Professional Documents
Culture Documents
Triangulo de Duval
Triangulo de Duval
Triangulo de Duval
Figure 1: The Duval Triangle 1 for transformers filled with The Duval Triangle for LTCs of the Vacuum
mineral oils. Bottle Type
For LTCs of the vacuum bottle type, the Duval Triangle 1 for
transformers should be used (and not the Duval Triangle 2 for
The identification of fault zones in Figures 2 and 3 is indicated LTCs of the oil type), because in LTCs of the vacuum bottle type,
in Table 1. In the second column of Table1, the types of faults the arc-breaking operation occurs in the vacuum bottle and not
mentioned are: D1 = Discharges of low energy; D2 = Discharges in the cooling oil around it (from which the oil sample is taken
of high energy; T2 = Thermal faults of temperature 300ºC < T < for DGA).
700ºC; T3 = Thermal faults of temperature > 700ºC. Gas concentrations in the cooling oil of LTCs of the vacuum
Numerical zone boundaries in Figures 2 and 3 are indicated bottle type are usually very low, and the rarely formed gases are
in Table 2. mainly of the overheating type (T1 to T3). However, some LTCs
The numerical zone boundaries indicated in Table 2 for the N
(normal operation) zone cover all types of LTCs of the oil type and
may be used by default. However, the N zone may be smaller for
N Normal operation
Abnormal arcing D1
D1 Inspect the LTC for small signs of arcing.
(outside of zone N).
Abnormal arcing D1
X1 Area still under investigation.
or thermal fault in progress
Note: to distinguish D2 from T3, rinse and change the oil. Run a few LTC operations (~100) then a DGA.
If the DGA point remains at the same place as before changing the oil, this may indicate a fault D2. If the
DGA point has moved to the left, a fault T3 is more likely.
of the vacuum bottle type may have sparking D1 in the selector A number of such test results have been published and are
switch (located in the cooling oil) as part as their normal opera- indicated in Figure 4 for silicone oil, synthetic ester (Midel), and
tion. natural esters/ vegetable oils (FR3 and BioTemp), using the Duval
Triangle 1 for transformers. References for these test results are
The Duval Triangle 3 for Non-Mineral Oils indicated in Figure 4. DGA results were obtained either by the
Mineral oil is the most widely used insulating fluid in electrical laboratory gas extraction method of Head Space (and were cor-
equipment. However, other non-mineral oils are increasingly used rected for the different Ostwald coefficients of the non-mineral
because they are less flammable or more environmentally friendly. oil [7]), or by the Toepler or Partial Degassing methods (and do
This has raised the question of whether new DGA interpretation not need significant corrections).
methods are needed for them, or if existing methods used for The differences in gas formation patterns observed in Figure 4
mineral oils can be adjusted for non-mineral oils. between mineral and non-mineral oils can be used to adjust zone
Very few inspected cases of faults in equipment filled with boundaries of the Duval Triangle 1 and to create a Duval Triangle
non-mineral oils are available, because these fluids have been 3 for each of the non-mineral oils, as indicated in Figure 5. Zone
used only for a small number of years and in a limited quantity boundaries of the Duval Triangle 3 for non-mineral oils are the
of equipment. To evaluate gas formation patterns in these fluids, same as those of the Duval Triangle 1 for mineral oils except for
therefore, one can only rely on tests simulating faults in the the boundaries (in % C2H4) between zones D1/ D2, T1/ T2, and
laboratory, and performed in parallel on both mineral oils and T2/ T3, as indicated in Figure 5 and Table 3.
the new fluids. Other cases of faults simulated in the laboratory for non-min-
eral oils will be given in the final report of CIGRE TF D1-01-15
[6] and may slightly modify the values indicated in Table 3. The
boundary between faults D2 and DT may also have to be modified
when actual cases of faults D2 (high-energy arcing) are reported
Table 2. Numerical zone boundaries in Figures 2–3 (in %).
in transformers in service filled with these non-mineral oils.
N CH4 = 19, C2H4 = 23, CH4 = 2, C2H4 = 6 The reason for the different gas patterns of mineral and non-
mineral oils can only be speculative at this stage and is outside
T3 C2H4 = 50, C2H2 = 15
the scope of this paper. These differences are probably related
X3 C2H4 = 23, C2H2 = 15 to the differences in chemical structure of the oils. For instance,
the carbon-oxygen bonds in natural and synthetic esters (FR3,
T2 C2H4 = 23, C2H2 = 15, C2H4 = 50
BioTemp and Midel), and the silicon-oxygen bonds in silicones,
D1 CH4 = 19, C2H4 = 6, CH4 = 2, C2H4 = 23 may slightly affect the chemical strength of neighbouring
carbon-carbon and carbon-hydrogen bonds, and might explain
X1 CH4 = 19, C2H4 = 23
the different relative amounts of hydrocarbon gases formed at
b d
Figure 4: Comparison of DGA results on couples of mineral and non-mineral oil subjected to the same faults (D1, PD, T1, T3)
simulated in the laboratory. Zone boundaries indicated are those of mineral oils.
the same levels of fault energy or temperature. The two natural The Duval Triangles 4 and 5 for Low-
esters (vegetable/seed oils) examined in this paper are based on Temperature Faults in Transformers
saturated/unsaturated oleic/fatty acids [13], and the synthetic ester The Duval Triangle 1 for transformers has proved quite efficient
on pentaerythritol. Non-mineral oils with different chemical struc- to determine the general type of fault occurring in transformers
tures may result in different gas patterns and zone boundaries. in service (PD, D1, D2, T1, T2, T3, DT). It is based on the use of
Silicone Midel
b d
FR3 Biotemp
Figure 5: The Duval Triangle 3 for non-mineral oils (silicone, Midel, FR3, and BioTemp). Zone boundaries specific for each non-
mineral oil are in color. Those in black are the same as for mineral oil.
3 gases (CH4, C2H4 and C2H2) representative of low-, high-, and at relatively low temperatures such as 80 to 200°C [15]. Stray
very high-energy or temperature faults, respectively [3]. gases may appear in the PD, T1, or T2 zones, and therefore may
When DGA results are close to the boundary between zones interfere with the identification of these faults in transformers.
PD and T1, however, it may sometimes be difficult to distinguish The Duval Triangles 4 and 5 for low-temperature faults in trans-
between these two types of faults. Also, some types of oils on the formers have been developed to remove these uncertainties. They
market tend to be “stray gassing”, i.e., to unexpectedly form gases should be applied only to faults identified by the Duval Triangle
D1/ D2 23 9 26 25 20
T1/ T2 20 16 39 43 52
S C2H6 = 44, H2 = 9, C2H6 = 24, CH4 = 36, CH4 = 15, C2H6 = 1. CH4 = 2
Figure 6: The Duval Triangle 4 for low-temperature faults in C CH4 = 36, C2H6 = 24
transformers filled with mineral oil. Warning: the 3 gases used
O H2 = 9, C2H6 = 24
in this version of the triangle are H2, CH4, and C2H6.
Idem, paper burst open 230 1000 500 3 280 230 5500 [17, B]
PD C2H4 = 1, C2H6 = 15
References
[1] Mineral Oil-Impregnated Electrical Equipment in Service - Guide to the
Interpretation of Dissolved and Free Gases Analysis. IEC Publication 60599 Michel Duval graduated from the Univer-
(1999-03), Mar. 1999. sity of Toulouse in 1966 with a B.Sc. degree
[2] Guide for the Interpretation of Gases Generated in Oil-Immersed
Transformers, IEEE Std C57.104-1991, 1991.
in chemical engineering, and received a
[3] M. Duval, “A review of faults detectable by gas-in-oil analysis in Ph.D. degree in polymer chemistry from
transformers,” IEEE Electr. Insul. Mag., vol. 18, no. 3, pp. 8–17, 2002. the University of Paris in 1970. Since
[4] P. Griffin, L. Lewand, et al., “Load tap changer diagnostics using oil tests then, he has worked for Hydro Quebec’s
– A key to condition-based maintenance,” Minutes of Doble Engineering
Conf., 2005.
Institute of Research (IREQ) on electrical
[5] S. Girard, “Protective maintenance at Chugach Electrical Association, insulating oils, dissolved gas analysis and
Anchorage, Alaska”, TechCon 2004 North America Conference, San lithium polymer batteries. A Fellow of IEEE
Antonio, TX, 2004. and the Chemical Institute of Canada, he
[6] M. Duval et al., Final Report of CIGRE TF D1-01-15, to be published in
2009.
holds 15 patents, has authored over 70 scientific papers, book
[7] Cooper Power Systems, Envirotemp FR3 Fluid – Dissolved Gas Guide, chapters, or international standards, and is very active in several
Technical Brochure R900-20-19, 2006. CIGRE, IEC, and IEEE working groups. He may be reached at
[8] P. Griffin, “Analysis for combustible gases in transformer silicone fluids”, IREQ, 1800 boul.Lionel Boulet, Varennes, J3X 1S1, Canada, or
Minutes of Doble Engineering Conf., 1985, Sec.10-701/ 707.
[9] H. Kuwahara, et al., Study of Explosion and Fire Hazards of Silicone Liquid
at duvalm@ireq.ca.
Under Arc Conditions, Mitsubishi Technical Brochure, 1987.