SOLID WALL HOUSING: PUSHING THE ENVELOPE 

BY 
CHRIS HOCKNELL 
 

Submitted in partial fulfilment  
of the requirements for the degree 
BSc (Hons) Quantity Surveying 
 
Leeds Metropolitan University 
April 2010
Abstract 

The UK has committed to reducing carbon dioxide (CO2) emissions by 80% by 2050 compared 
to 1990 levels.  UK housing currently accounts for 27% of all UK emissions and estimates state 
that  86%  of  existing  housing  will  still  be  standing  by  2050.    Of  the  22.19  million  homes  in 
England, 20.2 million would benefit from cost effective refurbishment measures to make them 
more  energy  efficient  and  therefore  reduce  their  CO2  emissions.    However,  there  are  6.6 
million solid wall dwellings that cannot incorporate cost‐effective energy efficiency measures.  
These are categorised as Hard to Treat dwellings. 

The aim of this dissertation was to address this problem and evaluate the specified solution of 
refurbishing the building envelope and heating system in order to ascertain whether an 80% 
reduction in CO2 emissions can be feasibly and cost‐effectively achieved in solid wall housing.  
The study was based on two refurbishment case studies that achieved significant reductions in 
their  carbon  emissions.    It  involved  a  quantitative  analysis  of  the  energy  consumption  of 
dwellings  through  the  use  of  the  domestic  energy  model  DEMScot.    The  energy  model  was 
utilised  to  substantiate  the  claims  of  the  two  case  studies  and  to  simulate  incremental 
improvements to investigate an optimum point of refurbishment.   

The work builds on previous reports and studies that identify refurbishment as the solution, 
but  have  not  overcome  the  barriers  to  its  implementation.    It  also  considers  some  of  the 
further barriers to refurbishments, such as the currently limited uptake rate of refurbishment 
measures,  the  disruption  caused  to  occupants  and  items  other  than  those  included  in  SAP 
analyses.  Solutions were specified for each of these barriers.   

The main findings were; firstly, the case studies are applicable to other dwellings and with the 
utilisation  of  innovative  materials,  reductions  of  up  to  70%  in  CO2  emissions  are  possible.  
Secondly,  for  both  dwellings  there was  a  point  where  the cost  to  carbon  saving  relationship 
deteriorated and only minor carbon savings were achieved for high costs.  Thirdly, the cost of 
refurbishment  could  be  reduced  by  developing  a  mass  market,  either  by  encouraging  the 
occupants  that  are  willing  to  pay  or  by  targeting  homes  in  fuel  poverty.    Finally,  an 
amendment of policy and Building Regulations could increase the currently low uptake rate of 
refurbishment measures, by ensuring that opportunities to carry out work are maximised and 
that inefficient appliances are removed from the market. 

The conclusion drawn from this study was that solid wall housing can contribute significantly 
to  the  80%  reduction  target.    The  evidence  suggests  that  providing  home  owners  accept 
refurbishment,  reductions  of  up  to  53%  could  be  made  for  minimal  costs.    However, 
refurbishment of solid wall housing must be supplemented by other means to achieve an 80% 
reduction in CO2 emissions. 

Following  the  findings,  one  of  the  key  recommendations  was  that  an  appropriate  body 
develops a method for maximising value in refurbishment, therefore ensuring that high carbon 
savings are delivered for optimum costs.  Furthermore, the government should swiftly amend 
current policy in order to maximise refurbishment opportunities and focus on encouraging the 
public  to  accept energy  efficiency works.    Finally, comprehensive  research  should  be carried 
out  that  investigates  how  and  to  what  extent,  solid  wall  housing  can  be  supplemented  by 
other means in order to develop an overall strategy for dealing with solid wall dwellings. 


Acknowledgements 

I  would  like  to  thank  the  many  people  who  have  assisted  me  during  this  dissertation  and 
throughout my studies.  Firstly, thank you to my dissertation tutor Robert Hayes for his time 
and guidance.  Secondly, I am extremely grateful for the support and encouragement given to 
me by Judith and Steve Hocknell throughout my studies.  Finally, I would like to thank Sandy 
Cowling  for  her  valuable  opinion  and  Katherine  Cowling  for  her  endless  encouragement 
throughout my time at university. 

I would also like to express my gratitude to the people at United House who provided me with 
the research data, and the individuals I contacted throughout the research that endeavoured 
to assist me.      

 
ii 
Contents 

Abstract                      i 

Acknowledgements                    ii 

Contents                      iii 

List of tables and figures                  v 

Abbreviations                      vi 

Chapter one: introduction                  1 

Problem specification                 1 

Literature review                  2 

Methodology                    5 

Chapter two: the UK housing stock                9 

Climate change                  9 

Dwelling emissions                  9 

Chapter three: improvement case studies              12 

Aubert Park                    12 

Midmoor Road                  19 

Chapter four: DEMScot, Scotland’s domestic energy model        24 

DEMScot configuration                24 

DEMScot and SAP outputs ‐ Aubert Park            26 

DEMScot and SAP outputs ‐ Midmoor Road            28 

Evaluation of the model’s outputs              29 

The Ecogen unit                  31 

Chapter five: cost, Value Carbon and other limitations          33 

iii 
Total cost and value                  33 

Value Carbon ‐ Aubert Park                34 

Value Carbon ‐ Midmoor Road              36 

Optimum refurbishment                 39 

The willingness‐to‐pay and reducing costs            40 

Solid wall insulation                  41 

Occupant disruption and occurring opportunities          43 

Items other than those included in the Standard Assessment Procedure     43 

Evaluation of key barriers                 44 

Chapter seven: conclusion and recommendations            46 

Conclusion                    46 

Recommendations                  48 

Bibliography                      49 

   

 
 

iv 
List of tables and figures 

Table  Title                      Page 

1   Average SAP, CO2 and percentage of English housing by construction date   10 

2  Aubert Park improvement measures             13 

3  Midmoor Road improvement measures            20 

4  Aubert Park before refurbishment, SAP and DEMScot outputs      27 

5  Aubert Park after refurbishment, SAP and DEMScot outputs      28 

6  Midmoor Road before refurbishment, SAP and DEMScot outputs      28 

7  Midmoor Road after refurbishment, SAP and DEMScot outputs      29 

8  Aubert Park refurbishment measures, Value Carbon        34 

9  Aubert Park incremental improvements            35 

10  Midmoor Road refurbishment measures, Value Carbon        36 

11  Midmoor Road incremental improvements            37 

Figure  Title                      Page 

1  Cross section of Spacetherm Aerogel insulation board        16 

2  Aubert Park Value Carbon Analysis graph            35 

3  Midmoor Road Value Carbon Analysis graph           38 

 

Abbreviations 

BRE  –  Building Research Establishment 

CHP  –  Combined heat and power 

CO2  –  Carbon dioxide 

DCLG  –  Department of Communities and Local Government 

EST  –  Energy Saving Trust 

HTT  –  Hard to treat 

IPCC   ‐  Intergovernmental Panel on Climate Change 

kWh  –  Kilowatt Hour 

Pa   –  Per annum 

SAP  –  Standard assessment procedure 

vi 
Chapter one: introduction 

Problem specification 

The  UK  has  committed  to  reducing  carbon  dioxide  (CO2)  emissions  by  34%  by  2020,  and  by 
80% by 2050 compared to 1990 levels (OPSI, 2010).  UK housing currently accounts for 27% of 
all UK emissions and it is estimated that 86% of that existing in 1996 will still be standing by 
2050 (Boardman, et al., 2005).  From these statistics, it is clear that the existing housing stock 
presents a substantial obstacle to achieving the UK Government’s emission reduction targets. 

The English House Condition Survey 2007 (DCLG, 2009) stated that of the 22.19 million homes 
in  England,  20.2  million  would  benefit  from  improvement  measures  to  make  them  more 
energy  efficient.    However  there  is  a  certain  sector  that  is  problematic.  This  is  those 
categorised  as  Hard  to  Treat  (HTT)  dwellings.    A  HTT  dwelling  is  defined  as  a  dwelling  that 
cannot  incorporate  token  or  cost‐effective  energy  efficiency  measures,  such  as  insulating 
currently  un‐insulated  or  poorly  insulated  cavity  walls  or  lofts.    Four  categories  of  HTT 
dwellings  have  been  identified  by  the  Building  Research  Establishment  (BRE):  solid  wall 
dwellings,  dwellings  that  are  off  the  gas  network,  dwellings  with  no  loft  space  and  high  rise 
flats.  Older dwellings are more likely to be HTT, 65% of the HTT stock was built before 1945 
(BRE, 2008a).  Dwellings built before this time are predominantly of solid wall construction as 
cavity wall construction only became increasingly common after 1930 (EST, 2006c). 

There are 9.2 million dwellings in England alone that can be considered HTT, comprising 43% 
of the total stock (BRE, 2008a).  Solid wall dwellings make up the biggest proportion with 6.6 
million  dwellings.    There  is  still  no  strategy  for  dealing  with  HTT  homes  and  there  is  a  clear 
divergence of opinion regarding the ability of the HTT housing stock to contribute to the 80% 
emission reduction target.  Recent reports suggest that greatly increasing demolition levels of 
inefficient  dwellings  and  replacing  them  with  efficient  new  builds  would  offset  the  CO2  that 
would  have  been  generated  by  these  inefficient  dwellings  (Boardman,  et  al.,  2005).    Other 
reports have suggested that a nationwide refurbishment programme must be implemented, in 
the form of building envelope renovation and in applicable cases, the installation of renewable 
energy generation technologies (Immendoerfer, et al., 2008).  These conflicting solutions have 
resulted  in  disagreements  between  various  organisations.    Because  of  the  restraints  of  this 
dissertation, the focus will be on refurbishment of the building envelope and heating systems 
in solid wall dwellings.  Renewable energy generation technologies will not be included as they 

are site specific (Mackay, 2009) and would require an extensive study of the geography and 
environment of the specific housing site, which is beyond the remit of this dissertation. 

The  key  to  a  dwelling  being  energy  efficient  is  the  thermal  performance  of  the  building 
envelope, coupled with an efficient energy source (Green Building Press, 2006).  In the context 
of solid wall housing, refurbishment to improve the energy efficiency of the envelope would 
take the form of external or internal wall insulation, insulation to the ground floor and loft (if 
possible),  replacement  of  windows  and  external  doors  and  draught  proofing  (EST,  2006c).  
These solutions would drastically improve the energy efficiency of the dwelling and therefore 
significantly  reduce  its  CO2  emissions  (EST,  2006c).    However,  they  are  not  without  their 
drawbacks.  Insulating a solid wall externally, using a render or cladding system is expensive 
and  alters  the  dwelling’s  appearance  (Immendoerfer,  et  al.,  2008).    Alternatively,  internal 
insulation  is  generally  cheaper  than  external  insulation,  but  disrupts  the  occupants,  reduces 
internal room sizes, increases the risk of thermal bridges and loses thermal mass benefits from 
the solid wall (Immendoerfer, et al., 2008).  Ground floor and loft insulation is only feasible in 
certain solid wall dwellings.  Replacement of windows and  doors is expensive so offers little 
payback  to  the  home  owner,  and  may  not  be  possible  in  some  areas  with  conservation 
interests.  Draft proofing is generally cheap and effective, but it can be difficult to access air 
leakage points (EST, 2006c).  Furthermore, the estimated installation costs of these measures 
can  vary  considerably,  which  leads  to  difficulty  when  trying  to  assess  the  cost‐effectiveness 
and feasibility of these measures.  If an 80% reduction in CO2 emissions is to be achieved by 
2050 the solid wall housing stock must be addressed and an appropriate solution specified. 

The aim of this dissertation therefore, is to evaluate the proposed solution of refurbishing the 
building  envelope  and  heating  system.    It  will  ascertain  whether  an  80%  reduction  in  CO2 
emissions can be feasibly and cost‐effectively achieved in solid wall housing. 

Literature review 

A  sizable  amount  of  literature  has  been  generated  in  recent  years  regarding  solid  wall 
dwellings.  The literature focuses on three main research methods which have examined the 
potential of solid wall housing and the merit given to its preservation.  These are: the use of 
computer  modelling  software,  case  study  analyses  and  consultations  with  specialists.  
Literature covering all these approaches will be appraised in this review.   


All sources examine the case for refurbishment, but there is a range of opinion as to the best 
solutions.  The majority of reports that recommend strategies for solid wall housing have used 
The English House Condition Survey (DCLG, 2009) as a data base.  The English House Condition 
Survey is the largest and most comprehensive data source with regards to the demography of 
the UK housing stock; it details the quantities and condition of over 22 million dwellings.  The 
limitation  of  this  data  is  that  surveys  are  not  conducted  for  every  home  in  the  country;  the 
quantities are derived from large sample surveys.  As a result, there will inevitably be a small 
margin of error in the data.   

The primary source that highlights the inadequacy of solid wall housing is The Environmental 
Change Institute.  This is demonstrated by the extensive report; 40% House (Boardman, et al., 
2005).  This work describes transforming the existing housing stock as an enormous challenge 
in terms of scale and cost, and states that there are limits to the improvements a building can 
incorporate.  As a result, the proposed strategy to achieve 80% emission reductions specifies 
demolishing 3.2 million of the worst houses i.e. solid wall dwellings and replacing them with 
efficient  new  builds.    Refurbishment  is  included  in  the  strategy,  but  only  for  newer  houses 
with superior building fabric performance.  The report was carried out by the Environmental 
Change Institute in collaboration with a number of universities and was funded by the Tyndall 
Centre  for  Climate  Change  Research.    The  shortcomings  of  this  report  are  that  it  does  not 
calculate the additional CO2 emissions generated by demolition and replacement new builds, 
and no detailed analysis of the solid wall housing stock to accept refurbishment measures is 
included  in the  report.   This  is  essential  when considering  the  trade‐off  between  demolition 
and refurbishment. 

The BRE report; Reducing carbon emissions from the UK housing stock (Shorrock, et al., 2005) 
provides a credible examination of the potential of solid wall housing.  The report estimates 
the  potential  CO2  savings  of  refurbishment  measures  and  their  cost‐effectiveness  by  using 
energy  modelling  software.    It  also  models  future  emission  scenarios  and  concludes  that 
insulative  measures  alone  will  not  achieve  the  original  UK  Government  target  of  a  60% 
reduction.    A  significant  take‐up  of  emerging  technologies  is  also  required.    The  report 
estimates  future  uptake  rates  for  refurbishment  measures  by  using  historic  trends.    It 
concludes that refurbishment measures will require an unprecedented uptake rate in order to 
achieve 60%.  Although this is a very important issue, the report does not examine this further.  
An  examination  of  how  to  increase  uptake  rates  is  essential  having  established  such  a 

significant limitation.  As with all future forecasts there is inevitably much scope for divergence 
and the report acknowledges this.  The report also lacks conclusiveness because high and low 
capital costs are used to represent outright purchase costs and marginal costs.  The result is a 
large variance in what is actually deemed to be cost‐effective  

Another  study  using  energy  modelling  software  was  conducted  in  the  report  Thermal 
Improvement  of  Existing  Dwellings  (Clarke,  et  al.,  2005).    The  report  includes  an  extensive 
breakdown  of  the  Scottish  housing  stock  and  features  test  studies  of  improvements  to  two 
solid wall dwellings.  The software was used to estimate the total CO2 reductions for a specific 
dwelling type and was applied to the rest of that house type and ultimately the entire Scottish 
housing  stock.    The  conclusion  was  that  a  50%  reduction  in  CO2  emissions  and  energy  use 
would  be  possible.    The  strength  of  this  work  lies  in  the  comprehensive  analysis  of  the 
dwellings’ construction, which leads to seemingly robust results; providing that the software 
used is accurate.  The limitation of this work is that the energy reduction figures stated may 
not  necessarily  translate  to  English  houses,  because  of  the  difference  in  climate  between 
Scotland and England (Met Office, 2010). 

The previous reports have taken an academic perspective when evaluating refurbishment of 
the solid wall housing stock.  An additional method of research is beneficial (Knight, Ruddock, 
2008) as it will provide a more robust appraisal of the potential of solid wall housing.  As an 
alternative  to  the  theoretical  framework  used  by  the  previous  sources,  Evidence  on  tackling 
Hard to treat properties (Roaf, et al., 2008) is of particular use as it tackles solid wall housing in 
a practical manner.  It includes case studies, which are of significant value, as they represent 
actual  examples  of  refurbishment  projects  as  opposed  to  hypothetical  scenarios.    The  case 
studies in this report demonstrate that substantial CO2 savings are available; however, certain 
improvement measures are expensive so the payback period for the owner can be significant.  
The work was produced for the Scottish Government by Heriot Watt University and SISTech 
Ltd  which  is  a  not‐for‐profit  research  institute.    As  with  Thermal  Improvement  of  Existing 
Dwellings the limitation of this work is that it was modelled around Scottish housing so energy 
consumption  and  therefore  the  associated  savings  may  be  higher  than  possible  in  English 
dwellings. 

With  the  exception  of  work  produced  by  the  Environmental  Change  Institute,  the  previous 
sources  have  demonstrated  reasonable  confidence  in  solid  wall  housing  contributing  to 


significant  reductions.    However,  all  have  fallen  short  of  80%.    The  primary  problem  stated 
throughout all the literature is uncertainty regarding the cost‐effectiveness of refurbishment 
measures,  and  subsequently  the  feasibility  of  implementing  a  UK  wide  refurbishment 
programme.    This  is  further  highlighted  by  Affordable  Warmth  in  Hard  to  Heat  Homes: 
Progress  report  (Pett,  2004).    This  report  is  mostly  concerned  with  Fuel  Poverty,  which  is 
predominantly caused by excessive heating costs because of poor performance of the building 
fabric in solid wall homes (Pett, 2004).  The report conducts a consultation with a wide variety 
of  experts  and  itemises  the  key  barriers  to  treating  solid  wall  homes  and  consequently 
alleviating  Fuel  Poverty.    The  most  significant  barriers  are:  the  cost  of  solutions,  lack  of 
dedicated  government  funds  and  the  awareness  and  disruption  of  homeowners  and 
occupiers. 

The  literature  reviewed  indicates  that  for  the  most  part  it  is  possible  to  decrease  CO2 
emissions by refurbishing solid wall housing.  However, the most consistently stated problems 
are  the  cost‐effectiveness  of  refurbishment  measures  and  the  feasibility  of  applying  these 
measures to the entire solid wall housing stock.  Problems such as disruption to the occupants 
and the lack of government funds have also been specified, although to a lesser extent.   

It  is  these  problems  that  have  so  far  dictated  the  role  that  solid  wall  housing  can  play  in 
reducing CO2 emissions by 80%, and it is these problems that will ultimately decide the fate of 
solid wall housing.  This dissertation will explore these highlighted issues in greater depth.  It 
will  also  incorporate  consideration  of  some  new  and  generally  untested  technologies  that 
could offer a great step toward the 80% target.  It must be noted that this dissertation will not 
engage in the demolition versus refurbishment debate; it will aim to build on previous reports 
and studies that identify refurbishment as the solution, but have not overcome the barriers to 
its implementation.  It will attempt to surmount the current barriers of high expense for little 
carbon saving, and will consider solutions to increasing the uptake of refurbishment measures, 
in order to determine what is required to achieve 80% emission reductions so to answer the 
question; what role can solid wall housing feasibly play in reducing CO2 emissions by 80%? 

Methodology 

This  dissertation  will  aim  to  answer  the  question,  ‘What  role  can  solid  wall  housing  feasibly 
play in reducing CO2 emissions by 80%?’  This question has been addressed by drawing from 
the  theoretical  frameworks  of  Quantity  Surveying  and  Building  Surveying.    It  involved  a 

quantitative  analysis  of  the  energy  consumption  of  dwellings,  i.e.  how  refurbishment 
measures would affect the energy efficiency of dwellings and how the value of these measures 
could be improved by lowering costs.  The answer to this question was investigated through a 
number of research methods.  Modelling was employed by using an energy model in order to 
substantiate  the  claims  of  existing  case  studies,  and  to  simulate  the  different  contributions 
that solid wall housing could make to the Government’s reduction targets.  There was also a 
strong  element  of  problem  solving  as  it  was  necessary  to  consider  systematically  the  main 
barriers to implementing refurbishment of solid wall housing and specify solutions based on 
the  simulation  outputs  and  existing  secondary  research  in  the  form  of  academic  reports, 
surveys and technical literature.   

The  research  starts  with  chapter  two:  the  UK  housing  stock.    This  involves  investigating  the 
amount of CO2 emissions that HTT housing currently contributes and the reductions that could 
be  achieved  by  the  improvement  measures  currently  considered  to  be  cost‐effective.    This 
provides  a  basis  of  comparison  which  is  required  to  place  solid  wall  housing  in  context  with 
the rest of the housing stock. 

Chapter three: improvement case studies, details the refurbishment case studies on which the 
research is based.  The case study method is particularly suited when testing a unique case or 
concept, so is appropriate in this circumstance (Yin, 2003).  All the measures that were applied 
in the refurbishments were examined individually in order to determine how replicable they 
are to other dwellings of that type.  Additionally, underlying assumptions were specified and 
justified.  The  case  studies  used  were  secondary  data.    The  use  of  secondary  data  was 
appropriate,  as  it  provided  a  detailed  in‐depth  analysis  of  the  problem  (Naoum,  2009).  
Furthermore,  the  data  was  generated  and  quality  controlled  by  reliable  sources;  it  would 
make sense to utilise this data (Baxter, et al., 2006). 

The  weakness  of  case  study  based  research  is  that  the  results  of  such  investigations  will  to 
some  extent  always  be  treated  with  a  degree  of  circumspection  because  they  rely  on  data 
from a single case.  It may be questionable how they can be generalised to other cases (Knight, 
Ruddock,  2008).    Consequently  the  relationships  demonstrated  can  only  be  discussed 
intellectually, as opposed to statistically when the sample is large (Naoum, 2009).  However, in 
order to limit the degree of circumspection and therefore promote a good theoretical starting 
point  i.e.  if  solid  wall  housing  can  effectively  be  refurbished  to  achieve  CO2  reductions,  a 


theory  can  be  corroborated  by  repeatedly  testing  it,  and  finding  that  it  is  valid  for  a  large 
number  of  cases  (Knight,  Ruddock,  2008).    Clearly,  repeatedly  renovating  dwellings  to 
establish  whether  they  can  be  effectively  refurbished  would  not  be  practical  or  financially 
viable.    Consequently  a  legitimate  alternative  is  to  use  simulation  of  a  case,  or  concept  to 
validate theoretical predictions, where experimentation on the system under study would be 
prohibitively expensive (Fellows, Liu, 2003).   

The model chosen to simulate and confirm the results of the refurbishments was the domestic 
energy  model  DEMScot  which  is  introduced  in  chapter  four  DEMScot:  Scotland’s  domestic 
energy  model.    The  DEMScot  model  substantiates  the  assertion  that  the  refurbishment 
measures  achieved  the  stated  reductions,  which  achieves  objective  evaluation  of  the  data 
(Fellows, Liu, 2003).  Furthermore, using DEMScot to simulate the refurbishments provided an 
opportunity to verify the model’s outputs with reality (Fellows, Liu, 2003).  This was essential 
to  provide  confidence  in  the  model.    This  chapter  consists  of  a  critique  of  the  BREDEM 
methodology  and  details  the  information  and  parameters  that  were  applied  to  the  model.  
The CO2 reductions stated by the DEMScot model are also presented in comparison with the 
original stated reductions in order to establish the differences that occur. 

The cost of refurbishing dwellings was then considered in chapter five; cost, Value Carbon and 
other limitations.  The DEMScot model was also utilised as a tool to investigate the concept of 
diminishing  returns  and  an  optimum  level  of  refurbishment.    This  investigation  was 
experimental  and  quantitative  in  nature.    An  experiment  is  a  situation  in  which  an 
independent variable is carefully manipulated by the investigator under known, tightly defined 
and  controlled  conditions,  with  respect  to  a  control  point  (Baxter,  et  al.,  2006).    The 
refurbishment measures were the independent variable in this scenario and the CO2 emissions 
were the dependent variable.  The control point was the dwelling before refurbishment.  This 
method was the most suitable as a quantitative experiment is the only research design which 
can in principle, yield causal relationships (Baxter, et al., 2006).  Additional consideration was 
also  given  to  reducing  costs,  as  cost  is  seen  as  one  of  the  most  substantial  barriers  to  the 
implementation  of  refurbishment  programmes.    This  chapter  also  targets  some  of  the 
additional  barriers  associated  with  refurbishment.    Solutions  to  these  barriers  were  sought 
from  existing  secondary  research  such  as  academic  reports  and  surveys.    Consideration  of 
further barriers was required as there are factors other than cost and technicality that affects 
the feasibility of solid wall housing to contribute to the 80% emission reduction target.   

Following this, the final chapter: conclusion begins with a reflection of the evidence presented 
in  the  previous  chapters.    The  individual  objectives  of  each  chapter  were  drawn  upon  to 
provide  an  overall  conclusion  regarding  the  role  that  solid  wall  housing  can  play  in  the  CO2 
emission  reduction  target  for  2050.    The  study  was  then  completed  by  a  collection  of 
recommendations that were deemed to be beneficial to the role of solid wall housing.  
 


Chapter two: the UK housing stock 

Climate change 

In 2004, the UK Government’s chief scientific advisor Sir David King stated that climate change 
is  the  most  severe  problem  the  world  faces  today  (King,  2004).    International  scientific 
consensus states that changes to the global climate are taking place primarily because of the 
increasing  levels  of  anthropogenic  greenhouse  gases  (IPCC,  2001).    Greenhouse  gases  are 
produced by burning fossils fuels to produce energy, the single most abundant greenhouse gas 
being  CO2  (Sturges,  2006).    Greenhouse  gases  present  in  the  earth’s  atmosphere  absorb 
outgoing infrared radiation and cause additional heat to be retained in the atmosphere.  This 
greenhouse property of the atmosphere causes the surface of the earth to be warmer than it 
would  otherwise  be  and  causes  a  change  in  the  global  climate  (IPCC,  2001).    In  2007,  total 
energy  use  by  the  UK  amounted  to  229.4  million  tonnes  of  oil  equivalent.    Of  this  energy, 
93.3% was derived from fossil fuels (Office of National Statistics, 2010).   

In  order  to  mitigate  the  effects  of  climate  change,  the  UK  Climate  Change  Bill  aims  to  have 
reduced total CO2 emissions by 80% in 2050.  Currently there has not been a definitive target 
allocated  specifically  to  domestic  energy;  only  an  approximate  figure  of  a  15%  reduction  in 
CO2 emissions by 2020 for the total stock has been suggested (DirectGov, 2010).  However, as 
housing currently accounts for 27% of all UK emissions, a significant contribution to the overall 
80% target must be made by improving the energy performance of housing.   

Dwelling emissions 

The  Government’s  Standard  Assessment  Procedure  (SAP)  is  the  tool  used  to  monitor  the 
energy  efficiency  of  homes.    It  is  based  on  a  home’s  energy  costs  per  m2  of  floor  area  for 
standard  occupancy  of  a  dwelling  and  a  standard  heating  regime.    It  does  not  incorporate 
geographical  location;  this  allows  buildings  to  be  compared  with  others  across  the  UK.    The 
energy costs take into account the costs of space and water heating, ventilation and lighting, 
less cost savings from energy generation technologies.  The rating is expressed on a scale of 1‐
100  and  is  presented  in  a  banding  system  of  G  to  A  for  Energy  Performance  Ratings.    A 
dwelling with a rating of 1 (band G) has poor energy efficiency and therefore high costs and a 
dwelling with a rating of 100 (band A) represents zero net energy cost per year. 


Energy performance is strongly related to the age of a dwelling because of the development of 
the Building Regulations (DCLG, 2010).  Approximately 22% of the current housing stock was 
built pre 1919; these dwellings have an average SAP rating of 40 and emit 9.0 tonnes of CO2  a 
year.  This can be compared with post 1990 homes which have an average SAP rating of 65 
and emit 4.5 tonnes of CO2 a year, as demonstrated in table 1. 

   Average  Average CO2  Total CO2  Total CO2  % of  % of 


SAP  per dwelling  emissions for the  emissions for  housing  housing 
(tonnes/pa)  whole tenure  the whole  stock  age that is 
(million  tenure (%)  HTT
tonnes/pa) 
Pre 1919  40.4  9  43  29%  22%  89%
1919 ‐ 1944  45.5  7.2  27.8  19%  17%  47%
1945 ‐ 1964  49.5  6.2  26.9  18%  20%  26%
1965 ‐ 1980  52.4  5.7  27.3  19%  22%  27%
1981 ‐ 1990  56.6  5.1  9.5  7%  9%  24%
Post 1990  64.7  4.5  11.3  8%  11%  19%
                  
All tenures  49.8  6.6  145.8  100%  100%  43%
Table 1: Average SAP, CO2 and percentage of English housing by construction date (DCLG, 2009) (BRE, 2008b) 

It is older housing which is most likely to be HTT.  Of the 9.2 (43% of total stock) million HTT 
homes  in  England,  5.91  million  (65%)  were  built  pre  1945  and  a  further  2.11  million  (22%) 
were  built  between  1945  and  1975  (BRE,  2008a).    Solid  wall  dwellings  make  up  the  biggest 
proportion with 6.6 million dwellings (31% of the total stock and 72% of the HTT stock).  Off 
the  gas  network  dwellings  make  up  the  next  biggest  proportion  with  2.8  million  dwellings 
(13% of the total stock and 30% of the HTT stock).  There are also approximately 1.8 million 
(8%  of  the  total  stock  and  19%  of  the  HTT  stock)  dwellings  that  have  more  than  one  HTT 
characteristic so can be considered particularly problematic (BRE, 2008a).  Dwellings of solid 
wall construction suffer from high fabric heat loss which leads to high energy consumption. 

It has been established that 20.2 million homes (91% of the total stock) in England could have 
their emissions reduced cost‐effectively by refurbishment measures.  Cost‐effective measures 
alone would benefit 81% of HTT housing and would leave 1.7 million HTT dwellings unable to 
receive any cost‐effective reductions (BRE, 2008a).  Measures that are considered to be cost‐
effective  are;  installation  or  upgrade  of  loft  insulation,  installation  of  cavity  wall  insulation, 
installation  or  upgrade  of  hot  water  cylinder  insulation,  upgrading  central  heating  controls, 
upgrading to a class A condensing boiler, upgrading storage radiators, installation of hot water 
cylinder thermostats and replacement of warm air units where the original units are pre‐1998 
(DCLG, 2009).   

10 
The greatest scope for improvement is housing built between 1919 and 1980.  This is because 
of the highest numbers of unfilled cavity walls and in which loft insulation top‐ups and heating 
control  upgrades  still  have  high  potential.    The  least  scope  for  improvement  is  in  the  most 
recently  built  homes  which  already  include  more  efficient  measures  in  their  design  and 
construction so already operate at a higher level of performance.  HTT homes (predominantly 
pre 1919) show relatively modest improvement potential because of the difficulty of applying 
cost‐effective  measures.    As  these  dwellings  have  very  high  CO2  emissions  to  begin  with, 
reductions  of  1.6  tonnes/year;  from  9.0  to  7.4  tonnes/year  are  possible  on  average  (DCLG, 
2009).    However,  a  HTT  dwelling  emitting  7.4  tonnes/year  post  refurbishment  is  still 
unacceptable given that post 1990 dwellings currently emit 4.5 tonnes/year. 

If all the cost‐effective improvement measures described previously were fully implemented, 
CO2  emissions  would  fall  on  average  by  1.5  tonnes/year  for  every  home  (DCLG,  2009).    This 
would  result  in  an  estimated  total  saving  of  33  million  tonnes  of  CO2;  22%  of  total  English 
housing  stock  emissions  (DCLG,  2009).    The  approximate  cost  of  carrying  out  these 
improvements is £30 billion (2009 prices) which equates to an average expenditure of £1,500 
for each of the 20.2 million homes that would benefit (DCLG, 2009).  Although a 22% reduction 
in  emissions  from  housing  is  a  considerable  step  towards  the  total  overall  UK  reduction  of 
80%,  it  is  insufficient.    Reductions  which  are  not  made  in  housing  will  have  to  be  made 
elsewhere in the transport, industry, agriculture and service sectors.  If an 80% reduction from 
the housing sector is to be achieved, measures beyond those currently considered to be cost‐
effective must be implemented.  

 
11 
Chapter three: improvement case studies 

Cost‐effective  improvement  measures  alone  will  only  achieve  a  22%  CO2  reduction; 
consequently  refurbishment  measures  that  achieve  higher  reductions  are  required.    HTT 
dwellings constitute 43% of the total housing stock and are responsible for emitting over half 
of UK domestic emissions (BRE, 2008b).  In order to establish what emission reductions can be 
achieved by refurbishment of the solid wall stock and the associated cost, two refurbishment 
case studies have been selected for analysis.  The objective of this chapter is to consider each 
of  the  refurbishment  measures  individually  and  evaluate  how  replicable  they  are  to  other 
dwellings.  Any assumptions that have been made will also be identified and justified.  Both 
projects  have  utilised  similar,  relatively  innovative  materials  and  equipment  to  achieve 
substantial savings. 

Aubert Park 

The  first  solid  wall  refurbishment  is  70a  Aubert  Park,  Islington,  London.    This  dwelling  is  a 
Victorian  ground  floor  terrace  flat  with  13"  and  9"  solid  brick  external  walls,  single  glazed 
timber sash windows and a floor area of 47m2.  The property is not in a conservation area but 
was not suitable for external insulation or replacement double glazed windows.  The project 
participants were United House and BRE.  United house carried out the works and BRE were 
utilised to independently assess the CO2 reduction results using SAP.   

BRE and United House differ in their conclusion of the total CO2 savings for this refurbishment.  
The difference in CO2 reductions is because of a lack of test data for the micro Combined Heat 
and  Power  (CHP)  unit  that  was  newly  installed,  consequently  BRE  based  their  modelling 
around a condensing boiler instead.  As a result BRE calculated that CO2  reductions were 60% 
and United House calculated that they were 70%.  In order to maintain absolute neutrality the 
data generated by BRE, the independent participant would preferably be used.  However, the 
BRE  data  will  not  used  for  three  reasons.    Firstly,  considerably  robust  results  by  the  Carbon 
Trust  relating  to  micro  CHP  test  data  suggests  that  United  House’s  calculations  are  very 
realistic, this is discussed in depth later.  Secondly, the opportunity to investigate innovative 
technology should be maximised in order to break new ground.  It would be unproductive to 
repeat  conventional  practices  and  reiterate  what  has  already  been  established  by  past 
refurbishments.    Thirdly,  the  differences  between  United  House  and  BRE  affect  various 

12 
calculations  so  results  from  both  sources  cannot  be  pooled,  analysis  is  only  possible  if  data 
from one source is used.  Consequently, the United House data will be used.  

There  was  no  CO2  reduction  target  for  this  refurbishment.    Instead,  a  contractor‐led  Value 
Engineering approach was taken, which focused on maximising the carbon saving for every £ 
spent; this method has been given the name Value Carbon.  This involved an extensive survey, 
detailed  analysis  of  the  data  and  careful  selection  of  the  improvement  measures.    Value 
Carbon  is  a  suitable  unit  of  measurement  because  it  includes  cost;  therefore  an  element  of 
value  is  incorporated.    Cost  is  a  substantial  barrier  to  improvement  measures  and  therefore 
must be considered (Pett, 2004); focusing on CO2 reductions alone would not provide this.  No 
renewable technologies were used, and the project also featured some innovative materials 
and equipment that were used for the first time in the UK.  The improvement measures are 
displayed in table 2. 

Measures 
1) Low energy lighting 
2) Draught proofing 
3) Micro CHP gas boiler 
4) Double glazing (vacuum) 
5) Insulate external walls 
6) Insulate floors 
7) Mechanical Ventilation with Heat Recovery (MVHR) 
8) Rainwater harvesting 
9) Insulate thermal bridges 
Table 2: Aubert Park improvement measures 

Each of the measures listed in table 2 will now be expanded upon and analysed using technical 
literature.    The  aim  of  this  is  to  critically  assess  how  replicable  these  measures  are  and 
consider  any  irregularities  in  this  project  that  would  limit  the  ability  of  applying  these 
measures to other dwellings.    

1) Low energy lighting 

• Before refurbishment: incandescent throughout. 

• After refurbishment: CFL low energy lighting installed throughout. 

CFL  bulbs  can  be  used in  almost  all  light  fittings  and  significant  savings  can  be made  quickly 
(Boardman, 2007).  This improvement measure is applicable to all dwellings.   

13 
2) Draught proofing 

• Before refurbishment: air tightness of 9.08 m3/hr/m2. 

• After refurbishment: design air tightness of 5.0 m3/hr/m2. 

Five individual air tightness tests were carried out to quantify individual leakage paths around 
the  flat.    Cracks  and  gaps  around  service  penetrations,  windows  and  doors  and  floors  were 
sealed.    Part  L1A  2006  requires  that  new  builds  have  a  Maximum  Air  Permeability  of  <  10 
m3/hr/m2  and  best  practice  is  considered  to  be  3  m3/hr/m2  (EST,  2005).    Existing  dwellings 
have no requirement but can reach up to 25 m3/hr/m2 (EST, 2005). 

The comprehensive draught proofing measures carried out on this flat were very effective; a 
recent  study  showed  that  of  100  new  dwellings  tested  for  air  tightness;  only  3  achieved 
5m3/hr/m2 (EST, 2005).  The level of air tightness will obviously vary from dwelling to dwelling; 
however, the benefits of draught proofing are significant across to all dwellings.  Energy loss 
due  to  ventilation  accounts  for  approximately  one  fifth  of  space  heating  demand  in  older 
dwellings  and  approximately  one  third  of  space  heating  demand  in  newer  well  insulated 
dwellings (EST,2006a); a greater proportion of energy loss occurs from air leakage as insulation 
increases  (Jennings,  2006).    Indicative  average  costs  and  associated  CO2  savings  for  draught 
proofing to a 3 bedroom semi detached dwelling were stated to be £100 for a 43kg CO2 saving 
(DCLG, 2006).  Based on the data that states very few dwellings achieve the best practice level 
of  air  tightness,  and  therefore  have  scope  for  significant  improvement,  this  improvement 
measure will be considered to be as effective and applicable on other dwellings.  

3) Micro CHP gas boiler 

• Before  refurbishment:  Ideal  Sprint  F  rated  combination  boiler  (65%  efficiency), 


programmer and room thermostat, room sealed fanned flue. 

• After refurbishment: Baxi Ecogen micro CHP (82% efficiency). 

A  micro  CHP  system  produces  both  heat  and  electricity.    This  system  is  heat  led  so  only 
produces electricity when the heating system is in operation.  This was the first unit to be used 
commercially in the UK and as a result test data was not available at the time of assessment.  
This resulted in two different sets of results being produced by BRE and United House.  Data 
determining  the  efficiency  of  the  Ecogen  is  discussed  further  in  chapter  four:  DEMScot, 
14 
Scotland’s  domestic  energy  model.    The  Ecogen  is  wall  hung  and  providing  the  system  is 
adequately sized for the dwellings heating demands, could be successfully integrated into all 
dwellings (Baxi, 2010a). 

4) Double glazing (vacuum) 

• Before refurbishment: single glazed sash windows, U‐value 4.91 W/m2K 

• After refurbishment: vacuum glazing to front facade only, average glazing U‐value 3.49 
W/m2K (U‐value 1.19 W/m2K for windows with vacuum glazing, including frame) 

Pilkington  Energikare  Legacy  vacuum  glazing  is  the  first  example  of  vacuum  glazing  that  is 
commercially available in the UK.  The glazing was installed in the two living room windows to 
the front of the dwelling.  Sash windows usually cannot accommodate double glazed units as 
the  rebates in  the  glazing  bars  are  not  deep enough  (Taylor,  1996).    Pilkington  Energikare  is 
intended for this application as the thermal performance can be improved whilst maintaining 
a  building’s  historic  façade.    Replacement  units  like  these  may  only  be  unacceptable  in  the 
exceptional circumstance of the building being listed (Taylor, 1996).  It is estimated that there 
are 300,000 residential buildings listed as architecturally important (Boardman, et al., 2005).  
Therefore,  unless  the  dwelling  is  listed  this  measure  will  be  applicable  to  all  dwellings.    The 
box  frame  was  retained  and  new  sashes  were  installed  to  hold  the  glazing.    Although  BRE 
states the old sashes could have been retained no allowance will be made to adjust the cost. 

5) Insulate external walls    

• Before  refurbishment:  solid  brick,  225mm  and  330mm  thicknesses  plus  internal 
partitions to unheated basement/corridor, average U‐value 1.19 W/m2K 

• After  refurbishment:  Spacetherm  Aerogel,  37mm  to  internal  surfaces  and  Sempatap 
flexible  thermal  lining  magic  wall  paper  to  communal  basement/corridor  partition, 
average U‐value 0.33 W/m2K 

15 
 
Figure 1: Cross section of Spacetherm Aerogel insulation board (Balson, 2009) 

Lengths  of  25mm  battens  were  fixed  to  the  internal  surfaces  of  all  exposed  walls  and 
Spacetherm Aerogel insulation board with three layers of matting was fixed to the battens, a 
25mm air gap was left between batten runs; figure 1.  This was the first project in the UK to 
use  this  material.    Spacetherm  is  particularly  appropriate  for  dwellings  of  smaller  floor  size 
where the reduction of internal space must be minimal.  Other insulation types may require a 
layer up to 120mm thick to achieve the same thermal performance, therefore making internal 
wall  insulation  impractical  because  of  the  loss  of  internal  space  (EST,  2006c).    Internal  wall 
insulation would not be applicable to dwellings where the disruption to occupants and fixtures 
would  be  too  great,  excessive  thermal  bridging  would  be  difficult  to  avoid  and  in  the 
exceptional instance that the interior of the building is protected under a listed building order 
(EST,  2006c).    However,  these  exemptions  are  rare  and  theoretically  internal  wall  insulation 
could be applied to the vast majority of dwellings (BRE, 2008b).  Although practically possible 
in  all  dwellings,  in  reality  there  are  other  factors  that  limit  its  applicability.    Further 
consideration  to  the  number  of  applicable  dwellings  will  be  discussed  in  chapter  five  Cost, 
Value Carbon and other limitations.  BRE states that because of a lack of experience in cutting 
this  material,  wastage  and  therefore  cost  was  high,  however  no  attempt  will  be  made  to 
adjust the cost for wastage, because the quantity is not known.  

 
16 
6) Insulate floors 

• Before refurbishment: suspended timber floor, U‐value 0.72 W/m2K and concrete floor 
in kitchen extension, U‐value 0.70 W/m2K 

• After  refurbishment:  fully  insulated  timber  floor,  U‐value  0.45  W/m2K  and  no  work 
done to concrete floor. 

Heat loss and air leakage were reduced by sealing off the cellar below the timber floor which 
was  too  small  to  be  used  as  a  living  space.    The  floor  boards  were  removed  and  100mm  of 
plaster  was  hacked  off  from  the  bases  of  the  walls.    A  breathable  airtight  barrier  was  laid 
across  and  between  the  joists  and  lapped  up  the  base  of  the  walls,  the  voids  between  the 
joists were then filled with Warmcell fibre insulation and the floor boards were replaced.  The 
bases of the walls were re‐plastered with the airtight barrier sealed into the plaster, the new 
skirting boards were then laid and gaps sealed. 

BRE commented that this improvement measure was time consuming and it would also not be 
possible to carry out while there were occupants present in the house because of health and 
safety  reasons  relating  to  the  fibre  insulation.    If  the  cellar  had  allowed  freer  access,  an 
alternative solution suggested by the BRE would be to leave the floor boards intact, board the 
underside  of  the  joists,  and  inject  spray  foam  insulation  between  the  joists.    This  method 
would achieve comparable air tightness with less disruption, and a consistent fill between the 
joists  would  offer  significantly  higher  thermal  performance.    If  access  from  above  were  the 
only option, an alternative that would be possible with the occupants present would be to lift 
the floor boards, drape a support netting over the joists and lay board or roll insulation on top 
of the netting (EST, 2006c).  Although the air tightness would be inferior, draughts from the 
floorboards could be reduced by fixing large area boards over the top or replacing them with 
moisture resistant chipboard with glued tongue and grooved joints.  As demonstrated by the 
above, suspended timber floors can be improved in practically all circumstances (EST, 2006c); 
therefore  improvement  of  the  floors  is  deemed  applicable  in  the  vast  majority  of                 
dwellings.      

7) Mechanical Heat Recovery Ventilation (MVHR) 

• Before refurbishment: two extract fans 

17 
• After refurbishment: Vent Axia HRE‐350 MVHR system (89% efficiency) 

The design air tightness of 5.0 m3/hr/m2 meant that mechanical ventilation could provide CO2 
savings.  The MVHR unit was installed in the kitchen, and a boxed in section was added to the 
kitchen  and  living  room,  a  lowered  ceiling  was  installed  in  the  hallway  to  distribute  the 
ductwork through the dwelling.  BRE stated that the significant amount of labour involved in 
installing the unit and the associated ductwork meant that it would be unfeasible to carry out 
the work with the tenant in place.  There were also additional air leakage paths created by the 
installation of the ductwork in the kitchen that required sealing.  This measure would only be 
applicable to dwellings where a major refurbishment takes place because the costs are high 
and an exceptional rate of air tightness must be reached in order for MVHR to provide carbon 
savings (EST, 2006a).   

8) Rainwater harvesting 

• Before refurbishment: standard taps, bath and WC.  

• After  refurbishment:  rainwater  harvesting,  Twyford  Galorie  Flushwise  4/2.6  litre  dual 
flush WC, Tapmagic inserts for taps, bath unchanged. 

The water saving measures on this refurbishment were regarded as giving no carbon saving.  
However,  all  the  measures  installed  resulted  in  a  24%  saving  in  water  use.    Although  water 
efficiency  is  a  major  goal  in  refurbishment  as  approximately  23%  of  CO2  emissions  are  from 
hot water use (EST, 2010b), only the tap inserts would reduce the consumption of hot water.  
Consequently  because  of  the  minor  reduction  in  CO2,  this  measure  will  not  be  considered 
when applying measures to other dwellings. 

9) Insulate thermal bridges 

• Before  refurbishment:  full  assessment  not  undertaken,  assumed  Y‐value  of  0.15 
W/m2K.  

• After refurbishment: full assessment not undertaken, retained Y‐value of 0.15 W/m2K. 

The  project  scope  did  not  allow  for  a  detailed  technical  assessment  of  thermal  bridging.  
Without dedicated modelling, the affect on thermal bridging by improvement measures could 
not be accurately assessed.  Consequently no credit could be gained in SAP as a Y‐value of 0.15 
18 
W/m2K was used in both before and after models.  However, effort was still made to reduce 
bridging  by  targeting  the  party  walls  and  bedroom  windows  reveals.    A  disadvantage  of 
internal  wall  insulation  is  that  at  the  junction  of  the  party  wall  with  the  external  wall,  cold 
spots can occur.   Internal insulation was returned along the party wall from its intersection 
with  the  external  wall,  therefore  reducing  the  temperature  gradient.    Voids  behind  the 
window  reveals  were  filled  with  mineral  wool.    Because  of  the  complex  nature  and  the 
detailed data required to conduct thermal bridge modelling (Abdullatiff, 2003), there will be 
no reductions made in the Y‐value when modelling other dwellings.  Consequently the cost of 
carrying out this work will not be included in other refurbishments.   

Midmoor Road 

The second solid wall refurbishment that achieved substantial savings was 46 Midmoor Road, 
Balham, London.  The dwelling is a Victorian 3 bedroom mid terrace with 225mm solid brick 
walls.  It is not in a conservation area and has a floor area of 99 m2.  The project was carried 
out  by  Family  Mosaic  housing  association.    It  must  be  noted  that  SAP  calculations  for  the 
dwelling  before  the  refurbishment  were  not  available,  only  SAP  data  was  available  for  the 
dwelling after the refurbishment.    Consequently, a SAP assessment was carried out using the 
SAP manual (BRE, 2009) and the data that was available.  U‐values before refurbishment for 
some of the building elements have been assumed based on technical literature (BRE, 2001).  
The  default  ventilation  rates  and  electrical  use  have  been  taken  from  the  SAP  manual  (BRE, 
2009)  and  the  English  Building  Regulations  (DCLG,  2010).    Furthermore,  an  assumption  has 
also been made for the specification of the heating system before refurbishment.      

This is one of the weaknesses in study; the pre refurbishment data for Midmoor Road should 
to  some  extent,  be  treated  as  indicative  because  of  the  assumptions  that  had  to  be  made.  
However, Family Mosaic achieved a 63% reduction in CO2 emissions from a refurbishment of 
an identical dwelling on the same road the following month.  The only difference between the 
two dwellings was that 46 Midmoor achieved a less airtight envelope.  Consequently, the CO2 
savings were lower in 46 Midmoor Road because of a higher space heating requirement (EST 
2006a). 

This  dwelling  is  unique  in  that  it  was  converted  into  two  1  bedroom  flats  several  years  ago; 
Family  Mosaic  converted  the  dwelling  back  to  a  3  bedroom  terrace  in  2009.    Consequently 

19 
there were works other than the energy efficiency measures involved in the project, such as 
minor demolition and construction of partitions, and re‐joining of services.  It must be noted 
that the incorporation of other works would most likely result in a reduction in the cost of the 
energy  efficiency  measures  (BRE,  2001).    The  measures  aimed  at  improving  the  energy 
efficiency of the dwelling are displayed in table 3: 
Measures 
1) Low energy lighting 
2) Draught proofing 
3) Loft insulation 
4) Micro CHP 
5) Insulate external walls 
6) Insulate timber floor 
7) Insulate concrete floor 
8) Mechanical Ventilation with Heat Recovery (MVHR) 
Table 3: Midmoor Road improvement measures 

Each  of  the  measures  listed  in  table  3  will  be  expanded  upon  and  analysed  using  technical 
literature to critically assess how replicable these measures are and any assumptions will be 
detailed and justified. 

1) Low energy lighting 
• Before refurbishment: incandescent throughout. 

• After refurbishment: CFL low energy lighting installed throughout. 

CFL  bulbs  can  be  used in  almost  all  light  fittings  and  significant  savings  can  be made  quickly 
(Boardman, 2007).  This improvement measure is applicable to all dwellings.   

2) Draught proofing 

• Before refurbishment: air tightness unknown. 

• After refurbishment: air tightness of 7.5 m3/hr/m2. 

The  draught  proofing  measures carried  out  achieved  a  good  level  of  air  tightness.    However 
the  degree  of  improvement  in  not  known  as  the  air  tightness  before  refurbishment  is 
unknown.  The air change rate in this dwelling is higher than could have been achieved as two 
chimneys  and  open  flues  were  left  vented  after  refurbishment.    The  redundant  fire  places 
were bricked up and then vented; these vents contribute significantly to the air changes per 
20 
hour  figure.    The  exact  reason  why  these  vents  were  left  unsealed  is  unknown.    However, 
because the moisture levels in sealed chimneys increase rapidly, it is therefore recommended 
that ventilation remains in redundant flues (Taylor, 2009).  This may have been the rationale 
when  refurbishing  this  dwelling,  although  as  a  result,  the  space  heating  requirement  was 
increased  because  of  these  remaining  ventilation  points.    As  with  Aubert  Park,  this 
improvement measure will be considered to be as effective to other dwellings. 

3) Loft insulation 

• Before refurbishment: 50mm insulation, U‐value 0.22 W/m2K assumed 

• After refurbishment: 270mm insulation, U‐value 0.14 W/m2K. 

Sheets of 100mm insulation were laid between joists and a blanket of 170mm was laid above 
joists.  The thickness of insulation before refurbishment is unknown, although the price in the 
bill  of  quantities  is  for  270mm.    The  assumption  of  50mm  has  been  made  for  two  reasons.  
Firstly, houses owned by housing associations such as Family Mosaic are much more likely to 
have  cost‐effective  measures  such  as  loft  insulation  utilised  (DCLG,  2009);  it  would  be  very 
rare for a housing association to let properties with no insulation in the loft.  Secondly, the U‐
value of a loft with no insulation is 1.14 W/m2K (BRE, 2001); if this U‐value were included in 
the model, a pre and post refurbishment comparison would show significant improvement in 
energy  consumption  and,  this  would  skew  the  actual  CO2  savings  resulting  from  the 
refurbishment.  This measure would be applicable to most other dwellings as 46% of all mid 
terraces, including both HTT and non HTT would benefit from additional loft insulation (DCLG, 
2009).    Furthermore,  only  6%  of  all  solid  wall  houses  have  no  loft  to  insulate  (BRE,  2008b).  
Consequently the measure will be deemed applicable to the majority of other dwellings.   

4) Micro CHP gas boiler 

• Before refurbishment: standard combination boiler (70% efficiency), assumed. 

• After refurbishment: Baxi Ecogen micro CHP (82% efficiency), assumed.   

A  full  replacement  of  the  hot  and  cold  water  system  was  carried  out  on  this  dwelling.  
Although  the  boiler  present  before  refurbishment  is  unknown;  an  assumption  of  70% 
efficiency  has  been  made  based  on  the  base  case  for  solid  wall  dwellings  (EST,  2006c).    A 

21 
conventional  gas  boiler  (87.3%  efficiency)  with  hot  water  storage  was  specified  for  the 
refurbishment  as  a  solar  panel  was  installed  on  the  roof  of  the  dwelling.    As  outlined 
previously; renewable energy generation technology is beyond the remit of this dissertation.  
This  presents  a  difficult  scenario  as  the  specification  of  the  heating  system  may  be  quite 
different without the solar panel being included.  Given that an entire boiler replacement was 
required, an assumption has been made that without the solar panel in the specification, the 
most likely replacement would have been a micro CHP.  This assumption has been made based 
on  the  current  refurbishment  project  of  84  Midmoor  Road  where  Family  Mosaic  have 
specified a Baxi Ecogen micro CHP.  The Ecogen unit was not commercially available when this 
refurbishment  originally  took  place  (Baxi,  2010b),  Family  Mosaic  suggest  this  may  be  the 
future preference for their refurbishments.  The Ecogen could be integrated into all dwellings 
(Baxi, 2010a). 

5) Insulate external walls    

• Before refurbishment: 225mm solid brick, U‐value 2.1 W/m2K 

• After  refurbishment:  Kingspan  Kooltherm  K17  dry  lining  board  32.5mm,  U‐value  0.55 
W/m2K 
Boards of Kingspan Kooltherm were fixed to internal surfaces of exposed walls and chimney 
breasts.    Kooltherm,  like  Spacetherm,  minimises  internal  space  intrusion  due  to  its  minimal 
thickness.    Further  consideration  to  the  number  of  applicable  dwellings  will  be  discussed  in 
chapter five: cost, Value carbon and other limitations. 

6 & 7) Insulate floors 

• Before  refurbishment:  suspended  timber  floor;  U‐value  0.72  W/m2K,  and  concrete 
floor in kitchen extension; U‐value 0.70 W/m2K 

• After  refurbishment:  fully  insulated  timber  floor;  U‐value  0.20  W/m2K,  new  concrete 
slab laid on insulation; U‐value 0.24 W/m2K. 

Floor boards were removed and netting was draped over the joists.  New Rockwool insulation 
was laid on top of the netting and new chipboard flooring was laid.  The concrete floor in the 
kitchen extension  was  completely  broken  out,  a  layer  of  insulation  was  then  laid and  a  new 
slab was poured.  As with Aubert Park the suspended timber floor improvement is considered 
22 
to be applicable to other dwellings.  However, the removal of the concrete slab would only be 
possible  in  dwellings  with  an  extension  and  cellar.    Moreover,  it  is  a  considerably  disruptive 
process and would most likely not be possible if the occupants were present (EST, 2010b). 

7) MVHR 

• Before refurbishment: natural ventilation 

• After refurbishment: Vent Axia MVHR system (86% efficiency) 

The  after‐refurbishment  air  tightness  of  7.5  m3/hr/m2  meant  that  mechanical  ventilation 
would most likely not provide CO2 savings (EST, 2006a).  Specifying MVHR was a poor decision 
by  the  project  team.    This  measure  would  only  be  applicable  to  dwellings  where  a  major 
refurbishment takes place because the costs are high and an exceptional rate of air tightness 
must be reached in order for MVHR to provide carbon savings (EST, 2006a).   

The refurbishment measures that were applied to both dwellings have been reviewed in order 
to establish how applicable they would be to others.  The majority of these measures could be 
applied  to  all  other  dwellings  of  the  same  type,  with  the  exception  of  the  internal  wall 
insulation in some circumstances, the MVHR and the concrete floor insulation.  The internal 
wall  insulation  is  an  essential  component  of  these  refurbishments  and  without  it  the  CO2 
reductions  would  be  much  lower.    This  presents  a  significant  barrier  which  will  be  fully 
considered in chapter five: cost, Value Carbon and other limitations.  The MVHR and concrete 
floor insulation have a less significant bearing on the CO2  reductions which is demonstrated in 
chapter five: cost, Value Carbon and other limitations.  With the exception of the above, these 
refurbishments are very applicable to others of that type.  The next chapter will model these 
case studies in order to verify the stated CO2 reductions.  

23 
Chapter four: DEMScot, Scotland’s domestic energy model 

DEMScot configuration  
Having  established  the  applicability  of  the  chosen  case  studies  to  other  dwellings,  the  next 
step  is  to  strengthen  reliability  in  the  case  studies  using  DEMScot.    Furthermore  using  the 
DEMScot  model  in  comparison  with  SAP  will  give  an  opportunity  to  view  where  DEMScot 
differs in its outputs.   Any differences will be considered when using the model to generate 
Value Carbon scenarios in chapter five: cost, Value Carbon and other limitations. 

DEMScot  was  developed  to  allow  the  Scottish  Government  to  see  the  impact  of  different 
policy  interventions  aimed  at  reducing  CO2  emissions  from  housing  (Scottish  Government 
Social  Research,  2010).    The  model  was  created  in  Microsoft  Excel  and  draws  heavily  on 
research  from  Scottish  housing,  CO2  emissions  and  economic  determinants  of  carbon 
emissions.    The  literature  reviewed  to  develop  the  tool  was  extensive;  134  separate 
references,  all  produced  since  1999,  the  majority  being  released  during  the  past  two  years.  
The  manual  for  DEMScot  critiques  the  existing  modelling  tool  used  to  determine  emissions 
and  energy  use  from  UK  dwellings:  BREDEM‐12.    The  DEMScot  team  state  there  are  several 
shortcomings in the BREDEM 12 methodology which is used for SAP that the DEMScot model 
aims  to  address.  These  are:  the  difference  in  Scottish  climate  data,  incorporating  the  latest 
fuel cost data and accurate future energy costs, behavioural aspects such as chosen internal 
temperature etc, accurate estimates of energy use by lighting, cooking and appliances and the 
performance  of  renewable  technologies.    The  following  are  the  shortcomings  stated  by 
DEMScot that are of particular relevance to the study of HTT dwellings. 

The first critique is that the BREDEM method does not provide accurate and realistic estimates 
of energy consumption, and carbon and other environmental emissions from lighting, cooking 
and  appliances.    Despite  minor  modifications,  algorithms  for  hot  water  consumption  date 
from  the  1980’s;  since  then  overall  use  has  been  affected  by  changes  in  equipment  and 
behaviour  i.e.  power‐showers  and  dishwashers  etc.    Although  algorithms  for  lighting  have 
been updated in the 2005 revision of SAP, algorithms for electrical appliances in SAP also date 
from  the  1980’s,  when  the  type  and  use  of  these  appliances  was  much  different  i.e.  low 
ownership of PCs, no internet and plasma TVs (Scottish Government Social Research, 2010).  
This stance is somewhat supported by literature that suggests electricity and lighting use has 
risen  sharply  over  the  last  30  years,  although,  the  same  data  states  that  this  rise  has  been 

24 
partially offset by a fall in energy use from cooking (Shorrock, Utley, 2003).  Recent research 
has shown that SAP 2005 may under estimate overall CO2 emissions for lights and appliances 
by  up  to  15%  (Lowe,  2007).    Additionally,  this  point  was  also  picked  up  in  technical  papers 
supporting SAP 2009, which recommended updating the equations for lights, appliances and 
associated gains, and water heating (Henderson, 2009). 

Secondly, the method does not accurately model badly heated homes by the fuel poor i.e. HTT 
dwellings.  BREDEM uses the two‐zone model with a temperature difference in the main living 
area and the rest of the dwelling.  It also assumes that dwellings are adequately heated and 
that the heating system is adequately sized.  DEMScot states that these assumptions can be 
considerably  inaccurate,  and  can  have  a  significant  impact  on  the  dwellings’  energy 
consumption.    In  respect  of  the  outputs  from  BREDEM;  space  heating  energy  use  in  older 
dwellings  can  be  overestimated  because  old  dwellings  are  often  heated  to  a  lower 
temperature  than  modern  ones;  a  compromise  between  running  costs  and  thermal  comfort 
on the part of the occupants of older dwellings (Scottish Government Social Research, 2010). 

The DEMScot model has three components that were adjusted to model the refurbishments: a 
Building  stock  database,  a  Building  physics  model  and  Factors  under  occupant  control.    The 
building stock database contains the physical parameters considered to have the most impact 
on the performance of dwellings i.e. dwelling age, wall construction, building form, dwelling 
size,  heating  system  and  the  number  of  floors.    The  model  also  allows  for  specific  selection 
and  modelling  of  HTT  dwellings.    Two  solid  wall  dwellings  were  added  to  the  database  for 
Aubert  Park  and  Midmoor  Road  with  all  the  characteristics  and  physical  parameters  of  the 
dwellings.    

The  building  physics  model  contains  extensive  data  and  formulae  to  calculate  energy 
consumption  and  emissions.    The  DEMScot  team  updated  the  methodologies  for  calculating 
lighting,  small  power,  cooking  and  water  consumption  in  respect  of  the  inadequacies 
previously  highlighted  in  the  BREDEM  model.    The  updated  methodology  accounts  more 
realistically for the number of occupants, behaviour and increased use of power over time. 

The  building  physics  model  also  contains  climate  data,  allowing  required  consumption  of 
energy  for  space  heating  and  lighting  to  be  derived  more  accurately.    The  default  mean 
external  temperatures,  annual  heating  degree  days,  monthly  solar  radiation  and  declination 

25 
were based on averages for East Scotland.  In order to model the refurbishment case studies 
accurately the climate data had to be adjusted.  The DEMScot model has the option to select 
mean  external  temperatures  for  the  Thames  area,  so  these  were  selected.    Annual  heating 
degree  days  were  adjusted  to  the  20  year  averages  for  Greater  London  obtained  from  the 
Oxford  Environmental  Change  Institute  (Oxford  Environmental  Change  Institute,  2010).  
Consideration  was  given  to  the  fact  that  mean  annual  temperatures  in  South  East  England 
have increased by 0.78°C based on 1961 – 1990 and 1991 – 2004 averages, and annual heating 
degree  days  have  decreased  by  13.9%  since  1961  (Perry,  2006).    However,  a  year  to  year 
analysis of climate data demonstrated that there can be a significant variance in temperatures 
and degree days.  To avoid the risk  of distorted outputs from the model, data for a 20 year 
average was chosen.   

Monthly solar radiation data for London was obtained from NASA’s Atmosphere Science Data 
Centre  (NASA,  2010).    Monthly  solar  declination  data  for  London  was  obtained  from  the  US 
Department  of  Commerce,  National  Oceanic  &  Atmospheric  Administration:  Earth  System 
Research  Laboratory  (National  Oceanic  &  Atmospheric  Administration,  2010).    In  order  to 
evaluate the accuracy of the data collected for the London climate, the Scottish climate data 
present in the DEMScot model was compared with the outputs for the Scottish climate from 
the above sources.  The data was found to be accurate to one decimal place. 

The Factors under occupant control component involves modifications to ventilation rates, hot 
water and electricity use.  This accounts for lifestyle and habits of the occupiers.  The model 
can also be manipulated to account for changes in behaviour as occupants become more or 
even less conscious of their CO2 emissions.  Occupants are divided into low, medium and high 
users; the split is 30%, 40% and 30% respectively.  This element was adjusted to 100% medium 
users; the assumptions made by the Scottish Government for medium use behaviour remain. 

DEMScot and SAP outputs ‐ Aubert Park 

Detailed  data  for  the  Aubert  Park  dwelling  before  refurbishment  such  as  the  construction 
materials, areas of the building elements, U‐values, plan shape efficiency, ventilation and air 
infiltration rates and the heating system were entered into the DEMScot housing database and 
a simulation was run.  The results of the simulation are shown in table 4. 
SAP  DEMScot  DEMScot 
Energy requirements (kWh pa) 
(BRE & United House)  (1 occupant)  (2 occupants) 

26 
Space heating*    11,912  10,531
Hot Water*    4,310  5,205
Cooking    544  635
Gas consumption SAP items  18,096  16,222  15,736
Gas consumption from all items  16,766  16,371
      
Appliances    1,772  2,152
Cooking    310  362
Lighting*    259  314
Pumps and fans*    196  196
Electric consumption SAP items  596  455  510
Electric consumption all items    2,537  3,024
      
CO2 emissions from SAP items (tonnes pa)  3.80  3.34  3.27
CO2 emissions from all items (tonnes pa)  3.80  4.32  4.45
      
* SAP items         
Table 4: Aubert Park before refurbishment, SAP and DEMScot outputs 

Table  4  demonstrates  a  definite  divergence  between  both  DEMScot  outputs  and  SAP  in  gas 
and  electric  consumption.    The  DEMScot  outputs  are  lower  than  SAP.    Gas  consumption  is 
lower by 10% and 13%, and electric by 14% and 24% depending on the number of occupants.  
SAP  calculations  are  based  on  standard  occupancy  and  climate  data,  and  regulated  use  of 
heating, hot water, lighting and ventilation systems (DECC, 2010b).  As SAP does not account 
for  behavioural  savings,  outputs  can  be  compared  across  the  UK.    Conversely,  DEMScot 
requires  defining  the  number  of  occupants  per  dwelling;  this  dictates  the  amount  of 
consumption  as  demonstrated  by  table  4.    Data  for  Aubert  Park  after  refurbishment  were 
entered  into  the  model  and  a  simulation  was  run.    The  results  of  the  full  refurbishment  are 
shown in table 5. 
SAP  SAP  DEMScot  DEMScot 
Energy requirements (kWh pa) 
(BRE)  (United House)  (1 occupants)  (2 occupants) 
Space heating*      5,248  4,626
Hot Water*      1,789  2,498
Cooking      544  635
Gas consumption SAP items  6,710  7,500  7,037  7,124
Gas consumption from all items      7,581  7,759
          
Appliances      1,772  2,152
Cooking      310  362
Lighting*      65  78
Pumps and fans*      284  284
Electric consumption SAP items  484  484  349  362
Electric consumption all items      2,431  2,876
          
Electric generated by micro CHP*  n/a  900  844  845
          
CO2 emissions from SAP items (tonnes pa)  1.51  1.14  1.03  1.06
CO2 emissions from all items (tonnes pa)      2.01  2.24
27 
           
* SAP items only     
**Deducted from CO2 emissions          
Table 5: Aubert Park after refurbishment, SAP and DEMScot outputs 

Table  5  demonstrates  that  again  there  is  a  definite  divergence  for  gas  and  electric 
consumption  between  both  DEMScot  and  the  United  House  SAP  estimates.    The  DEMScot 
outputs are lower than SAP.  Gas consumption is lower by 6% and 5%, and electric by 28% and 
25%, depending on the number of occupants.  There is also a significant variation in the gas 
consumption and associated CO2 emissions between the two SAP analyses.  This is because of 
the Baxi Ecogen CHP unit.  The Ecogen is a new product that is not commercially available till 
spring 2010; Aubert Park was the first project to use the unit in a dwelling.  Because of the test 
data for the Ecogen not being available at the time of the BRE SAP analysis, BRE based their 
SAP  calculations  on  a  class  A  condensing  boiler  (91%  efficiency)  and  overall  CO2  reductions 
were  calculated  to  be  60%.    BRE  stated  that  Baxi  have  since  provided  indicative  data  that 
suggests  overall  CO2  reductions  could  have  been  70%  with  the  micro  CHP.    United  House 
included  the  micro  CHP  unit  based  on  Baxi’s  indicative  data  and  consequently  their 
calculations produced a 70% reduction in overall CO2.  DEMScot calculates CO2  reductions at 
69% and 68% for one and two occupants respectively.  

DEMScot and SAP outputs ‐ Midmoor Road 

The full details of Midmoor Road were entered into DEMScot and a simulation was run, the 
results are shown in table 6.  
DEMScot  DEMScot  DEMScot 
Energy requirements (kWh pa)  SAP 
(2 occupants)  (3 occupants)  (4 occupants) 
Space heating*  28,573  26,670  24,974  23,876
Hot Water*  3,507  3,851  4,676  5,502
Cooking    631  721  811
Gas consumption SAP items  32,080  30,521  29,650  29,378
Gas consumption from all items  n/a  31,152  30,371  30,189
          
Appliances    2,964  3,755  4,546
Cooking    359  410  462
Lighting*  932  437  554  671
Pumps and fans*  214  214  214  214
Electric consumption SAP items  1,146  651  768  885
Electric consumption all items  n/a  3,974  4,933  5,893
          
CO2 emissions from SAP items (tonnes pa)  6.71  6.20  6.08  6.07
CO2 emissions from all items (tonnes pa)  n/a  7.71  7.97  8.34
          
* SAP items only            
28 
Table 6: Midmoor Road before refurbishment, SAP and DEMScot outputs 

Similarly to Aubert Park, table 6 demonstrates a definite divergence between both DEMScot 
outputs and SAP in gas and electric consumption.  The DEMScot outputs are lower than SAP.  
Gas consumption is lower by 5% to 8% and electric by 43% to 23%, depending on the number 
of occupants.  Data for Midmoor Road after the refurbishment were entered in DEMScot and 
a simulation was run, the results of the full refurbishment are shown in table 7. 
DEMScot  DEMScot  DEMScot 
Energy requirements (kWh pa)  SAP 
(2 occupants)  (3 occupants)  (4 occupants) 
Space heating*  11,501  10,532  9,737  9,000
Hot Water*  2,994  2,480  3,184  3,889
Cooking    631  721  811
Gas consumption SAP items  14,495  13,012  12,921  12,889
Gas consumption from all items  n/a  13,643  13,642  13,700
          
Appliances    2,964  3,755  4,546
Cooking    359  410  462
Lighting*  441  109  138  168
Pumps and fans*  488  488  488  488
Electric consumption SAP items  929  597  626  656
Electric consumption all items  n/a  3,920  4,791  5,664
           
Electric generated by micro CHP*  1739  1561  1550  1546
           
CO2 emissions from SAP items (tonnes pa)  2.22  1.89  1.89  1.90
CO2 emissions from all items (tonnes pa)  n/a  3.41  3.79  4.01
          
* SAP items only       
**Deduction from overall figure           
Table 7: Midmoor Road after refurbishment, SAP and DEMScot outputs 

Again similarly to Aubert Park, table 7 demonstrates that there is a marked divergence of gas 
and electric consumption between both DEMScot and the United House SAP estimates.  The 
DEMScot outputs are lower than SAP.  Gas consumption is lower by 12% to 11%, and electric 
by  36%  to  29%,  depending  on  the  number  of  occupants.    SAP  calculates  the  overall  CO2 
reduction to be 67% and DEMScot calculates the overall reduction to be 70% and 69% for two, 
three and four occupants respectively. 

Evaluation of the model’s outputs  

For both dwellings, the DEMScot outputs are lower than SAP for gas consumption, both before 
and  after  refurbishment.    However  the  lower  outputs  are  markedly  lower  before 
refurbishment.  This supports the DEMScot comments that SAP overestimates heating in badly 
heated  HTT  homes  owing  to  the  effects  of  fuel  poverty,  as  after  refurbishment  the  owners 
29 
would no longer suffer fuel poverty so presumably their heating requirements would not be in 
effect capped.  The primary reason for the overall lower outputs in gas consumption appears 
to  be  because  of  the  climate  data.    DEMScot’s  climate  data  was  changed  from  the  default 
settings of East Scotland to Greater London in order to model Aubert Park and Midmoor Road 
accurately.  SAP’s climate data is based on mean external temperatures for all of the UK.  The 
mean external temperature in Greater London is lower than East Scotland (Met Office, 2010) 
(Scharmer,  Greif,  2000),  therefore  the  internal  heating  demand  would  be  decreased 
(Mavrogianni, 2009). 

In order to test this, a sensitivity analysis was carried out by modelling both case studies with 
climate data for East Scotland; this is the default climate setting for the model.  The result was 
that  the  overall  percentage  of  CO2  reduction  was  the  same  as  when  the  climate  data  for 
London  was  used.    However,  the  space  heating  requirements  increased  so  that  the  gas 
consumption  was  higher  than  in  the  SAP  estimates.    This  suggests  that  the  reason  for  the 
overall  lower  outputs  is  primarily  because  of  the  climate  data  being  changed  to  Greater 
London.   

One  significant  difference  in  the  modelling  results  concerns  lighting.    DEMScot’s  estimate  of 
electricity use after low energy lighting has been installed, is significantly lower than that of 
SAP.  The greater reduction produced by the DEMScot model is supported by data from the 
Energy Saving Trust, which states that low energy lighting can save up to 80% of the electricity 
used  by  standard  lighting  (EST,  2010a).    However,  the  difference  in  electric  use  has  a 
substantial  impact  on  the  average  CO2  reduction;  if  the  DEMScot  lighting  consumption 
calculation  was  substituted,  the  overall  CO2  reductions  in  SAP  for  the  Midmoor  Road 
simulation  would  increase  from  67%  to  70%.  With  the  exception  of  lighting,  the  DEMScot 
outputs are very close to SAP’s.   

Overall,  the  SAP  and  DEMScot  simulations  calculated  a  CO2  reduction  of  68%  to  70%  for 
Aubert Park, and 67% to 70% for Midmoor Road.  Although this differs from SAP slightly, the 
DEMScot  model  was  designed  to  account  for  inadequacies  in  the  SAP  methodology,  so  by 
virtue of its purpose the outputs would differ to some extent.  The major contributor to these 
savings  is  the  Baxi  Ecogen  micro  CHP.    Its  influence  is  demonstrated  in  the  Aubert  Park 
simulation where the incorporation of the Ecogen resulted in an additional 10% CO2 reduction. 

30 
The Ecogen unit 

Such  a  reduction  in  CO2  is  significant  and  therefore  must  be  examined  and  verified.    The 
Carbon Trust is currently conducting one of the most comprehensive field trial assessments of 
micro CHP systems, with interim results released in 2007.  The Ecogen unit was not included in 
the  trial;  however  the  report  contained  two  important  factors  relating to  the  overall  carbon 
performance  of  micro  CHPs  when  compared  with  condensing  boiler  systems.    Firstly,  as  the 
heat the demand increases, the likelihood of CO2 savings increases because more electricity is 
generated.  At low heat demands of less than 6000 kWh pa micro CHPs and condensing boilers 
are  generally  indistinguishable.    However,  with  heat  demands  of  more  than  12,000  kWh  pa 
there  is  a  statistical  likelihood  that  micro  CHP  systems  will  outperform  condensing  boilers.  
Consequently micro CHP units are most appropriate and beneficial for houses with higher heat 
demands  of  over  20,000  kWh,  such  as  larger  houses  with  3  bedrooms  or  more  and  older 
houses i.e. solid wall houses.  In this capacity typical savings are expected to range from 5% to 
10%  (Carbon  Trust,  2007).    The  BRE  referred  to  the  results  of  the  Carbon  Trust’s  trial  and 
implied that the Ecogen unit may not be fully utilised in a dwelling of lower heat demand like 
Aubert Park.  The second factor is that current micro CHP units typically need to operate for a 
minimum  cycle  of  over  one  hour  to  provide  an  overall  CO2  saving  benefit  relative  to  a 
condensing  boiler  (Carbon  Trust,  2007).    If  appropriate  use  was  adopted  benefits  could  be 
realised.  

In  Aubert  Park’s  case,  the  heating  demand  had  been  significantly  reduced  by  improvement 
measures  to  the  building  envelope,  resulting  in  space  heating  and  water  demand  reducing 
dramatically to approximately 6000 kWh pa.  In spite of this, the Ecogen is a new product that 
claims  unprecedented  efficiency,  and  production  of  1  kWh  of  electricity  during  a  period  of 
heat  demand  (Baxi,  2010b).    Allowing  for  this  exceptional  efficiency  and  the  new  heating 
controls that were installed in the dwelling, it is conceivable that the Ecogen could be capable 
of  producing  an  increased  saving  relative  to  a  condensing  boiler.    United  House  used  an 
efficiency figure of 82% in their calculations.  Baxi now state an efficiency of 92% (Baxi, 2010a).  
To  provide  a  basis  for  comparison  and  to  avoid  a  potentially  optimistic  efficiency  figure,  an 
efficiency of 82% was used in the DEMScot model.      

The  Ecogen’s  influence  is  increased  further  because  of  the  carbon  bonus  for  electricity 
generated  and  returned  back  to  the  grid.    The  carbon  intensity  for  gas  and  electric  used  in 

31 
dwellings  is  0.194  kg  CO2/kWh  and  0.422  kg  CO2/kWh  respectively.    The  current  SAP 
methodology  allows  micro‐generated  electricity  to  displace  grid  emissions  at  0.568  kg 
CO2/kWh, while grid electricity consumption has a carbon intensity of 0.422 kg CO2/kWh (Cole, 
2008).  The 0.422 kg CO2/kWh figure is based on the Government’s long‐term projections for 
the average mix of grid electricity from 2005 to 2010.  The 0.568 kg CO2/kWh figure is based 
on  the  1998–1999  marginal  mix  of  generating  plant  plus  a  factor  to  account  for  new  build 
from 2005 to 2010, assuming that it would be combined cycle gas turbines (Bergman, et al., 
2010).    Because  of  this,  the  figure  is  contentious  and  has  been  challenged  (Bergman,  et  al., 
2010).  It is likely that the 0.568 kg CO2/kWh will revised in later editions of SAP (Bergman, et 
al., 2010)  

This is a potential weakness in the study.  Because of the carbon bonus for electricity returned 
to  the  grid,  refurbishments  can  claim  high  savings.    If  the  long  term  average  grid‐mix 
assumption of 0.43 kg CO2/kWh is used instead, the relative CO2 benefits of CHP would reduce 
accordingly  (Carbon  Trust,  2007).    The  DEMScot  model  avoids  the  possibility  of  inflated 
reductions as the carbon intensity of CHP  generated and returned electricity is the same as 
the  grid;  0.422  kg  CO2/kWh,  consequently  the  actual  carbon  savings  generated  by  the 
DEMScot  model  for  Aubert  Park  are  1.16  and  1.18  tonnes  of  CO2  pa  for  1  and  2  occupants 
respectively.    However,  in  order  for  a  direct  comparison  to  the  SAP  data,  the  0.568  kg 
CO2/kWh figure has been used in the DEMScot outputs shown in tables 5 and 7.   

It  has  been  confirmed  that  with  the  correct  types  of  materials  and  heating  systems  utilised, 
savings of up to 70% can be made from two types of solid wall dwellings.  The next chapter 
will  consider  the  costs  that  are  incurred  in  order  to  achieve  savings  of  this  magnitude.  
Moreover,  given  that  up  to  a  70%  reduction  in  CO2  can  be  made  by  employing  all  of  the 
measures in these dwellings, the next chapter will seek to examine at what reductions can be 
made by employing fewer measures and at what point does the financial investment of these 
measures begin to yield lower returns in terms of carbon.  
 

32 
Chapter five: cost, Value Carbon and other limitations 

The previous chapter has established what reductions are practically feasible for two types of 
solid  wall  dwellings.    The  objective  of  this  chapter  is  to  examine  the  additional  barriers  that 
were highlighted in chapter 1: introduction.  It will consider the barrier of cost and investigate 
the  optimal  point  of  refurbishment.    Furthermore,  it  will  also  consider  some  of  the  wider 
issues  that  affect  the  feasibility  of  solid  wall  housing  in  contributing  to  80%  reductions.    All 
these issues must be examined in order to determine the true potential of solid wall housing.   

Total cost and value 

Aubert Park and Midmoor Road achieved CO2 savings in the order of 68% to 70% and 69% to 
70%  for  a  total  capital  cost  of  £21,190  and  £18,210  respectively  at  2009  prices.    It  must  be 
noted  that  Aubert  Park  does  not  necessarily  represent  the  average  converted  flat.    The 
average converted flat in England produces 5.8 tonnes of CO2 pa, has a floor area is 66m2, and 
an average SAP rating of 44 (DCLG, 2009).  Aubert Park produced less CO2 emissions and had a 
smaller floor area; although it had a higher SAP rating before refurbishment, making it harder 
to achieve higher savings than other dwellings with low SAP ratings (DCLG, 2009).  Additionally 
the average medium to large terrace produces 5.8 tonnes of CO2 pa, has a floor area of 94m2, 
and an average SAP rating of 50.4 (DCLG, 2009).   Midmoor Road had higher CO2 emissions, a 
larger  floor  area,  and  a  lower  SAP  rating  before  refurbishment  making  it  easier  to  achieve 
higher savings than other dwellings with higher SAP ratings (DCLG, 2009) 

It  would  be  improvident  to  adopt  an  all‐encompassing  approach  and  presume  all  of  these 
dwellings could achieve the same level of CO2 reductions for the same cost.  However, a rough 
order  of  magnitude  case  will  be  presented.    Of  the  6.599  million  solid  wall  dwellings  in 
England, approximately 490,000 are converted flats and 1.094 million are mid‐terraces (DCLG, 
2009).    If  all  490,000  flats  and  1.094  million  mid‐terraces  were  refurbished  to  the  same 
specification as Aubert Park and  Midmoor Road, the cost would be £10.4 and  £19.91 billion 
respectively, which is clearly a substantial sum of money.  There are currently a small number 
of major sources of funding and loans available to homeowners and occupiers.  The two most 
significant are the Carbon Emissions Reduction Target scheme, which has available funding of 
£1.5 billion (Jenkins, 2010), and the interest free UK Energy Efficiency Home Loan which has a 
total of £700 million allocated per annum.   

33 
The  cost  of  refurbishing  existing  dwellings  is  seen  to  be  one  of  the  key  barriers  to  home 
owners  implementing  refurbishments  (Pett,  2004).    In  light  of  this  it  seems  essential  to 
investigate the relationship between expenditure and CO2 savings in order to maximise value.  
This  concept  was  integrated  into  the  design  phase  of  the  Aubert  Park  refurbishment,  and  is 
very  similar  to  the  process  of  Value  Engineering;  the  name  given  to  this  approach  is  Value 
Carbon.  Value Carbon is a unit that illustrates the cost for every kg of CO2 saved, the lower the 
lower the figure, the more cost‐effective the refurbishment measure is. 

Value Carbon ‐ Aubert Park  

The Aubert Park refurbishment measures were simulated individually in DEMScot in order to 
determine their separate carbon savings so that a Value Carbon figure could be established.  
The results are presented in table 8. 
Installed cost  Carbon saved  Value Carbon 
Measures 
(kg CO2)  (£/kg) 
1) Low energy lighting  £40  70  0.57 
2) Draught proofing  £650  104  6.23 
3) Micro CHP gas boiler  £4,800  1685  2.85 
4) Insulate external walls  £6,100  513  11.90 
5) Double glazing (vacuum)  £600  21  28.90 
6) Insulate floors  £3,700  118  31.32 
7) MVHR  £6,300  80  78.80 
8) Rainwater harvesting  £1,000  0  n/a 
9) Insulate thermal bridges  £2,000  0  n/a 
Table 8: Aubert Park refurbishment measures, Value Carbon 

As table 8 shows, there is a large variance in the cost and effectiveness with a 79:1 difference 
between the most and least effective measures.  Following this, measures were grouped into 
incremental improvements based on their Value Carbon figure and the ease with which they 
could  be  applied  to  a  dwelling.    Increment  1  consists  of  measures  1)  and  2),  increment  2 
consists of measures 1) to 3), increment 3 consists of measures 1) to 5), increment 4 consists 
of  measures  1)  to  6),  and  increment  5  consists  of  all  measures  that  had  an  effect  on  CO2 
reduction.    The  increments  were  modelled  as  one  package;  the  reduction  in  consumption  is 
shown in table 9.   
Increment  Increment  Increment  Increment  Increment 
Saving (kWh pa) 
1  2  3  4  5 
Space heating  385  1,947  4,803  5,422  5,905
Hot Water  0  2,707  2,707  2,707  2,707
Cooking  0  0  0  0  0
            
34 
Appliances  0  0  0  0  0
Cooking  0  0  0  0  0
Lighting  236  236  236  236  236
Pumps and fans  0  ‐20  ‐20  ‐20  ‐88
            
Electric generated by micro CHP  0  1,318  987  902  845
Gas consumption  385  4,654  7,510  8,129  8,612
Electric consumption  236  216  216  216  148
            
Reduction in CO2 (tonnes pa)  0.17  1.74  2.11  2.18  2.21
Total % saving  5%  53%  65%  67%  68%
Cost (£)   £690   £5,490   £12,190   £15,890    £22,190 
Overall CO2 emissions (tonnes pa)  3.09  1.53  1.16  1.09  1.05
Table 9: Aubert Park incremental improvements 

Table  9  shows  that  for  relatively  low  cost,  substantial  reductions  in  CO2  emissions  can  be 
made,  a  total  of  1.74  tonnes  of  CO2  (53%)  for  £5,490.    It  also  shows  that  there  are  two 
significant  jumps  in  the  CO2  reductions;  increment  1  to  2  because  of  the  micro  CHP  and 
increment 2 to 3 because of the solid wall insulation.  After these measures have been applied 
there is severely diminished carbon saving potential.  This is better illustrated by figure 2. 

Value Carbon Analysis ‐ Aubert Park
£24,000

£22,000 Increment 5

£20,000

£18,000

£16,000 Increment 4

£14,000
Cost (£)

£12,000 Increment 3

SAP CO2
£10,000
Grid CO2

£8,000

£6,000
Increment 2 

£4,000

£2,000
Increment 1
£‐
0% 10% 20% 30% 40% 50% 60% 70% 80%

Reduction in CO2 (%)
 
Figure 2: Aubert Park Value Carbon Analysis graph 

35 
Figure 2 demonstrates the payback in terms of CO2 reductions for each £ spent.  The curve is 
similar  to  an  exponential  growth  curve;  after  increment  2  the  curve  becomes  dramatically 
steeper, following increment 3 the carbon saved is minimal and the cost is high.  The SAP CO2 
curve  is  based  on  the  carbon  intensity  of  electricity  returned  to  the  grid  based  on  the  SAP 
methodology  of  0.568  kg  CO2/kWh.    The  Grid  CO2  is  based  on  the  carbon  intensity  of 
electricity returned to the grid based on the long term average grid‐mix assumption of 0.43 kg 
CO2/kWh.   This has been added in respect of the criticism it has received and the likelihood 
that it will be revised in future versions of SAP (Bergman, et al., 2010). 

Value Carbon ‐ Midmoor Road 

The Midmoor Road refurbishment measures were simulated individually in DEMScot in order 
to determine their separate carbon savings so that a Value Carbon figure could be established.  
The results are presented in table 10. 
Installed cost  Carbon saved  Value Carbon 
 Measures 
(kg CO2)  (£/kg) 
1) Low energy lighting  80  118  0.68 
2) Draught proofing  310  234  1.32 
3) Loft insulation  1,050  140  7.50 
4) Micro CHP  6,000  2,231  2.69 
5) Insulate external walls  4,300  1,805  2.38 
6) Insulate timber floor  2,050  163  12.56 
7) Insulate concrete floor  2,100  86  24.49 
8) MVHR  2,400  ‐49  ‐48.51 
Table 10: Midmoor Road refurbishment measures, Value Carbon 

Table  10  shows  a  less  dramatic  variance  in  the  cost  and  effectiveness  in  comparison  with 
Aubert  Park,  with  a  25:1  difference  between  the  most  and  least  effective  measures.  
Additionally  it  shows  that  the  MVHR  was  detrimental  to  the  carbon  reductions.    The  MVHR 
saved  energy  by  reducing  space  heating  demand  as  a  portion  of  the  dwellings  heat  was 
recovered.  However, the electricity used in operating the ventilation system’s fans offset this 
saving.    Energy  savings  are  only  realised  in  airtight  properties  (<5m3/hr/m2  at  50Pa)  where 
almost all ventilation air passes through the heat exchanger (EST, 2006a).  This dwelling had 
only achieved an air tightness of 7.5m3/hr/m2 at 50Pa because the chimneys were vented. 

Following  the  calculation  of  table  10,  measures  were  again  grouped  into  incremental 
improvements  based  on  their  Value  Carbon  figure  and  the  ease  with  which  they  could  be 
applied  to  a  dwelling.    Increment  1  consists  of  measures  1)  and  2),  increment  2  consists  of 
36 
measures 1) to 4), increment 3 consists if measures 1) to 5), increment 4 consists of measures 
1) to 7), and increment 5 is the full upgrade and consists of all measures.  The increments were 
modelled as one package and the reduction in consumption is shown in table 11. 
Increment  Increment  Increment  Increment  Increment 
Saving (kWh) 
1  2  3  4  5 
Space heating  1,348  5,357  13,880  15,200  15,225
Hot Water  0  1,492  1,494  1,494  1,494
Cooking  0  0  0  0  0
             
Appliances  0  0  0  0  0
Cooking  0  0  0  0  0
Lighting  416  416  416  416  416
Pumps and fans  0  ‐75  ‐75  ‐75  ‐199
            
Electric generated by micro CHP    2,734  1,712  1,542  1,550
Gas consumption saving  1,348  6,849  15,374  16,694  16,719
Electric consumption saving  416  341  341  341  217
         
Reduction in CO2 (tonnes pa)  0.44  3.03  4.10  4.26  4.22
Total % saving  7%  50%  67%  70%  69%
Cost (£)   £390   £7,440   £11,740   £15,890  £18,210
Overall CO2 emissions (tonnes pa)  5.64  3.05  1.98  1.82  1.86
Table 11: Midmoor Road incremental improvements 

Table  11,  like  table  9,  shows  that  for  a  relatively  low  cost,  substantial  reductions  in  CO2 
emissions  can  be  made,  a  total  of  3.03  tonnes  of  CO2  (50%)  for  £7,440.    It  also  shows  that 
there are two significant jumps in the CO2  reductions; increment 1 to 2 because of the micro 
CHP  and  increment  2  to  3  because  of  the  solid  wall  insulation.    After  increment  3  has  been 
applied  there  is  a  severely  diminished  carbon  saving  potential  and  the  cost  is  high.    This  is 
better illustrated by figure 3. 

37 
Value Carbon Analysis ‐ Midmoor Road
£20,000

£18,000 Increment 5

£16,000 Increment 4

£14,000

£12,000 Increment 3
Cost (£)

£10,000 SAP CO2
Grid CO2
£8,000
Increment 2

£6,000

£4,000

£2,000

Increment 1
£‐
0% 10% 20% 30% 40% 50% 60% 70% 80%

Reduction in CO2 (%)
 
Figure 3: Midmoor Road Value Carbon Analysis graph 

Figure  3  demonstrates  the  payback  in  terms  of  CO2  reductions  for  each  £  spent.    Between 
increments  1  and  3,  the  curve  is  almost  linear,  following  increment  3  the  gradient  changes 
radically and there is very little carbon saving for a relatively high cost.  The difference in the 
gradient between increments 1 and 3 in the two dwellings is primarily because of cost.  Aubert 
Park  and  Midmoor  Road  achieved  53%  and  50%  CO2  reductions  by  increment  2,  and 
reductions  of  65%  and  67%  by  increment  3  respectively.    However,  by  increment  2,  Aubert 
Park  and  Midmoor  Road  had  cost  £5,490  and  £7,440,  and  by  increment  3  they  had  cost 
£12,190 and £11,740 respectively.  This difference in cost is because Midmoor Road included 
£1,050  of  loft  insulation  in  increment  2,  and  the  installation  of  the  micro  CHP  cost  £1,200 
more  because  of  additional  plumbing  work.    Contrast  this  with  Aubert  Park,  where  in 
increment 3 the solid wall insulation had cost £1,400 more and glazing had been included at a 
cost of £600.   

38 
Optimum refurbishment  

The  data  illustrates  that  for  different  dwellings  with  somewhat  different  refurbishment 
measure  requirements,  the  gradient  of  the  Value  Carbon  curve  can  vary.    However,  in  both 
cases there was a critical tipping point whereby additional measures were costly and provided 
little carbon saving in return.  This invites the question of what might be the optimum level of 
refurbishment.  This issue has been given little consideration in previous reports and studies, 
perhaps because most HTT refurbishments have only achieved reasonable but not exceptional 
reductions (Energy Efficiency Partnerships for Homes, 2004).  One report has considered this 
concept and specifies costs in the region of £6,500 per dwelling (WWF, 2008).  However, close 
inspection  reveals  that  the  study  relies  on  radical  decarbonisation  of  the  national  grid  to  a 
carbon  intensity  less  than  half  of  the  current  carbon  intensity  (Ecotricity,  2010);  this  is  not 
included  in  the  costs.    Numerous  sources  agree  that  decarbonisation  of  the  nation  grid  is 
essential  to  achieve  the  required  CO2  reductions  (EST,  2006c)  (Lowe,  2007),  but  it  is  not 
guaranteed  to  happen  (EST,  2008).    Consequently,  the  refurbishment  measures  specified  in 
this  report  would  only  achieve  a  31%  reduction  in  CO2  emissions  if  the  nation  grid  was  not 
decarbonised (WWF, 2008). 

With  the  introduction  of  micro  CHPs  and  innovative  insulation,  there  is  the  opportunity  to 
achieve  significant  reductions  in  solid  wall  dwellings  beyond  what  has  been  achieved  in 
previous  refurbishments.    However,  pursuing  maximum  reductions  without  considering  the 
obvious diminishing returns demonstrated by the previous data would not necessarily provide 
the best option in terms of cost and CO2. 

Given  that  the  cost  of  refurbishment  measures  is  regarded  as  a  substantial  barrier,  the 
opportunity  cost  of  the  finance  required  to  refurbish  dwellings  must  be  given  adequate 
attention.    For  example,  Aubert  Park  can  achieve  a  53%  (1.74  tonnes)  CO2  reduction  for 
£5,490, 65% (2.11 tonnes) for £12,190 and 68% (2.21 tonnes) for £22,190.  Consequently, it 
would be more cost and carbon effective to refurbish 70a, 70b and 70c Aubert Park to each 
achieve a reduction of 53%, therefore resulting in total reduction of 5.22 tonnes for £16,470, 
as opposed to refurbishing 70a alone to achieve a reduction of 68%, therefore resulting in a 
total reduction of 2.21 tonnes for £22,190.  The same principle also applies to Midmoor Road. 

This trade‐off analysis would be required for each individual case, as the diversity of the UK 
stock  means  that  there  is  no  standard  refurbishment  package  for  a  dwelling.    The  same 
39 
measures  could  be  applied  to  different  dwellings  and  achieve  different  CO2  reductions  for 
different costs (Jenkins, 2010).  However, the diminishing returns are evident in both the case 
studies and almost certainly would apply to other dwellings.   

The willingness‐to‐pay and reducing costs 

Achieving high levels of reductions will rely on implementing measures that are not necessarily 
deemed to be cost‐effective, in that they are unlikely to present an economic payback that is 
attractive  to  the  consumer  (Peacock,  et  al.,  2009)  (Pett,  2004).    A  willingness‐to‐pay  survey 
conducted  in  2008  found  two  key  findings  in  relation  to  this.    Firstly,  78%  of  home  owners 
thought it was the responsibility of the Government or Local Authorities to pay for at least half 
of  the  cost  of  refurbishment  measures,  only  17%  felt  that  the  home  owner  should  be 
responsible for paying for most of it (Peacock, et al., 2009).  Secondly, the principal motivating 
factor for reducing their energy consumption was reducing their energy bills (Peacock, et al., 
2009).  Not surprisingly, the occupants’ willingness to pay for measures themselves increased 
with the total household income, the time that they were intending to stay in that property, 
and the perceived asset value of their properties as a result of the measures.  These results 
suggest  that  the  majority  of  respondents  feel  that  climate  change  is  a  problem  has  been 
caused by the wider society rather than the individual, and consequently should be paid for by 
a societal agent.  Delivering substantial CO2 reductions in the housing sector is fundamental to 
climate  change  policy,  and  therefore  motivating  homeowners  to  adopt  responsibility  for 
implementing energy saving measures is essential. 

One way to address this problem would be make refurbishment measures more economic.  To 
do this the market would have to be improved (Jenkins, 2010).  However, the current reliance 
on  market  related  solutions  to  achieve  infiltration  of  newer  technologies  and  refurbishment 
measures into dwellings is limited, as there is a clear lack of working exemplars available.  A 
lack of information relating to performance and reliability of these measures makes it difficult 
to encourage a mass market (Jenkins, 2010).  One approach would be to focus on the willing‐
to‐pay sector; households with significant disposable income and ambitions to improve energy 
efficiency  and  therefore  reduce  their  CO2  emissions  (Geroski,  2000).    This  has  been 
demonstrated  with  the  capital  cost  of  IT  equipment  (Jenkins,  2010).    The  reduction  in  the 
capital cost of a measure as the number of units produced increases, could result in cheaper 

40 
measures for the mass market, and therefore encourage higher uptake rates of that measure 
(Peacock, et al., 2009).     

Another approach would be to focus on fuel poor social housing, as this could provide a large 
number  of  exemplar  refurbishments  as  well  as  reducing  fuel  poverty  (Jenkins,  2010).    This 
would  in  turn  stimulate  the  private  buyer  and  the  manufacturers,  therefore  improving 
confidence and reducing capital costs (Jenkins, 2010).  This approach would require significant 
subsidies to be made available to social housing associations.  However, substantial reductions 
in  the  cost  of  carrying  out  the  work  could  be  made  because  of  the  economies  of  scale 
associated  with  bulk  buying  and  large  scale  projects  (Plimmer,  2008).    This  would  provide 
better  value  for  the  government.    Some  of  the  wider  benefits  of  this  would  be  boosts  in 
employment and Gross Domestic Product (WWF, 2008). 

Solid wall insulation 

The  data  presented  in  chapter  three:  DEMScot:  Scotland’s  domestic  energy  model  and 
numerous other research reports demonstrate that solid wall insulation has a vital role to play 
in reducing CO2 emissions.  However, the current rate of installation is low (BRE, 2008b).  The 
reasons for this are the reduction in the usable floor area of dwellings (in the case of internal 
insulation),  change  of  external  appearance  of  dwellings  (in  the  case  of  external  insulation), 
high costs and disruption to the occupants (BRE, 2008b).  These barriers must be overcome in 
order to increase the uptake of this measure. 

There are a variety of different solid wall types and associated finishes.  The predominant wall 
finish is masonry pointing (55%); the other significant proportion is a rendered finish (33%).  A 
further  10%  has  a  mixture  of  both,  and  the  remaining  2%  has  a  non  masonry  natural  finish 
(BRE,  2008b).    Following  this,  solid  wall  insulation  can  be  specified  according  to  the  type  of 
finish and in the presence of other obstacles.  

In theory external or internal wall insulation could be applied to almost any dwelling except in 
the  instance  of  listed  buildings.    External  insulation  is  applied  in  either  a  wet  render  or  a 
cladding system. It offers the advantage of little disruption to the occupants, reduces the risk 
of  thermal  bridging,  can  improve  the  look  of  an  ageing  and  weathered  facade,  and  can  be 
specified  in  order  to  solve  rain  penetration  and  frost  damage  (Sustainable  Energy  Ireland, 
2005).    A  minor  barrier  is  that  external  wall  insulation  may  require  planning  consent  as  it 

41 
changes the appearance of a dwelling (Impetus Consulting, 2004), although this is unlikely to 
apply to dwellings that are already rendered (BRE, 2008b).  Another barrier may be in the case 
of converted or purpose built flats, where all the occupiers would have to agree to change the 
external  appearance  (BRE,  2008b).    The  primary  barrier  is  that  occupants  may  be  averse  to 
changes in the external appearance of their homes (BRE, 2008b).  In order to overcome this, 
external wall insulation should be targeted at the 45% of dwellings that have render and non 
masonry  natural  finishes.    It  can  be  incorporated  when  work  to  the  exterior  is  desired  or 
necessary, thus eliminating the barrier as the work will be carried out anyway.  Any additional 
costs could be covered by government or local authority grants.   

Internal insulation is applied as a rigid insulation board or insulation fitted between studwork.  
One  of  the  barriers  to  internal  insulation  is  the  loss  of  usable  floor  area,  which  has  more 
significance in dwellings under 60m2 (BRE, 2008b).  However, this was an issue in the Aubert 
Park refurbishment and was mostly overcome by utilising new materials that are much thinner 
than  the  standard  application  of  80mm  to  120mm  of  insulation.    These  high  performance 
materials  could  be  subsidised  by  grants  in  order  to  make  them  more  competitive  in 
comparison with the standard application.  The major barrier to this measure is the amount of 
disruption  to  the  occupants.    Realistically  this  could  only  be  applied  when  a  major 
refurbishment  takes  place,  or  on  a  room  by  room  basis  when  redecoration  takes  place 
(Impetus  Consulting,  2004).    Internal  wall  insulation  can  also  be  applied  on  a  DIY  basis;  this 
improves  its  appeal  to  home  owners  (Sustainable  Energy  Ireland,  2005).    Internal  wall 
insulation lends itself to dwellings with masonry pointing where the occupants are averse to 
changes in the external appearance of their dwelling and in the case of flats where not all the 
occupants are in agreement of external wall insulation (BRE, 2008b).   It should therefore be 
targeted for the other 55% of dwellings where the occupants would resist any change to the 
external appearance of their homes. 

This is somewhat of a simplified arrangement, and clearly the applicability of one method of 
wall insulation does not preclude another.  If the occupant is averse to internal disruption, but 
will forego the undesired change in external appearance, then external wall insulation could 
be specified.  The method of selection could be approached in the manner of a flow chart that 
represents  an  algorithm.    Under  the  assumption  that  either  external  or  internal  insulation 
could be applied in respect of the previous solutions, 6.3 million dwellings could be insulated 
(BRE,  2008b),  excepting  the  300,000  residential  buildings  listed  as  architecturally  important 
42 
(Boardman,  et  al.,  2005).    Realistically,  solid  wall  insulation  would  be  best  if  it  was 
incorporated into other works in order to marginalise the problems stated previously; this is 
discussed subsequently. 

Occupant disruption and occurring opportunities 

Midmoor Road incorporated the energy efficiency measures into a major refurbishment of the 
whole property.  This is a common feature in demonstration refurbishment projects as both 
costs and disruption are kept to a minimum (Killip, 2008).  In 2005 £23.9 billion was spent on 
repair,  maintenance  and  improvement  (Department  for  Business  Enterprise  and  Regulatory 
Reform,  2007).    Work  which  does  not  incorporate  energy  efficiency  measures  represents  a 
major missed opportunity, as it is unlikely that further substantial refurbishment work will not 
be carried out for sometime afterwards (EST, 2006c). 

These naturally occurring opportunities to incorporate energy efficiency measures need to be 
taken advantage of; they have been named trigger points (EST, 2008).  Trigger points with the 
potential  to  deliver  CO2  savings  are;  moving  home,  building  an  extension,  new  kitchen  or 
bathroom,  loft  conversion,  new  windows,  new  heating  system  and  new  flooring.    These 
scenarios  offer  the  following  advantages;  the  home  owner  is  already  considering  work  so  is 
receptive,  workpeople  may  already  be  on  site  so  the  disruption  is  minimal,  the  cost  of 
improvement will be less and there is scope to incorporate improvements that would not be 
included  after  the  work  is  complete  (EST,  2008).    In  order  to  promote  the  uptake  of  these 
measures  it  is  essential  that  these  trigger  points  are  maximised,  this  can  be  done  by  three 
methods.  Firstly, start a programme of public engagement to encourage the public to support 
technologies and policy.  Secondly, modify the Building Regulations to extend the coverage of 
triggers  for  improving  the  energy  performance  of  homes  in  the  case  of  extensions  and  loft 
conversions.    Finally,  increase  incentives  and  awareness  raising  activity that  targets  people’s 
behaviour (EST, 2008).  

Items other than those included in the Standard Assessment Procedure  

The data presented in chapter 3: DEMScot: Scotland’s domestic energy model confirmed that 
reductions of up to 70% are possible from solid wall housing.  However, these reductions are 
based on SAP items only; therefore emissions from cooking and appliances are not included.  
The past four decades have seen an unprecedented increase in the use of electrical appliances 
43 
and  time  saving  devices  (EST,  2006d).    Although  the  energy  efficiency of  these  products  has 
greatly  increased,  this  saving  has  been  outstripped  by  a  massive  increase  in  demand.    On 
average,  appliances  and  cooking  account  for  21%  of  total  emissions  (DCLG,  2007).    If  items 
other  than  SAP  items  were  included  in  the  Aubert  Park  and  Midmoor  Road  refurbishments, 
the CO2  reductions would be reduced to 50% and 52% respectively if a full refurbishment was 
implemented.    Although  energy  use  for  cooking  has  been  declining  (Shorrock,  Utley,  2003), 
the  increase  in  appliances  is  viewed  as  a  serious  threat  to  achieving  the  Government’s  CO2 
reduction targets (EST, 2006d).  However, appliances have a high turnover and it is likely that 
they  will  be  replaced  3  to  4  times  by  2050  (Boardman,  et  al.,  2005).    This  presents  an 
opportunity for savings as appliances are traded goods and savings can be implemented by EU 
and UK policy initiatives.  Products with improved electrical efficiency need to be brought into 
the market; however, this relies on strong policy from the EU and UK (Boardman, et al., 2005).  
This  could  be  executed  by  the  UK  Government  pressing  for  25%  of  the  most  electrically 
inefficient products to be removed from the market every 3 to 5 years, luxury products with 
disproportionately high energy use, i.e. patio heaters, should be subject to increased tax (EST, 
2006d).  Furthermore, the Building Regulations could be revised so that property developers 
must install the most efficient appliances available (Boardman, 2007).  

Evaluation of key barriers  

It  is  clear  that  cost  is  a  significant  barrier  to  the  implementation  of  energy  efficient 
refurbishment measures.  This chapter has presented the most viable solutions to overcoming 
this  barrier  and  encouraging  the  uptake  of  measures.    However,  even  accounting  for 
reductions  in  overall  costs  resulting  from  market  forces,  refurbishment  measures  will  still 
come at a fee, either to the home owner or the Government that has to subsidise the cost.  
The attitudes presented in the willing‐to‐pay survey pose a severe threat to achieving the 80% 
target.  It is obviously in the Governments’ best interest to transfer as much of the costs to the 
willing‐to‐pay sector.  What the Government can or cannot afford is beyond the remit of this 
dissertation.  However, the cost of  refurbishing all solid wall housing is a substantial burden 
for the Government to bear.  Consequently, the major UK political parties have only pledged 
funding  for  the  cost‐effective  measures  stated  in  chapter  two:  the  UK  housing  stock  (BBC, 
2010). 

44 
Barriers above the technical feasibility and cost of refurbishment will also affect the potential 
of  solid  wall  housing  to  reduced  CO2  emissions.    The  additional  three  other  major  barriers 
other than cost (solid wall insulation, occupant disruption and opportunities and items other 
than SAP), have been addressed and an appropriate solution suggested.  However, for all the 
barriers there was no easy or quick fix solution because they all require reinforcement from 
government  regulation  and  policy  if  they  are  to  be  surmounted.    Having  analysed  the 
remaining  barriers  to  refurbishment,  the  study  will  move  onto  the  following  chapter  where 
conclusions and recommendations will be presented.   

 
 

   

 
 
 
 
 
 
 
 
 
 
45 
Chapter seven: conclusion and recommendations 

Conclusion 

The aim of this dissertation was to evaluate the proposed solution of refurbishing the building 
envelope and heating system, in order to determine what is required to achieve 80% emission 
reductions  so  to  answer  the  question;  what  role  can  solid  wall  housing  feasibly  play  in 
reducing CO2 emissions by 80%? 

The  first  objective  was  to  assess  the  improvement  measures  that  were  applied  to  the  two 
chosen  dwellings  individually  in  order  to  ascertain  the  applicability  of  the  refurbishment 
package to other dwellings of that type.  The outcome was that with the exception of MVHR, 
concrete  floor  insulation  and  the  solid  wall  insulation  in  some  circumstances,  the 
refurbishment measures represent a package that could be applied to other dwellings without 
major disruption and therefore could produce comparable results. 

The  second  objective  was  to  confirm  that  the  case  studies  were  capable  of  achieving  the 
reduction  in  emissions  that  were  advocated.    This  was  carried  out  by  using  the  DEMScot 
model which utilised the assumptions and methodology made by the DEMScot team relating 
to  occupants  behaviour  and  the  use  of  lights,  cooking  and  hot  water.    There  were  minor 
differences in the results for Aubert Park and Midmoor Road, as they achieved a 2% lower and 
a 2% to 3% higher reduction respectively, in comparison to their SAP assessments.  The results 
from the modelling process suggest that it is technically feasible to achieve the claimed level 
of reductions, providing the Baxi Ecogen can deliver the performance it claims.   

The  third  objective  was  to  investigate  the  main  barriers  to  the  refurbishment  of  solid  wall 
dwellings.  Cost is one of the primary factors that limit the feasibility of solid wall housing in 
achieving  significant  reductions.    This  was  dealt  with  by  exploring  the  possibility  of  less 
comprehensive improvements and considering the Value Carbon factor thereby bridging the 
disincentive of a significant capital cost.  The results from this established that there is a very 
clear tipping point where the diminishing returns are acute.  Consequently pursing a path of 
all‐out refurbishment would not necessarily be a prudent use of funds when considering the 
opportunity cost of the finance available. 

46 
The issue of cost reduction was also explored in response to an indication that home owners 
expect  the  costs  to  be  heavily  subsidised  by  Government  or  a  Local  Authority.    A  possible 
solution was that market forces would be capable of reducing prices and therefore addressing 
the issues of cost.  However either the willing‐to‐pay sector had to be targeted to initiate this, 
or  homes  in  fuel  poverty  could  be  utilised  to  create  a  mass  market  whilst  reducing  fuel 
poverty.    The  overall  evidence  relating  to  cost  suggests  that  costs  can  be  reduced  by  either 
specifying less work that achieves a high Value Carbon rating, or by improving the market to 
make refurbishment measures more economic. 

Some  of  the  wider  limitations  and  issues  that  reduce  the  ability  of  the  solid  wall  stock  to 
achieve  CO2  reductions  were  also  considered.    For  solid  wall  insulation  the  solution  was  to 
specify the type on the basis of the original wall finish or by an algorithmic process.  However, 
the  evidence  shows  that  there  is  little  that  can  be  done  about  the  disruption  caused  to  the 
occupants  from  internal  wall  insulation.    The  only  possible  solution  is  to  ensure  that  on 
occasions  where  there  is  work  being  carried  out  or  the  occupants  are  in  transition,  the 
opportunity  is  maximised  by  increasing  incentives  and  awareness,  and  by  making 
refurbishment works compulsory through the Building Regulations.   

Furthermore, the CO2 emissions produced by appliances presents a serious barrier to the 80% 
reduction target as they are not included in the SAP analyses which currently rates the energy 
performance  of  dwellings.    The  evidence  suggests  that  this  barrier  requires  strong  policy 
intervention  from  the  UK  Government  to  reduce  the  number  inefficient  appliances,  and  to 
ensure only efficient appliance are used.    

Overall,  the  objectives  have  clarified  the  ability  of  solid  wall  housing  to  contribute  to  80% 
reductions.  They have aimed to answer the question; what role can solid wall housing feasibly 
play in reducing CO2 emissions by 80%?  It can be concluded that the role solid wall housing 
can  play  is  certainly  significant  but  refurbishment  alone  will  not  be  enough.    Considerable 
emission reductions can be achieved by using innovative materials and technology.  However, 
home owners need to start accepting responsibility for making their homes energy efficient.  
Refurbishment can be cost‐effective; reductions of 50% to 53% are possible for a reasonable 
expense,  and  reductions  of  65%  to  67%  are  possible  if  the  cost  threshold  is  raised.  
Nevertheless, refurbishment measures must be supplemented by other means to achieve the 
80% reduction target. 

47 
Recommendations  

Given these conclusions, a number of recommendations can be proposed that aim to address 
the barriers previously highlighted and to advance this field of study.  Firstly, an appropriate 
body  such  as  the  Carbon  Trust  carries  out  a  trial  on  the  Baxi  Ecogen  unit.    This  technology 
could greatly assist the delivery of the 80% reduction target if it can deliver what Baxi claims. 

Secondly,  a  Value  Carbon  methodology  should  be  developed  by  the  BRE  to  ensure  property 
developers,  housing  associations  and  any  other  persons  that  are  involved  in  refurbishment, 
carry  out  work  that  delivers  high  carbon  savings  for  the  lowest  cost.    This  would  also 
encourage the up‐take of refurbishments. 

Thirdly,  considerable  progress  is  made  regarding  the  attitudes  of  the  public.    This  could  be 
through  awareness  campaigns  or  by  heavily  incentivising  refurbishment  work  through 
financial  rebates.    The  Government  needs  to  dismantle  public  resistance  and  progress  the 
refurbishment market from the research stage to mass adoption.   

Fourthly,  a  swift  and  robust  amendment  of  policy  and  regulation  is  implemented  by  the  UK 
Government.    Primarily  in  the  Building  Regulations  so  that  the  opportunities  to  improve  the 
energy performance of dwellings is not lost when renovation and maintenance is carried out.  
This  policy  should  encompass  white  goods  and  appliances  to  ensure  that  the  efforts  to 
improve energy performance of the building fabric and heating system are not offset by the 
demand  for  electronics  and  appliances;  this  may  involve  working  with  the  manufacturers 
themselves. 

Finally, having established that refurbishment of solid wall  housing will not achieve the 80% 
reduction  target;  extensive  research  is  carried  out  that  investigates  how  and  to  what  extent 
solid wall housing can be supplemented by other means so that an overall strategy for dealing 
with Hard to treat dwellings can be specified. 

          

 
48 
Bibliography 

Abdullatiff, E. (2003) Development of an integrated dynamic thermal bridging assessment 
environment. Energy and Buildings 35 (4), 375‐382. 

Balson, T. (2009) T‐Zero Case Study: Green Living 70a Aubert Park, Islington, London. 
Watford, BRE bookshop. 

Baxter, L., et al. (2006) How to research. 3rd Ed, Maidenhead, Open University Press. 

Baxi. (2010a) Baxi Ecogen – FAQ’s. [Internet] Available from: 
<http://www.baxi.co.uk/products/frequently‐asked‐questions.htm> [Accessed 12 April] 

Baxi. (2010b) Baxi Ecogen ‐ Free Piston Stirling Engine. [Internet] Available from: 
<http://www.baxi.co.uk/baxiecogen> [Accessed 08 April] 

BBC. (2010) Where They Stand: Guide to party election policies. [Internet] Available from: 
<http://news.bbc.co.uk/1/hi/uk_politics/election_2010/8515961.stm#subject=environment&
col1=conservative&col2=labour&col3=libdem> [Accessed 26 April] 

Bergman, N., et al. (2010) UK Micro Generation Policy and Behavioural Aspects. Energy 162, 
23‐36. 

Boardman, B. (2007) Home Truths: A Low‐carbon Strategy to Reduce UK Housing Emissions 
by 80% by 2050. Research Report 34. Oxford, Environmental Change institute.  

Boardman, B., et al. (2005) 40% House. Research Report 31. Oxford, Environmental Change 
institute.  

Building Research Establishment. (2001) Energy‐efficient refurbishment of existing housing. 
Good practice guide 155, Watford, BRE bookshop. 

Building Research Establishment. (2008a) Energy Analysis Focus Report: A Study of Hard to 
Treat Housing using the English House Condition Survey Part 1. Watford, BRE bookshop. 

Building Research Establishment. (2008b) Energy Analysis Focus Report: A Study of Hard to 
Treat Housing using the English House Condition Survey Part 2. Watford, BRE bookshop. 

Building Research Establishment. (2009) The Government’s standard Assessment 
Procedure for Energy Rating of Dwellings.  2005 Ed, revision 3, Watford, BRE Bookshop. 

Carbon Trust. (2007) Micro CHP Accelerator. Interim Report. London, Carbon Trust. 

49 
Clarke, J. A., et al. (2005) Thermal Improvement of Existing Dwellings. Glasgow, Energy 
Systems Research Unit. 

Cole, C. (2008) CHP and SAP – Part II. [Internet] Available from: 
<http://carbonlimited.org/2008/03/20/chp‐and‐sap‐part‐ii/> [Accessed 06 April 2010] 

Department for Business Enterprise and Regulatory Reform. (2007) Construction Statistics 
Annual 2007 [Internet] Available from: <http://www.berr.gov.uk/files/file42061.pdf> 
[Accessed 16 April 2010] 

Department of Communities and Local Government. (2006) Review of Sustainability of 
Existing Buildings. London, Communities and Local Government Publications. 

Department of Communities and Local Government. (2007) Building a Greener Future: policy 
statement. London, Department for Communities and Local Government. 

Department of Communities and Local Government. (2009) English House Condition Survey 
2007. London, Communities and Local Government Publications. 

Department of Communities and Local Government. (2010) Building Regulations. [Internet] 
Available from: <http://www.communities.gov.uk/planningandbuilding/buildingregulations/> 
[Accessed 06 April 2010] 

Department of Energy and Climate Change. (2010b) The Standard Assessment Procedure 
(SAP) [Internet] Available from: 
<http://www.decc.gov.uk/en/content/cms/what_we_do/consumers/saving_energy/std_asses
s/std_assess.aspx> [Accessed 06 April 2010] 

Direct.Gov. (2010) How the UK will meet CO2 emissions targets. [Internet] Available from: 
<http://www.direct.gov.uk/en/Nl1/Newsroom/DG_179190> [Accessed 14 April 2010] 

Ecotricity. (2010) UK Grid live. [Internet] Available from: 
<http://www.ecotricity.co.uk/about/live‐grid‐carbon‐intensity> [Accessed 14 April 2010] 

Energy Efficiency Partnerships for Homes. (2004) Insulating solid walls: a challenge for local 
authorities and housing associations. London, Energy Efficiency Partnerships for Homes. 

Energy Saving Trust (2005) Improving airtightness in dwellings. Research Report 224. London, 
Energy Saving Trust. 

Energy Saving Trust. (2006a) Energy efficient ventilation in dwellings.  Research Report GPG 
268. London, Energy Saving Trust. 

Energy Saving Trust. (2006b) Practical refurbishment of solid‐walled houses. Research Report 
184. London, Energy Saving Trust. 

50 
Energy Saving Trust. (2006c) Refurbishing Dwellings – a summary of best practice. Research 
Report 189. London, Energy Saving Trust. 

Energy Saving Trust. (2006d) The rise of the machines. London, Energy Saving Trust. 

Energy Saving Trust. (2008) Towards a long‐term strategy for reducing carbon dioxide 
emissions from our housing stock. London, Energy Saving Trust. 

Energy Saving Trust. (2010a) Lighting. [Internet] Available from:  
<http://www.energysavingtrust.org.uk/corporate/Corporate‐and‐media‐site/Media‐
centre/Energy‐saving‐statistics‐and‐facts/Lighting> [Accessed 20 April 2010] 

Energy Saving Trust. (2010b) Sustainable refurbishment. Research Report CE309. London, 
Energy Saving Trust. 

Fellows, R., Liu, A. (2003) Research Methods for Construction. 2nd Ed, Oxford, Blackwell 
Publishing Ltd. 

Geroski, P.A. (2000) Models of technology diffusion. Research Policy 29, 603–625 

Green Building Press. (2006) The Green building bible volume 1. Volume 1. 3rd Edition. 
Llandysul, Green Building Press. 

Henderson, J. (2009) Review of auxiliary energy use and the internal heat gains assumptions 
in SAP. (STP 09/AUX01), Watford, BRE. 

Immendoerfer, A., et al. (2008) Fit for the future: the green homes retrofit manual. London, 
Housing Corporation. 

Impetus Consulting. (2004) Insulating solid walls a challenge for policy makers and scheme 
managers. London, Energy Efficiency Partnerships for Homes. 

Intergovernmental Panel on Climate Change. (2001) Climate change 2001: the scientific basis. 
Technical Summary, Intergovernmental Panel on Climate Change, Geneva. 

Jenkins, D.P. (2010) The value of retrofitting carbon‐saving measures into fuel poor social 
housing. Energy Policy 38 (2), 832‐839. 

Jennings, P. (2006) The Green Building Bible Volume 1. 3rd Edition, Llandysul, Green Building 
Press. 

Killip, G. (2008) Transforming the UK’s Existing Housing Stock. London, Federation of Master 
Builders. 

51 
King, D.A. (2004) Climate change science: Adapt, mitigate or ignore? Science 303 (5655), 176‐
177. 

Knight, A. (2008) Advanced Research Methods in the Built Environment. Chichester, Wiley‐
Blackwell Publishing Ltd. 

Lowe, R. (2007) Technical options and strategies for decarbonizing UK housing. Building 
Research and Information 35(4), 412–425. 

Mackay, D. (2009) Sustainable Energy ‐ without the hot air. Cambridge, UIT Cambridge. 

Mavrogianni, A. (2009) Space heating demand and heatwave vulnerability: London domestic 
stock. Building Research and Information 37 (5), 583–597. 

Met Office. (2010) UK mapped climate averages. [Internet] Available from: 
<http://www.metoffice.gov.uk/climate/uk/averages/ukmapavge.html> [Accessed 13 April 
2010] 

Naoum, S.G. (2009) Dissertation research & writing for construction students. 2nd Edition, 
Oxford, Elsevier Ltd.  

NASA. (2010) Surface meteorology and Solar Energy. [Internet] Available from: 
<http://eosweb.larc.nasa.gov/cgi‐bin/sse/sse.cgi?+s01#s01> [Accessed 16 March 2010] 

National Oceanic Atmospheric Administration. (2010) NOAA Solar Calculator. [Internet] 
Available from: <http://www.esrl.noaa.gov/gmd/grad/solcalc/> [Accessed 16 March 2010] 

Office for National Statistics. (2010) Industry Consumption of Energy & Output. [Internet] 
Available from: <http://www.statistics.gov.uk/cci/nugget.asp?id=151> [Accessed 17 January 
2010]  

OPSI. (2010) Climate Change Act 2008 [Internet] Available from:  
<http://services.parliament.uk/bills/2007‐08/climatechangehl.html> [Accessed 10 April 2010] 

Oxford Environmental Change Institute. (2010) Degree Days for energy management. 
[Internet] Available from: <http://www.eci.ox.ac.uk/research/energy/degreedays.php> 
[Accessed 11 March 2010] 

Peacock, A.D., et al. (2009) Market development potential of residential refurbishment 
package. European Council for an Energy Efficient Economy (ECEEE), Summer Study, Cote 
d’Azur,  

Perry, M. (2006) A spatial analysis of trends in the UK climate since 1914 using gridded 
datasets. Climate Memorandum No.21. Exeter, Met Office.  

52 
Pett, J. (2004) Affordable Warmth in ‘Hard to Heat’ Homes: a progress report. Research 
Report v1.1. London, Association of the Conservation of Energy. 

Plimmer, F., et al. (2008) Knock it down or do it up? Watford, BRE bookshop. 

Roaf, S., et al. (2008) Evidence on Tackling Hard to Treat Properties. Edinburgh, Scottish 
Government Social Research. 

Scharmer, K., Greif, J. (2000) THE EUROPEAN SOLAR RADIATION ATLAS Vol. 1: Fundamentals 
and maps. Paris, Presses de l'École des Mines. 

Scottish Government Social Research. (2010) Modelling Greenhouse Gas Emissions from 
Scottish Housing: Manual and Model. Glasgow, Scottish Government Social Research. 

Shorrock, L.D., et al. (2005) Reducing carbon emissions from the UK housing stock. Research 
Report 480. Watford, BRE Bookshop.  

Shorrock, L.D., Utley, J.I. (2003) Domestic Energy Fact File 2003. BRE457. Watford, BRE. 

Sturges, J. (2006) Planet earth: what we need to know about it. Leeds, Leeds Metropolitan 
University. 

Sustainable Energy Ireland. (2005) A detailed guide to insulating your home. Dublin, 
Sustainable Energy Ireland. 

Taylor, R. (1996) The Conservation and Thermal Improvement of Timber Windows. [Internet] 
Available from: < >[Accessed 12 April 2010] 

Taylor, R. (2009) Chimneys and Flues. [Internet] Available from: 
<http://www.buildingconservation.com/articles/services/chimney.htm> [Accessed 05 April 
2010] 

WWF. (2008) How Low–Achieving Optimal Carbon Savings from the UK’s Existing Housing 
Stock. WWF, London, UK. 

Yin, R.K. (2003) Case Study Research: Design and Methods. 3rd Edition. Thousand Oaks, CA, 
Sage. 