Professional Documents
Culture Documents
Plant - Compressed Air - Energy Audit
Plant - Compressed Air - Energy Audit
............................................................................................................................................
In this report, results regarding compressed air system have been reported together with
energy saving proposal definition.
Some investigations have been conducted in order to measure the electric consumptions
of the compressors and the amount of compressed air lost through lacks in the network.
At the moment, the system used to control the compressed air production is semi-
automatic and allows only an on-off regulation of the all compressors. It detects the pressure
inside the manifold and maintains it inside a preset range (6,8÷7,2 bar). Normally, production
centre knows the air demand of the plant and turns on the compressors necessary to satisfy it. The
regulation is done by an on-off control of one compressor, while the remaining compressors are
kept in operation at full load. The on-off controlled compressor is normally an Atlas Copco
GA1408 type. In this configuration the manifold pressure is not constant, but varies within the
range 6,8÷7,2 bar, based on the air required by the industrial plant and on the air production.
Figure 0-1 shows the lay out of the production centre and it can be noted that the air produced by
compressor flows through the dryers and feeds the network.
Pipelines are connected to the same manifold and receive air at the same pressure.
Moreover pipelines are not equipped by flow meter, so the amount of air sent to each line is not
known.
Figure 0-2 shows the lay out of the compressed air network.
Figure 0-2: Lay out of the compressed air network
1.3 Compressors measurement
The compressors energy consumptions have been measured in order to evaluate the total
consumption of the area, the specific consumption of each compressor, the specific cost of a cube
meter of air and the cost of air losses along the network.
Compressors are not equipped with flow meter and an air production at full load (as
reported in the compressor catalogue) has been considered in the following measurements.
GA1408 20 m3/min
The capacity of a compressor is defined as the full rated volume of compressed air flowed
and delivered under conditions of total temperature, total pressure and composition prevailing at
the compressor inlet. It can be considered that the values presented above are the flows of air sent
to the network when the compressors work. When they are in idle, the air sent to the network is
equal to zero even if the electric consumption is not null. While a compressor is in idle, electric
motor spins freely and the compressor (the screw) is off.
Analyzer installed in each electrical station have been used to collect the energy
consumption along a month. The analysis of this data allows to know how many hours the
compressors work and also the total energy consumption of the compressed air area.
1.3.1 Compressor GA1408 n°1
Maximum air flow at 7,5 bar: 20 m3/min
The measurements of air leaks have been done by subtracting the amount of air required
by Rosa (that was always constant) from the compressed air produced by the compressors within
a certain range of time. Rosa is an external supplier of Electrolux sits inside the Porcia plant and
it uses the compressed air produced by the compressed air centre. The results of the evaluation
gives exactly the air wasted through leaks in the network, as all machines fed by compressed air
were turned off. Air leaks, in general, occur at joints, flange connections, elbows, reducing bushes,
sudden expansions, valve systems, filters, hoses, check valves, relief valves, extensions, and at
equipment connected to the compressed air lines.
The energy consumption of the compressor ZR315 n°4 has been evaluated in 6 cases,
when different users were fed. The cases were:
1. Rosa;
2. Rosa, injection molding area;
3. Rosa, assembly area;
4. Rosa, drum line, maintenance area, cutting centre and modeling area;
5. Rosa, varnishing area and plate presses area;
6. Rosa, packaging area.
Figure 0-10: Energy consumption of compressor n°4 – Case 1
Table 0-8 shows the amount of waste compressed air in different areas when the line are
fed, but the factory is not in operation. The area that works well enough is the packaging one, in
fact it presents the lowest air losses. Other areas have a lot of dissipations, especially in the
connection close to the users. Other dissipations have been detected in valves, filters and so on.
1.4 Energy consumption of the area
Thanks to the four analyzers installed in the compressed air area, it was possible to
evaluate the total energy consumption of the area and also to understand how many hours a day
compressors work. With this data it was then calculated the specific cost of compressed air
necessary to evaluate the energy and the economic savings obtainable thanks to the improvements
proposed. Data were collected during 4 weeks, between the end of August and the beginning of
September, when factory worked regularly 5 days a week, on 2 shifts.
The four TA analyzers were connected with four electrical stations which feed all
compressors of the area:
Figures presented above show that energy consumption is quite constant during working
days, while it diminishes on Saturday and it is almost zero on Sunday, except for few Sundays
when Rosa works. In Figure 0-19 it can be noted that there is a lower consumption on Wednesday.
The reason is that it was a day off.
With the data collected it is possible to consider a typical week as a reference. In this way,
detection of not motivated inefficiencies will be easier.
Total yearly net energy consumption of compressed air area: 4.841 MWh/y
Total yearly cost of compressed air area: 510 k€/y
The results introduced in the previous paragraphs have been used to evaluate the cost of
compressed air produced in the area.
Cost of compressed air during a typical working day (2 compressors ZR315 at full load,
2 GA1408 at full load and 1 at partial load) (71% of the total time) 0,0110 €/m3
Cost of compressed air during a typical working night (2 GA1408 at full load and 1 at
partial load) (29% of the total time) 0,0138 €/m3
It has been evaluated the profitability of the installation of an inverter in one of the
compressor GA1408 (20 m3/min). Assuming that the same compressor would be equipped with
a drive, the free air delivered that can be regulated would be the 75% of the nominal flow (15
m3/min).
A simulation with and without inverter has been performed. In Figure 0-21 it can be seen
that a compressor with inverter needs as much power as one without inverter at full load and about
20% less at 25% of the load. So that, the energy saving due to the installation of the inverter is
strongly affected by the variation of the demand during the whole year. The evaluation of the
amount of energy and money savings due to the installation of drives has been performed
assuming that a compressor that regulates the air compressed systems works 7.350 hours per year
at 65% of load level.
Figure 0-21: Simulation of GA1408 working at partial load with and without inverter
When the inverter is installed in almost one compressor, the pressure of the manifold will
be constant as well as the pressure of other compressors. This means that the reduction of energy
consumption can be achieved also by the compressors that work always at full load and it can be
estimated equal to 29 MWh and 3 k€ per year.
Table 0-10 shows that compressors of the same kind need different amount of energy to
produce the same amount of air at the same conditions. This situation can be solved by planning
maintenance interventions in compressors that show performance losses.
At the moment the compressors work alternatively and assuming that they can work better
after maintenance, the total energy that can be saved is reported below:
Total yearly net energy consumption of compressed air area: 4.637 MWh/y
Investment cost cannot be evaluated and investigation with the compressors supplier
(Atlas Group) need to be done.
1.5.3 Leaks prevention
In the Electrolux Porcia Plant, leaks are a significant source of wasted energy and
normally, during working day, 38% of a compressor’s output is wasted. In addition leaks can, by
being source of wasted energy, make air tolls less efficient and adversely affect production,
shorten the life of equipments, lead to additional maintenance requirements and increase
unscheduled downtime. To prevent performance losses, the plant asks to the air compressed centre
to increase the line pressure, and this produces further losses, and increases energy and
maintenance cost of compressed air area.
The cost of compressed-air leaks is the cost of the energy required to compress the volume
of lost air, from the atmospheric pressure to the line pressure.
This cost has been evaluated in Table 0-11, assuming 19 hours a day, 5 days per week,
and 49 weeks per year.
During air leaks measurements have been identified some air leaks that generally occur
at joints, flange connections, elbows, reducing bushes, sudden expansions, valve systems, filters,
hoses, check valves, relief valves, extensions, and at the equipment connected to the compressed-
air lines.
The cost of compressed-air leaks increases exponentially as the diameter of the leak
increases. Leaks should be repaired as soon as it is practical, and may easily be located through
their hissing when other plant operations are idle. In some situations, it may be necessary to wait
for a scheduled plant shutdown. Temporary repairs can often be made by placing a clamp over
the leak. The best way to detect leaks is to use an ultrasonic acoustic detector, which can recognize
the high frequency hissing sounds associated with the air leaks. Ultrasonic leak detection
equipment is an essential component to successful leak abatement programs. This equipment
facilitates the identification of even the smallest leak regardless of the baseline ambient noise
level in an industrial plant. Figure 0-22 shows and ultrasonic leak detector.
Total elimination of air leaks is impractical, but 40% leakage rate is considered
acceptable.
Investment depends on the improvements required to lower pressure drop in the line. If
there is an interest in this direction, more analysis can be done and cost of improvement will be
evaluated.
Average energy for moving water inside the plant is 0,4 kWh/m3 (2009 values) (0,042
€/m3).
Table 0-13 shows the annual energy and cost of compressor cooling systems.
Compression chiller;
Trigeneration systems.
When the cost of water withdrawn from the ground is greater than 0,3 €/m3 a new cooling
systems with compression chillers will become profitable.
1.6 Conclusions
Analysis carried out in compressed air area allowed to identify some wastes and to
propose new solutions in order to save money thanks to energy savings. The analysis carried out
have been reported in paragraphs number 1.3 and 1.4, while the proposals have been introduced
in paragraph number 1.5.
Current costs:
Savings:
Compressed air area represents the 19,6% of the total electricity consumption of
the factory (related to year 2009) and so these improvements can reduce the electric bill
by about 5%.