15-20
250 17 205 50-55 250 25 16 205 50-55
300 13 110 45-50 300 22 18 110 45-50
2200 2200
350 11 60 35-40 350 18 15 60 35-40
400 9 25 20-25 400 15 13 25 20-25
300 15 140 45-50 300 25 20 140 45-50
2500 350 13 70 35-40 2500 350 21 19 70 35-40
400 10 35 25-30 400 16 14 35 25-30
300 17 180 50-55 350 24 20 88 40-45
2800
2800 350 15 88 40-45 400 19 16 45 30-35
400 12 45 30-35 3000 400 21 17 50 35-40
300 18 190 50-55 3500 400 22 18 65 35-40
3000 350 15.5 95 40-45 4000 400 24 20 90 40-45
400 13 50 35-40
350 18 135 45-50
3500
400 16 65 35-40
4000 400 18 90 40-45

6 www.cic-jo.com Cooling Industries Company


Jet Nozzles

Model: CI - Air JET - L

Description:

Jet nozzles are used in applications require the supply


air from the diffuser has to travel a long distance to the
required air conditioned area. Such as sport halls, airports,
large rooms ,mosques ,churches ,etc.

Many factors could effect the direction, and length of this


air stream such us air velocity from the nozzle, air flow,
temperature difference between the supply air and the
room, and local convection effects or draughts within the
room.

CIC jet nozzles are designed to be manually adjusted ‘in any direction’ for an angle of ±27° in order to
minimize these factors, and direct the suppl y air to the desired location. Also pneumatic or electric control
systems could be used for this adjustment.
Normally the jet nozzles should be adjusted upwards (for cooling), and downwards (for heating).

Noise level:

The well-designed, aerodynamically efficient shape of CIC jet nozzles results a low noise characteristics.
Which allow the utilization of these jet nozzles in critical areas such as concert halls, theaters, museums etc.

Construction CIC jet nozzle consists of a aerodynamic spherical discharge nozzle 1,mounted in a round
housing 2,complete with a front mounting flange 3,decorative ring 4,and circular spigot 5,for direct
connection to a flexible round duct.

Installation:

Jet nozzles could be installed in the side walls, or on the top of the areas.
CIC jet nozzles could be installed easily by screwing or riveting the circular un drilled flange to the wall, a
sealing strip preferably to be fitted first, then the decorative ring to be twist fixing to cover the screws or
rivets.

Alternatively the jet nozzle can be screw fixed to the duct side The spigot to be connected directly to spiral
or flexible circular ducts. The spigot diameter accepts standard circular duct sizes.

Material and finish The discharge nozzle, cover ring, round housing, and spigot.
All are made of Aluminum, and colored with white RAL9016. Other colors are available on request.

Cooling Industries Company www.cic-jo.com 7


Jet Nozzles
Performance Data

Model: CI - Air JET - L

Dimension
Nominal Size A B C T F
(mm) (mm) (mm) (mm) (mm) (mm)
150 200 25 30 150 100
200 265 25 45 200 135
250 310 25 45 250 165
310 380 28 45 310 185
400 470 30 70 400 210

Final Velocity Air Throw Jet Nozzle Dia Air Flow Deflection b - (m) At Temp. Diffr Pressure Drop Noise Level
M/s L (m) (mm) M3 / h 5c 10c 15c (Pa) (dB)
150 160 0.4 0.5 0.7 50 20-25
200 215 0.25 0.4 0.6 28 15-20
5
250 280 0.35 0.6 0.9 16 10-15
310 340 0.4 0.7 1 10 10-15
150 180 0.25 0.5 0.7 60 25-30
200 235 0.28 0.6 0.85 30 15-20
6
250 325 0.3 0.65 0.9 26 15-20
310 400 0.4 0.7 1.2 13 10-15
150 250 0.28 0.6 0.8 100 40-45
200 325 0.3 0.65 0.9 70 30-35
1
8 250 430 0.51 1 1.5 32 20-25
310 540 0.6 1.4 1.75 23 15-20
400 720 0.65 1.5 2.2 12 10-15
200 575 0.3 0.6 0.9 160 40-45
250 735 0.8 1.8 2.5 110 40-45
14
310 935 0.9 1.9 2.8 80 35-40
400 1300 1.2 2 3 90 40-45
310 1260 1.3 2.2 3.5 125 40-45
18
400 1655 1.5 2.8 4 70 35-40
20 400 1835 1.6 2.9 4.2 90 40-45

8 www.cic-jo.com Cooling Industries Company


Jet Nozzles
Performance Data

Model: CI - Air JET - L

Final Velocity Air Throw Jet Nozzle Dia Air Flow Deflection b - (m) At Temp. Diffr Pressure Drop Noise Level
M/s L (m) (mm) M3 / h 5c 10c 15c (Pa) (dB)
150 180 0.5 0.9 1.5 53 25-30
8 200 235 0.8 1.7 2.5 33 20-25
250 310 0.9 1.9 2.7 20 15-20
150 290 0.5 1 1.5 125 35-40
200 360 0.85 1.8 2.5 75 30-35
0.7 12
250 485 1.4 2.5 3.5 35 20-25
310 615 0.9 1.9 2.5 25 15-20
250 650 2 3.5 6 75 30-35
18 310 845 2.8 5.5 8 60 30-35
400 1115 2.7 5.4 7.7 30 25-30
150 180 3 5.7 8 55 25-30
14 200 235 3.2 6.5 10 33 20-25
250 310 3.4 7 11 20 15-20
150 270 4.2 8 12 110 35-40
200 340 4.5 9 14 75 30-35
20
0.4 250 450 6 12 18 35 20-25
310 575 13 16 20 25 15-20
200 430 6 12 18 90 35-40
250 540 7.1 15 20 60 30-35
25
310 685 8 16 21 35 25-35
400 935 9 18 22 20 15-20

Cooling Industries Company www.cic-jo.com 9


Drum Shaped Diffusers
HCD Series

Structure

- One rotational drum inside adjustable vanes.


- Drum can be adjustable up-adn-down 60°
(See Figure 1 in next page).
- Extruded aluminium drum, vanes and mounting
frame.
- Frontal detent mechanism decides the angle of
adjustable drum (See Figure 2 in next page).
- Vanes rod and tensioning device can be adjusted
under high volume.
- Mounting frame with gasket.
Standard
- Felt sealed the drum and mounting frame.
- Extra flexibility provided by central divider and
Grille HCD1
prolonged controller.
Direct line grille HCD1D - Rotational steel damper painted black finishing.
Optional

Grille HCD2 Form / Finishing Options


Direct line grille HCD2D Form Style
Surface design 19/16"(40) in tint F
Centralized are the divider, diffluence vane and
prolonged controller. Fastening
Countersink head screw A
Application Oval-head screw
Accessories
- Long throw air pattern worked by one senior Pole of operator bracket (see Figure 3
directional controller. in next page) for size 48" (1219) wide POB
- adjustable vanes used for spread control, while or less
rotatable drum-shaped vanes control vertical air
diffluence.
- Ideal diffusers for shopping malls, industrial Finishes Powder Coating
plants, stages, gymnasiums or other great orbicular White B12
indoor space. Aluminum B15
- HCD cannot outlet air in the duck system and Mill,Finish MILL
other places under architectural restrictions. Optional Finishing, SPL

Product Selection Listing

1) Select unit size based on desired performance.


2) Select outlet type by model (core style, damper).
3) Select pole of operator bracket according to installation requirements.
4) Select finishing, like 24x12/ HCD1/B 12.

10 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
HCD Series
Product Information

Figure 1 Drum rotated angle of 30° alongside Figure 2 Detent mechanism for positioning
Central line. Drum.

30°

30°

Figure 3 Pole of operator bracket.

Dimensional Data
Size 6 10 12 15
A 2¾" 33/8" 47/8" 63/8"
(70) (86) (124) (162)

Cooling Industries Company www.cic-jo.com 11


Drum Shaped Diffusers
HCD Series
Product Information

12 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
HCD Series
Product Information

Table 1 Dimension (Imperial inches/Metric mm)


Size
W A B C E F H
Inch

6'' 7 1/16 (179) 8 7/8 (255) 3 3/8 (66) 3 (76) 11 1/16 (43) 3 7/8 (96) 4 7/16 (113)

10'' 10 3/4 (273) 12 9/18 (319) 5 7/8 (149) 6 (152) 2 7/16 (149) 6 (152) 5 3/16 (148)

12'' 12 5/8 (321) 14 7/16 (367) 6 7/16 (175) 6 (152) 3 (76) 6 1/16 (154) 6 1/4 (110)

15'' 15 3/8 (401) 17 5/8 (448) 9 13/16 (249) 6 (152) 3 13/16 (97) 7 9/16 (292) 4 7/16 (113)

Table 2 Available Dimension


Nominal Length (Dimensional L)
Nom.
Size 9" 12" 15" 18" 24" 30" 36" 42" 48" 54" 60" 66" 72"
Width (229) (305) (381) (457) (610) (762) (914) (1067) (1219) (1372) (1524) (1676) (1829)
6 N/A N/A
10 N/A N/A N/A
12 N/A N/A N/A
15 N/A N/A N/A

Cooling Industries Company www.cic-jo.com 13


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in inch 0.046 0.077 0.123 0.169 0.238 0.308 0.384 0.477 0.692

Flow rate in CFM 113 150 188 225 263 300 338 375 450
6/9
NC (Noise criteria) - - 18 24 29 34 38 42 48

Throw 150 100 50 15-20-29 19-24-33 21-26-37 24-29-41 25-31-44 27-33-47 29-35-50 30-37-53 33-41-58

Total pressure in inch 0.042 0.070 0.112 0.154 0.216 0.279 0.349 0.433 0.628

Flow rate in CFM 150 200 250 300 350 400 450 500 600
6/12
NC (Noise criteria) - - 19 25 30 35 39 43 49

Throw 150 100 50 16-24-33 22-27-38 25-30-43 27-33-47 29-36-51 31-38-54 33-41-58 35-43-61 38-47-67

Total pressure in inch 0.039 0.065 0.104 0.142 0.021 0.259 0.324 0.401 0.582

Flow rate in CFM 188 250 313 375 438 500 563 625 750
6/15
NC (Noise criteria) - - 19 26 31 36 40 44 50

Throw 150 100 50 18-26-37 24-30-43 28-34-48 30-37-53 33-40-57 35-43-61 37-46-64 39-48-68 43-53-74

Total pressure in inch 0.037 0.061 0.097 0.134 0.189 0.243 0.304 0.377 0.548

Flow rate in CFM 225 300 375 450 525 600 675 750 900
6/18
NC (Noise criteria) - 16 20 26 32 36 40 44 51

Throw 150 100 50 19-29-41 26-33-47 30-37-53 33-41-58 36-44-62 38-47-67 41-50-71 43-53-74 47-58-81

Total pressure in inch 0.033 0.055 0.088 0.121 0.171 0.221 0.276 0.342 0.497

Flow rate in CFM 300 400 500 600 700 800 900 1000 1200
6/24
NC (Noise criteria) - - 21 27 32 37 41 45 51

Throw 150 100 50 21-32-47 29-38-54 35-43-61 38-47-67 41-51-72 44-54-77 47-58-81 50-61-86 54-67-94

Total pressure in inch 0.031 0.051 0.82 0.113 0.159 0.205 0.256 0.318 0.461

Flow rate in CFM 375 500 625 750 875 1000 1125 1250 1500
6/30
NC (Noise criteria) - - 21 28 33 38 42 46 52

Throw 150 100 50 23-35-53 31-43-61 39-48-68 43-53-74 46-57-80 50-61-86 53-64-91 55-68-96 61-74-105

14 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in inch 0.029 0.048 0.077 0.160 0.149 0.193 0.241 0.299 0.433

Flow rate in CFM 450 600 750 900 1050 1200 1350 1500 1800
6/36
NC (Noise criteria) - - 22 28 34 38 43 46 53

Throw 150 100 50 25-38-58 34-47-57 42-53-74 47-58-81 51-62-88 54-67-94 58-71-100 61-74-105 67-81-115

Total pressure in inch 0.027 0.076 0.073 0.101 0.1042 0.183 0.229 0.283 0.411

Flow rate in CFM 525 700 875 1050 1225 1400 1575 1750 2100
6/42
NC (Noise criteria) - - 22 29 34 39 43 47 53

Throw 150 100 50 27-40-62 36-51-72 45-57-80 51-62-88 55-67-95 59-72-102 62-76-108 66-80-114 72-88-124

Total pressure in inch 0.026 0.044 0.070 0.096 0.135 0.175 0.218 0.271 0.393

Flow rate in CFM 600 800 1000 1200 1400 1600 1800 2000 2400
6/48
NC (Noise criteria) - - 23 29 35 39 43 47 54

Throw 150 100 50 28-42-67 38-54-77 47-61-86 54-76-94 59-72-102 63-77-109 67-81-115 70-86-121 77-94-133

Total pressure in inch 0.025 0.042 0.067 0.092 0.130 0.168 0.210 0.260 0.378

Flow rate in CFM 675 900 1125 1350 1575 1800 2025 2250 2700
6/54
NC (Noise criteria) - 15 23 29 35 40 44 47 54

Throw 150 100 50 29-44-71 39-58-81 49-64-91 58-71-100 62-76-108 67-81-115 71-86-122 74-190-129 81-100-141

Total pressure in inch 0.024 0.041 0.065 0.089 0.126 0.162 0.203 0.251 0.365

Flow rate in CFM 750 1000 1250 1500 1750 2000 2250 2500 3000
6/60
NC (Noise criteria) - 16 23 30 35 40 44 48 54

Throw 150 100 50 31-46-74 41-61-86 51-68-96 61-74-105 66-80-114 70-86-121 74-91-129 78-96-136 86-105-149

Cooling Industries Company www.cic-jo.com 15


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.031 0.051 0.082 0.113 0.159 0.205 0.265 0.318 0.461

Flow rate in CFM 375 500 625 750 875 1000 1125 1250 1500
10/18
NC (Noise criteria) - - 21 28 33 38 42 46 52

Throw 150 100 50 23-35-53 31-43-61 39-48-68 43-53-74 48-57-80 50-61-86 53-64-91 55-68-96 61-74-105

Total pressure in WG 0.028 0.046 0.074 0.102 0.144 0.186 0.232 0.288 0.418

Flow rate in CFM 500 667 833 1000 1167 1333 1500 1667 2000
10/24
NC (Noise criteria) - - 22 29 34 39 43 47 53

Throw 150 100 50 26-39-61 35-50-70 44-55-78 50-61-86 54-66-93 57-70-99 61-74-105 64-78-111 70-86-121

Total pressure in WG 0.025 0.043 0.069 0.095 0.134 0.172 0.216 0.267 0.388

Flow rate in CFM 625 833 1042 1250 1458 1667 1875 2083 2500
10/30
NC (Noise criteria) - - 23 29 35 39 44 47 54

Throw 150 100 50 29-43-68 38-55-78 48-62-88 55-68-96 60-73-104 64-78-111 68-83-118 72-88-124 78-96-136

Total pressure in WG 0.024 0.041 0.065 0.089 0.126 0.162 0.203 0.251 0.365

Flow rate in CFM 750 1000 1250 1500 1750 2000 2250 2500 3000
10/36
NC (Noise criteria) - 16 23 30 35 40 44 48 54

Throw 150 100 50 31-46-74 41-61-86 51-68-96 61-74-105 66-80-114 70-86-121 74-91-129 78-96-136 86-105-149

Total pressure in WG 0.023 0.038 0.062 0.085 0.119 0.154 0.192 0.239 0.346

Flow rate in CFM 875 1167 1458 1750 2042 2333 2625 2917 3500
10/42
NC (Noise criteria) - 16 24 30 36 40 45 48 55

Throw 150 100 50 33-49-80 43-65-93 54-73-104 65-80-114 71-87-123 76-93-131 80-98-139 85-104-147 93-114-161

16 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.022 0.037 0.059 0.081 0.114 0.147 0.184 0.228 0.331

Flow rate in CFM 1000 1333 1667 2000 2333 2667 3000 3333 4000
10/48
NC (Noise criteria) - 16 24 31 36 41 45 49 55

Throw 150 100 50 34-52-86 46-69-99 57-78-111 69-86-121 76-93-131 81-99-140 86-105-149 91-111-157 99-121-172

Total pressure in WG 0.021 0.035 0.057 0.078 0.110 0.141 0.177 0.219 0.318

Flow rate in CFM 1125 1500 1875 2250 2625 3000 3375 3750 4500
10/54
NC (Noise criteria) - 17 25 31 36 41 45 49 55

Throw 150 100 50 36-54-91 48-72-105 60-83-118 72-91-129 80-98-139 86-105-147 91-112-158 96-118-166 105-129-182

Total pressure in WG 0.020 0.034 0.055 0.075 0.106 0.136 0.171 0.211 0.307

Flow rate in CFM 1250 1667 2083 2500 2917 3333 3750 4167 5000
10/60
NC (Noise criteria) - 17 25 31 37 41 46 49 56

Throw 150 100 50 37-56-96 50-75-111 62-88-124 75-96-136 85-104-147 91-111-157 96-118-166 101-124-175 111-136-192

Total pressure in WG 0.020 0.033 0.053 0.073 0.102 0.132 0.165 0.205 0.297

Flow rate in CFM 1375 1833 2292 2750 3208 3667 4125 4583 5500
10/66
NC (Noise criteria) - 17 25 32 37 42 46 50 56

42-95-116-
Throw 150 100 50 39-58-101 52-78-116 65-92-130 78-101-142 89-109-154
164
101-123-174 106-130-184 116-142-201

Total pressure in WG 0.019 0.032 0.051 0.071 0.099 0.128 0.160 0.199 0.289

Flow rate in CFM 1500 2000 2500 3000 3500 4000 4500 5000 6000
10/72
NC (Noise criteria) - 18 26 32 37 42 46 50 56

Throw 150 100 50 40-60-105 54-81-121 67-96-136 81-105-149 93-114-161 99-121-172 105-129-182 111-136-192 121-149-210

Cooling Industries Company www.cic-jo.com 17


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.029 0.048 0.077 0.106 0.149 0.193 0.241 0.299 0.433

Flow rate in CFM 450 600 750 900 1050 1200 1350 1500 1800
12/18
NC (Noise criteria) - - 22 28 34 38 43 46 53

Throw 150 100 50 25-38-58 34-47-67 42-53-74 47-58-51 51-62-88 54-67-94 58-71-100 61-74-105 67-81-115

Total pressure in WG 0.026 0.044 0.070 0.096 0.135 0.175 0.218 0.271 0.0393

Flow rate in CFM 600 800 1000 1200 1400 1600 1800 2000 2400
12/24
NC (Noise criteria) - - 23 29 35 39 43 47 54

Throw 150 100 50 28-42-67 38-54-77 47-61-86 54-67-94 59-72-102 63-77-109 67-81-115 70-86-121 77-94-133

Total pressure in WG 0.024 0.041 0.065 0.089 0.126 0.162 0.203 0.251 0.365

Flow rate in CFM 750 1000 1250 1500 1750 2000 2250 2500 3000
12/30
NC (Noise criteria) - 16 23 30 35 40 44 48 54

Throw 150 100 50 31-46-74 41-61-86 51-68-96 61-74-105 66-80-114 70-86-121 74-91-129 78-96-136 86-105-149

Total pressure in WG 0.023 0.038 0.061 0.084 0.118 0.152 0.191 0.236 0.343

Flow rate in CFM 900 1200 1500 1800 2100 2400 2700 3000 3600
12/36
NC (Noise criteria) - 16 24 30 36 40 45 48 55

Throw 150 100 50 33-49-81 44-66-94 55-74-105 66-81-115 72-88-124 77-94-133 81-100-141 86-105-149 94-115-163

Total pressure in WG 0.022 0.036 0.058 0.080 0.112 0.145 0.181 0.224 0.326

Flow rate in CFM 1050 1400 1750 2100 2450 2800 3150 3500 4200
12/42
NC (Noise criteria) - 17 24 31 36 41 45 49 55

Throw 150 100 50 35-53-88 47-70-102 58-80-114 70-88-124 78-95-134 83-102-144 88-108-152 93-114-161 102-124-176

18 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.021 0.035 0.055 0.076 0.107 0.138 0.173 0.214 0.311

Flow rate in CFM 1200 1600 2000 2400 2800 3200 3600 4000 4800
12/48
NC (Noise criteria) - 17 25 31 37 41 46 49 56

Throw 150 100 50 37-55-94 49-74-109 62-86-121 74-94-133 83-102-144 89-109-154 94-115-163 99-121-172 109-133-188

Total pressure in WG 0.020 0.033 0.053 0.073 0.103 0.133 0.166 0.206 0.299

Flow rate in CFM 1350 1800 2250 2700 3150 3600 4050 4500 5400
12/54
NC (Noise criteria) - 17 25 32 37 42 46 50 56

Throw 150 100 50 39-58-100 52-77-115 64-91-129 77-100-141 88-108-152 94-115-163 100-122-173 105-129-182 115-141-200

Total pressure in WG 0.019 0.032 0.051 0.071 0.099 0.128 0.160 0.199 0.289

Flow rate in CFM 1500 2000 2500 3000 3500 4000 4500 5000 6000
12/60
NC (Noise criteria) - 18 26 32 37 42 46 50 56

Throw 150 100 50 40-60-105 54-81-121 67-96-136 81-105-149 93-114-161 99-121-172 105-129-182 111-136-192 121-149-210

Total pressure in WG 0.019 0.031 0.050 0.068 0.096 0.124 0.155 0.193 0.280

Flow rate in CFM 1650 2200 2750 3300 3850 4400 4950 5500 6600
12/66
NC (Noise criteria) - 18 26 32 38 42 46 50 57

70-101- 104-127-
Throw 150 100 50 42-63-110 56-84-127
142
84-110-156 97-119-168
180
110-135-191 116-142-201 127-156-221

Total pressure in WG 0.018 0.030 0.048 0.066 0.093 0.121 0.151 0.187 0.271

Flow rate in CFM 1800 2400 3000 3600 4200 4800 5400 6000 7200
12/72
NC (Noise criteria) - 18 26 32 38 43 47 50 57

72-105- 101-124- 109-133-


Throw 150 100 50 43-65-115 58-87-133
149
87-115-163
176 188
115-141-200 121-149-210 133-163-230

Cooling Industries Company www.cic-jo.com 19


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.027 0.045 0.071 0.098 0.138 0.179 0.223 0.277 0.402

Flow rate in CFM 563 750 938 1125 1313 1500 1688 1875 2250
15/18
NC (Noise criteria) - - 23 29 34 39 43 47 53

Throw 150 100 50 27-41-64 37-53-74 46-59-83 53-64-91 57-70-98 61-74-105 64-79-112 68-83-118 74-91-129

Total pressure in WG 0.024 0.041 0.065 0.089 0.126 0.162 0.203 0.251 0.365

Flow rate in CFM 750 1000 1250 1500 1750 2000 2250 2500 3000
15/24
NC (Noise criteria) - 16 23 30 35 40 44 48 54

Throw 150 100 50 31-46-74 41-61-86 51-68-96 61-74-105 66-80-114 70-86-121 74-91-129 78-96-136 86-105-149

Total pressure in WG 0.023 0.038 0.060 0.083 0.117 0.150 0.188 0.233 0.338

Flow rate in CFM 938 1250 1563 1875 2188 2500 2813 3125 3750
15/30
NC (Noise criteria) - 16 24 30 36 41 45 48 55

Throw 150 100 50 34-50-83 45-67-96 56-76-107 67-83-118 73-90-127 78-96-136 83-102-144 88-107-152 96-118-166

Total pressure in WG 0.021 0.035 0.057 0.078 0.110 0.141 0.177 0.219 0.318

Flow rate in CFM 1125 1500 1875 2250 2625 3000 3375 3750 4500
15/36
NC (Noise criteria) - 17 25 31 36 41 45 49 55

Throw 150 100 50 36-54-91 48-72-105 60-83-118 72-91-129 80-98-139 86-105-149 91-112-158 96-118-166 105-129-182

Total pressure in WG 0.020 0.034 0.054 0.074 0.104 0.134 0.168 0.208 0.302

Flow rate in CFM 1313 1750 2188 2625 3063 3500 3938 4375 5250
15/42
NC (Noise criteria) - 17 25 32 37 42 46 49 56

Throw 150 100 50 38-57-98 51-76-114 64-90-127 76-98-139 87-106-150 93-114-161 98-120-170 104-127-180 114-139-197

20 www.cic-jo.com Cooling Industries Company


Drum Shaped Diffusers
Performance Table

Neck Velocity in inches/min 300 400 500 600 700 800 900 1000 1200
Size
Pressure Velocity in w.g. 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.090

Total pressure in WG 0.019 0.032 0.051 0.071 0.099 0.128 0.160 0.199 0.289

Flow rate in CFM 1500 2000 2500 3000 3500 4000 4500 5000 6000
15/48
NC (Noise criteria) - 18 26 32 37 42 46 50 56

Throw 150 100 50 40-60-105 54-81-121 67-93-136 81-105-149 93-114-161 99-121-172 105-129-182 111-136-192 121-149-210

Total pressure in WG 0.018 0.031 0.049 0.068 0.096 0.123 0.154 0.191 0.277

Flow rate in CFM 1688 2250 2813 3375 3938 4500 5063 5625 6750
15/54
NC (Noise criteria) - 18 26 32 38 42 47 50 57

Throw 150 100 50 42-63-112 56-64-129 70-102-144 84-112-158 98-120-170 105-129-182 112-137-193 118-144-204 129-158-223

Total pressure in WG 0.018 0.030 0.048 0.065 0.092 0.119 0.149 0.184 0.268

Flow rate in CFM 1875 2500 3125 3750 4375 5000 5652 6250 7500
15/60
NC (Noise criteria) - 18 26 33 38 43 47 51 57

Throw 150 100 50 44-66-118 59-88-136 73-107-152 88-118-166 103-127-180 111-139-192 118-144-204 124-152-215 136-165-235

Total pressure in WG 0.017 0.029 0.046 0.063 0.089 0.115 0.144 0.179 0.259

Flow rate in CFM 2063 2750 3438 4125 4813 5500 6188 6875 8250
15/66
NC (Noise criteria) - 19 26 33 38 43 47 51 57

Throw 150 100 50 46-68-123 61-91-142 76-113-159 91-123-174 106-133-188 116-142-201 123-151-214 130-159-225 142-174-247

Total pressure in WG 0.017 0.028 0.045 0.062 0.087 0.112 0.140 0.173 0.252

Flow rate in CFM 2250 3000 3750 4500 5250 6000 6750 7500 9000
15/72
NC (Noise criteria) - 19 27 33 39 43 47 51 58

Throw 150 100 50 47-71-129 63-94-149 79-118-166 94-129-182 110-139-197 121-149-210 129-158-223 136-166-235 149-182-258

Cooling Industries Company www.cic-jo.com 21


Drum Shaped Diffusers
HCD Series
Product Information

Remark:

1- Tested in accordance with ASHRAE 70-1991 , Approved American National Standerd Method of Testing
for Rating the Performance of Air Outlets and Inlets.
2- All pressure calculated in inch of water.
3- NC value calculated by absorbing 10dB per 10-12 Watt in a room.
4- Blanks (—) indicate an NC value below 15 dB.
5- Throw value calculated by isothermal indoor air flow.

HCD1 HCD2
Deflection type
0° 15° 30° 0° 15° 30°
NC — +4 +9 — +4 +9
Throw — X 0.85 X 0.73 — X 0.85 X 0.73
Total — X 1.5 X 1.9 X 1.3 X 1.7 X 2.2
Press

Based on HCD1 deflection at 0°,


Modify other factors as shown in above table.

Example:
12 X 36HCD2

Flow rate = 1800 CFM


Deflection = 15°
NX = 30 + 4 = 34 dB
Throw (50FPM) = 115 X 0.85 = 98 ft
Total pressure = 0.086 X 1.7 = 0.146 In.W.G.

All Metric dimensions can be converted into Imperial dimension, while the latter must be converted to the
former to the nearest millimeter.

22 www.cic-jo.com Cooling Industries Company


Exhaust Air Valves

Model: CI - Air EV - R

The application of EV-R Exhaust Air Valves is suitable and recommended to bathrooms, Kitchens,
Storerooms, photographic laboratories, archives, press halls, photocopying centers, shops and soon.

The offer a great operating efficiency and such a pleasant aesthetic appearance to even go unnoticed
most of the times.

Exhaust Air Valves can be mounted to walls, ceiling or directly on ducts, with a great capability to sult any
kind of requirement.
Adjustment of air delivery is handled in a very simple way by turning central value from the max.
Opining position of the fully closed one, That distinctive feature makes system calibration remarkable
easier.

Exhaust Air Valves EV-R Model is worth mentioning especially for its low price, good operating conditions
with optimal pressure drops and very easy mounting procedure.
Standard color is white, washable, weather resistances, made of aluminium, with shaft and nut in
galvanized steel.
The valve is flat and fully covers the exhaust air valves entry.
Mounting is made easier by the use of appearing screws fitted on proper counterframe.

Size:
Exhaust Air Valves EV-R are available in nominal diameters of 100,125,150 and 200mm.

Nominal diameter ØB ØD
H
Dn (Inch)/mm (mm) (mm)

(4") 100 140 50

(5") 125 165 50

(6") 150 200 50

(8") 200 250 50

Cooling Industries Company www.cic-jo.com 23


Exhaust Air Valves
Performance Data

Model: CI - Air EV - R

Performance of EV-R Exhaust Air Valves are outlined on diagrams, one for each diameter of Exhaust Air
Valves.
Access to diagram is normally done according to the following data:

* Air Flow Rate (m3/h).


* Available Static Pressure (pa).

So that following valves can determined:

* Nominal Diameter (mm).


* Disc Entry (mm).
* Sound Level (dB).

Nominal diameter
Air Flow (m3/h) Pressure Drop (pa) Sound Level dB
Dn (Inch)/mm

(4") /100mm 100-150 55-100 25-40

(5") /125mm 120-200 55-110 25-40

(6") /160mm 150-250 55-100 25-40

(8") /205mm 220-320 55-110 25-40

24 www.cic-jo.com Cooling Industries Company


LOUVERS

Page Contents

2 Air Louvers
3 Air Louvers - Performance Data
5 Gravity Shutter
6 Gravity Shutter - Performance Data
7 Sand Trap Louvers
8 Sand Trap Louvers - Performance Data
9 Ordering System
10 Sand Louvers
14 Penthouse Louvers
20 Stationary Stormproof Louvers
Air Louvers

Model: CI - Air L - H

CI - Air L - H
CI - Air L - H

Features:

Designed for use as air intakes or air exhaust louvers for commercial or industrial air conditioning systems.
Combines fine architectural design with good performance meets most requirements.

Produced From heavy gauge extruded anodized finish aluminum bars.


Blades and frame are mechanically fastened to provide rigid and mitred joints.

Louvers are completely weather proof and rain proof blade lips.
Can be provided with bird or insect screens, White and anodized aluminum are the standard color,
other colors are available upon request.

2 www.cic-jo.com Cooling Industries Company


Air Louvers
Performance Data

Free Area in Sq. Ft.


Width. Inches (CMS)
Height
12 14 16 18 20 24 30 36 42 48 54 60 72
Inches
(30) (36) (41) (46) (51) (61) (76) (91) (107) (122) (137) (152) (183)
(CMS)
12
0.22 0.26 0.30 0.34 0.38 0.46 0.58 0.70 0.82 0.94 1.06 1.18 1.42
(30)

16
0.37 0.43 0.50 0.57 0.64 0.77 0.98 1.18 1.38 1.59 1.79 1.99 2.40
(41)

20
0.52 0.61 0.71 0.80 0.90 1.09 1.38 1.66 1.95 2.24 2.52 2.81 3.38
(51)

24
0.67 0.79 0.91 1.04 1.16 1.41 1.78 2.15 2.52 2.89 3.26 3.63 4.37
(61)

28
0.82 0.79 1.12 1.27 1.42 1.72 2.18 2.63 3.08 3.54 3.99 4.44 5.35
(71)

32
0.97 1.04 1.32 1.505 1.68 2.04 2.58 3.11 3.65 4.18 4.72 5.26 6.33
(81)

36
1.12 1.32 1.53 1.74 1.94 2.36 2.98 3.60 4.22 4.84 5.46 6.08 7.32
(91)

40
1.27 1.50 1.73 1.97 2.20 2.67 3.38 4.08 4.78 5.49 6.19 6.86 8.30
(102)

44
1.41 1.68 1.94 2.20 2.46 2.98 3.78 4.55 5.34 6.12 6.91 7.69 9.26
(112)

48
1.57 1.86 2.15 2.44 2.736 3.31 4.18 5.05 5.92 6.79 7.66 8.53 10.27
(122)

52(
1.72 2.03 2.35 2.67 2.99 3.62 4.58 5.53 6.48 7.44 8.39 9.34 11.25
(132)

56
1.87 2.21 2.56 2.90 2.25 3.94 4.98 6.01 7.05 8.08 9.12 10.16 12.23
(142)

60
2.02 2.39 2.67 3.14 3.51 4.26 5.38 6.50 7.62 8.74 9.86 10.98 13.22
(152)

Cooling Industries Company www.cic-jo.com 3


Air Louvers
Performance Data

Note: 1.0
For sizes not shown, the approximate free
area in square feet can be calculated by
using the formula below: 0.5

Free area = (0.5 H-0.26) (W-0.1) 0.4

0.3
W= Width on feet
H= Height on feet 0.2

CFM = Free Area x Face Velocity

Ps)
Ps)

T (+
(Sq. Ft.) X (fpm) 0.1

E (-

US
AK

HA
INT

EX
Pressure Loss Inches w. g.

0.05

0.04

0.03

0.02

0.01

0.005

0.004

0.003

0.002

0.001
100 200 300 400 600 1000 2000 3000 4000 5000

Free Area Velocity (fpm.)

4 www.cic-jo.com Cooling Industries Company


Gravity Shutter
Horizontal Operatable Pressure Relief Shutter

Model: CI - Air GS-H

CI - Air GS-H

CI - Air GS-H
Features:

A horizontal operatable shutter which operates to equalize the pressure across it.
The frame and blades are constructed of extruded aluminum anodized as standard painted, powder
coated are available on request.
The frame has a typical wall thickness of 1/16” and separated from the movable blades by an extruded
rigid PVC track which is riveted to and becomes an integral part of the frame. A1/8” thick, 3/8” wide foam
tape is installed on the blades where they overlap to insure a good seal and to reduce noise.

Each shutter is carefully designed to equalize the pressure in such areas as a compressor of fan room with
the outside.
The blades are designed and positioned in such a way that if the pressure in the room increase the blades
automatically lift and open relieving the pressure in the room.
When the room pressure is normalized the blades drop to the closed position by gravity.

These devices are also employed at the end of exhaust ducts where they would open when the exhaust
fan was turned on and would close when the fan was turned off.

Cooling Industries Company www.cic-jo.com 5


Gravity Shutter
Performance Data

Technical Data and Listed Sizes Area Factor

Listed Height
(Inches) 12 14 16 18 20 24 30 36 42 48 54 60 72
12 0.81 0.96 1.10 1.25 1.40 1.64 2.08 2.47 2.91 3.30 3.74 4.13 4.96
16 1.08 1.27 1.47 2.66 1.86 2.18 2.77 3.29 3.87 4.44 5.02 5.49 6.60
20 1.36 1.60 1.85 2.09 2.33 2.75 3.48 4.13 4.87 5.52 6.25 6.91 8.30
24 1.62 1.92 2.21 2.50 2.79 3.29 4.16 4.95 5.82 6.61 7.48 8.17 9.93
Listed Height

28 1.89 2.23 2.57 2.91 3.25 3.83 4.85 5.76 6.78 7.69 8.71 9.63 11.56
32 2.16 2.55 2.93 3.32 3.71 4.37 5.53 6.57 7.74 8.78 9.94 10.99 13.19
36 2.44 2.87 3.31 3.75 4.19 4.93 6.24 7.42 8.73 9.91 11.22 12.40 14.89
40 2.70 3.19 3.68 4.16 4.65 5.47 6.93 8.23 9.69 11.00 12.45 13.76 16.52
44 2.97 3.50 4.04 4.57 5.11 6.01 7.61 9.05 10.65 12.08 13.68 15.12 18.16
48 3.25 3.83 4.42 5.00 5.59 6.57 8.32 9.89 11.64 13.21 14.97 16.54 19.86
52 3.52 4.15 4.78 5.41 6.04 7.11 9.01 10.71 12.60 14.30 16.20 17.89 21.49
56 3.78 4.46 5.14 5.82 6.50 7.65 9.69 11.52 13.56 15.39 17.43 19.25 23.12
60 4.06 4.79 5.52 6.25 6.98 8.21 10.40 12.36 14.55 16.52 18.71 20.67 24.82

Note: Pressure Loss

For sizes not shown, the approximate area factor


can be calculated by using the formula below:
0.875 (Height) x (Width - 1.5)
* Area Factor:
144
Pressure Drop Inches w. g.

To calculate the Air Volume (CFM) multiply the area


factor by the face velocity.

CFM = Area Factor x Face Velocity

* Area factor calculation assumes gravity shutter


blades being 100% open.

Face Velocity fpm

6 www.cic-jo.com Cooling Industries Company


Sand Trap Louvers

Model: CI - Air SL-H

CI - Air SL-H

Features:

The sand trap louver is made of Aluminum section.


It is composed of two sets of inverted U-channels, mounted vertically on two opposite rows.

The sand trap louver is used to lower the dust loading of conventional filtration as it is designed to separate
large size sand particles at low to medium speeds.

It is also fitted with a bird screen mesh made of galvanized steel to protect against the unwanted objects.
The sand trap louver is a self emptying system, it has a set of holes at the bottom face of the casing to
discharge separated sand particles.

Cooling Industries Company www.cic-jo.com 7


Sand Trap Louvers
Performance Data

Effective Pressure Area Ft2

Height Width (inches)


(inches)
12 18 24 30 36 42 48 54 60 66 72 78 84 90
12 0.31 0.47 0.64 0.79 0.96 1.12 1.28 1.44 1.60 1.77 1.93 2.09 2.25 2.41
18 0.47 0.72 0.96 1.21 1.45 1.70 1.94 2.19 2.43 2.68 2.92 3.17 3.41 3.66
24 0.64 0.96 1.29 1.62 1.95 2.78 2.60 2.93 3.26 3.59 3.92 4.24 4.57 4.90
30 0.79 1.21 1.62 2.03 2.44 2.85 3.27 3.68 4.09 4.50 4.91 5.32 5.73 6.15
36 0.96 1.45 1.95 2.44 2.94 3.43 3.93 4.42 4.92 5.41 5.91 6.40 6.89 7.39
42 1.04 1.57 2.11 2.65 3.19 3.72 4.26 4.79 5.33 5.87 6.40 6.96 7.47 8.01
48 1.20 1.82 2.44 3.06 3.68 4.30 4.92 5.54 6.16 6.78 7.40 8.02 8.69 9.26
54 1.36 2.06 2.77 3.47 4.17 4.87 5.58 6.28 6.98 7.69 8.39 9.10 9.80 10.50
60 1.52 2.31 3.09 3.88 4.67 5.45 6.24 7.03 7.81 8.60 9.39 10.17 10.96 11.75
66 1.69 2.55 3.42 4.29 2.16 6.03 6.90 7.77 8.64 9.51 10.38 11.25 12.12 13.00
72 1.85 2.80 3.75 4.71 5.68 6.61 7.57 8.52 9.47 10.42 11.38 12.33 13.28 14.23
78 2.01 3.04 4.08 5.12 6.15 7.19 8.23 9.26 1030 11.33 12.37 13.41 14.44 15.48
84 2.17 3.29 4.41 5.53 6.65 7.77 8.87 10.01 11.13 12.25 13.37 14.49 15.61 16.72
90 2.33 3.53 4.74 5.69 7.14 8.35 9.55 10.75 11.96 13.16 14.36 15.56 16.77 17.97

Performance:

Test results conducted on similar equipment


indicate a typical efficiency of 80% on AC
coarse.
(20 - 200 microns) and 50% on AC Fine test
duct (1 to 70 microns).
Pressure Drop Inches W.G.
Efficiency

Face Velocity Based on W x H, FPM

8 www.cic-jo.com Cooling Industries Company


Sand Trap Louvers

Available Types of Finishing: Standard Sizes:


Powder coated (painted to RAL codes). (Use any combination of width & length)

* To convert into Imperial units use Width Length


(1 inch = 25mm). (B) (A)
* Non Standard Sizes are Available Upon (mm) (mm)
Request. 300 300
450 450
600 600
750 750
900 900
1050 1050
1200 1200
1350 1350
1500 1500

Ordering System:

Type Size Finish

Ral : Powder coated Finish as per RAL Codes.

Size : Width x Lenght

STL : Sand trap louver


Example : STL 1050 X 150 RAL 9016

Cooling Industries Company www.cic-jo.com 9


Sand Louvers
CI - Air DL - H

General:

CIC Sand Louver CI - Air DL- H are architectural air inlets. They are
widely used for building exteriors and are suitable for different
HVAC and industrial applications to prevent sand entry.

The blades are carefully designed to provide a low resistance to


air flow and a high free area.

Description: Sand Louver (CI - Air DL- H)

CI - Air DL- H louvers have 2 inch deep horizontal fixed blades designed carefully for low pressure drop and
to prevent entry of sand.
The frame is 1.25” wide (flat or curved) flanged type and is mechanically joined to give a rugged
construction to the louver.
These louvers are available as optional with galvanized bird screen, aluminum type air filter in 1”, 2” and 4”
thickness and volume control damper.
They are manufactured in a wide range of standard sizes however, they can be supplied in non-standard
sizes, depths or architectural shapes to suit customers requirements.

Material and Finish:

CI - Air DL- H sand louvers are made of heavy extruded aluminium profiles.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request.
Bird screens are made of galvanized expanded metal sheets.

10 www.cic-jo.com Cooling Industries Company


Sand Louvers
CI - Air DL - H
Product Code

CIC Sand Louver CI - Air DL- H - W - H - C

Width in inch.

Height in inch.

Accessories:
B : Bird screen
D : Volume Control Damper (VCD)
BD : Bird screen & VCD.
I : Insect Screen.
F1 : Aluminium Filter 1” thick.
F2 : Aluminium Filter 2” thick.
F4 : Aluminium Filter 4” thick.

Use the code of CI - Air DL- H to refer to CIC sand louver with flat frame.

Example:
• CI - Air DL- H - 30 - 18 - B:
CIC Sand Louver - size 30” x 18” with bird screen.
• CI - Air DL- H - 24 - 20 BDF1:
CIC Sand Louver - size 24” x 20” with bird screen, volume control damper and 1” thick aluminium filter.

A special assembly of sand louver with a bird screen, volume


control damper and a washable aluminium filter.
(All are enclosed in a galvanized box).

Example: CI - Air DL- H - W - H - BDF2

Cooling Industries Company www.cic-jo.com 11


Sand Louvers
CI - Air DL - H
Dimensional Data

CIC Sand Louver with flat frame - (CI - Air DL- H)

Selection Procedure:

To select a suitable size of a sand louver (CI - Air DL- H) for a certain application, follow exactly the same
procedure as been explained previously.

Note:
The approximate effective free area in square feet can be calculated by using the following formula:-

Effective free area (Ak) = (0.45 H-0.08) x (W-0.1)

Where, H is Height in ft and W is Width in ft.

12 www.cic-jo.com Cooling Industries Company


Sand Louvers
CI - Air DL - H
Performance Data

Available Standard Sizes


12x12 12x14 12x16 12x18 12x20 12x24 12x30 12x36 12x42 12x48
16x12 16x14 16x16 16x18 16x20 16x24 16x30 16x36 16x42 16x48
20x12 20x14 20x16 20x18 20x20 20x24 20x30 20x36 20x42 20x48
24x12 24x14 24x16 24x18 24x20 24x24 24x30 24x36 24x42 24x48
28x12 28x14 28x16 28x18 28x20 28x24 28x30 28x36 28x42 28x48
32x12 32x14 32x16 32x18 32x20 32x24 32x30 32x36 32x42 32x48
36x12 36x14 36x16 36x18 36x20 36x24 36x30 36x36 36x42 36x48
40x12 40x14 40x16 40x18 40x20 40x24 40x30 40x36 40x42 40x48
44x12 44x14 44x16 44x18 44x20 44x24 44x30 44x36 44x42 44x48
48x12 48x14 48x16 48x18 48x20 48x24 48x30 48x36 48x42 48x48

Table No. 1 CI - Air DL- H standard sizes available (HxW) in inches.

Pressure Requirement
Face Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD° W.G. 0.007 0.016 0.028 0.044 0.063 0.086 0.112 0.141 0.175 0.252 0.338 0.433

Table No. 2 Intake pressure drop in inches of water as a function of face velocity in FPM for CI - Air DL- H.

Effective Free Area

Height Width (Inches)


(Inches) 12 14 16 18 20 24 30 36 42 48
12 0.33 0.40 0.46 0.52 0.58 0.70 0.89 1.07 1.26 1.45
16 0.47 0.55 0.64 0.73 0.81 0.99 1.25 1.51 1.77 2.00
20 0.60 0.71 0.83 0.94 1.05 1.27 1.61 1.94 2.28 2.61
24 0.74 0.87 1.01 1.15 1.28 1.56 1.97 2.38 2.79 3.20
28 0.87 1.03 1.20 1.36 1.52 1.84 2.33 2.81 3.30 3.78
32 1.00 1.19 1.38 1.57 1.75 2.12 2.69 3.25 3.81 4.37
36 1.14 1.35 1.57 1.78 1.99 2.41 3.05 3.70 4.32 4.95
40 1.28 1.51 1.75 1.99 2.22 2.70 3.41 4.12 4.83 5.54
44 1.41 1.67 1.94 2.20 2.46 2.98 3.77 4.55 5.34 6.12
48 1.55 1.83 2.12 2.41 2.69 3.30 4.13 5.00 5.85 6.71

Table No. 3. Effective free area in ft² factor) for CI - Air DL- H.

Cooling Industries Company www.cic-jo.com 13


Penthouse Louvers
CI - Air PHL - H

General:

CIC penthouse louvers CI - Air PHL - H are considered as typical louver units for both air intake and exhaust
applications.
They are designed and built to become a permanent part of the building.
They maintain their pleasant appearance and effective weather protection as a result of their rugged,
durable, extruded aluminium construction and careful workmanship.
They are usually furnished with either mullion or mitered corners and incorporate the normal CIC fresh air
louver blades CI - Air PHL - H as standard. However, any other type of CIC louver blades can also be used
as optional.

Penthouse Louver (CI - Air PHL - H) Penthouse Louvers (CI - Air PHL - H)
With Mullion Corner With Mitered Corner

Description:

CI - Air PHL - H penthouse louvers have as a standard 2” deep fixed horizontal blades.
The blades are carefully designed to get low pressure drop, maximum free area and to prevent rain-water
penetration.
They are available in 1.25” flanged frame and are built and mounted to an internal framing with mullion
corners.
The integral framing mullion structures are furnished with a standard 1.6” x 1.6” extruded aluminium
profiles.
For the other mitered corners type penthouse louvers, blades are beveled and welded internally at the
end.
The top of the penthouses are covered with flat or pitched roofs of aluminium sheets.
All of the four louver sides are of removable type for easy maintenance purposes, Penthouse louvers can
also be supplied as optional with galvanized bird or insect screens and / or aluminium washable air filters
of 1”, 2”, or 4” thickness.

14 www.cic-jo.com Cooling Industries Company


Penthouse Louvers
CI - Air PHL - H
Product Code

Material and Finish:

CI - Air PHL - H penthouse louvers are made of heavy gauge extruded aluminium profiles. They are
available in white polyester powder coated finish or any other RAL standard colour upon customer’s
request.
Structural mullion corners are of strong aluminium profiles while roof tops are of aluminium sheets
as a standard.
However, galvanized roofs are also available upon request.
Bird screens are made of galvanized expanded metal sheets.

CIC Penthouse Louver CI - Air PHL - H - W - L - H - C

Width in inch.

Length in inch.

Height in inch.

Accessories:

B : Bird Screen
I : Insect Screen
F : Aluminium Filter 1” thick.
F2 : Aluminium Filter 2” thick.
F4 : Aluminium Filter 4” thick.

Example:

CI - Air PHL - H - 18 - 18 - 24 - B:
CIC penthouse louver with 18” x 18” basement
size, 24” height and bird screen.

CI - Air PHL - H - 24 - 18 - 36 - BF2:


CIC penthouse louver with 24” x 18” basement
size, 36” height, bird screen and 2” thick aluminium air filter.

Cooling Industries Company www.cic-jo.com 15


Penthouse Louvers
CI - Air PHL - H
Definitions

Definitions:
: Is the air stream velocity measured at the face of a louver in FPM
Face velocity
and it corresponds to the effective free area.

CFM : Is the air flow rate in cubic feet per minute.

: Is in ft2 , and is related to the other parameters by the equation :


Effective free area CFM = Free Area x Face velocity
= Ak x Vk

: Is the inside basement perimeter in feet and is calculated from:


Penthouse louver perimeter P= 2W + 2L, W and L are the horizontal dimensions of the penthouse
louver.

Total pressure drop : Is the sum of static pressure and velocity pressure given in inches W.G

CI - Air PHL - H - F2

16 www.cic-jo.com Cooling Industries Company


Penthouse Louvers
CI - Air PHL - H
Dimensional Data

Ci - Air PHL - H (with mullion corners)

Ci - Air PHL - H (with mitered corners)

Cooling Industries Company www.cic-jo.com 17


Penthouse Louvers
CI - Air PHL - H
Selection Procedure

Example:

Select a penthouse louver for an exhaust requirements of 3300 CFM with a total pressure drop of 0.1” W.G.

1) From the pressure requirement table 2 it shows that an 800 FPM velocity results an exhaust pressure
drop of 0.1” W.G.
2) Determine the effective free area:

CFM
Effective free area Ak =
Vk
3000
= = 4.125 ft2
800
3) From table 3 the 4.125 ft2 effective free area is suitable for the following penthouse louver’s sizes:
• P = 5 ft, H = 28 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12” x 18”.
• P = 6 ft, H = 24 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12”x24” or 18” x 18”
depending on the duct size.

Note:
The approximate effective free area in square feet can be calculated by using the following formula:-

Effective free area (Ak) = (H-0.5) x (0.5P-0.25)


Where, H is height in ft and P is Inside Perimeter in ft.

Pressure Requirement:
Free Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD" W.G. 0.006 0.011 0.023 0.037 0.050 0.066 0.087 0.110 0.142 0.193 0.280 0.390
Exhaust PD" W.G. 0.007 0.014 0.028 0.044 0.059 0.080 0.10 0.128 0.159 0.255 0.310 0.425

Table No. 4 Pressure drop in inches of water as a function of face velocity


through the free area in FPM for CI - Air PHL - H.

18 www.cic-jo.com Cooling Industries Company


Inside Perimeter in feet (2W + 2L)
Height
(Inches)
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

12 0.875 1.125 1.375 1.625 1.875 2.125 2.375 2.625 2.875 3.125 3.375 3.625 3.875 4.125 4.375 4.625 4.875 5.125 5.375 5.625 5.875

16 1.458 1.875 2.292 2.708 3.125 3.542 3.958 4.375 4.792 5.208 5.625 6.042 6.458 6.875 7.292 7.708 8.125 8.542 8.958 9.375 9.792
CI - Air PHL - H

Cooling Industries Company


20 2.042 2.625 3.208 3.792 4.375 4.958 5.542 6.125 6.708 7.292 7.875 8.458 9.042 9.625 10.208 10.792 11.375 11.958 12.542 13.125 13.708
Performance Data
Penthouse Louvers

24 2.625 3.375 4.125 4.875 5.625 6.375 7.125 7.875 8.625 9.375 10.125 10.875 11.625 12.375 13.125 13.875 14.625 15.375 16.125 16.875 17.625

28 3.208 4.125 4.842 5.958 6.875 7.792 8.708 9.625 10.542 11.458 12.375 13.292 14.208 15.125 16.042 16.958 17.875 18.792 19.708 20.625 21.542

32 3.792 4.875 5.958 7.042 8.125 9.208 10.292 11.375 12.458 13.542 14.625 15.708 16.792 17.875 18.958 20.042 21.125 22.208 23.292 24.375 25.458

36 4.375 5.625 6.875 8.125 9.375 10.625 11.875 13.125 14.375 15.625 16.875 18.125 19.375 20.625 21.875 23.125 24.375 25.625 26.875 28.125 29.375

40 4.958 6.375 7.792 9.208 10.625 12.042 13.458 14.875 16.292 17.708 19.125 20.542 21.958 23.375 24.792 26.208 27.625 29.042 30.458 31.875 33.292

44 5.542 7.125 8.708 10.292 11.875 13.458 15.042 16.625 18.208 19.792 21.375 22.958 24.542 26.125 27.708 29.292 30.785 32.458 34.042 35.625 37.208

48 6.125 7.785 9.625 11.375 13.125 14.785 16.625 18.375 20.125 21.875 23.625 25.375 27.125 28.875 30.625 32.375 34.125 35.875 37.625 39.375 41.125

52 6.708 8.625 10.542 12.458 14.375 16.292 18.208 20.125 22.042 23.958 25.875 27.792 29.708 31.625 33.542 35.458 37.375 39.292 41.208 43.125 45.042

56 7.292 9.375 11.458 13.542 15.625 17.708 19.792 21.875 23.958 26.042 28.125 30.208 32.292 34.375 36.458 39.542 40.625 42.708 44.792 46.875 48.958

60 7.875 10.125 12.375 14.625 16.875 19.125 21.375 23.625 25.875 28.125 30.375 32.625 34.875 37.125 39.375 41.625 43.875 46.125 48.375 50.625 52.875

64 8.458 10.875 13.292 15.708 18.125 20.542 22.958 25.375 27.792 30.208 32.625 35.042 37.458 39.875 42.292 44.708 47.125 49.542 51.958 54.375 56.792

68 9.042 11.625 14.208 16.792 19.375 21.958 24.542 27.125 29.708 32.292 34.875 37.458 40.042 42.625 45.208 47.792 50.375 52.958 55.542 58.125 60.708

www.cic-jo.com
72 9.625 12.375 15.125 17.875 20.625 23.375 26.125 28.875 31.625 34.375 37.125 39.875 42.625 45.375 48.125 50.875 53.625 56.375 59.125 61.875 64.625

Table No. 5. Effective free area in ft2 (Ak Factor) for CI - Air PHL - H

19
Stationary Stormproof Louvers
CI - Air SSL - H

General:

CIC stationary stormproof louvers CI - Air SSL-H are mainly


designed to protect air intake and exhaust openings in building
exterior walls and are recommended for applications where low
water penetration is required.

They are carefully designed to provide high free area, maximum


resistance to rain and extreme weather conditions with minimum
resistance to airflow.

Description:

CI - Air SSL-H louvers have heavy gauge horizontal blades


of 1.8 mm thick aluminium extruded profile. They are carefully
designed to get low pressure drop, maximum free area and to
prevent rain water penetration with high efficiency to extreme Stationary Stormproof Louver
weather conditions. (CI - Air SSL-H)
They are available in 1.6” flanged curved frame of heavy gauge aluminium extruded profile which in turn
is mechanically joined to give the highest rigidity and strength.

Louvers can be supplied with galvanized bird or aluminium insect screen, volume control damper and
aluminium air filter of 1”, 2” and 4” thickness.

The filters are accessable from the side or backward of the louver depending upon type of installation and
must be specified by the customer.

These louvers are available in standard given sizes, however they can also be supplied in other requested
sizes and architectural shapes upon customers requirements.

Material and Finish:

CI - Air SSL-H louvers are made of heavy gauge extruded aluminium profiles.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request.
Bird screens are made of galvanized expanded metal sheets.

20 www.cic-jo.com Cooling Industries Company


Stationary Stormproof Louvers
CI - Air SSL - H
Product Code & Dimensional Data

CIC Stationary Stormproof Louver CI - Air SSL-H - W - H - C

Width in inch.

Height in inch.

Accessories:

B : Bird Screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F3 :Aluminium Filter 4” thick.
Dimensional Data

Example:

• CI - Air SSL-H - 24 - 36 - BF1:


CIC stormproof louver size 24” x 36” with
bird screen and I” thick aluminium filter.

• CI - Air SSL-H - 48 - 48 - BDF2


CIC stormproof louver size 48”x48” with bird
screen, volume control damper (VCD) and 2” thick
aluminium filter.

CIC Stationary Stormproof Louver


CI - Air SSL-H

Cooling Industries Company www.cic-jo.com 21


Stationary Stormproof Louvers
CI - Air SSL - H
Selection Procedure

Example:

Louver size required for an exhaust requirements of 1200 CFM with a total pressure drop of 0.07” W.G.

1) From the pressure requirement table 7 it shows that a 600 FPM velocity results an exhaust pressure
drop of 0.07” W.G.
2) Determine the effective free area:

CFM
Effective free area Ak =
Vk
1200
= = 2.0 ft2
600

3) From table 8 the 2.0 ft2 effective area is mostly suitable for the size 42” x 18”.

Note:
For other louver sizes not shown in table 8. The approximate effective free area in square feet can be
calculated by using the following formula:-

Effective free area (Ak) = (0.58H-0.34) x (W-0.3)


Where, H is Height in ft and W is Width in ft.

Available Standard Sizes:


12x12 12x18 12x24 12x30 12x36 12x42 12x48 12x54 12x60 12x66 12x72 12x78 12x84 12x90
18x12 18x18 18x24 18x30 18x36 18x42 18x48 18x54 18x60 18x66 18x72 18x78 18x84 18x90
24x12 24x18 24x24 24x30 24x36 24x42 24x48 24x54 24x60 24x66 24x72 24x78 24x84 24x90
30x12 30x18 30x24 30x30 30x36 30x42 30x48 30x54 30x60 30x66 30x72 30x78 30x84 30x90
36x12 36x18 36x24 36x30 36x36 36x42 36x48 36x54 36x60 36x66 36x72 36x78 36x84 36x90
42x12 42x18 42x24 42x30 42x36 42x42 42x48 42x54 42x60 42x66 42x72 42x78 42x84 42x90
48x12 48x18 48x24 48x30 48x36 48x42 48x48 48x54 48x60 48x66 48x72 48x78 48x84 48x90
54x12 54x18 54x24 54x30 54x36 54x42 54x48 54x54 54x60 54x66 54x72 54x78 54x84 54x90
60x12 60x18 60x24 60x30 60x36 60x42 60x48 60x54 60x60 60x66 60x72 60x78 60x84 60x90
66x12 66x18 66x24 66x30 66x36 66x42 66x48 66x54 66x60 66x66 66x72 66x78 66x84 66x90
72x12 72x18 72x24 72x30 72x36 72x42 72x48 72x54 72x60 72x66 72x72 72x78 72x84 72x90
78x12 78x18 78x24 78x30 78x36 78x42 78x48 78x54 78x60 78x66 78x72 78x78 78x84 78x90
84x12 84x18 84x24 84x30 84x36 84x42 84x48 84x54 84x60 84x66 84x72 84x78 84x84 84x90
90x12 90x18 90x24 90x30 90x36 90x42 90x48 90x54 90x60 90x66 90x72 90x78 90x84 90x90

Table No. 6 CI - Air SSL-H standard sizes available (HxW) in inches.

22 www.cic-jo.com Cooling Industries Company


Stationary Stormproof Louvers
CI - Air SSL - H
Performance Data

Pressure Requirement:
Free Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD" W.G. 0.007 0.018 0.031 0.047 0.070 0.092 0.112 0.145 0.183 0.271 0.380 0.50

Table No. 7 Total pressure drop in inches of water as a function of face velocity in FPM for CI - Air SSL-H.

Effective Free Area

Height Width (Inches)


(Inches) 12 18 24 30 36 42 48 54 60 66 72 78 84 90
12 0.168 0.288 0.408 0.528 0.648 0.768 0.888 1.008 1.128 1.248 1.368 1.488 1.608 1.728

18 0.371 0.636 0.901 1.166 1.431 1.696 1.961 2.226 2.491 2.756 3.021 3.286 3.551 3.816

24 0.574 0.984 1.394 1.804 2.214 2.624 3.034 3.444 3.854 4.264 4.674 5.084 5.494 5.904

30 0.777 1.332 1.887 2.442 2.997 3.552 4.107 4.662 5.217 5.772 6.327 6.882 7.437 7.992

36 0.980 1.680 2.380 3.080 3.780 4.480 5.180 5.880 6.580 7.280 7.980 8.680 9.380 10.080

42 1.183 2.028 2.873 3.718 4.563 5.408 6.253 7.098 7.943 8.788 9.633 10.478 11.323 12.168

48 1.386 2.376 3.366 4.356 5.346 6.336 7.326 8.316 9.306 10.296 11.286 12.276 13.266 14.256

54 1.589 2.724 3.859 4.994 6.129 7.264 8.399 9.534 10.669 11.804 12.939 14.074 15.209 16.344

60 1.792 3.072 4.352 5.632 6.912 8.192 9.472 10.752 12.032 13.312 14.592 15.872 17.152 18.432

66 1.995 3.420 4.845 6.270 7.695 9.120 10.545 11.970 13.395 14.820 16.245 17.670 19.095 20.520

72 2.198 3.768 5.338 6.908 8.478 10.048 11.618 13.188 14.758 16.328 17.898 19.468 21.038 22.608

78 2.401 4.116 5.831 7.546 9.261 10.976 12.691 14.406 16.121 17.836 19.551 21.266 22.981 24.696

84 2.604 4.464 6.324 8.184 10.044 11.904 13.764 15.624 17.484 19.344 21.204 23.064 24.924 26.784

90 2.807 4.812 6.817 8.822 10.827 12.832 14.837 16.842 18.847 20.852 22.857 24.862 26.867 28.872

Table No. 8. Effective free area in ft² (Ak factor) for CI - Air SSL-H.

CI - Air SSL-H CI - Air SSL-H


(Cross section)
Cooling Industries Company www.cic-jo.com 23
AIR FILTERS

Page Contents

2 Aluminum Cleanable Air Filters


3 Technical information
Aluminum Cleanable Air Filters
CI-Air Filters

Synthetic Filter Aluminium Filter

Features:

Cooling industries dry type air-filters model CI-AF is designed to provide maximum arrestance, large
dust holding capacity and low resistance.

The frame is constructed of extruded anodized aluminium alloy.


The filter media is constructed of multiple layers at crimped corrugated wire screen and expanded
Galvanized steel arranged to provide filtering area, uniform air flow, lower resistance and maximum dust
arrestance.
Available in 1”, 2” & 4” thickness.

2 www.cic-jo.com Cooling Industries Company


CI-Air Filters
Technical information

Model No. CIAF-1 CIAF-2 CIAF-4


Initial resistance * (in w.g) 0.05 0.07 0.09
Final resistance (in w.g) 1.00 1.00 1.00
Average arrestance (%) 67 72 78
Dust holding capacity (gm) 225 220 270

List of standard sizes, other sizes available on request


Initia 1 Resistance* Face Air
Nominal size in inches
1” thick 2” thick 4” thick Velocity Flow

Width x Height (in w.g.) (in w.g.) (in w.g.) (FPM) (CFM)
20x10 0.05 0.07 0.09 300 420
25x12 0.05 0.07 0.09 300 625
20x14 0.05 0.07 0.09 300 585
22x14 0.05 0.07 0.09 300 640
25x14 0.05 0.07 0.09 300 730
25x15 0.05 0.07 0.09 300 780
20x16 0.05 0.07 0.09 300 670
25x16 0.05 0.07 0.09 300 835
20x20 0.05 0.07 0.09 300 835
25x20 0.05 0.07 0.09 300 1040
24x24 0.05 0.07 0.09 300 1200
25x25 0.05 0.07 0.09 300 1300

* Initial resistance at 300 FPM nominal face velocity.


To calculate resistance at other face velocity use the following relationships:

- 1 inch thick filter:


Resistance (in w.g.) = 0.008 (v/100)1.65
- 2 inch thick filter:
Resistance (in w.g.) = 0.011 (v/100)1.7
- 4 inch thick filter:
Resistance (in w.g.) = 0.0116 (v/100)1.8

Cooling Industries Company www.cic-jo.com 3


GYPSUM ACCESS PANEL

Page Contents

2 Gypsum Access Panel With Pushing Lock and Wire Hook


Gypsum Access Panel
With Pushing Lock and Wire Hook

Size:
200x200mm, 300x300, 400x400mm, 500x500mm, 600x600mm, etc
Special size or design available per customer's requirement

Main Material:
Aluminium alloy frame with gypsum board inlay
Spare parts anti-rust treated
Fire-resistant and water-resistant is optional.

Characteristic:
A- Removable door panel
B- Precision component, perfect finishing
C- Perfect design, easy to install and operate
D- Light weight but strong, moisture resistance

Product in Details Material:


Frame extruded Aluminium sections
Flap lid Aluminium
Gypsum plaster insert 12mm

Description:
The installation frame of the inspection flap consist of 4 single mitered aluminium profiles that are firmly
Connected with each other through hidden corner plates and a mortise joint.

Thanks to the removables flap lid, easy installation on the wall or the ceiling in ensured .
The inspection flap is equipped with a safety catch on front side ,

The bearing sheets on the flap lid and the counter sheet on the frame allow the inspection flap to be both
wall-mounted and ceiling mounted.
The concealed snap locks open the inspection flap when pushed

Normal Size (MM)


Item No.
A B C D E
GA2020 200 200 12.5 30 40
GA3030 200 300 12.5 30 40
GA4040 200 400 12.5 30 40
GA3030 300 300 12.5 30 40
GA3060 300 600 12.5 30 40
GA4040 400 400 12.5 30 40
GA4060 400 600 12.5 30 40
GA4545 450 450 12.5 30 40
GA5050 500 500 12.5 30 40
GA6060 600 600 12.5 30 40
GA8080 800 800 12.5 30 40
GA60120 600 1200 12.5 30 40

2 www.cic-jo.com Cooling Industries Company


Gypsum Access Panel
With Pushing Lock and Wire Hook

Assembly Instructions:
A- Check inspection flap for proper function
B- Cut out opening aprox. 6mm larger than the nominal size inceling or wall using a compass saw
C- Remove flap lid. diagonall push the frame through the opening and install it

Attention : Make sure the base is clean

Installation:
align the frame with wall installation ensure snap lock is facing upwards-chuck with screw clamp or the
like and pre-drill.
When using screws with drill points, pre-drilling in no required

Attention :
The frame has to be bolted on each side up to 300mm frame length, 2 screws per side of frame as from
400mm frame length, 3 screws per side of frame.
Evenly distribute the drill holes over the entire length screw in drywall screws scres heads have to be
slightly countersunk in the ceiling or wall plate and cover the thread ends that are pointing out on the
rear side with the provided protictive caps, Flush seal the space between the gypsum plaster plate and the
frame with drywall adhesive.

Attention :
It is important to remove the flap lid before hand seal flap lid while remove. Carefully clean inside of frame
and flap lid, diagonally push flap lid into frame, and check its correct functioning, fix safety catch and close
it.

Attention : with wall installation ensure that the locks always face upwards

Field of Application:
The inspection flap is predominantly used in drywall suitable for wall and ceiling installation.
The impregnated gypsum board plaster insert and the corrosion resistant material of the inspection flap
allow for application in damp rooms.

For the wall and ceiling installation with concealed snap locks , integrated gypsum plaster board 12mm,
removable flap lid including installation kit, suitable for damp rooms.

Cooling Industries Company www.cic-jo.com 3

You might also like