Professional Documents
Culture Documents
UN 5000 User's Manual: Commissioning
UN 5000 User's Manual: Commissioning
Chapter 6
Commissioning
6.1 General
This document contains the information required for the commissioning of an excitation
system of the type UNITROL5000.
Please read this manual carefully before you start work on commissioning. This document
contains:
• Information on safety and servicing
• Advice on safe and correct commissioning
This manual is primarily aimed at commissioning personnel. This personnel should possess
both deep electrical engineering as well as good basic technical knowledge. Commissioning
may only be carried out by personnel specially trained in the UNITROL5000. This training is
carried out periodically by ABB Industrie AG.
Danger Extreme care is required when carrying out work inside the
Electricity control cabinets.
Danger Serious injury can result from contact with live parts of the
Electricity system. Personnel may not enter the cabinets without the
necessary specialised knowledge and without protective
measures being taken. All live parts in the regulator cabinet
(+1ER) with a potential over 50V are protected against
accidental contact.
Note Warning signs are affixed to all cabinet doors to warn of the
operating voltages present in the control cabinets (over 50
volts), but above all to warn of the voltages which occur in
the power section (over 1000 volts possible) and the
enormously high short-circuit currents. These signs are
intended to point out that the doors may not be opened
during operation.
Fire extinguishers are filled with halon, carbon dioxide (CO2) or foam.
CO2 fire extinguishers are intended to be used to fight fires in electrical installations and
may not be pointed at persons.
Foam extinguishers are intended to be used to fight fires in utility objects. They may not be
used to fight electrical fires. They may be used on persons.
1. First switch off the excitation, locally or from the control room, or if
necessary using the emergency shutdown mechanism (see user‘s
manual). Then switch off all power supplies to the installation.
2. Free the victim from their endangered situation and lay them flat.
Perform first aid in accordance with training and taking into account the
rules applying to electrical installations. Call for assistance.
General:
• Travel
• Meetings
• Equip workplace (table, chair, lighting)
• Make changes if necessary
The times stated refer to the actual time required for trials/tests. The work can only be
completed in the stated time if the installation is only available for the exciter tests and the
network does not impose any restrictions.
Depending on their importance, the following tests are to be carried out on both channels
(CH I, CH II):
• Visual check for transport damage, correct erection.
• Compare terminal connections with schematic (correct connection, cross section,
earthing, check screws).
• Basic settings on equipment.
• Visual check of high-voltage circuits, de-excitation circuits, dielectric resistances.
• External AC, DC supplies, rotating field, polarity, step-by-step connection of protective
circuit breakers & checking of individual pieces of equipment, fans etc. and their function.
• Loading of software and parameter list, ARCnet communication.
• Consider and set parameters, calculate RTM and PSS.
• Interface – digital inputs and outputs, incl. alarms.
• Interface – analogue inputs and outputs.
• Control – field circuit breaker, field flashing, control circuits etc., operation from local
panel.
• Trip circuits – protection, generator circuit breaker (input and output), separately for CH I
& CH II.
• Check control commands from control room, Synchrotact, fieldbus etc.
• Program internal measuring transformer if required.
• External voltage and current transformer circuits, transformation ratio (possibly already
dealt with by customer).
• Check pulse channels.
• Request field resistance from customer or measure.
Depending on their importance, the following tests are to be carried out on both
channels (CH I, CH II):
Synchronising:
Initial synchronising with voltage regulator in manual mode.
Remarks:
The approximate times stated above apply under the following conditions:
• Preparations prior to commissioning (see above) were carried out by customer.
• During the stated times, the machine is fully available to the AVR commissioning
engineer, i.e. no other tests such as generator, protection or turbine tests may be
carried out.
• No waiting times arise.
• Normal network conditions;
i.e. the generator can be operated within the entire power chart range and can be
switched from one power chart range to the other within minutes.
Document number Lang. Rev. ind. Sheet