Professional Documents
Culture Documents
E-08-Maintenance and Troubleshooring PDF
E-08-Maintenance and Troubleshooring PDF
E-08-Maintenance and Troubleshooring PDF
Chapter 8
Maintenance and
Trouble Shooting Instructions
SW version 41.304
8.1 General
In particular, the field breaker and components in the field discharge circuit, which are
connected directly to the rotor field winding, present a great danger of electric shocks.
For this reason, the cabinets are fitted with safety guards to prevent accidental contact
with live parts.
If the removal of the safety guard is unavoidable, the personnel must be aware of the
dangerously high voltages and the enormously high short circuit currents and act
accordingly.
Warning signs are placed on all cabinet doors to warn of the operating voltages
present in the control cabinets (over 50 volts), but most importantly to warn of the
voltages occurring in the power section (possibly over 1000 volts) and the enormously
high short circuit currents. These signs are intended to prevent the doors being
opened during operation.
Maintenance work may only be carried out on the electrical system once the exposed
voltage-carrying parts have been completely switched off and protective grounds
installed. If this is not possible, the following special precautions must be taken:
• Access to the work area must be restricted by means of a safety zone (fence) with
a yellow warning sign "Danger! High Voltage".
• Countermeasures should be taken to prevent the system being switched on again
through a control error or by a third party after it has been switched off (e.g. prevent
switching on by means of key-switches, etc.).
Danger If the safety guards in the cabinets are removed while the
Electricity system is under voltage, there is an increased danger of
electric shock, not only to the personnel carrying out work,
but also to any third parties who approach the
installations.
If the scheduled maintenance work is not carried out, or is only partially carried out,
damage can occur which results in high repair costs. In particular, accumulations of
dirt and dust on the converter lead to a high risk of voltage flash-overs which can
cause enormous damage.
• CO2 fire extinguishers are intended for fighting fires in electrical installations and
may not be directed at persons.
• Foam extinguishers are intended for fighting fires in non-electrical equipment.
They may not be used to fight fires in electrical equipment. They may be directed at
persons.
In case of fire in the system:
First switch off excitation, either locally or from the control room, or if necessary
through the emergency shutdown mechanism (see operating manual). Then switch off
all power supplies to the system.
When fighting fires in energized cabinets, only use CO2 fire extinguishers, no foam,
no water!
Return to:
ABB Industrie AG, Service and Support ICS, CH-5300 Turgi/Switzerland
Fax: +41 56 299 30 00
E-Mail: PES.support@ch.abb.com
Company/Address: ........................................................................................................................
Location of plant:............................................................................................................................
3. What did happen just before the fault has occurred? Please specify:
5. When did the fault occur? (year, month, day, time) ............................................................
7. Could you localize and clear the failure and restart the system? Yes No
9. Fault Indications
Fault Indications at the local Control Panel (press à or Ä to show additional faults)
No. Text
First Fault*
Fault indications at the local service Panel: Press “ACT” + to display the fault logger
Indication in Channel 2
Time stamp Text
If you are equipped with CMT tool (see chapter 3) send the fault logger and parameter file
(*.qop) or fax the print of both files of channel 1 and 2 to our ABB office.
8.2.1 Introduction
Although electronic components show no signs of wear and only slight signs of aging,
the excitation equipment contains a series of conventional electromechanical
components such as breakers, contractors and fans which are subject to a certain
amount of mechanical wear.
While in operation, the correct function of the control electronics is constantly checked
by automatic self diagnostic functions. Redundant circuits, such as the non-active
channel in the two channel version, are also monitored as far as possible. However,
protection equipment cannot be automatically checked, since it is only active in fault
situations. The periodic function checks serve to check this equipment and activate all
redundant circuits for test purposes.
In addition to the periodic check, a more thorough function check, as described below,
is required after cleaning work on components and/or plug-in assemblies.
Dust builds up in electronic circuits and in the converter due to air circulation.
Vibrations may cause screw terminal connections to be loosened.
High voltages and currents (direct current!) occur in the excitation circuit. Soiled
insulation increases the risk of serious damage due to voltage flashover. Periodic
maintenance of the system reduces this risk considerably.
This manual covers the maintenance work for normal operation. Special operating
modes, such as short-circuit tests, inputs etc., are not covered. Such operating modes
require extensive knowledge of all parts of the system (excitation, generator, etc.), and
should therefore only be carried out by a specialist.
The individual points in the maintenance table will be subsequently explained in more
detail. Both groups, 3-monthly and annual maintenance, will be handled separately.
The first group essentially only involves visual inspections, whereas the actual
maintenance work is listed in the second group.
The intervals in the maintenance schedule at which maintenance work is to be carried
out must be strictly adhered to, especially in the first year of operation. An optimum
maintenance interval can then be worked out on the basis of the results of the regular
inspections. In particular, the accumulation of dirt must be monitored in the first year of
operation. If a lot of dirt has accumulated, then the interval should be reduced; if the
level of dirt is very high, the IP mode of protection must be re-evaluated or changed.
Converter # Signal #
1 Fan 1 10518
Fan 2 10519
2 Fan 1 10528
Fan 2 10529
3 Fan 1 10538
Fan 2 10539
X Fan 1 for additional converters 105X8
Fan 2 105X9
3 Checking the air filters for contamination: The filter cartridges are to be
changed if they are very dirty.
Converter # Signal #
1 Sensor 1 10516
Sensor 2 10517
2 Sensor 1 10526
Sensor 2 10527
3 Sensor 1 10536
Sensor 2 10537
X Sensor 1 for additional converters 105X6
Sensor 2 105X7
Note After testing has been completed, make sure the AUTO
operating mode is selected.
1 (Operating condition c) Clean off dirt with a dry cloth, vacuum cleaner or
compressed air (not high pressure!). Do not use any solvents.
Converter:
2 Inspection of the converter fans for dirt, normal airflow and abnormal
noises (operating condition d or e): Since it is not possible to lubricate the
bearings, fans with increased noise must be replaced.
Converter # Signal #
1 Fan 1 10518
Fan 2 10519
2 Fan 1 10528
Fan 2 10529
3 Fan 1 10538
Fan 2 10539
X Fan 1 for additional converters 105X8
Fan 2 105X9
3 Inspect air filter for contamination (operating condition dor e): change the
filter cartridges if they are very dirty.
4 Inspection of the heat sinks for dirt (operating condition c): Clean with
brush and vacuum cleaner or compressed air (not high pressure!). On no
account use solvents!
Converter # Signal #
4 Sensor 1 10516
Sensor 2 10517
5 Sensor 1 10526
Sensor 2 10527
6 Sensor 1 10536
Sensor 2 10537
X Sensor 1 for additional converters 105X6
Sensor 2 105X7
Circuit breakers:
6 Field breaker (Q02) (operating condition c): Check for dirt and contact
charring. Clean with a brush and dry cloth. If necessary, remove charring using
emery paper. Lubricate all sliding surfaces using an appropriate grease. Check
the arc chamber each time the breaker is tripped due to short circuit, remove
smoke residue and dust using compressed air, scrub off cinder. Consult the
separate maintenance instructions for the breaker.
7 Check screw connections (operating condition c): Check that all screw
connections on screw terminals, bus bars etc. are tight.
8 Check insulators for dirt and loose screws (operating condition c): If
necessary, clean with a dry cloth. We recommend that all screw connections
are checked (point 7 & 8) after the first year of operation, thereafter
approximately every 4 years.
Control electronics:
9 Check the printed circuit boards for dirt (operating condition c).
Dirt and dust should not accumulate on the printed circuit boards under
normal conditions. Use vacuum cleaner and soft brushes to clean the
boards. On no account use solvents!
Note After testing has been completed, make sure the AUTO
operating mode is selected.
Open the field breaker and install grounds on both sides of the exciter. The
regulator electronics continue to be supplied from the station’s battery through
the input circuit.
After switching over to local operation, the field breaker can be closed from the
control panel again when the system is under no voltage. The following
protection equipment and functions can now be tested, if they are part of the
system. The fault must be reset and the field breaker re-closed each time a
protection feature has been triggered.
The following points must be observed before work is started on the excitation system:
Note: The field breaker must not be switched neither ON nor OFF while
voltage is present.
2. Measure the voltage between terminals of the main supply input (L1 - L2 - L3 –
PE). The measuring range of the voltmeter should be at least Uac = 1000 V.
Although the supply voltage has been disconnected with the main switch of the
excitation system, voltage may still be present from the auxiliary power supply.
3. Voltage withstanding tests may not be carried out on any component of the
system.
Note The settings applicable for your installation are entered in the
commissioning protocol.
Fuses may only be replaced and measurements carried out on semiconductors if the
converter has been disconnected beforehand by a circuit breaker or emergency switch.
In addition, to ensure the safety of personnel, a voltmeter should be used to check
whether any voltage is present at the input and output terminals of the converter.
Countermeasures should be taken to prevent the system being switched on again
through a control error or by a third party after it has been switched off.
Wrong errovalue
COB initializing
ARCnet initializing
Loading firmware
Start Sequence
Trouble Shooting
• Replace the COB board UNS2880.
01 UNITROL FLASH memory test error
Operator Information
The test of the FLASH PROM failed, e.g. due to a defective system program
having been stored.
Trouble Shooting
• Replace the COB board UNS2880.
02 RAM memory test error
Operator Information
A fault was detected in the RAM memory circuit.
Trouble Shooting
• Try to restart the UNITROL 5000 system.
• If this error message appears again after restarting the UNITROL 5000
system, replace the COB board UNS2880.
05 No control program in memory
Operator Information
There is no system program loaded in the Flash PROM.
Trouble Shooting
• Because there is no program stored in the Flash PROMs (not even a boot-
up program), no new program can be downloaded.
• If the fault is repeated, replace the COB board UNS2880.
06 ASIC error
Operator Information
There is Fault of the COB ASIC occurred
Trouble Shooting
• Try to restart the UNITROL 5000 system.
• If this error message appears again after restarting the UNITROL 5000
system, replace the COB board UNS2880.
Trouble Shooting
• Try to restart the UNITROL 5000 system.
• If this error message appears again after restarting the UNITROL 5000
system, replace the COB board UNS2880.
39 ARCnet Communication error
Operator Information
The ARCnet Communication from COB is disturbed
Trouble Shooting
• Try to restart the UNITROL 5000 system.
• If this error message appears again after restarting the UNITROL 5000
system, replace the COB board UNS2880.
TRIP_FAULT
1
Fault Word 1
2
.
.
.
.
.
Channel 2 .
16
Hardware Channel 1
(Software not 1 Hard- and
shown, same as
Fault Memory
Fault Word 2
2
Software
Fault Signals
.
Channel 1) .
.
.
.
.
16
Fault Word 3
2
.
.
.
.
.
Fault Logger
.
16
1
Fault Word 4
2
.
.
.
.
.
.
16
Alarm Signals
1
Fault Word 5
2
.
.
.
.
.
.
16
CHANNEL 2 1
Fault Word 6
2
(-A20) .
.
.
.
.
.
16
DO 01 DO 01
CHNL OK TRANSFER_CTRL CHNL OK
DO 02 DO 02
EXC TRIP_CMD EXC TRIP_CMD
DO18 DO18
COM ALARM AVR_FAULT COM ALARM
INH_OF_START
COB COB
UNS 2880 UNS 2880
EGC_RUN_BACKUP EGC_RUN_BACKUP
EGC_TRIP EGC_TRIP
ALARM ALARM
CHANNEL 1
EGC (-A10) EGC
UNS 2882 UNS 2882
Fail Fail
Ch2 Ch1
FIO1 (-U70)
UNS 0883
1L 102.5% II 1L 102.5% II
UNITROL 5000 UNITROL 5000
*** WARNING *** *** FAULT ***
Alarm Text Message Fault Text Message
After operating 2 times one of the double arrow keys, the Fault Logger is entered and
the last entry is displayed with time stamp:
1L 102.5% II 1L 102.5% II
1 LAST WARNING 1 LAST FAULT
+Alarm Text Message Fault Text Message
YY.MM.DD-HH:MM:SS.xx YY.MM.DD-HH:MM:SS.xx
With the ∆ arrow the Fault Logger history is displayed entry by entry. The time stamp
has the format:
YY=Year, MM=Month, DD=Day, HH=Hour, MM=Minute, SS=Second, xx=decimal
fraction
Note:
1. The ALARM or FAULT code No. is not displayed and must be evaluated from the
ALARM or FAULT table sorted in alphanumeric order.
2. Only a “blinking” Fault (or Alarm if it’s not self resetting) can be RESET by RESET
key. Therefore the LOCAL mode is required by operating “LOC/REM” key.
If the Fault is still present, only the display is reset and the Fault message is
displayed again after approx. 60s. Most of the Alarms are self resetting. See Alarm
table below for more information.
3. Any accepted RESET action according 2. is entered to the Fault Logger with time
stamp.
The local control panel can display up to 8 Fault Logger entries at the same time (8
rows). Only the ALARM or FAULT code No. and the same Text Message as in the
Fault Logger is displayed.
Note:
1. The messages are not sorted with respect to time of occurrence, as per Fault
Logger List, but only with respect to the BIT No. of the relevant ALARM or FAULT
Word. Use the Service Panel SPA or the CMT for time stamp and sequence
information
SP-164/165
5324 RESET 1
! OUT RESET 10352
1 10355 RESET
5339
SP-156
Local
10372 5349
S 10377 LOCAL &
REMOTE R
FAULT
1
RESET
RESET
ALARM
Display
Alarm- & Fault Words
Memory
Fault Logger RESET is only possible if an Alarm or Fault BIT is set in the Alarm-
or Fault Words, and LOCAL mode is true. Therefore the LOCAL mode is required
by operating “Local” key.
4. Because of the Display Memory, the LCP display can contain already disappeared
(self reset) Alarms. Therefore push the Acknowledge key to clear or refresh the
LCP display.
5. Any accepted RESET action according 3. are entered to the Fault Logger with time
stamp.
Fault Reset is analog to the Service Panel SPA when Control Panel is put to LOCAL
mode.
The following Fault and Alarm tables contain, sorted per Fault Code:
Document number Lang. Rev. ind. Sheet
Table Remarks:
1) Text for SPA, LCP Panels and CMT Fault Logger. LCP and CMT are showing
also the ALARM- and FAULT-CODE No.
2) System Configurations S..., D..., A..., Q..., ..T-.. according to UNITROL 5000
Type Code
3) S1 = Step 1 If after an ACTION the same Fault is also TRUE in the active
System.
S2 = Step 2 If after an ACTION the same Fault is also TRUE in the Standby
System.
ACTIONS:
C Converter Faults which are summed in the Fault Evaluation Logic. The
sum is evaluated to generate 3 level signals:
Sum >= SET_FAIL_LEVEL_1 (928) -> ALARM 197 "Conv. fail level 1"
and signal LEVEL1_CONV_FAIL (10925). (DEFAULT not used)
Sum >= SET_FAIL_LEVEL_2 (929) -> ALARM 198 "Conv. fail level 2"
and signal LEVEL2_CONV_FAIL (10926). (DEFAULT: not used,
depending on application, this signal is used to reduce ceiling capability
or max. cont. current)
Sum >= SET_FAIL_LEVEL_3 (930) -> CH FAULT 43 "Converter fault"
and signal LEVEL3_CONV_FAIL (10927). (DEFAULT not used)
E Event: only logged into the Fault Logger, no further message to remote
system
I Ihibt of START-UP
4) RESET versions:
S Self Reset, i.e. the remote ALARM message disappears after d.h. fault
condition isn't TRUE anymore. The Fault Logger is signing the entrance
as "+" and the disappearance as "-".
6) Function blocked:
7) Message appears together with the message of the converter No. I.e. with the
Alarm No. "Conveter x" 161...168
8) Depending on the setting of the paramter type [1101, 05, 09, 13, 17, 21]
following actions are released:
100) To prevent from tripping in case of Gate CTRL fault (e.g. missing output
pulses), there is an emergency channel transfer and/or transfer to the Back Up
EGC prior to the final TRIP cmd.
Note: the faulty branch No. will also be indicated on the Converter
Display Panel CDP.
102) To prevent from tripping in case of USYN Measuring X-ducer fault, there is an
emergency channel transfer and/or transfer to the Back Up EGC prior to the
final TRIP cmd.
103) In the case where the EGC is serving as Gate CTRL for fn<50Hz applications,
this signal is including also all Converter Monitoring signals. Ref. to Fault- and
Alarm list of EGC.
Trouble Shooting
Note: The MUB board, which supplies the COB has supply monitoring
functions too. If Fault 54 “MUB fault/power fail” is also present,
refer to that first.
• Reset the fault message. If the fault message is repeated, the fault may
lie in the COB board
• Check the connection between the MUB and COB board (X37).
Trouble Shooting
Note: Short delay times are used in order to achieve converter
redundancy. Refer first to Faults 40 “Exciter internal SC” and 41
“Exciter external SC” if one those appeared.
• If the fault can be reset, check:
- wether there is an other converter system fault indicated. Trace those
first.
- with a single converter used (type x5E….) or if redundancy was losst
already with TWIN converter (type x5T…), wether all thyristor fuses in
the converter section are OK (normally indicated by fault 34 "Exciter
fault").
- the converter is dimensioned correctly or that no changes in load have
occurred [normally protected by limiters and overcurrent protection
(Alarm 106 "OC1 inverse time“, Fault 3 "OC2 inverse time“)].
- converter output connections are OK.
- the field circuit is OK (no short circuits).
• If the fault message is repeated several times, the (remaining) converter
may be overloaded.
• Check the the current actual value I EXC RELATIVE (10503), the
burden signal on PSI and also the connection between the PSI and the
COB boards (X12), if signal does’t correlate to the real excitation
current.
• Replace PSI, if burden signal not correct
• Check whether the setting of the parameter I EXCITER MAX VAL (402)
is correct.
• If the fault message is repeated, replace also the COB board.
Trouble Shooting
• In addition to the checks for alarm 106 "OC1 inverse time", the backup
system (second channel) must be checked as follows:
Single and Dual Channel CTRL type S5x-…: and D5x…-
- MANUAL mode was also not able to take over control. This means
that there is a possibly fault in the gate control unit.
- Check excitation current signal as per Fault 2
- Replace the COB board.
2 Channel CTRL type A5x…:
- Even the standby channel and/or its MANUAL control were not able to
take over control. This means that there is a fault in the gate control
unit of both channels or manual control of both channels have been
above permissible operation point.
- Check the manual CTRL (set point, operation point, etc).
- Replace the COB board
5 Loss of exc. Trip
Operator Information
This fault message occurred due to previous initiation of CH fault 14
„Loss of exc. Channel“, changeover to second channel (config. A5x…) or
back up controller EGC (config. D5x-… ) failed to take place within 2 sec.
Trouble Shooting
• -Ref. to Fault 14 instructions (in both channel for config. A5x…)
6 Trafo overtemp. Trip
Operator Information
The temperature of the excitation transformer has risen higher than the
maximum permitted value set by TRTEMP DEG FAULT in case PT100
temp. sensors, or determined by the 2nd stage PTC elements
temperature in case of PTC are used in the transformer windings.
Trouble Shooting
• If this fault occurs without Alarm 103 "Trafo temp. alarm“ having
responded beforehand, then this fault may have been caused by a bad
connection to the PTC temperature sensor (a broken connection will
cause a trip!).
• If both stages have responded, follow instructions for alarm 103 "Trafo
temp. alarm“.
Note:
The exciter and synchronous machine must be shut down to prevent
damage to the transformer. Report the problem to ABB.
Document number Lang. Rev. ind. Sheet
Trouble Shooting
• If the Fault and Alarm are triggered practically simultaneously (see entry
in Fault Logger), the measuring circuits for excitation voltage and
excitation current should be checked first.
• If there is a delay between the triggering of the fault and alarm
messages, for fault tracing follow Alarm 104 instructions.
12 Standby S5/D5 conf
Operator Information
The partner channel in a double channel system is not configured
correctly. Parameter 308 is set to either the values 0 (S5x) or 4 (D5x)
instead of 1 or 2 (A5x).
Trouble Shooting
• Set parameter 308 in the other channel to
1 if the other channel is channel 1
2 if the other channel is channel 2.
Note:
This fault will also occure if you prepare the system for maintenance work
in one channel. In order to block the defective channel, you will set
parameter 308 = 0 in the healthy, active channel. The inactive channel
will then by blocked and will display fault F12.
Trouble Shooting
• The system should be configured according to its function using
following parameters:
308 CH_CONFIG
401 MAX_CONV_TEMP
507 I_EXC_SENS_A
508 U_EXC_SENS_V
510 CONVERTER_TYPE
511 QUADR_TYP
(Default=1 for normal 2Q application)
CH CONFIG (308). Single Channel (S5…), Channel 1 (A5..CH1) or
Channel 2 (A5..CH2).
For a "software update", refer to the document update.doc on the
installation diskette.
Trouble Shooting
• Check the converter supply. At SHUNT supply configuration, this is
normally indicated by fault 23 "Loss conv. Supply".
• If this fault was the result of severe voltage drop at the generator
terminals caused by an external fault (e.g. line short circuit), then no
fault is to be expected within the excitation system. Change back to first
channel or restart the system following a trip.
• It is possible that the underexcitation limiter is too sluggish or the gain
and/or boundary values are set too low. Check the relevant parameter
settings of the underexcitation limiter (Group 15) and monitoring (Group
9).
• If the power supply is O.K., also check the gate control and converter in
accordance with the commissioning instructions (faulty converter
functions are normally indicated by fault 34 "Converter failed").
• In a 2 Channel system, changeover to the standby channel (second
channel) always has first priority. Check the relevant MUB transducer
function and output signals and the required signals
(I, P, Q, I SINPHI, I COSPHI) of Group 1 using the control panel or CMT
software, and compare them with those of the running (intact) channel
or Control Room instruments.
Trouble Shooting
• Usually, this fault occurs after a download of a new program. In this
case, the problem can be solved as follows:
Save the new parameters to Parameter Flash using the command
BACKUPSTOREMODE (11201). Activate the command SAVE
PARAM1 SET. During saving, the display on the control panel first
changes to 8 = ERASING..., then to 10 = PROGRAMMING and finally
to 0 = NONE.
• It is possible that the Flash PROM(s) are defective. Replace the COB
board.
Trouble Shooting
• Check the whole converter supply system from the source to the
converter input of the faulty channel.
• Check the excitation transformer and connections up to the converter
input for short circuit.
• Check the actual value of the converter supply voltage U SYN
RELATIVE (10503) and U SYN V (10504) and compare them with the
real voltage at the converter input. U SYN RELATIVE (10503) is 100 %
at the set parameter value U SYN V NOMINAL (504).
Note:
U SYN RELATIVE (10503) drops several per cent with increasing
excitation. This must be taken into consideration when setting the
margin DEV U MONITORING (907).
• Check the connection between PSI and COB or EGC boards (flat
cables X12).
Replace the PSI, COB or EGC board. If EGC is provided in a 2 Channel
CTRL configuration, USYN signal is buffered in on EGC and fed over
EGC X121 to COB X12
Trouble Shooting
• Check whether a generator short circuit occurred for longer than CMPD
MAX TIME (307).
• Check whether the compounding supply (batteries) is present.
• If the compounding effect is too great or too small, check the
compounding control circuit (external contactors etc.). Check the
compounding current at standstill by switching on the excitation.
Note:
Don’t use "TEST SUPPLY" from the auxiliary power circuit for this test,
nor simulate it.
• Check whether the parameters CMPD ON LEVEL (306),
CMPD MAX TIME (307) and SUPPLY MODE (901) have been set
correctly.
Trouble Shooting
• Check if field flashing supply (battery or AC line) is present and M.C.B.
–Q03 is closed.
• Check that the (AC or DC) field breaker is closed and that no de-
excitation command is in effective.
• Ensure that the field flashing current is sufficient to provide 5…10 V
supply voltage at converter input (setting of series resistor of the field
flashing module –A03).
• Check the field flashing circuit and the function of the field flashing
contactor.
• Check the measurement circuits for generator voltage from the voltage
transformer to the software and the synchronous voltage from the
converter input terminals to the software. Use a multimeter to check
whether the real measured values correspond with the software signals
U MACH RELATIVE (10101) and U SYN RELATIVE (10503).
• Ensure that the parameters FLASH OFF LEVEL (304), FLASH MAX
TIME (305) and SUPPLY MODE (901) are set correctly.
Note:
In a static excitation system, the field flashing circuit may only be
activated for one minute per hour. After six (10 second) unsuccessful
attempts to activate, a period of at least one hour must be paused
before field flashing is attempted again.
Trouble Shooting
• Check if there was (or is) a real overvoltage at the converter input.
• Check whether the displayed measured value U SYN RELATIVE
(10503) corresponds to the real converter input voltage. If not, check
setting of the parameter U SYN V NOMINAL (504).
• Check the hardware setting of the PSI board according to the "Test
Report"
• Check the EGC regarding the buffering of the USYN signal in a 2
Channel with back up CTRL configuration (Q5x-…). EGC input signal at
X12 must be the same as output signal at X121.
31 Not in synchronism
Operator Information
Although the converter supply is present, the gate control wasn’t line
synchronized any more.
Trouble Shooting
• If fault 23 "Loss conv. Supply" occurs with shunt supply configuration,
one phase (U or V) of the synchronous voltage is missing.
• Hardware fault on the COB board. The NMI signal for the CPU is
missing.
• Check the connection between the PSI and COB (flat cable X12). If the
fault occurs again, replace the PSI or COB type UNS2880 board. This
signal is fed via EGC in 2 Channel with back up CTRL configuration
(Q5x-…). EGC input signal at X12 must be the same as output signal at
X121.
32 D/O driver fault: X1
Operator Information
The relay driver on COB for the basic FIO connected to X1 is defective.
Trouble Shooting
• Check the connection between COB X1 and FIO X31 (flat cables)
regarding SC.
• If Fault can be reset after unplugging X1, replace basic FIO board
(U70).
• If Fault can’t be reset after unplugging X1, the driver itself is broken and
therefore COB board must be replaced.
Trouble Shooting
• If Alarm 180 “Thyristor fuse fail” was also logged, trace the fault as per
Alarm 180 instructions.
• Check the phase sequence of the converter supply and that the
parameter PHASE SEQ CW (503) is set correctly. Check that the input
[SEL SEQUENCE] (5501) corresponds to the actual phase sequence.
• Check that all thyristors are fired correctly by checking converter output
voltage with an oscilloscope. There should be 6 pulses of same shape
during a supply voltage cycle (20/16.66ms; 50/60Hz).
• Check the gate connections between Gate Driver GDI and thyristor
itself.
• Check that the measured value U SYN V (10504) displayed on the
control unit corresponds to the real voltage at the converter input. If the
displayed value is lower, it is possible that a phase is missing. Check the
connections from COB X12 up to the PSI. In a shunt supply
configuration, this failure is indicated as Fault 23 "Loss conv. supply".
• Check branch fuses (type C3 having no fuse indicators)
• Measure the gate-cathode resistance of all thyristors (with an
ohmmeter). Compare these results and if one resistance value is clearly
higher than the others, exchange this thyristor as per specific converter
instructions
• If no thyristor fault can be found and the fault cannot be reset, also
check the connections between the current transformers and the PSI
board and between the PSI and COB (ev. via EGC) board. The ripple
voltage across the burden resistor must be less than 90 mVpp (<6 %
set system rated current I EXC SENS A (507)).
Replace current transformers (C.T.), PSI or COB board.
Trouble Shooting
• Negative field overvoltage occurs if an interruption occurs in the power
supply or field circuit (e.g. fuses, circuit breakers)
Check:
- the function of the field breaker at the input or output of the converter
- connection line and insulation resistance of the field winding
• Positive field overvoltage is usually caused by a generator fault, which
induces negative field current, as pole slip, short circuit at the generator
terminals etc.
Check whether there is (or has been) a problem with the generator. If
no such situation exists, report the problem to ABB.
36 D/O driver fault: X3
Operator Information
The relay driver on COB for the extended FIO connected to X3 is
defective.
Trouble Shooting
• Check the connection between COB X3 and FIO (No. 2) X31 (flat
cables) regarding SC.
• If Fault can be reset after unplugging X3, replace extended FIO board
(U71).
• If Fault can’t be reset after unplugging X3, the driver itself is broken and
therefore COB board must be replaced.
40 Exciter internal SC
Operator Information
This message comes from COB located EXCITER MONITORING, which
monitors for a single running converter (x5E… or x5T… configuration) or
if only one is left from x5S… configuration.
Trouble Shooting
• If Alarm 180 “Thyristor fuse fail” was also logged, trace the fault as per
Alarm 180 instructions.
• Check branch fuses (type C3 having no fuse indicators)
• Exchange faulty thyristor(s) as per specific converter instructions.
Trouble Shooting
• Trace for an external short circuit fault between converter otput and field
windings
43 Converter failure
Operator Information
Converter redundancy was lost completely and therefore the excitation
system was shut down. This fault message is always the result onto
previous converter alarm message(s).
Trouble Shooting
• Follow the trouble shooting instructions of the previous indicated fault
and alarm messages.
45 MUB data fault
Operator Information
The analog to digital data convertion on the MUB board has failed. The
board has to be replaced as soon as possible.
Trouble Shooting
• Reinitialize the MUB board (UNS 2881) by disconnecting and
reconnecting the power supply. Pull directly the connector block X1 on
the MUB board.
• The board may restart but will most likely fail again. Replace and return
for repair as soon as possible.
.
Trouble Shooting
• If everything else is O.K., it is possible that the safety margin or delay
time were set too restrictively.
• A voltage transformer failure was not detected correctly.
Note:
In MANUAL mode, the V/Hz limiter is blocked when ON LINE.
Trouble Shooting
• Check the protected components (converter) for overload, short circuits
etc. with reference to the hardware diagrams.
50 Crowbar failure
Operator Information
The monitor has at least 2 negative crowbar current pulses detected (the
1st current pulse released the Alarm 140 “Loss of synchronism”), although
the machine main breaker was tripped by the 1st. pulse. I.e. the converter
supplied current to the faulty crowbar.
Trouble Shooting
• Check the crowbar thyristor for negative current (positive overvoltage)
e.g. –V1 of UNS4016 or UNS4023, with reference to the hardware
diagrams.
• Replace the faulty thyristor according crowbar instructions
Trouble Shooting
• Check the isolating resistance step by step from the field windings up to
the transformer secondary windings. Use a megger for this tests.
• Check the Ground Fault relay and it’s performance according separate
relay instructions.
53 TRIP by EGC
Operator Information
The Extended Gate Controller (EGC) has shut down the system (LED
“TRIP” on EGC ON) because:
When the EGC is active (and COB Fault logger is still alive):
1. The converter transfer because of an converter “branch S.C.” or
“branch not conducting” fault (on of the EGC LED’s BRANCH FAIL
R+…T- ON) in a x5T… configuration was not successful.
2. A “branch not conducting” fault (on of the EGC LED’s BRANCH FAIL
R+…T- ON) occurred in a single converter configuration (or no
converter redundancy anymore).
3. There is a converter output short circuit fault.
Trouble Shooting
• Check the system as per Faults 2, 3, 34, 40, 41
54 MUB fault/power fail
Operator Information
“Watch Dog” or power supply monitor of the MUB board responded.
Trouble Shooting
• Replace MUB board.
Trouble Shooting
• Check the ARCnet T-connector on X61 of COB boards (UNS 2880)
• Check whether both coaxial cables are correctly fit to the T-connector
• Check the 7 segment display for the ARCnet status (see also section
8.3.5.1)
• Check the node addresses on the COB boards (UNS 2880). Channel 1
must be set to 1 (dez) and channel 2 to 2 (dez). For further information,
see also section 4 of this manual.
• Chck whether there is a termination element connected to both ends of
the ARCnet cable (normally one end is the LCP, the other end is the
last CIN board)
• Replace COB board (UNS 2880)
60 Fieldbus timeout
Operator Information
Transmission between COB and the bus adapter module is disturbed.
This fault is only generated when parameter FLDBFAULT MODE (917) is
set to CHANNEL FAULT or EXCITATION TRIP. The number of bad
messages before fault raising, is given by parameter 4007.
Trouble Shooting
• Ref to Alarm 122 instructions
Trouble Shooting
• Check if the transformer was overloaded for a long time.
• Check transformer cooling and the ambient temperature around the
transformer. If the transformer is overheating despite normal
environmental conditions, the transformer may be incorrectly
dimensioned. An internal fault could also be the cause. Keep an eye on
the transformer temperature.
• Check transformer temperature. If the transformer temperature is not as
high as the alarm temperature, check the function of the PTC and
temperature relay UNS 0006. Detect overtemperature. This fault has to
be reset on the UNS 0006 itself.
• Check the wiring from the UNS 0006 to the PTC (a broken connection
will cause an alarm!).
104 Rotor temp. Alarm
Operator Information
UNITROL 5000 monitors the rotor temperature, which is calculated from
the excitation current, excitation voltage and the resulting field resistance.
Alarm is triggered if this value exceeds the set temp.
RTEMP_DEG_ALARM (1009).
Note:
If SEL_RTM_MODE (1001) is set to ON/ALARM, there is only a new alarm
issued instead of a TRIP, when the 2nd level set by RTEMP_DEG_FAULT
(1010) is exceeded.
Trouble Shooting
• Check whether the rotor has been overloaded for a long time and
whether the rotor cooling system is working properly.
Trouble Shooting
• Single Channel system type S5x-...:
If the system remains stable in MANUAL operation, no fault is to be
expected from the gate control (thyristor firing). Try to switch back to
AUTO mode.
• Two-channel system:
• Changeover to the standby channel takes place first. If it is not possible
to switch back because the automatic follow-up control cannot follow (no
"Ready for transfer" RDY XFER TWIN (12120) or if the same faults
occur again, the fault could lie in the gate control or in the measurement
of the excitation current (section I EXC). Check the relevant channel at
the next shutdown.
Note: The standby channel receives I EXC signals from the active
channel.
• It is possible that the excitation current limiter is too sluggish or the gain
and/or boundary values are set too low. Check the relevant parameter
settings of the excitation current limiter (group 13, 19) and monitoring
(group 9).
107 CH transfer failed
Operator Information
The operating modes AUTO, MANUAL, excitation ON/OFF, superimposed
regulator ON/OFF and their pre-selection (COS PHI or Q-controller) are
the same for both channels and only one channel may be active.
Trouble Shooting
• Try restarting both channels at the same time.
• Notify ABB service if the fault occurs repeatedly.
Trouble Shooting
• The RAM supply capacitor is empty (after long storage or standstill
period without COB supply). The board must be supplied for at least ½
hour to get enough RAM supply voltage.
• Shut down the whole excitation system and try to restart it.
• If the fault is repeated, replace the COB type UNS2880 board.
110 System restart
Operator Information
This is simply a display which appears following a cold start-up, but it is
stored in the fault logger.
111 Common STBY fault
Operator Information
The active channel has received the common CH FAIL (10342) signal
from the standby channel. This causes switchover to this channel, if the
necessary conditions are fulfilled (see Alarm 109).
Trouble Shooting
• Connect the control panel (or CMT) with the standby channel, which is
now the active channel, and read the entries in the fault logger.
• See also alarm 109.
113 STBY ARCnet fault
Operator Information
Data transmission to the other channel via ARCnet has failed. Emergency
changeover caused by a CH FAIL is still possible via the hardwire
connection (TCHFN), as is changeover to MANUAL mode.
Trouble Shooting
• Check the ARCnet T-connector on X61 of COB boards (UNS 2880)
• Check whether both coaxial cables are correctly fit to the T-connector
• Check the 7 segment display for the ARCnet status (see also section
8.3.5.1)
• Check the node addresses on the COB boards (UNS 2880). Channel 1
must be set to 1 (dez) and channel 2 to 2 (dez). For further information,
see also section 4 of this manual.
• Chck whether there is a termination element connected to both ends of
the ARCnet cable (normally one end is the LCP, the other end is the last
CIN board)
• Replace COB board (UNS 2880) of the other channel
Trouble Shooting
• Select the standby channel on the control panel or connect to PC (CMT
software). Read the entries in the fault logger.
Note: To avoid this alarm during short circuit tests of the machine, set
parameter 915 to 0.
Trouble Shooting
• Check the voltages from the P.T. (generator terminal voltage) to the
software signal U MACH RELATIVE (10201) according to the hardware
diagrams. If everything is O.K., the setting of the dynamic P.T. failure
monitor may be too sensitive. Check the settings in accordance with the
instructions in the parameter list and commissioning instructions.
• Compare the measured values with values from other instruments
• Check the signal scaling of the machine voltage U MACH RELATIVE
(10201): This must be 100 % of the rated voltage.
• Check the ribbon cable connection from X31 on the MUB board
(UNS 2881) to X31 on the COB board (UNS 2880).
Trouble Shooting
• Check connection with the bus adapter.
• Replace the cable.
• Replace the bus adapter.
• Replace the COB type UNS2880 board.
Trouble Shooting
• Check all analog inputs to see, whether there is a broken connection.
• Check the programming and burden resistors of the analog inputs on the
FIO (UNS 0883 board), are the 0 Ohm burden resistors cut out
correctly?
• Check the ribbon cable connection –W131 and –W132 from the first FIO
to the COB boards of both channels:
–U70:X31 to –A10-A1:X1 and
–U70:X32 to –A20-A1:X1
• Replace the first FIO board (UNS 0883) and the COB boards
(UNS 2880) if required.
124 Exciter failed
Operator Information
Converter type C1 ...C3
Interruption in a thyristor branch. This can also be the result of a short
circuit which was switched off by the fuses. Depending on the design, the
system can continue operation, possibly with reduced current.
Trouble Shooting
• The signal BRANCH NO (10515) indicates the defective branch. The
branch must be repaired at the next shutdown. See fault 34 for further
checks.
Trouble Shooting
• If the field breaker did not close, check the wiring of the field breaker
control circuit according to the hardware diagrams.
• Check whether the coils of the field breaker (Q02) are damaged.
• If the field breaker did close, check the wiring of the feedback circuit of
the field breaker according to the hardware diagrams.
• Check whether the signal is correctly received by the binary input card
FIO (UNS 0883). Each activated input lits the corresponding green LED.
• Check the ribbon cable connections –W141, -W142 between the FIO
board (UNS 0883) and the COB boards (UNS 2880):
–U70:X41 to –A10-A1:X2 and
–U70:X42 to –A20-A1:X2
Trouble Shooting
• Check connection between the control panel UNS 0874 and the COB
type UNS2880 board (flat cable X34).
• Replace control panel UNS 0874 or the COB type UNS2880 board.
130 Init values read, S2
Operator Information
During start-up (start of the system program), the default values were read
from the FPROM as a result of the hardware setting (jumper S2 on the
COB type UNS2880 board). This means that all the parameters have
been set to their initial values, and the customer-specific user parameters
are no longer effective.
Trouble Shooting
• If the initial values were downloaded intentionally, this alarm can be
ignored (don’t forget to reset the jumper (S2).
• If you did not wish to read the initial values, check the setting of the
jumper on the COB type UNS2880. For normal start-up (reading of user-
specific parameters), the jumper must be in the position 3-4 (right-hand
side). Shut down the UNITROL F system, fit the jumper in the correct
position and start up again.
• If the fault is still present, replace the COB type UNS2880 board.
Trouble Shooting
• If it was your intention to use the second parameter set, check the
setting of the parameter PARAMETER SET2 (5326) and the signal
BACKUPSTOREMODE (11201).
• Save the settings of the parameters selected as the second parameter
set by setting the signal BACKUPSTOREMODE (11201) to 2 = SAVE
PARAM2 SET
Trouble Shooting
• The field breaker must be open in order to load a parameter set.
135 Crowbar failed
Operator Information
Only with static field discharge circuit (without discharge contact):
There was no current feedback signal from the crowbar during field
discharge.
Trouble Shooting
• Check crowbar current sensor up to firmware input ID>0 (5908) in case
of external current monitor, or the crowbar current signal I_CB_A
(10929) in case the CUS current sensor is used (the latter is the
standard UN5000 application).
• Check whether the crowbar is flashed correctly in the event of a field
breaker trip command.
Trouble Shooting
• Try to save the parameters again. If the alarm is repeated, the COB type
UNS2880 board must be replaced.
137 Standby trip
Operator Information
In a 2 channel system, a trip EXC_TRIP (10350) of some kind has
occurred in the standby channel. This event (137) is only logged as an
ALARM in the fault logger for this channel.
Trouble Shooting
• Select the standby channel with the control panel or connect to the PC
(CMT software) and read the entries in the fault logger.
138 Init values read
Operator Information
As a result of action by the operator (jumper on COB, CMT software or
control panel), the DEFAULT values are read into the system from the
program FPROM. This means that all the parameters are set to their initial
values and the customer-specific user parameters are no longer effective.
The default values were read into the system either following the user
command BACKUPSTOREMODE (11201) or following a download
(Note: RAM and FPROM parameter versions are not necessarily the
same).
Trouble Shooting
• If it was your intention to read the initial values, this alarm can be
ignored. It will be reset by the next BACKUPSTOREMODE (11201).
Trouble Shooting
• If the cause is assumed to be from excitation system, check
underexcitation limiter and loss of excitation monitor.
141 Aux. AC fail
Operator Information
One of the two redundant 24V power supplies to the control electronics
has failed. The system remains in operation and is supplied from the
backup battery. However, the redundancy is lost and this problem should
be solved as soon as possible.
Trouble Shooting
• Visual checks:
power supply unit –G05: is the green LED on?
circuit breaker –Q05 closed?
fuses –F15 O.K.?
• Check the AC input voltage on the power supply –G05, terminals (3,2).
• If necessary replace power pack –G05
Note:
With shunt excitation, this alarm is only released at EXCITATION ON.
142 Auxiliaries OFF
Operator Information
This alarm indicates that the miniature circuit breaker for one of the
auxiliary supplies is off.
Trouble Shooting
• Check all ciruit breakers in panel +ER.
• If the alarm is still present, check the wiring of this alarm circuit
according to the hardware diagram.
Note:
Alarm 142 is generated from input DI 14 on the FIO device (UNS 0883).
In normal condition , the input must be on 24V level. A 0V signal is
interpreted as alarm condition.
Trouble Shooting
• Check whether the trip was issued by the generator protection system.
• Is the breaker equipped with an automatic overcurrent release? Is the
setting of the overcurrent release correct?
• Was the breaker opened manually by pushing the push-buttons on the
breaker itself?
• Check the auxiliary contacts of the breaker.
Trouble Shooting
• Visual checks:
power supply unit –G15: is the green LED on?
circuit breaker –Q15 closed?
• Check the DC input voltage:
on the power supply –G15, terminals (3,2)
on the input terminals to the excitation system (see sheet 900 of the
drawing set)
• If necessary replace power pack –G15.
145 Test Supply
Operator Information
The excitation system with a shunt supply system was switched over to
auxiliary supply. The reference value for MANUAL mode is set to the
second preset value PRESET2 REF MAN (2108).
Trouble Shooting
• Switch over to normal mode = shunt supply
• Check the setting of the parameter SUPPLY MODE (901).
Note:
For safety reasons, the field breaker is automatically opened when
switching over and with indirect excitation.
Trouble Shooting
• Check the above mentioned components
• If the alarm is still present, check the wiring of this alarm circuit
according to the hardware diagram.
Note:
Alarm 146 is generated from input DI 10 on the FIO device (UNS 0883).
In normal condition , the input must be on 24V level. A 0V signal is
interpreted as alarm condition.
147 LCP node fail
Operator Information
There is no answer from Local Control Panel (LPC) ARCnet node (AF
C094)
Trouble Shooting
• At commissioning check/set up the LCP node address to 10 decimal
• Check the LCP coaxial connector
• Check the LCP supply (display remains dark after operating of any
button and there is not any button LED ON)
• Replace LCP (Note: this must be loaded with the right alarm text library.
If no or mismatch alarm text is displayed, call for ABB service)
Trouble Shooting
• At commissioning check/set up the FBC No.1…4 node address to
33…36 decimal of the FBC’s (provided)
• Check all FBC’s coaxial connector
• Check all FBC’s supply
• Replace faulty FBC(s) (or possibly RIO, DIO if fault disappears after
disconnecting them from FBC)
149 AIO node fail
Operator Information
There is no answer from any provided analog Field Bus Coupler (AIO)
ARCnet node (UA C096)
Trouble Shooting
• Ref to 3.6.1 for ARCnet status indications by 7 segment display
• At commissioning check/set up the AIO No. 1/2 node address to 17/18
decimal of the AIO’s (provided)
• Check all AIO(s) coaxial connector
• Check all AIO(s) supply (7 segment display is dark)
• Replace faulty AIO(s)
152 Rotor ground fault
Operator Information
The separate Rotor Ground Fault Relay level 1 has responded. The
system continues to remain in operation, but this problem should be
solved as soon as possible in order to keep the insulation damages low.
Trouble Shooting
• At next stand still, check the isolating resistance step by step from the
field windings up to the transformer secondary windings. Use a megger
for this tests.
• Check the Ground Fault relay and it’s performance according separate
relay instructions.
Trouble Shooting
• In a double channel with back up configuration Q5X-…, use this channel
for operation to keep the EGC back up function in case of a later
emergency channel transfer to the channel with the healthy EGC.
• Replace the EGC board at next standstill.
• Under certain circumstances, it’s also possible to replace the EGC in
operation. Follow separate instructions.
155 CH ARCnet fault
Operator Information
Data transmission to the CIN boards and to the other channel in a double
channel system has failed.
Trouble Shooting
• Check the ARCnet T-connector on X61 of COB boards (UNS 2880)
• Check whether both coaxial cables are correctly fit to the T-connector
• Check the 7 segment display for the ARCnet status (see also section
8.3.5.1)
• Check the node addresses on the COB boards (UNS 2880). Channel 1
must be set to 1 (dez) and channel 2 to 2 (dez). For further information,
see also section 4 of this manual.
• Chck whether there is a termination element connected to both ends of
the ARCnet cable (normally one end is the LCP, the other end is the last
CIN board)
• Replace COB board (UNS 2880)
Trouble Shooting
• Follow the instructions of the Alarm (Alarm 178…196) with the same
time stamp.
Trouble Shooting
• In cold standby converter schema x5T…, use the converter with the
healthy temperature monitoring. Toggle converter, by applying a pulse to
firmware input signal CHANGE CONV (5403), if the alarm is from the
running converter and the other has no alarm.
• Check, replace temperature sensor at next standstill or at isolated
converter.
• Replace CIN board at next standstill or at isolated converter following
separate instructions.
• Under certain circumstances, it’s possible to replace the CIN board
during system operation following separate instructions
179 Curr. Equal. Fail
Operator Information
The automatic converter current equalizing controller of a x5S…
configuration has reached its setting limit. I.e. fully current equalizing of at
least one branch is not longer possible by any reason. This entered to the
Fault logger as an Event only.
Possible reasons:
- Thyristor changed its characteristic
- Branch fuse overheated
- Poor contact (thyristor surface, fuse connection, bar connections)
- Bad positioning of the current sensors CUS (UNS0884)
Trouble Shooting
• To find the branch which causes the problem, read the “relative firing
delay” of each branch from signal CONVn_SEL_ACT (1051n3) where
n = No. of converter pointed, after selecting one by one branch (R+….T-)
by parameter SEL_ACT_CONV(n) (520). Use manual ctrl to get stable
excitation current. The results are indicated in µs. Compare the values to
each other. The branch with the longest delay has to be checked and
faulty elements have to be replaced at next stop (thyristor, fuse,
connection points)
• Check the feedback signals of the CUS at blocked converter while the
others are running. The signal should be as small as possible (<1% of
total current).
Trouble Shooting
• x5S… configuration:
The branch No.(s) is indicated by further alarm message(s) 181…186.
X5E… and x5T… configurations:
Only one branch No. can be displayed by COB’s “Ripple Monitor”. Check
also the other branches of the faulty half bridge.
• Check and replace faulty thyristors
• Check and replace blown fuses
• Check converter current equalizing control after next start
Trouble Shooting
• Refer also to CH Fault No. 34 regarding Fault RESET for x5S… and
x5T… configurations.
• If there is no internal or external short circuit expected (fuse not blown):
Check at running converter the thyristor gate current using an isolating
current probe.
Note: there is converter supply voltage level at the GDI outputs as long
the gate lines are connected.
• If no gate current measured check the GDI output voltage after
unplugging the gate line, to distinguish between faults on thyristor or
CIN, GDI side.
• If no GDI output voltage measured, replace GDI and/or CIN following
extra instructions
• If GDI output voltage present, check thyristor gate connection, or replace
thyristor following extra instructions (only possible at stand still or with
isolated converter)
• If fuse blown: Check thyristor and replace fuse and faulty thyristor of this
branch following extra instructions. Check the thyristors of the other half
bridge branches too, regarding blocking voltages.
(only possible at stand still or with isolated converter)
• In case of external short circuit, trace the reason and rectify the problem
Trouble Shooting
• In cold standby converter schema x5T…, use the cold standby
converter. Toggle converter, by applying a pulse to firmware input signal
CHANGE CONV (5403), if the alarm is from the running converter and
the other has no alarm.
• Check the cooling system. Most probably the inlet air filters need to be
cleaned up, or the airflow is restricted by other reason.
• If the ambient temperature is above specified max., reduce excitation
current
• If the converter current is equal to the currents of other (x5S… config.)
but they have no alarm, check temperature measurement and rectify
problem according Alarm 178
188 Overtemp. Trip
Operator Information
The actions following Alarm 187 “Overtemp. Alarm” have not been
successful and temperature rose at least by another 10K and exceeding
the maximum temperature, determined by parameter MAX CONV TEMP
(401).
Action: Converter blocked (x5S) or transferred (x5T). Counted for Alarm
197, 198 “CONV fail level 1, 2” and Fault 43 “Converter fault”.
Trouble Shooting
• Follow Alarm 187 instructions
Trouble Shooting
• In cold standby converter schema x5T…, use the cold standby converter
to have the full cooling redundancy again. Toggle converter, by applying
a pulse to firmware input signal CHANGE CONV (5403) if the alarm is
from the running converter and the other has no alarm.
• Check whether the fans(s) have been overloaded by airflow restriction.
Clean, replace filters if necessary.
• Replace the faulty fan(s) at next standstill (extra instructions)
• The fan box (UNL133…) can also be pulled out during system operation,
if the converter can be isolated, or if it’s well protected at open door (at
least IP 10)
• After rectifying the problem, this alarm must be RESET
• After replacing a fan, reset also the relevant “fan operating hour counter”
to zero. See Parameters 522…524
190 Cooling Trip
Operator Information
The cooling of a converter has been lost completely (single fan, no
redundancy available any more).
Possible reasons: see Alarm 189
Action: Converter blocked (x5S) or transferred (x5T). Counted for Alarm
197, 198 “CONV fail level 1, 2” and Fault 43 “Converter fault”.
Trouble Shooting
• As per Alarm 189 instructions.
Trouble Shooting
• Check CUS signals on CIN test points TP 601 (CUS +) or TP 602
(CUS+) to GND (2mV/A). If signal O.K. replace CIN board and if signal
not O.K. check, replace CUS and/or it’s connection cable at next
standstill.
Note: CUS and it’s connecting cable can normally only replaced after
removing cabinet back panel, or after removing the converter itself (ref.
to extra instructions).
192 Snubber failure
Operator Information
The combined Snubber’s line fuse(s) are blown or the fuse link is open
(e.g. UNL133… converter).
Note: This Fault is independent counted from other converter faults (no
converter blocking).
Action: Counted for Alarm 197, 198 “CONV fail level 1, 2” and Fault 43
“Converter fault”.
Possible reasons:
- Short circuit in rectifier, capacitor, resistor or it’s connections.
Trouble Shooting
• The snubber is not in the save area. I.e. there is also no access after
opening of a provided converter isolator!
• Check the snubber components and connections regarding short circuit
and replace them at next standstill.
• Replace the blown fuse(s)
Trouble Shooting
• Check pulse cable connector X13
• Replace CIN according extra instructions. Under certain circumstances,
the board can also be replaced during system operation.
Note: CUS scaling parameters are individual saved in CIN’s FLASH prom.
Therefore use the FLASH from the former board, or CUS sensing
must be tuned at next standstill.
194 CONV isolated
Operator Information
The converter isolator has been opened.
Action: Converter blocked (x5S) or transferred (x5T). Counted for Alarm
197, 198 “CONV fail level 1, 2” and Fault 43 “Converter fault”.
Trouble Shooting
• After closing of the converter isolator, this Alarm is reset
195 ARCnet node fail
Operator Information
There is no ARCnet communication to the pointed CIN board.
Possible reasons:
- ARCnet connector X61 on CIN board disconnected
- CIN ARCnet controller failed.
Actions:
x5E/T.. nur Alarm
x5S.. Converter blocked and therefore indirectly counted for Alarm 197,
198 “CONV fail level 1, 2” and Fault 43 “Converter fault” via Alarm
193 “CIN failure”, or CONV x P BLKD signal
Trouble Shooting
• Check ARCnet connector X61 on pointed CIN board
• Replace CIN as per Alarm 193
Trouble Shooting
• Follow the instructions of the other Alarm messages.
• RESET after first power up, e.g. after replacing a CIN Board
197 CONV fail level 1
Operator Information
The sum of the same kind of converter faults has reached the level set by
parameter SET FAIL LEVEL 1 (928).
Same kind of converter faults could be:
- Alarm 181…186 “Branch xx failure” (each branch No. is summed
separately)
- Alarm 188 “Overtemp Trip”
- Alarm 190 “Cooling Trip”
- Alarm 193 “CIN failure”
- Alarm 196 “Converter blocked”
- Alarm 199 “Converter isolated”
Action: In Default version not used. Ref. to application software regarding
signal 10925 connection.
Trouble Shooting
• Follow the instructions of the previous displayed converter Alarm
messages.
Trouble Shooting
• Follow the instructions of the previous displayed converter Alarm
messages.
21x User Event 1 … 6
22x Operator Information
23x There are 6 USER EVENT blocks, which are only used by application
24x programming. The task of this blocks are documented in the application
software diagram.
25x Each block has a TYPE parameter, which determines the action after the
26x input is TRUE for longer than the set delay (parameter DLY). The setting
of the TYPE parameter determines also the last digit (x) of the Fault No.
as follows:
TYPE: x ACTION
EXCITATION TRIP 1 Emergency excitation stop command
CHANNEL FAULT 2 Channel transfer at A5x… configurations
Transfer to back up control at D5x…
configuration
AVR FAULT 3 A5x..: channel transfer if Standby o.k.
transfer to Manual CTRL if no Standby available.
ALARM 4 Only a common Alarm message is given
EVENT 5 Only an entry to the Fault logger is made
Trouble Shooting
• Ref. to the application software diagram for the function of the USER
EVENT block(s) and trace the Fault regarding the given information
there.