GRUNDFOS DATA BOOKLET

Hydro EN
Grundfos firefighting systems

Compliant with the EN 12845, UNI 10779 and UNI 11292 standards
Hydro EN

1. Performance range 3
Table of contents

2. Application 4
General introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3. Type key 5

4. Operating conditions 6
Operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Starting the motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Remote signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5. Functional diagram 7

6. Mechanical and hydraulic configuration 8

7. Hydraulic components 10

8. Pump description 11
Jockey pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical-driven duty pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Diesel-driven duty pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

9. Control panel 12
Control panel for the jockey pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control panel for the electrical-driven duty pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control panel for the diesel-driven duty pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10. Versions on request and accessories 14


Suction kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Test kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Acoustic and visual alarm panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
GSM and WEB alarm panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
MultiLed alarm panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Switches for main valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Diesel engine spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Priming tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Residential silencer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Manual pump for diesel-tank filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Emergency power supply unit for drainage pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Drainage pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
After-sales service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

11. Installation 17
Positive head installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Suction-lift installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

12. Choosing a pump set 18


Cooling flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Motors and types of starting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Type of water supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Pre-calculated HHP and HHS systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

13. Data and performance of the duty pumps 19

14. Performance curves 21


How to read the curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

15. Performance curves and technical data 23

16. Documentation 35

17. Grundfos Product Center 36

2
H
[m]

150
Hydro EN
Hydro EN

ISO 9906

140

130
125-315
120

110

100
1. Performance range

125-250
90
150-400.2

80
40-250 50-250 80-250 125-250.1

70

60

50
32-200 50-200 65-200 80-200 100-200

40

30

20

10

0
7 8 9 10 20 30 40 50 60 70 80 90100
100 200 300 400 500 600 Q [m³/h]

118 200 400 600 800 1000 2000 4000 6000 8000 Q [l/min]

TM066083 0616

3
Performance range
1
Hydro EN
2

2. Application
Application

The Hydro EN pump set for automatic sprinkler The range consists of the following types:
systems is in compliance the following standards: • Hydro EN-S: One or two duty pumps operated by an
• EN 12845 - automatic firefighting sprinkler systems electric motor.
• UNI 10779 - hydrant networks • Hydro EN-Y: Two duty pumps. One pump is
• UNI 11292 - compartments for installation of operated by an electric motor and the other pump is
firefighting pump sets. operated by a diesel engine.
The pump set covers the performance range up to 650 • Hydro EN-T: One or two duty pumps are operated
m3/h and heads up to 140 m for each duty pump. by a diesel engine.
Contact Grundfos for performance values in excess of The systems described above include the following:
the range described in this data booklet. • One electrical-driven jockey pump which is
controlled by a control panel. The jockey has a 24-
General introduction litre tank to restore the system pressure in the case
of small leaks.
The pump set is designed for operation with clean • An independent control panel for each duty pump
water and for automatic sprinkler systems such as with operation and control buttons. Two pressure
single, superior single, double or combined water switches for each duty pump which are hydraulically
supply sources. connected to each other with a manifold of 15 mm in
The pump set is compact, robust, modular and diameter.
supplied in pre-assembled macro blocks to make • A pressure switch on each duty pump to detect the
transportation, handling and installation easier. actual pressure supplied.
The pumps are of the back pull-out design, enabling • Connection for the priming circuit and connection
removal of the motor, coupling, bearing bracket and for the recirculation circuit to prevent overheating of
impeller without disturbing the pump housing or the pump when operating against closed valves.
pipework.
As required by the EN 12845 standard, the periodic
The shape of the QH curve is stable. The motors or pump set performance check must be carried out by
engines deliver, as minimum, the required power up to the installer of the firefighting system or by qualified
the flow rate corresponding to the NPSHr value which personnel. The activities performed must be
is 16 m. documented in a dedicated register kept in the
building.
P2
[kW] ø219 The pump sets are equipped with the necessary
20
ø207
instrumentation to simplify these operations during
16
tests and commissioning.
ø194 NPSH
[m] These accessories can be provided:
12 20
ø170 • A suction kit dedicated for installation in suction lift
16
8
12
or in positive head conditions, including an eccentric
divergent pipe with a controlled taper, a vacuum
TM066084 0616

8
4
4 pressure gauge, a compensation joint on the pipe
ø170 (Min. NPSH) ø219 (Max. NPSH)
0 0 connection side and an isolating valve (not included
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [m³/h] in the version for installation in suction lift
conditions). All accessories are sized according to
Fig. 1 Size criteria for the motor and engine the prescriptions provided by the standard.
The diesel engine makes it possible to operate • A testing kit including a flowmeter, valves and
continuously at full load with a continuous power rating straight pipe sections to get the optimum flow rate
in compliance with the ISO 3046 standard. reading.
The diesel-driven pump is cooled in one of the An industrial silencer is supplied as standard for
following ways: diesel-driven pump sets.
• With direct air.
• With water and heat exchanger. This solution
provides adequate operation that is as unrestricted
as possible by the heat elimination conditions of the
technical control room.
The diesel tank is sized to ensure at least 6 hours of
continuous operation and is equipped with a
containment basin and vent connection in compliance
with the UNI 11292 standard.
All pump sets are supplied as factory-tested units. In
addition, the diesel-driven pumps are supplied with a
factory-test report as required by the EN 12845
standard.

4
Hydro EN
3

3. Type key

Type key
-

Example Hydro EN -Y 50-250/263 JS -A SD -U3 -B -X

Pump set type

Hydro EN

Configuration

S1 One electrical-driven duty pump (100 %)


S2 One electrical-driven duty pump and one electrical-driven standby pump
(100 % + 100 %)
S3 Two electrical-driven duty pumps and one electrical-driven standby pump
(50 % + 50 % + 50 %)
T1 One diesel-driven duty pump (100 %)
T2 One diesel-driven duty pump and one diesel-driven standby pump (100 % + 100 %)
T3 Two diesel-driven duty pumps and one diesel-driven standby pump
(50 % + 50 % + 50 %)
Y One electrical-driven duty pump and one diesel-driven standby pump
(100 % + 100 %)
Y1 Two electrical-driven duty pumps and one diesel-driven standby pump
(50 % + 50 % + 50 %)
Y2 One electrical-driven duty pump and one diesel-driven duty pump and one diesel-
driven standby pump (50 % + 50 % + 50 %)

Pump type

50-250/263 Example: NKF 50-250 impeller ∅263

Jockey pump

JS With a standard jockey pump


JV With a customised jockey pump (upon request)
NJ Without a jockey pump (upon request)

Control panels

A Standard
B IP55
N Without control panel
X Special execution control panel

Starting

DL Direct on line
ST Star-delta

Main supply

U1 3 x 400 V/50 Hz electrical-driven duty pump (or standby pump) - 3 x 400 V/50 Hz electrical-driven jockey pump
U2 1 x 220 V/50 Hz diesel-driven duty pump (or standby) - 3 x 400 V/50 Hz electrical-driven jockey pump
U3 3 x 400 V/50 Hz electrical-driven duty pump (or standby pump) - 1 x 220 V/50 Hz diesel-driven duty pump (or standby
pump) - 3 x 400 V/50 Hz electrical-driven jockey pump

Diesel-engine cooling, if present

A Direct air with fan


B Water/water heat exchanger

Other versions

X Other versions based on customer specifications (upon request)

5
Hydro EN
4

4. Operating conditions
Operating conditions

Installation:
Indoors, waterproof room, protect against Starting the motors
freezing.
Installation level: Up to 300 m above sea level. The starting of the electrical motors is available as
See the specific curve of the model. standard in the following configurations:
Performance:
Performance according to ISO 9906.
• direct on line, DL, for powers up to 30 kW;
Nominal pressure: Components and materials PN16.
Fluid pumped: Solid and fibre-free water. • star-delta, SD, for powers from 37 kW and higher.
Water temperature: 0-50 °C. You start the diesel engine with two direct current
Ambient temperature
4-40 °C. batteries, which are constantly charged.
Minimum 10 °C for diesel-driven pumps.
According to specific performance of the
An electronic circuit allows alternate use of the two
Suction capacity: batteries alternating at every startup and automatic
model chosen.
The maximum inlet pressure is linked to cut-out of the battery if it is inefficient.
the maximum shut-off pressure delivered
by the pump, meaning that the sum of the
Maximum inlet pressure:
inlet pressure with the shut-off pressure
must be less than the nominal pressure of
Remote signals
the pump.
According to the requirements of the EN 12845
According to specific performance of the
Electric power:
model chosen. standard, you must connect a remote alarm unit to the
Direct up to 30 kW. control panels of the duty pumps in order to monitor
Starting:
Star-delta starting from 37 kW. the pump set status. The alarm unit must be complete
3 x 400 V, 50 Hz for electrical-driven with visual and acoustic signal and installed in a
pump.
Power supply:
1 x 230 V, 50 Hz. Imax = 4 A for diesel- permanently attended room.
driven pumps. For this reason, the panels of the duty pumps have the
following outputs available on the terminal block.
Operation mode Diesel-driven pump panel:
The jockey pump starts and stops automatically, • automatic mode off
ensuring pressurisation of the firefighting system in • diesel engine start failure
case of leaks and preventing unjustified starting of the • pump running
duty pumps. • control panel failure.
When the network pressure drops, the first duty pump Electrical-driven pump panel:
is started automatically by the pressure switches (two • electric motor powered
redundant). If present on the pump set, the second
• pump starting request
duty pump is activated automatically if the network
pressure drops further. • pump running
You can only stop the duty pumps manually by • start failure
pressing the button on the front door of the control • mains power not available.
panel.
The standard scope of supply always includes an
adjustable timer to automatically shut down the duty
pump that permits operation. You can activate the
function during commissioning, if necessary.
Specific selectors allow you to start and stop every
single pump at any time. This is useful also for the
commissioning and the periodic operation check.

6
Hydro EN
5

5. Functional diagram

Functional diagram
Priming tanks,
upon request

9 9
14 12
10

PSS PSS PSS PSS


PSSS
6 7
8
4 5

PSL PSL
1 2

Electrical-driven

TM066085 0616
11
13
duty pump Jockey pump Diesel-driven
standby pump

Scope of supply limits

Fig. 2 Functional diagram

Symbol Description Ref. Connection

Independent inlet connection for electrical-driven duty


Check valve 1
pump

Independent inlet connection for diesel-driven standby


Ball valve 2
pump

Butterfly valve 3 Inlet connection for jockey pump

Recirculation circuit connection for electrical-driven duty


Concentric divergent 4
pump or standby pump

Recirculation circuit connection for diesel-driven duty


Eccentric divergent 5
pump or standby pump with direct air cooling.

Priming circuit connection for electrical-driven duty


Compensation joint 6
pump or standby pump

Priming circuit connection for diesel-driven duty pump or


Flowmeter 7
standby pump

PSS Pressure switch 8 Priming circuit connection for the jockey pump

Pressure gauge 9 System outlet connection

Diaphragm pressure tank 10 Connection for technical room sprinkler

Control panel 11 Test circuit outlet

Drain connection 12 Diesel tank vent

Cooling circuit outlet with water/water heat exchanger, if


Power and signal electric connections 13
present

Main and auxiliary flow pipes 14 Diesel engine exhaust gas outlet

7
Hydro EN
6

6. Mechanical and hydraulic configuration


Mechanical and hydraulic configuration

The following drawing shows the standard


configuration of the pump sets.
In the order, you can define any changes, adaptations
to specific requests, integration of optional
components and/or accessories not listed in our
standard equipment described in this catalogue.
Control panel for the diesel-driven Connection for Outlet manifold
Diesel tank sized to ensure at least standby pump diaphragm pressure
six hours of continuous operation tank
complete with containment basin

Isolating valve

Electrical-driven
duty pump control
panel Starting circuit
complete with two
pressure switches
and a pressure
Connection for
gauge
sprinkler circuit in
the technical
control room
Check valve

Connection for Compensation joint


priming the jockey
pump

Connection to
Control panel for priming circuit
the jockey pump

Concentric
divergent with
Jockey pump controlled taper

Pressure switch to
detect pump
operation

TM066086 0616
Electrical-driven
duty pump with Inlet for Standby diesel-
spacer coupling independent pump driven pump with
spacer coupling

Fig. 3 Example of Hydro EN-Y configuration

8
Hydro EN
6
The modular construction concept of the Hydro EN

Mechanical and hydraulic configuration


range makes transport, handling and positioning at the
place of installation easier. All pump sets are supplied
in macro blocks which are usually split as below:
• A baseplate for duty pump, jockey pump, relevant
control panels with brackets and hydraulic
components, in the case of pump sets with two duty
pumps
• a second baseplate for the second standby pump,
control panel with brackets and hydraulic
components.
The arrangement of the parts provides immediate
reading of the measurement instruments and signals,
making the operations during commissioning and
periodic checks of the pumping unit easier.
The following accessories are available on request:
Testing kit Suction kit

Isolating valve Suction lift installation Positive head installation

Eccentric cone with


Flowmeter controlled taper

TM06 6089 0616 - TM06 6088 0616


Vacuum pressure gauge
TM06 6087 0616

Compensation joint

Adjustment valve Isolating valve

Fig. 4 Accessories

9
Hydro EN
7

7. Hydraulic components
Hydraulic components

The hydraulic components are selected and sized in Accessories can be provided to complete the supply,
order to minimise the pressure losses and the water including the following:
speed in compliance with the requirements in the EN • A suction kit for positive head or suction head
12845 standard, at any flow rate value stated on the installation including an eccentric divergent pipe
performance curve. with controlled taper, a vacuum pressure gauge, an
The following components are placed on the outlet isolating valve and a compensation joint on the pipe
side of each duty or standby pump: connection side. All accessories are sized
• A concentric divergent pipe with controlled taper according to the requirements stated in the EN
mounted on the outlet side of the pump inclusive 12845 standard. You can choose the suction kit that
connection for the recirculation circuit in order to is best suited for the type of installation that you
prevent overheating of the pump when operated want.
against closed valves. • A testing kit including a flowmeter, adjustment
• A compensation joint placed on the long side of the valves and spacers to get optimum flow rate
divergent pipe. reading.
• A check valve.
• A isolating valve of the butterfly type with a lockable
handle and status indicator. Operation is by
handwheel with gearbox for sizes higher than DN
100.
• A 1/2" drain valve on the outlet side of the pump
according to the diagram of the standard. See fig. 6.
• A starting device complete with two starting
pressure switches, a glycerine bath manometer with
16 bar full scale, an isolating valve, a bypass with a
check and drain valve. The operation mode requires
two pressure switches for each pump that are
connected so that each one can provide automatic
start while stopping is manual.
• A 1" connection for the sprinkler circuit of the
technical control room.
• A pressure switch on the outlet side to detect that
the pump is delivering pressure.
• A flanged outlet manifold for the connection to the
system and the testing kit.
The jockey pump is equipped with the following
components:
• a connection for priming
• a 1" check valve on the outlet side
• two isolating valves of the ball type with lever
operation, one on the outlet side (1") and one on
inlet side (1 1/4")
• a pressure switch for starting and stopping the
pump
• a diaphragm tank pre-charged at the factory for the
optimal jockey pump operation.

10
Hydro EN
8

8. Pump description

Pump description
The duty pumps are of the flanged single impeller Diesel-driven duty pumps
centrifugal NKF type with horizontal axis and volute
casing, axial intake port and radial delivery port with The diesel-driven duty pumps are driven by a diesel
flanges compliant with the EN 1092-2 standard. engine capable of delivering at least the power
required for the flow rate corresponding to the value of
All pumps are dynamically balanced to prevent
a NPSHr equal to 16 m.
unbalancing of the rotating masses and to ensure their
reliability and durability. The diesel engines are able to operate continuously at
full load. The delivered power is chosen from the
The duty pumps are made in class PN 16 and
continuous power curve (ICN, ICFN, ICXN or NA)
therefore for a pressure of 1.6 MPa (16 bar).
according to the ISO 3046 standard and can supply, as
The maximum intake pressure allowed is equal to the minimum, the power required by the pump at the flow
difference between 16 bar and the maximum head of rate corresponding to the NPSHr value of 16 m.
the specific model.
The pump is coupled to the diesel engine via a spacer
The pumps are suitable for operation with clean, non- coupling so that the pump and the engine can be
dense, non-explosive liquids that contain neither solids removed independently in order for you to perform
nor fibres, mechanically or chemically non-aggressive maintenance on the parts inside the pump without
for the pump. having to remove the inlet or outlet pipes.
The mechanical seal has standard dimensions The fuel tank complete with containment basin and
compliant with the DIN 24960 standard and is of the connection for the vent pipe is sized to ensure at least
Grundfos BAQE type. six hours of operation.
The starting of the diesel engine is guaranteed by two
Jockey pumps 12 V DC batteries that are constantly charged by two
battery chargers.
The jockey pumps are either a Grundfos CM or
Grundfos CR series. The battery charger is electronically controlled to
achieve consistent and calibrated performance to
The jockey pumps are horizontal multistage centrifugal
ensure maximum effectiveness and extended battery
pumps, not self-priming, with direct-start motor
life.
Install the jockey pump to avoid unnecessary starting
The automatic and manual starting systems are
of the duty pump and to maintain the system pressure
independent and use four separate power relays.
in case of small leakages.
The starting of the diesel engines requires an
The performance of the jockey pump does not
automatic sequence of six alternating attempts, each
contribute to the calculation of the nominal flow of the
lasting from 5 to 10 seconds with a maximum pause of
system. According to the standard description, the
10 seconds, on the two batteries
performance of the jockey pump must not be sufficient
to supply a single sprinkler. Automatic battery changeover is made at every
starting attempt and an automatic cut-out of the
inefficient battery improves the system reliability.
Electrical-driven duty pumps The exhaust silencer is included in the scope of
The electrical-driven duty pumps are built as back-pull- supply, either integrated or loose for mounting during
out and are driven by an electric motor capable of installation. In the latter case, a flexible pipe is
delivering at least the power required for the flow rate supplied to ease the connection between the silencer
corresponding to the value of a NPSHr equal to 16 m. and the exhaust manifold of the diesel engine.
The pump is coupled to the motor via a spacer In compliance with the requirements of the standard,
coupling so that the pump and engine can be removed all diesel-driven pumps are factory-tested and
independently in order for you to perform maintenance accompanied by a test bulletin.
on the parts inside the pump without having to remove
the inlet or outlet pipes.
Pump performance is compliant with the ISO
9906:2012 - Grade 3B standard. The characteristic
curve QH is stable.

11
Hydro EN
9

9. Control panel
Control panel

Control panel for the jockey pump Signalling Description

The jockey pump is controlled by a specific panel that Electric mains: Mains voltage is missing.
automatically manages its operation. Motor voltage: There is no voltage to the motor.
Starting request: Request for starting the electrical-driven pump.
The panel is equipped with a general mains switch, Pump in operation: Start of the electrical-driven pump.
padlockable for easy and safe maintenance. Failure to start: The pump did not start.
Starting and stopping of the jockey pump is controlled
The panels include the following components and
by a low voltage pressure switch which is isolated from
functions available in the door:
the mains by a transformer.
An input to connect a device protecting against dry Pos. Component
running is provided. A Ammeter
You can manually start the pump with the button (B) on TEST-0-AUT operation mode selector with a removable key
B
the front of the panel. This is useful, for example, for in AUT position
priming operations during the commissioning of the C Mains switch, padlockable
pump set. D EPC 300 control unit with buttons and warning lights

The starting of the electrical-driven motor is by direct


start. To ensure greater safety for the operators, the
control pressure switch and the input for dry-running
are powered by low voltage isolated from the mains. A

D
TM066090 0616

Control panel for the jockey pump

TM066091 0616
Fig. 5
B C
Control panel for the electrical-
driven duty pump
Fig. 6 Control panel for the electric pump
The electrical-driven duty pumps are controlled by an
independent control panel which provides easy The user interface of the EPC 300 control unit (D)
reading of the measurement instruments and signals shows the following signal lights and operation
from a single observation point. buttons:
The starting of the electrical motors is available as • stop button
standard in the following configurations: • start button
• direct, DL, for powers up to 30 kW • pressure switch 1, test button
• star/delta, SD, for 37 kW and higher. • pressure switch 2, test button
To ensure greater safety for operators, the control • signal light, test button
pressure switch is powered by low voltage isolated • power not available, LED
from the mains by a transformer.
• pump on demand, LED
The outputs listed below are provided for supervising
• pump running, LED
the pump set from a control room:
• power available to the motor, LED
Contact type: AC1, potential-free relay contacts.
• start failure, LED.
Maximum voltage: 115 V.
Maximum current: 2 A.

12
Hydro EN
9
Control panel for the diesel-driven The user interface has a backlit LCD display so you

Control panel
can read it even when the room lighting is poor. By
duty pump means of the light signals, the pump set status is
The diesel-driven duty pump is controlled by an always under control.
independent control panel which provides easy The indications and their functions are divided as
reading of the measurement instruments and signals follows.
from a single observation point. The LCD display has eight parameters in simultaneous
The outputs listed below are provided for supervising reading:
the pump set from a system control room. • engine status or speed with the engine running
Contact type: AC1, potential-free relay contacts. • selector status of the operation mode (F)
Maximum voltage: 115 V. • operation hour counter
Maximum current: 2 A. • engine temperature
Signalling Description • oil pressure
Pump in • diesel fuel level
Start of the diesel-driven pump.
operation: • battery 1 voltage
Indicates the tripping of one of the following alarm
conditions: battery charger failure, battery • battery 2 voltage.
undervoltage or overvoltage, mains power supply, Note: In the case of an alarm, the description of the
General alarm: low oil pressure, high motor temperature, failure to
start, panel in operating mode other than alarm will be displayed instead of the battery voltage.
automatic, fuel reserve, oil or water preheating
alarm. Programming area:
Failure to start: The diesel engine did not start after six attempts. • Parameter selection button
The operation mode selector is positioned on
Operating mode
TEST or 0, or the group is not ready to start if • programming button
not in automatic:
requested • confirmation button
Control panel
failure:
The DPC 300 control unit is not operating correctly • reset button
• LED operation check button.
The independent battery chargers and all the
electromechanical components needed are placed Battery 1:
inside the panel. • battery charger failure (flashing LED) or battery
The panel includes the following components and failure (LED is permanently on).
functions available in the door: Battery 2:
• battery charger failure (flashing LED) or battery
Pos. Component failure (LED is permanently on).
A Mains switch, padlockable
Alarm indication area:
DPC 300 control unit with buttons, warning lights and LCD
B
multifunction display • Control panel failure
Manual engine start button using battery 1 or 2, protected by • low oil pressure.
C
breakable glass
D Manual engine stop button • high engine temperature.
E Engine test start button • short-circuit of oil or water pre-heating system
F
TEST-0-AUT operation mode selector, with removable key • diesel reserve
in AUT position
• engine start failure.
Status area:
• Automatic start disabled
• pump in operation
• mains present.
B ALARMS ALARMS

STATUS TEST
Test area:
• Button for pressure switch 1: test and operation
check of the emergency starting circuit
• button for pressure switch 2: test and operation
check of the emergency starting circuit.
E
PUMP START-TEST
TM066092 0616

AVVIAMENTO
START

A
D F C

Fig. 7 Control panel for the diesel pump

13
Hydro EN
10

10. Versions on request and accessories


Versions on request and accessories

The following versions are available upon request:


• starting configuration other than standard
• one electrical-driven pump, two diesel-driven duty
pumps and one electrical-driven jockey pump
• three electrical-driven duty pumps and one
electrical-driven jockey pump

TM066093 0616
• three diesel-driven duty pumps and one electrical-
driven jockey pump
• with performance values in excess of the range
described in this catalogue
• with suction manifold Fig. 8 Acoustic and visual alarm panel
• IP55 panels.
Contact Grundfos for more information about versions GSM and WEB alarm panels
not listed above or for accessories not listed in the
equipment described in this document. GSM version
The following accessories are available upon request. The Micro Alarm 2 GSM (CIU 251) alarm panel meets
the requirements of the EN 12845 standard for remote
monitoring of pump functions. When there is an alarm,
Suction kit the alarm panel sends a text message to the user.
To make sure that an installation comply with the The following functions are added to the features of
guidelines in the EN 12845 standard, you need an the acoustic and visual alarm panel described above:
installation kit including an eccentric divergent pipe • Integrated modem for sending text messages to four
with a controlled taper, a vacuum pressure gauge, an phone numbers.
isolating valve and a compensation joint on the side
• One analog and three digital inputs that can receive
where the pipe is connected. The components are
an alarm signal for sending text messages.
sized in accordance with the requirements of the
standard regarding the minimum diameter and the WEB versions
maximum water velocity prescribed at the maximum The CIU 271 alarm panel meets the requirements of
flow rate stated on the performance curve: the EN 12845 standard for remote monitoring of pump
• positive head installation: minimum permissible functions.
diameter DN 65 for the standard and maximum The alarm panel has the same functions as the CIU
water speed of 1.8 m/s 251 alarm panel. In addition, CIU 271 also displays
• suction lift installation: minimum permissible alarms and the analog input parameter via WEB on a
diameter DN 80 for the standard and maximum Grundfos website.
water speed of 1.5 m/s.

Test kit
A complete flow rate test circuit is available as an
option. The test circuit includes a flowmeter, spacers
and an adjustment valve. With this configuration you
can measure the flow rate with adequate accuracy.
TM066094 0616

This accessory is essential in order to verify the


performance as required by the standard when
carrying out inspection and periodic verifications.
Fig. 9 Micro Alarm 2 GSM
Acoustic and visual alarm panel
The panel allows you to monitor the operation of the
pumps from a permanently attended room. The panel
provides a visual and acoustic indication of the alarms
from the duty pump panels. The panel meets the
requirements of the EN 12845 standard:
• seven digital alarm inputs
• a yellow control lamp and acoustic alarm, 85 dB
• a buffer battery with 30 hours of continuous
operation and battery charger
• a mains control lamp
• a lamp and acoustic signal test button
• an acoustic alarm silencing button.

14
Hydro EN
10
MultiLed alarm panel

Versions on request and accessories


There are 12 yellow LEDs for alarm type B and four
red LEDs for alarm type A available. The purpose of

TM066096 0616
the LEDs is to monitor system components as well as
the pump set alarms.
A label system allows the user to customise the
description of each LED alarm.
Due to a buffer battery, the panel ensures the display Fig. 11 Micro switch
of the alarms, individually selectable NO or NC, even
in the absence of mains voltage.
When an alarm is activated, the LED lights up on the
Diesel engine spare parts
panel and a buzzer and a yellow control lamp are To meet the requirements of the EN 12845 standard,
activated. you can request a set of diesel-engine spare parts:
A type A alarm relay and type B alarm relay are • two series of fuel filters with seals
activated at the same time. • two series of oil filters with seals
You can decide to store the alarm. In that case, the • two series of belts, if used on the engine
LED remains on even if the alarm disappears. In this • a full set of connections, seals and hoses for the
case, use the R button to turn off the LED. engine
You can use a button that mute the buzzer with time • two injector nozzles.
recovery. If you press this button for more than three
seconds, it tests the LEDs and buzzer.
There is also an RS 485 port with Modbus-RTU
protocol that allows various information to be
communicated.

TM066097 0616
Fig. 12 Spare parts kit

Priming tank
A 500-litre water priming tank suitable for suction lift
installation and complete with accessories is available
on request.
TM066095 0616

Fig. 10 MultiLed alarm panel TM066098 0616

Switches for main valves


According to the EN 12845 standard, you must monitor
the status of each isolating valve remotely.
Upon request, the following isolating valves can be Fig. 13 Priming tank
equipped with a micro-switch:
• inlet valve*
• outlet valve
• test circuit valve*.
* If the relevant kit is included.
The use and connection of the monitoring system is
the responsibility of the installer.

15
Hydro EN
10
Residential silencer
Versions on request and accessories

The residential silencer is either integrated or loose for


mounting during installation. In case of the latter, a
flexible pipe is delivered to ease the connection
between the silencer and the exhaust manifold of the
diesel engine.
A diesel engine equipped with a residential silencer for
further reduction of the noise generated by the motor
exhaust is available on request.

TM066099 0616

TM066101 0616
Fig. 14 Residential silencer

Fig. 16 SE 2000
Manual pump for diesel-tank filling
A manual pump for diesel-tank filling is available on
request. The manual pump makes it easy to refill the
Drainage pump
diesel tank as you can build a fixed filling system on To be compliant with the UNI 11292, the system must
the outside of the technical control room. consist of two properly sized pumps.
Contact Grundfos for more information about drainage
pumps that are suitable to combine with the
emergency power supply unit described above.
TM066100 0616

Fig. 15 Manual fuel pump

Emergency power supply unit for


drainage pump
The emergency power supply unit, SE 2000, is ideal in

TM066103 0616
case of electricity blackouts as the unit automatically
goes into operation and generates electricity from a
series of buffer batteries.
Combined with a single-phase Grundfos drainage
Fig. 17 Drainage pump
pump, the unit meets the requirements of the UNI
11292 standard.
Characteristics: After-sales service
• Output voltage: single-phase 230 VAC, 50 Hz Grundfos offers after-sales service with competent
• input voltage, batteries: 48 V personnel and original spare parts.
• nominal power rating: 2000 VA This service can be extended with a maintenance
• metal enclosure IP20 contract or check and inspection agreements
depending on your needs.
• warning lights indicating the operating status of the
emergency power supply unit
• protection against reversing the battery connection
• thermal protection of the panel
• protection fuses for output.

16
Hydro EN
11

11. Installation

Installation
The criteria for installing firefighting pump sets are
described in the EN 12845 and UNI 11292 standards.
Refer to these standards for all the necessary
guidelines.
In order for the pump set to perform efficiently, it is
important that the inlet pipes comply with the criteria
listed in the EN 12845 standard regarding the water
speed in the pipes:
• 1.8 m/s for positive head installation
• 1.5 m/s for suction lift installation.
We recommend that you select a suction kit according
to the type of installation. The suction kit is available
on request.
The points of the EN 12845 standard regarding the
installation type are summarised below.

Positive head installation


To be in accordance with the EN 12845 standard, you
must install the firefighting pump sets in positive head
and according to the following conditions:
• At least two-thirds of the water reserve must be
above the level of the duty pump axis.
• The minimum water level in the inlet tank is no more
than 2 metres below the level of the pump axis.
• You must install a foot valve if the axis of the duty
pump is above the minimum level of the water to be
sucked.

Suction-lift installation
You can install the firefighting pump sets in the suction
lift as long as the following conditions are met:
• The minimum water level in the inlet tank must be
no more than 3.2 metres below the level of the
pump axis.
• You must install a foot valve in the lowest point of
the inlet pipe.

17
Hydro EN
12

12. Choosing a pump set


Choosing a pump set

Before choosing the pump set, check the requirements Motors and types of starting
and specifications of the equipment designer, the
prescriptions of the authorities and local regulations, The motors deliver, as minimum, the required power
the implications regarding the place and method of up to the flow rate corresponding to the NPSHr value
installation, etc. which is 16 m.
To assess the effect of the installation conditions on The electrical data refer to single electrical-driven duty
the performance provided, proceed as follows when pumps.
selecting the pump model for the pump set. In the standard version, the electrical motor starting is
The tables in the hydraulic data and performance direct, DL, for powers up to 30 kW, and star/delta, SD,
section provide the single pump performance values. for powers 37 kW and higher.
You find complete data in the performance curves
section. Type of water supply
1. Use the above-mentioned values to choose the
The pump sets are designed for water supplies where
pump set.
each duty pump must deliver the following:
2. Use a part of the generated flow as a continuous
• 100 % of the specified performance if there are one
flow to prevent overheating when the pump
or two pumps installed. The second duty pump is
operates against a closed valve or to feed the heat
considered a standby pump.
exchanger to cool the diesel engine, if available.
• 50 % of the specified performance if there are three
3. Add this flow rate to the design flow rate in order to
pumps installed. The third duty pump is considered
make the selection.
a standby pump. The three-pump version is
4. The outlet pressure is influenced by the installation available on request.
conditions:
According to the EN 12845 standard, when more than
•Suction lift installation: Deduct the height in metres on pump is installed in a superior or duplicate water
between the level of the pump axis and the supply, only one pump must be driven by an electric
minimum water level in the inlet tank from the motor.
head values specified in the tables.
•Positive head installation: Add the height in metres
between the level of the pump axis and the Pre-calculated HHP and HHS
minimum water level in the inlet tank to the head systems
values specified in the tables.
According to the EN 12845 standard, the pump for the
5. Deduct the friction losses in the inlet line (foot
pre-calculated HHP and HHS systems must supply
valve, pipes, curves, etc.), calculated at the design
140 % of the design flow rate at a head of minimum 70
flow rate, from the head value.
% of the head at the design flow rate of the pump.
6. Respect the minimum condition NPSHd ≥ NPSHr
+1 [m] including the suction head and the suction
head losses that has to be evaluated by the
designer. You find the NPSHr value in the
performance curve section.

Cooling flow
As specified in the EN 12845 standard, you must
install a device on the pump set that meets the
following purposes:
• prevent overheating when the pump operates
against close valves.
• supply the water/water heat exchanger for diesel
engine cooling, if available
See the performance curves and technical data for
more information about the minimum flow rate values
which are necessary to meet the purposes listed
above.

18
Hydro EN
13

13. Data and performance of the duty pumps

Data and performance of the duty pumps


The complete performance curves and the technical data for each pump are shown in the specific charts
You can use the values shown entirely, and the last point is not the end of the curve. The cells corresponding at
NPSHr values less than or equal to 5 metres are highlighted with a grey background. The sections with white
background indicate the pump performance that is the maximum limit suggested.
Always check that the requirements in the standard are met when you select the pump: NPSHd ≥ NPSHr + 1 [m].
A part of the flow rate delivered by the pump is used as a cooling flow and therefore it must be added to the design
flow rate, as specified by the EN 12845 standard. For more information on the specific data, see the pump
performance curves.

Electric-driven Diesel-driven Flow rate


Model 0 10 15 20 25 30 33 35 40 45 48
pump [kW] pump [kW] [m3/h]

Hydro EN 32-200/171 4 4.5 37 36 34 32 29 25 22 19 13 5

Hydro EN 32-200/185 5.5 6.6 45 44 43 41 39 35 33 31 25 18 13


Head [m]
Hydro EN 32-200/200 7.5 11.2 55 53 52 51 49 47 45 44 39 34 29

Hydro EN 32-200/219 11 14.8 67 67 66 65 63 60 57 56 51 46 43

Electric-driven Diesel-driven Flow rate


Model 0 10 20 30 35 40 43 45 50 55 60
pump [kW] pump [kW] [m3/h]

Hydro EN 40-250/210 11 14.8 62 62 61 57 53 50 47 45

Hydro EN 40-250/230 15 18.7 75 74 73 70 68 65 63 61 57

Hydro EN 40-250/238 18.5 18.7 Head [m] 80 80 79 76 74 71 69 68 64 60

Hydro EN 40-250/250 22 28.5 88 88 87 85 83 81 79 78 75 71 67

Hydro EN 40-250/260 30 28.5 96 95 95 93 92 90 88 87 84 81 77

Electric-driven Diesel-driven Flow rate


Model 0 40 50 60 70 80 90 93 100 105 110
pump [kW] pump [kW] [m3/h]

Hydro EN 50-200/170 11 14.8 39 37 36 35 33 30 26 25

Hydro EN 50-200/194 15 18.7 50 48 47 46 45 42 39 38 35 33


Head [m]
Hydro EN 50-200/207 18.5 28.5 56 55 54 53 52 50 47 46 44 42 40

Hydro EN 50-200/219 22 28.5 62 62 61 60 59 57 54 53 51 49 47

Electric-driven Diesel-driven Flow rate


Model 0 40 50 60 70 80 90 96 98 100 105
pump [kW] pump [kW] [m3/h]

Hydro EN 50-250/205 18.5 18.7 57 56 54 52 49 45 40 37 35

Hydro EN 50-250/220 22 28.5 66 65 64 62 60 57 53 50 49 48


Head [m]
Hydro EN 50-250/249 30 36.5 87 86 85 83 80 77 73 70 69 68 65

Hydro EN 50-250/263 37 53.0 96 95 94 93 91 89 85 83 82 81 79

Electric-driven Diesel-driven Flow rate


Model 0 80 85 90 95 100 110 120 125 135 150
pump [kW] pump [kW] [m3/h]

Hydro EN 65-200/170 15 14.8 40 35 34 33 32 30 28 25 23 20

Hydro EN 65-200/185 18.5 28.5 48 44 43 42 41 40 38 35 34 31


Head [m]
Hydro EN 65-200/195 22 28.5 51 47 47 46 45 44 42 40 39 36

Hydro EN 65-200/215 30 36.5 63 60 59 59 58 57 55 53 52 50 45

19
Hydro EN
13
Data and performance of the duty pumps

Electric-driven Diesel-driven Flow rate


Model 0 100 120 140 160 180 200 220 240 270 290
pump [kW] pump [kW] [m3/h]

Hydro EN 80-200/188 30 36.5 48 46 45 44 42 39 36 32

Hydro EN 80-200/202 37 53 55 54 53 52 50 48 45 42 38 32
Head [m]
Hydro EN 80-200/213 45 53 63 62 61 60 58 56 54 51 48 42 38

Hydro EN 80-200/222 55 73.5 68 67 66 65 63 61 59 57 54 48 44

Electric-driven Diesel-driven Flow rate


Model 0 50 100 120 160 180 200 220 240 250 260
pump [kW] pump [kW] [m3/h]

Hydro EN 80-250/216 45 53 65 65 64 62 58 55 51 47 42

Hydro EN 80-250/233 55 73.5 75 75 74 73 69 66 63 59 55 53


Head [m]
Hydro EN 80-250/255 75 104.8 91 91 90 89 86 84 81 78 74 72 70

Hydro EN 80-250/270 90 104.8 106 106 104 103 100 98 95 92 89 87 85

Electric-driven Diesel-driven Flow rate


Model 0 200 220 240 260 300 310 330 350 370 390
pump [kW] pump [kW] [m3/h]

Hydro EN 100-200/209 45 53 61 55 53 51 49 43 42 39 35 32

Hydro EN 100-200/215 55 73.5 Head [m] 65 60 59 57 55 50 49 46 43 40 37

Hydro EN 100-200/219 75 73.5 69 66 65 63 61 57 56 54 51 48 45

Electric-driven Diesel-driven Flow rate


Model 0 150 200 250 300 350 375 400 425 450 475
pump [kW] pump [kW] [m3/h]

Hydro EN 125-250.1/238 90 104.8 75 76 75 74 71 67 65 62 59 56

Hydro EN 125-250.1/251 110 145 Head [m] 85 86 85 84 82 79 77 75 73 71 68

Hydro EN 125-250.1/263 132 145 95 95 95 93 91 89 87 86 84 81 79

Electric-driven Diesel-driven Flow rate


Model 0 150 200 250 300 350 375 400 425 450 500
pump [kW] pump [kW] [m3/h]

Hydro EN 125-250/237 110 145 76 76 75 75 73 71 70 69 67 65 61

Hydro EN 125-250/245 132 145 83 83 83 83 82 80 79 78 77 76 72


Head [m]
Hydro EN 125-250/255 160 197 93 93 93 93 92 91 91 90 89 88 85

Hydro EN 125-250/269 200 222 103 103 103 103 103 102 101 101 100 99 97

Electric-driven Diesel-driven Flow rate


Model 0 100 150 200 250 300 350 400 425 475 525
pump [kW] pump [kW] [m3/h]

Hydro EN 125-315/289 132 145 116 116 115 113 110 105 99 90 85 74 60

Hydro EN 125-315/302 160 197 Head [m] 129 129 128 127 124 120 115 107 103 93 81

Hydro EN 125-315/316 200 222 145 145 145 144 142 139 134 129 125 117 107

Electric-driven Diesel-driven Flow rate


Model 0 300 350 400 450 500 550 600 650 700 740
pump [kW] pump [kW] [m3/h]

Hydro EN 150-400.2/351 - 180 87 86 84 82 80 77 73 69 65 60

Hydro EN 150-400.2/366 - 206 94 94 92 91 88 85 82 78 74 69 65

Hydro EN 150-400.2/384 - 290 104 103 102 101 99 96 93 89 85 81 76


Head [m]
Hydro EN 150-400.2/398 - 290 111 111 110 109 107 104 101 98 94 89 85

Hydro EN 150-400.2/418 - 290 122 121 120 118 116 114 111 107 103 99 95

Hydro EN 150-400.2/420 - 290 123 122 121 120 118 115 112 109 105 100 96

20
Hydro EN
14

14. Performance curves

Performance curves
How to read the curves
Performance curve table

C D A

H
[m] Hydro EN
B
110
ø270 80-250
105 2950 rpm
NPSH 5m
100 ISO 9906

95
ø255
90
85
80
ø233
75
70
ø216
65
60
55
E
50
45
40
35
30
25
20
F
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 Q [m³/h]

P2
[kW] ø270
80
70 ø255
NPSH
60 [m]
ø233
50
ø216
40 ø270 (NPSH)
30 16
ø216 (NPSH) 12
20 8
10 4
0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 Q [m³/h]
G
Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá
Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U” H


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
I Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 80-250/216 45,0 77,0 4,0 z 48,2(53,0) 4,0 CM 3-10 1,20 2,60
Hydro EN 80-250/233 55,0 99,5 4,0 z 66,8 (73,5) 6,0 CM 3-12 1,58 3,10
Hydro EN 80-250/255 75,0 134,0 4,0 z 95,3 (104,8) 6,0 CM 3-13 1,58 3,10
Hydro EN 80-250/270 90,0 160,0 4,0 z 95,3 (104,8) 6,0 CM 3-14 2,20 4,10
TM066104 0616

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

L M N O P Q R S T

21
Hydro EN
14
Performance curves

Pos. Description
A Indicates the size of the pump.
B Indicates the diameter in mm of the impeller installed on the duty pumps.
The bold part of the curve indicates the performance, QH, corresponding to a NPSHr less than 5 metres.
C
You should not select a pump set with a performance left of the bold part of the curve.
D Indicates the limit of 5 metres of NPSHr.
E Indicates the maximum limit suggested for this pump.
F Power curve [P2].
G NPSHr curve extended up to 16 metres regarding the maximum impeller diameter in this pump.
H NPSHr curve extended up to 16 m regarding the minimum impeller diameter in this pump.
I Pump set.
L Electric motor power installed on the electrical-driven duty pump, if available.
M Rated current of the electric motor installed on the electrical-driven duty pump, if available.
N Flow rate of the recirculation circuit installed on the electrical-driven duty pump.
Cooling system used by the diesel engine, if available:
O ❍: direct air-cooled engine
● : liquid-cooled engine by a water/water heat exchanger.
P Rated power of the diesel engine compliant with the ISO 3046 standard.
In the case of pump sets equipped with air-cooled motors, it indicates the flow of the recirculation circuit on the diesel-driven duty pump.
The first number indicates the power available for firefighting use, while the number in brackets indicates the rated power supplied by the
Q engine.
In the case of liquid-cooled motors, the number indicates the cooling flow rate of the diesel engine. It also acts as recirculation for the pump
coupled to the diesel engine.
R The version of the installed jockey pump.
S Electric motor power installed on the electrical-driven jockey pump, if available.
T Rated current of the electric motor installed on electrical-driven jockey pump, if available.

22
15

Performance curves and technical data


15. Performance curves and technical data
H
[m] Hydro EN
70 ø219
32-200
2950 rpm
65 ISO 9906

60
ø200
55
NPSH 5m
50 Limite max suggerito
ø185 Max suggested limit
45
40 ø171
35
30

25

20
15
Nella scelta del modello di pompa sommare il flusso di
10 ricircolo (vedi tabella in calce) alla portata di progetto.
5 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
0
0 5 10 15 20 25 30 35 40 45 50 Q [m³/h]

P2
[kW] ø219

8
ø200 NPSH
6 [m]
ø185
4 ø171 16
ø185 (NPSH) 12
2 8
ø219 (NPSH) 4
0 0
0 5 10 15 20 25 30 35 40 45 50 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 32-200/171 4,0 8,0 0,5 { 4,1 (4,5) 0,5 CM 1-7 0,65 1,6
Hydro EN 32-200/185 5,5 11,2 0,5 { 5,9 (6,6) 0,5 CM 1-8 0,65 1,6
Hydro EN 32-200/200 7,5 14,8 0,5 { 10,2 (11,2) 0,5 CM 1-8 0,65 1,6
TM06 6300 0816

Hydro EN 32-200/219 11,0 21,2 0,5 { 13,5 (14,8) 0,5 CM 1-10 0,85 1,6

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

23
15
Performance curves and technical data

H
[m] Hydro EN
100
ø260 40-250
2950 rpm
90 ø250 ISO 9906
NPSH 5m
ø238 Limite max suggerito
80 Max suggested limit
ø230

70
ø210
60

50

40

30
Nella scelta del modello di pompa sommare il flusso di
20 ricircolo (vedi tabella in calce) alla portata di progetto.
When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
10
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Q [m³/h]

P2
[kW] ø260

20 ø250
ø238
16
ø230 NPSH
12 [m]
ø210
ø260 (NPSH) 16
8 ø210 (NPSH)
12
4 8
4
0 0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 40-250/210 11,0 21,2 1,0 { 13,5 (14,8) 1,0 CM 1-10 0,85 1,60
Hydro EN 40-250/230 15,0 28,5 1,0 { 17,0 (18,7) 1,0 CM 1-11 0,85 1,60
Hydro EN 40-250/238 18,5 35,0 1,0 { 17,0 (18,7) 1,0 CM 1-12 0,85 1,60
TM06 6133 0816

Hydro EN 40-250/250 22,0 41,5 1,0 { 26,1 (28,5) 1,0 CM 1-13 1,20 2,60
Hydro EN 40-250/260 30,0 53,0 1,0 { 26,1 (28,5) 1,0 CM 1-13 1,20 2,60

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

24
15

Performance curves and technical data


H
[m] Hydro EN
ø219 50-200
60 2950 rpm
ø207 ISO 9906

55
NPSH 5m
50 ø194
Limite max suggerito
Max suggested limit
45

40 ø170

35

30

25

20
Nella scelta del modello di pompa sommare il flusso di
ricircolo (vedi tabella in calce) alla portata di progetto.
15
When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
10
0 10 20 30 40 50 60 70 80 90 100 110 120 Q [m³/h]

P2
[kW]
ø219
20
ø207
16
ø194
NPSH
12 [m]
ø170
8 ø219 (NPSH)
ø170 (NPSH) 16
4 8
0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 50-200/170 11,0 21,2 2,0 { 13,5 (14,8) 2,0 CM 1-7 0,65 1,60
Hydro EN 50-200/194 15,0 28,5 2,0 { 17,0 (18,7) 2,0 CM 1-8 0,65 1,60
Hydro EN 50-200/207 18,5 35,0 2,0 { 26,1 (28,5) 2,0 CM 1-9 0,65 1,60
TM06 6134 0816

Hydro EN 50-200/219 22,0 41,5 2,0 { 26,1 (28,5) 2,0 CM 1-10 0,85 2,60

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

25
15
Performance curves and technical data

H
[m] Hydro EN
100
ø263 50-250
95
2950 rpm
90 ø249 ISO 9906
NPSH 5m
85
80 Limite max suggerito
Max suggested limit
75
70
ø220
65
60 ø205
55
50
45
40
35
30
25 Nella scelta del modello di pompa sommare il flusso di
20 ricircolo (vedi tabella in calce) alla portata di progetto.
When choosing the pump model, the by-pass flow
15
(see table at the bottom) must be added to the design flow rate.
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [m³/h]

P2
[kW] ø263

30 ø249
25
ø220 NPSH
20
ø205 [m]
15
ø205 (NPSH) ø263 (NPSH)
10 16
5 8
0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 50-250/205 18,5 35,0 2,0 { 17,0 (18,7) 2,0 CM 1-9 0,65 1,60
Hydro EN 50-250/220 22,0 41,5 2,0 { 26,1 (28,5) 2,0 CM 1-10 0,85 1,60
Hydro EN 50-250/249 z 33,2 (36,5)
{
TM06 6135 0816

30,0 54,5 2,0 2,0 CM 1-13 1,20 2,60


Hydro EN 50-250/263 37,0 66,5 2,0 z 48,2 (53,0)
{ 3,0 CM 1-13 1,20 2,60

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

26
15

Performance curves and technical data


H
[m] Hydro EN
ø215
65-200
60 2950 rpm
ISO 9906
NPSH 5m
55
ø195 Limite max suggerito
50 ø185 Max suggested limit

45
ø170
40

35

30

25

20
Nella scelta del modello di pompa sommare il flusso di
ricircolo (vedi tabella in calce) alla portata di progetto.
15
When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 Q [m³/h]

P2
[kW]
30 ø214
25
ø195 NPSH
20
ø186 [m]
15
ø170
10 ø214 (NPSH)
ø170 (NPSH) 16
5 8
0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 65-200/170 15,0 28,5 2,5 { 13,5 (14,8) 2,5 CM 3-6 0,65 1,60
Hydro EN 65-200/185 18,5 35,0 2,5 { 26,1 (28,5) 2,5 CM 3-7 0,85 1,60
Hydro EN 65-200/195 22,0 41,5 2,5 { 26,1 (28,5) 2,5 CM 3-8 1,20 2,60
TM06 6136 0816

Hydro EN 65-200/215 30,0 54,5 2,5 z


{ 33,2 (36,5) 3,0 CM 3-10 1,20 2,60

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore diesel raffreddato a liquido / Diesel engine Liquid cooled

27
15
Performance curves and technical data

H
[m] Hydro EN
80-200
70 ø222 2950 rpm
ISO 9906
65 ø213

60
ø202
55

50
ø188 NPSH 5m
45

40

35

30

25 Nella scelta del modello di pompa sommare il flusso di Limite max suggerito
ricircolo (vedi tabella in calce) alla portata di progetto. Max suggested limit
20 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
15
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [m³/h]

P2
[kW]
ø222
ø213
40
ø202 NPSH
30 ø188 [m]
20 ø222 (NPSH)
ø188 (NPSH) 16
10 8
0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [k W ] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 80-200/188 30,0 54,5 4,0 z 33,2 (36,5) 4,0 CM 3-7 0,85 1,60
Hydro EN 80-200/202 37,0 66,5 4,0 z 48,2 (53,0) 4,0 CM 3-8 1,20 2,60
Hydro EN 80-200/213 45,0 80,5 4,0 z 48,2 (53,0) 4,0 CM 3-10 1,20 2,60
TM06 6137 0816

Hydro EN 80-200/222 55,0 99,5 4,0 z 66,8 (73,5) 4,0 CM 3-10 1,20 2,60

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

28
15

Performance curves and technical data


H
[m] Hydro EN
110
ø270 80-250
105 2950 rpm
NPSH 5m
100 ISO 9906

95 Limite max suggerito


ø255
90 Max suggested limit
85
80
ø233
75
70
ø216
65
60
55
50
45
40
35 Nella scelta del modello di pompa sommare il flusso di
30 ricircolo (vedi tabella in calce) alla portata di progetto.
When choosing the pump model, the by-pass flow
25
(see table at the bottom) must be added to the design flow rate.
20
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 Q [m³/h]

P2
[kW] ø270
80
70 ø255
NPSH
60 [m]
ø233
50
ø216
40 ø270 (NPSH)
30 16
ø216 (NPSH) 12
20 8
10 4
0 0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 80-250/216 45,0 77,0 4,0 z 48,2(53,0) 4,0 CM 3-10 1,20 2,60
Hydro EN 80-250/233 55,0 99,5 4,0 z 66,8 (73,5) 6,0 CM 3-12 1,58 3,10
Hydro EN 80-250/255 75,0 134,0 4,0 z 95,3 (104,8) 6,0 CM 3-13 1,58 3,10
TM06 6138 0816

Hydro EN 80-250/270 90,0 160,0 4,0 z 95,3 (104,8) 6,0 CM 3-14 2,20 4,10

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

29
15
Performance curves and technical data

H
[m] ø219 Hydro EN
ø215 100-200
65 2950 rpm
ø209 ISO 9906
60
NPSH 5m
55 Limite max suggerito
Max suggested limit
50

45

40

35

30

25

20 Nella scelta del modello di pompa sommare il flusso di


ricircolo (vedi tabella in calce) alla portata di progetto.
15 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
10
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 Q [m³/h]

P2
[kW]
ø219 NPSH
60
50 ø215 [m]
40 ø209 16
30 12
ø209 (NPSH) ø219 (NPSH)
20 8
10 4
0 0
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 100-200/209 45,0 77,0 5,0 z 48,2 (53,0) 5,0 CM 3-10 1,20 2,60
Hydro EN 100-200/215 55,0 93,0 5,0 z 66,8 (73,5) 6,0 CM 3-10 1,20 2,60
Hydro EN 100-200/219 75,0 134,0 5,0 z 66,8 (73,5) 6,0 CM 3-10 1,20 2,60
TM06 6139 0816

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

30
15

Performance curves and technical data


H
[m] Hydro EN
125-250.1
100 2950 rpm
ø263 ISO 9906
NPSH 5m
90
ø251
Limite max suggerito
80 Max suggested limit
ø238

70

60

50

40

30

20 Nella scelta del modello di pompa sommare il flusso di


ricircolo (vedi tabella in calce) alla portata di progetto.
10 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
0
0 50 100 150 200 250 300 350 400 450 500 550 Q [m³/h]

P2
[kW] ø263
ø251
100 NPSH
ø238
80 [m]
60 16
ø238 (NPSH)
40 12
ø263 (NPSH)
8
20
4
0 0
0 50 100 150 200 250 300 350 400 450 500 550 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 125-250.1/238 90,0 151,0 9,0 z 95,3 (104,8) 9,0 CM 3-12 1,58 3,10
Hydro EN 125-250.1/251 110,0 191,0 9,0 z 132,0 (145,0) 9,0 CM 3-12 1,58 3,10
Hydro EN 125-250.1/263 132,0 236,0 9,0 z 132,0 (145,0) 9,0 CM 3-13 1,58 3,10
TM06 6140 0816

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

31
15
Performance curves and technical data

H
[m] Hydro EN
110 125-250
NPSH 5m 2950 rpm
105 ø269
ISO 9906

100
95 ø255
90
85 ø245

80
ø237
75
70
65

60
55
Nella scelta del modello di pompa sommare il flusso di
50
ricircolo (vedi tabella in calce) alla portata di progetto. Limite max suggerito
45 When choosing the pump model, the by-pass flow Max suggested limit
(see table at the bottom) must be added to the design flow rate.
40
0 50 100 150 200 250 300 350 400 450 500 550 600 Q [m³/h]

P2
ø269
[kW]
160 ø255
140 NPSH
ø245
120 ø237 [m]
100
80 16
60 12
ø269 (NPSH) ø237 (NPSH)
40 8
20 4
0 0
0 50 100 150 200 250 300 350 400 450 500 550 600 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 125-250/237 110,0 191,0 9,0 z 132,0 (145,0) 9,0 CM 3-12 1,58 3,10
Hydro EN 125-250/245 132,0 236,0 9,0 z 132,0 (145,0) 9,0 CM 3-12 1,58 3,10
Hydro EN 125-250/255 160,0 282,0 9,0 z 179,0 (197,0) 9,0 CM 3-13 1,58 3,10
TM06 6141 0816

Hydro EN 125-250/269 200,0 356,0 9,0 z 202,0 (222,0) 9,0 CM 3-14 2,20 4,10

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

32
15

Performance curves and technical data


H
[m] ø316 Hydro EN
140 NPSH 5m
125-315
ø302 2950 rpm
130 ISO 9906
120 ø289

110

100
90
80

70
60

50
Limite max suggerito
40 Max suggested limit
30
Nella scelta del modello di pompa sommare il flusso di
20
ricircolo (vedi tabella in calce) alla portata di progetto.
10 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
0
0 50 100 150 200 250 300 350 400 450 500 550 Q [m³/h]

P2
[kW] ø316
180
160 ø302
140
NPSH
ø289 [m]
120
100
80 ø316 (NPSH) 16
60 12
ø289 (NPSH)
40 8
20 4
0 0
0 50 100 150 200 250 300 350 400 450 500 550 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Elettropompa Ricircolo Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Electric pump By-pass Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. P [kW] I1/1 [A] Qmin [m³/h] [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 125-315/289 132,0 236,0 9,0 z 132,0 (145,0) 9,0 CR 3-21 2,20 4,45
Hydro EN 125-315/302 160,0 282,0 9,0 z 179,0 (197,0) 9,0 CR 3-23 2,20 4,45
Hydro EN 125-315/316 200,0 356,0 9,0 z 202,0 (222,0) 9,0 CR 3-23 2,20 4,45
TM06 6142 0816

{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

33
15
Performance curves and technical data

H
[m]
130 Hydro EN
ø420 150-400.2
120 ø418 2100 rpm
ø398 NPSH 5m
110 ISO 9906
ø384
Limite max suggerito
100
ø366 Max suggested limit
90 ø351

80

70

60

50

40

30

20 Nella scelta del modello di pompa sommare il flusso di


ricircolo (vedi tabella in calce) alla portata di progetto.
10 When choosing the pump model, the by-pass flow
(see table at the bottom) must be added to the design flow rate.
0
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]

P2
[kW]
ø420
240
ø418 NPSH
ø398
200 ø384 [m]
ø366
160 ø351 20
120 15
ø420 (NPSHR)
80 10
ø351 (NPSHR)
40 5
0 0
0 100 200 300 400 500 600 700 800 900 1000 Q [m³/h]

Il tratto in grassetto della curva indica prestazioni ( Q - H )FRQ136+Uá


Le condizioni in aspirazione del sistema (es.: perdite di carico, livello minimo vasca, ecc.) devono garantire il
rispetto del punto di norma EN 12845 (10.6.2.1): NPSHD â NPSHR + >P@
Contattare Grundfos per prestazioni eccedenti il limite max. suggerito riportato nel grafico.

The bold part of the curve indicates the performances ( Q - H )ZLWK136+U”


The system suction conditions (i.e.: friction loss, minimun water level, etc.) must allow to respect the following
norm prescription EN 12845 (10.6.2.1): NPSH D • NPSH R + >P@
Please contact Grundfos, for performance exceeding the max. suggested limit shown in the chart.

Gruppo pompaggio Motopompa Ricircolo Pompa mantenimento pressione


Pumping set Diesel Pump By-pass Jockey pump
Na (Nb)
Mod. [kW] Qmin [m³/h] Mod. P [kW] I1/1 [A]
Hydro EN 150-400.2/351 z 164,0 (180,0) 7,0 CM 3-13 1,58 3,10
Hydro EN 150-400.2/366 z 187,0 (206,0) 7,0 CM 3-13 1,58 3,10
Hydro EN 150-400.2/384 z 263,6 (290,0) 18,0 CM 3-14 2,20 4,10
TM06 6143 0816

Hydro EN 150-400.2/398 z 263,6 (290,0) 18,0 CM 3-14 2,20 4,10


Hydro EN 150-400.2/418 z 263,6 (290,0) 18,0 CM 3-14 2,20 4,10
Hydro EN 150-400.2/420 z 263,6 (290,0) 18,0 CR 3-21 2,20 4,45
{ Motore diesel raffreddato ad Aria / Diesel engine Air cooled z Motore disele raffreddamento a liquido / Diesel engine Liquid cooled

34
Hydro EN
16

16. Documentation

Documentation
All pump sets are delivered with the following
documents in hard copy:
• installation and operating instructions for the pump
set with EC declaration of conformity
• installation and operating instructions for the
electrical-driven duty pumps
• installation and operating instructions for the
electrical-driven jockey pumps
• installation and operating instructions for the
pressure switches
• electrical diagrams of the control panels
• assembling and setting verification
• two copies of the nameplate of the pump set in
addition to the one on the base frame of the pump
set
• pump performance curves.
If available, the kit for measuring the flow rate is
supplied with the installation and operating instructions
of the flowmeter.
If a diesel-driven pump is available, the following
documents are also delivered:
• installation and operating instructions for the diesel
engine
• safety data sheet for the batteries
• factory test report for the diesel-driven pump as
described in the EN 12845 standard.
If you need specific documents or any additional hard
or digital copies of the documents listed above, please
request these in the bidding process.

35
Hydro EN
17

17. Grundfos Product Center


Grundfos Product Center

Online search and sizing tool to help you


make the right choice.

http://product-selection.grundfos.com

"SIZING" enables you to "REPLACEMENT" enables you to find a


size a pump based on replacement product. Search results will include
entered data and information on the following:
selection choices.
• the lowest purchase price
• the lowest energy consumption
• the lowest total life cycle cost.

"CATALOGUE" gives you "LIQUIDS" enables you to find pumps


access to the Grundfos designed for aggressive, flammable
product catalogue. or other special liquids.

All the information you need in one place Downloads


Performance curves, technical specifications, pictures, dimensional drawings, motor On the product pages, you can download
curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. installation and operating instructions, data
The Product Center displays any recent and saved items - including complete projects - booklets, service instructions, etc. in PDF format.
right on the main page.

Subject to alterations.

36
37
38
39
ECM: 1181214
99001958 0416

GRUNDFOS A/S

www.grundfos.com
Telephone: +45 87 50 14 00
DK-8850 Bjerringbro . Denmark
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S