NTH Consultants, Ltd. (NTH) was retained by 6556 McNichols LLC to provide
environmental consulting services related to removal of three underground storage tanks
(USTs) from the 6556 East McNichols Road property in Detroit, Michigan.
NTH completed a Phase I Environmental Site Assessment (ESA) for the property, dated
January 5, 2018. The Phase I ESA identified three USTs under the canopy area near the
southwest corner of the building. Review of the UST Facility File obtained from the
Michigan Department of Licensing and Regulatory Affairs (LARA) indicated that the USTs
were each 1,000 gallons in capacity and were installed in 1957. The USTs were reported to
contain cutting oil, lubrication oil and waste oil, and remained in use until the early 1990s.
Prior to removal, the USTs were gauged and each contained approximately two feet of liquid.
The approximate locations of the USTs are indicated on Figure 1 in Appendix A. A site
showing the property layout is included as Figure 2 in Appendix A.
On April 23, 2018, NTH submitted an Intent of Removal form for the USTs to the LARA.
The Intent of Removal form also registered 6556 McNichols LLC as the new owner of the
USTs. LARA responded by email on April 24, 2018, approving the tank removal activities to
commence after May 24, 2018. Copies of the Intent of Removal form and LARA response
are included in Appendix B.
On May 29, 2018, NTH visited the site to observe HM remove the USTs. The USTs were of
single-wall steel construction. Prior to excavation, HM used a vacuum truck to remove
residual liquid from the USTs. Once the USTs were exposed, HM created an opening in the
top of each UST. Oily sludge remaining in the bottom of each UST was placed into drums.
The UST interiors were then cleaned using water spray. HM used an excavator to remove the
USTs from the ground. Multiple corrosion holes were visible in the bottom of each UST.
Stained soil with petroleum odors was observed in the excavation.
Approximately 800 gallons of liquid were removed and transported to Environmental Geo-
Technologies LLC of Romulus, Michigan for disposal. Copies of the disposal manifests are
included in Appendix C. The USTs were transported to McNichols Scrap Iron and Metal
Company upon removal.
Prior to backfilling, three floor samples were collected, one from beneath each fill port as
depicted on Figure 1. These samples were not analyzed as the analysis was not expected to
yield additional relevant data based on the known contents of the USTs and results of
previous Phase II ESA. The UST excavation was backfilled with excavated soil followed by
a layer of crushed stone.
Based on visual and olfactory evidence observed during the UST removals, a release to the
environment was evident. As such, NTH submitted a Confirmed Release Report to LARA.
The report was submitted at 11:19 am on May 30, 2018. LARA assigned confirmed release
number C-0087-18. A copy of the Release Report is included in Appendix B.
LEGEND
1
DESIGNED BY: PLOT DATE:
NTH Consultants, Ltd.
DRAWN BY: DRAWING SCALE: Infrastructure Engineering
and Environmental Services 6556 E MCNICHOLS RD
CHECKED BY: INCEPTION DATE:
DETROIT, MICHIGAN
McNICHOLS ROAD (6 MILE ROAD)
N
GIRARDIN STREET
LEGEND
2
DESIGNED BY: PLOT DATE:
NTH Consultants, Ltd.
DRAWN BY: DRAWING SCALE: Infrastructure Engineering
and Environmental Services 6556 E. McNICHOLS ROAD
CHECKED BY: INCEPTION DATE:
DETROIT, MICHIGAN
APPENDIX B
// REGULATORY DOCUMENTS
Department of Licensing and Regulatory Affairs, Bureau of Fire Services, Storage Tank Division
P.O. Box 30033, Lansing, MI 48909
Phone 517-241-8847, Fax 517-332-1428
THIS INFORMATION IS REQUIRED UNDER 1994 PA 451, AS AMENDED (Act 451). FACILITY ID NUMBER ENTRY DATE
FAILURE TO COMPLY WITH THE PROVISIONS OF THIS ACT MAY RESULT IN A
MISDEMEANOR AND/OR CIVIL PENALTIES NOT TO EXCEED $5000 PER DAY, PER
TANK.
INSTRUCTIONS: This form applies to releases of petroleum and hazardous UPGRADE/CANCEL DATE INCIDENT NUMBER
substances from underground storage tanks regulated under Part 211,
Underground Storage Tanks, of the Natural Resources and Environmental DATE REPORTED TIME REPORTED
Protection Act, 1994 PA 451, as amended (PA 451).
AM PM
The owner or operator must report suspected and confirmed releases to the Bureau of
REPORTED BY: FAX E-MAIL REGULAR MAIL
Fire Services (BFS) within 24 hours of discovery. The report may be made by a
consultant on behalf of the owner/operator. FAX this form to 517-332-1428 or call
517-335-7210. All information on this form must be provided regardless of whether the
release is reported by telephone or FAX. For further information see page 2.
Signature
PERSON REPORTING RELEASE COMPANY (IF NOT OWNER/OPERATOR) AREA CODE & TELEPHONE NUMBER
Ashley Lesser NTH Consultants, Ltd. (248) 553-6300
TANK REMOVAL CONTRACTOR CONTRACTOR CONTACT CONTRACTOR AREA CODE & TELEPHONE NUMBER
HM Environmental Services Inc. Bob Borst (586) 469-0041
I. OWNERSHIP OF TANKS II. LOCATION OF TANKS
NAME OF OWNER (CORPORATION, INDIVIDUAL, ETC.) FACILITY NAME OR COMPANY SITE IDENTIFIER
6556 McNichols LLC 6556 McNichols Site
STREET ADDRESS STREET ADDRESS (P.O. Box Not Acceptable)
1437 Woodward Avenue, Apt. 414 6556 E. McNichols Road
CITY STATE ZIP CODE CITY COUNTY STATE ZIP CODE
Detroit MI 48226 Detroit Wayne MI 48212
AREA CODE & TELEPHONE NUMBER AREA CODE & TELEPHONE NUMBER
(248) 770-5097 N/A (unoccupied site)
DATE RELEASE DISCOVERED: May 29, 2018 CONTACT PERSON FOR LOCATION
TIME RELEASE DISCOVERED: 12:10 AM PM Cort Kwiecinski
TANK NUMBER1 (if known) 1 / UTK-042218-15 2 / UTK-055115-15 3 / UTK-055118-15
SIZE OF TANK (gallons) 1,000 1,000 1,000
SUBSTANCE RELEASED Used Oil Used Oil Used Oil
CONSTRUCTION OF TANK Steel Steel Steel
REASON FOR RELEASE Corrosion of tank Corrosion of tank Corrosion of tank
HOW WAS LEAK Tank Removal Tank Removal Tank Removal Tank Removal Tank Removal
DETECTED Inventory Records Inventory Records Inventory Records Inventory Records Inventory Records
(Check all that apply) Repairs Repairs Repairs Repairs Repairs
Stained Soil Stained Soil Stained Soil Stained Soil Stained Soil
Petroleum Odors Petroleum Odors Petroleum Odors Petroleum Odors Petroleum Odors
Analytical Data Analytical Data Analytical Data Analytical Data Analytical Data
Free Product and/or Free Product and/or Oil Free Product and/or Oil Free Product and/or Oil Free Product and/or Oil
Oil Sheen in Sheen in Groundwater Sheen in Groundwater Sheen in Groundwater Sheen in Groundwater
Groundwater
COMMENTS (attach additional sheets if necessary): Facility ID: 00019920. Corrosion holes were noted on all 3 USTs.
1
Copy this page for additional tanks if needed. Page 1 of 2 BFS-3826 (Rev 12/17)
Department of Licensing and Regulatory Affairs, Bureau of Fire Services, Storage Tank Division
REGISTRATION OF UNDERGROUND STORAGE TANKS
The information in this form is required under “Part 211, Underground Storage Tank Regulations, of the Natural Resources and Environmental Protection Act,
1994 PA 451, as amended.” Any owner who knowingly fails to notify or submits false information shall be subject to a misdemeanor and/or civil penalties not
to exceed $5,000 per day for each tank for which notification is not given or for which false information is submitted.
If sending form, mail to: LARA, Bureau of Fire Services, Storage Tank Division, FACILITY
P.O. Box 30033, Lansing, MI 48909
NEW REGISTRATION ID NUMBER
If sending form OVERNIGHT: LARA, Bureau of Fire Services, Storage Tank (if known)
AMENDED INFORMATION Division, 3101 Technology Blvd, Suite H, Lansing, MI 48910
00019920
(for Registered USTs Only)
V. CONTACT PERSON
Name Job Title Area Code & Phone No.
Cort Kwiecinski ( 248 ) 770-5097
Class A operator: Name: Company Area Code & Phone No.
N/A – No USTs Present
Class B operator: Name: Company Area Code & Phone No.
N/A – No USTs Present
VI. CERTIFICATION
I CERTIFY UNDER PENALTY OF LAW THAT I HAVE PERSONALLY EXAMINED AND AM FAMILIAR WITH THE INFORMATION SUBMITTED IN THIS FORM AND ALL
ATTACHED DOCUMENTS AND THAT I HAVE VERIFIED THAT THE INFORMATION IS TRUE, ACCURATE, AND COMPLETE.
NAME AND OFFICIAL TITLE OF OWNER OR OWNERS’ AUTHORIZED REPRESENTATIVE SIGNATURE DATE
Ashley Lesser, NTH Consultants, Ltd. 6/25/18
Page 2 of 6 BFS-3821 (Rev 12/17)
VII. DESCRIPTION OF UNDERGROUND STORAGE TANKS
(Complete the following pages for each tank at this location. Copy these pages for additional tanks if needed.)
TANK IDENTIFICATION NUMBER 1 / UTK-042218-15 2 / UTK-055115-15 3 / UTK-055118-15
VIII. TANKS OUT-OF-USE OR CHANGE-IN-SERVICE (Skip this section if this does not apply and go to Section IX.)
NOTE: A SITE ASSESSMENT MUST BE COMPLETED UNLESS YOU REPORT A CONFIRMED RELEASE
WASTE OIL
USED OIL
HAZARDOUS SUBSTANCE
HEATING OIL
MIXTURE
TANK HAS COMPARTMENTS
_____USTs were removed from the ground on May 25, 2018. Based on visual and olfactory evidence observed during removal, a_______
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________________________________
_______________________________________________________________________________________ ____________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________
Report Summary
Lab Sample ID(s): S87344.01-S87344.02
Project: Christoph Holdings LLC
Collected Date: 02/05/2018
Submitted Date/Time: 02/05/2018 13:51
Sampled by: Unknown
P.O. #:
Table of Contents
Cover Page (Page 1)
General Report Notes (Page 2)
Report Narrative (Page 2)
Laboratory Certifications (Page 3)
Qualifier Descriptions (Page 3)
Glossary of Abbreviations (Page 3)
Method Summary (Page 4)
Sample Summary (Page 5)
Maya Murshak
Technical Director
Report Narrative
There is no additional narrative for this analytical report
Laboratory Certifications
Authority Certification ID
Michigan DEQ #9956
DOD ELAP/ISO 17025 #69699
WBENC #2005110032
Ohio VAP #CL0002
Indiana DOH #C-MI-07
New York NELAC #11814
North Carolina DENR #680
North Carolina DOH #26702
Alaska CSLAP #17-001
Qualifier Descriptions
Qualifier Description
! Result is outside of stated limit criteria
B Compound also found in associated method blank
E Concentration exceeds calibration range
F Analysis run outside of holding time
G Estimated result due to extraction run outside of holding time
H Sample submitted and run outside of holding time
I Matrix interference with internal standard
J Estimated value less than reporting limit, but greater than MDL
L Elevated reporting limit due to low sample amount
M Result reported to MDL not RDL
O Analysis performed by outside laboratory. See attached report.
R Preliminary result
S Surrogate recovery outside of control limits
T No correction for total solids
X Elevated reporting limit due to matrix interference
Y Elevated reporting limit due to high target concentration
b Value detected less than reporting limit, but greater than MDL
e Reported value estimated due to interference
j Analyte also found in associated method blank
p Benzo(b)Fluoranthene and Benzo(k)Fluoranthene integrated as one peak.
x Preserved from bulk sample
Glossary of Abbreviations
Abbreviation Description
RL/RDL Reporting Limit
MDL Method Detection Limit
MS Matrix Spike
MSD Matrix Spike Duplicate
SW EPA SW 846 (Soil and Wastewater) Methods
E EPA Methods
SM Standard Methods
Method Summary
Method Version
ASTMD3278 - 96 ASTM Method D3278 - 96(2011)
SW1311 SW 846 Method 1311 Revision 0 July 1992
SW3015A SW 846 Method 3015A Revision 1 February 2007
SW3510C SW 846 Method 3510C Revision 3 December 1996
SW3550C SW 846 Method 3550C Revision 3 February 2007
SW5030C/8260C SW 846 Method 8260C Revision 3 August 2006 / 5030C Revision 3 May 2003
SW6020A SW 846 Method 6020A Revision 1 February 2007
SW7471B SW 846 Method 7471B Revision 2 February 2007
SW8082A SW 846 Method 8082A Revision 1 February 2007
SW8270D SW 846 Method 8270D Revision 4 February 2007
SW9010B SW 846 Method 9010B Revision 2 December 1996
SW9030B SW 846 Method 9030B Revision 2 December 1996
SW9045D SW 846 Method 9045D Revision 4 November 2004
Sample Containers
# Type Preservative(s) Refrigerated? Arrival Temp. (C) Thermometer #
1 32oz Glass None Yes 4.6 IR
TCLP Extraction
Inital Sample pH <0.5% SW1311 02/06/18 11:35-02/06 JBL
pH after 3.5 ml HCl <0.5% SW1311 02/06/18 11:35-02/06 JBL
% Solids <0.5% SW1311 02/06/18 11:35-02/06 JBL
Sample Used g <0.5% SW1311 02/06/18 11:35-02/06 JBL
Final Volume mL <0.5% SW1311 02/06/18 11:35-02/06 JBL
TCLP Extraction Fluid <0.5% SW1311 02/06/18 11:35-02/06 JBL
Final Extract pH <0.5% SW1311 02/06/18 11:35-02/06 JBL
Inorganics
Flash Point* Not detected oF 180 ASTMD3278 - 96 02/07/18 16:55 PL <140
pH/ Corrosivity* 5.29 STD Units 0.01 SW9045D 02/08/18 18:54 ASB 2-12.5
Reactive Cyanide* Not detected mg/kg 0.5 SW9010B 02/08/18 13:22 JDP
Reactive Sulfide* Not detected mg/kg 2.0 SW9030B 02/08/18 11:20 JDP
Metals
Arsenic, TCLP Not detected mg/L 0.02 SW6020A 02/07/18 13:45 CCM 5.0
Barium, TCLP 0.41 mg/L 0.05 SW6020A 02/07/18 13:45 CCM 100.0
Cadmium, TCLP Not detected mg/L 0.005 SW6020A 02/07/18 13:45 CCM 1.0
Chromium, TCLP Not detected mg/L 0.05 SW6020A 02/07/18 13:45 CCM 5.0
Lead, TCLP Not detected mg/L 0.03 SW6020A 02/07/18 13:45 CCM 5.0
Mercury, TCLP* Not detected mg/L 0.0005 SW7471B 02/08/18 12:46 JRH 0.2
Selenium, TCLP Not detected mg/L 0.05 SW6020A 02/07/18 13:45 CCM 1.0
Silver, TCLP Not detected mg/L 0.005 SW6020A 02/07/18 13:45 CCM 5.0
Organics - Semi-Volatiles
TCLP Semi Volatiles
o-Cresol* Not detected ug/L 1,000 SW8270D 02/07/18 20:57 PL 200,000
p,m-Cresol Not detected ug/L 1,000 SW8270D 02/07/18 20:57 PL 200,000
Pentachlorophenol Not detected ug/L 1,000 SW8270D 02/07/18 20:57 PL 100,000
2,4,5-Trichlorophenol Not detected ug/L 1,000 SW8270D 02/07/18 20:57 PL 400,000
2,4,6-Trichlorophenol Not detected ug/L 1,000 SW8270D 02/07/18 20:57 PL 2,000
2,4-Dinitrotoluene Not detected ug/L 90 SW8270D 02/07/18 20:57 PL 130
Hexachlorobenzene Not detected ug/L 90 SW8270D 02/07/18 20:57 PL 130
Hexachlorobutadiene Not detected ug/L 100 SW8270D 02/07/18 20:57 PL 500
Hexachloroethane Not detected ug/L 100 SW8270D 02/07/18 20:57 PL 3,000
Nitrobenzene Not detected ug/L 100 SW8270D 02/07/18 20:57 PL 2,000
Pyridine Not detected ug/L 100 SW8270D 02/07/18 20:57 PL 5,000
Sample Containers
# Type Preservative(s) Refrigerated? Arrival Temp. (C) Thermometer #
1 32oz Glass None Yes 4.6 IR
Organics - PCBs/Pesticides
PCB List
PCB-1016* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1242* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1221* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1232* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1248* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1254* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN
PCB-1260* Not detected ug/kg 1,000 SW8082A 02/07/18 18:48 JAN