29-120F
Page 1
October 1997
Series C®
Mailed to: E, D, C/29-100A, 31-400A,
31-500A
Molded Case
Circuit Breakers
F-Frame
10-225 Amperes
Dimensions, Inches (mm) STANDARDS
No. of Poles Width Height Depth
Series C molded case circuit breakers are
1 1.375 (35) 6 (152) 3.375 (86) designed to conform with the following
2 2.75 (70) 6 (152) 3.375 (86) standards:
3 4.125 (105) 6 (152) 3.375 (86)
4 5.5 (140) 6 (152) 3.375 (86) • Australian Standard AS 2184, Molded
Case Circuit Breakers
Approximate Shipping Weight, Lbs. (kg) • British Standards Institution Standard BS
Breaker Number of Poles 4752: Part 1, Switchgear and Control
Type Gear Part 1: Circuit Breakers
1 2 3 4
ED, EDH, — 3 4.5 — • Canadian Standards Association
EDC (1.361) (2.041) Standard C22.2 No. 5, Service Entrance
EHD, FDB, 2 3 4.5 6 and Branch Circuit Breakers
FD, HFD (.907) (1.361) (2.041) (2.721) • International Electrotechnical Commis-
FDC — 3.25 4.75 6.35 sion Recommendations IEC 157-1, Circuit
(1.474) (2.155) (2.880) Breakers
INTERRUPTING CAPACITY RATINGS HFDDC — — 4.5
(2.041)
—
• Japanese T-Mark Standard Molded Case
Circuit Breakers
UL489 Interrupting Capacity Ratings
• National Electrical Manufacturers
Circuit Number Interrupting Capacity (Symmetrical Amperes) Association Standards Publication No.
Breaker of Volts Ac (50/60 Hz) Volts Dc➄ AB1-1993, Molded Case Circuit Breakers
Type Poles
240 277 480 600 125 250➀➁ • South African Bureau of Standards,
Standard SABS 156, Standard Specifica-
ED 2, 3 65,000 ...... ...... ...... 10,000 ......
EDH 2, 3 100,000 ...... ...... ...... 10,000 ...... tion for Molded Case Circuit Breakers
EDC 2, 3 200,000 ...... ...... ...... 10,000 ...... • Swiss Electro-Technical Association
EHD 1 ...... 14,000 ...... ...... 10,000 ...... Standard SEV 157-1, Safety Regulations
2, 3 18,000 ...... 14,000 ...... ...... 10,000 for Circuit Breakers
FDB 2, 3, 4 18,000 ...... 14,000 14,000 ...... 10,000
• Underwriters Laboratories, Inc., Stan-
FD 1 ...... 25,000 ...... ...... 10,000 ...... dard UL 489, Molded Case Circuit
2, 3, 4 65,000 ...... 25,000 18,000 ...... 10,000
Breakers and Circuit Breaker Enclosures,
HFD 1 ...... 65,000 ...... ...... 10,000 ...... including Marine Circuit Breakers File
2, 3, 4 100,000 ...... 65,000 25,000 ...... 22,000 E7819
•
FDC 2, 3, 4 200,000 ...... 100,000 35,000 ...... 22,000
Union Technique de l’Electricite Stan-
HFDDC➂ 3 ...... ...... ...... ...... ...... 42,000➃
dard NF C 63-120, Low Voltage
IEC 157-1 Interrupting Capacity Ratings (P1) Switchgear and Control Gear Circuit
Breaker Requirements
•
Circuit Number Interrupting Capacity (Symmetrical Amperes)
Breaker of Verband Deutscher Elektrotechnike
Volts Ac (50/60 Hz) Volts Dc➄ (Association of German Electrical Engi-
Type Poles
220, 240 380, 415 440 500 125 250➀ neers) Standard VDE 0660, Low Voltage
ED 2, 3 65,000 ...... ...... ...... 10,000 ......
Switchgear and Control Gear, Circuit
EDH 2, 3 100,000 ...... ...... ...... 10,000 ...... Breakers
EDC 2, 3 200,000 ...... ...... ...... 10,000 ......
FDB 2, 3, 4 18,000 14,000 14,000 14,000 ...... 10,000 Conformance with these standards satisfies
most local and international codes, assum-
FD 1 25,000 ...... ...... ...... 10,000 ......
2, 3, 4 65,000 35,000 35,000 18,000 ...... 10,000 ing user acceptability and simplified appli-
cation.
HFD 1 65,000 ...... ...... ...... 10,000 ......
2, 3, 4 100,000 65,000 65,000 25,000 ...... 22,000
Series C molded case circuit breakers equal
FDC 2, 3, 4 200,000 100,000 100,000 35,000 ...... 22,000
or exceed Federal Specification Classifica-
➀ 2-pole circuit breaker, or two poles of 3-pole circuit breaker. tion W-C-375b requirements for the particu-
➁ Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA. lar class associated with the circuit breaker
➂ HFDDC is UL only and is not tested to other standards. frame being considered.
➃ Interrupting rating is 35,000 amps at 600-volt Dc with 3 poles in series, for ungrounded systems only.
➄ Dc ratings apply to substantially non-inductive circuits.
Selection Data
29-120F
Page 2
Circuit Breaker Number of Trip Suffix Circuit Breaker Number of Trip Suffix
Type Poles Amps Type Poles Amps
EHD 1: 1-Pole 10 E: 100% Protected (4 P only) ED 2: 2-Pole 100 L: Line and Load Terminals
FDB 2: 2-Pole 15 Neutral Pole EDH 3: 3-Pole 125 W: Without Terminals
FD 3: 3-Pole 20 EH: 50% Protected (4 P only) EDC 150 Y: Line Terminals Only
HFD 4: 4-Pole 25 K: High Mag Molded Case Sw. 175 Z: Alum. Terminals
FDC 30 L: Line and Load Terminals 200
HFDDC 35 S: Stainless Steel Terminals 225
40 V: 50°C Calibration
45 W: Without Terminals
50 Y: Line Terminals Only
60 Z: Alum. Terminals
70
80
90
100
110
125
150
175 (FD, HFD, FDC 2-, 3-, 4-Pole Only)
200 (FD, HFD, FDC 2-, 3-, 4-Pole Only)
225 (FD, HFD, FDC 2-, 3-, 4-Pole Only)
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 3
October 1997
Series C®
Mailed to: E, D, C/29-100A, 31-400A,
31-500A
Molded Case
Circuit Breakers
F-Frame
10-225 Amperes
THERMAL-MAGNETIC CIRCUIT BREAKERS
Sealed Breakers with Non-interchangeable Trip Units
Maximum 277 Vac Maximum, 125 Vdc 480 Vac Maximum, 250 Vdc
Continuous 14 kAIC @ 277 Vac 14 kAIC @ 480 Vac
Ampere
Rating Type EHD
@ 40°C 1-Pole 2-Pole 3-Pole
CATALOG NUMBERS (Includes Terminals on Load End Only)
10➀ EHD1010 EHD2010 EHD3010
15 EHD1015➁ EHD2015 EHD3015
20 EHD1020➁ EHD2020 EHD3020
25 EHD1025 EHD2025 EHD3025
30 EHD1030 EHD2030 EHD3030
35 EHD1035 EHD2035 EHD3035
40 EHD1040 EHD2040 EHD3040
45 EHD1045 EHD2045 EHD3045
50 EHD1050 EHD2050 EHD3050
60 EHD1060 EHD2060 EHD3060
70 EHD1070 EHD2070 EHD3070
80 EHD1080 EHD2080 EHD3080
90 EHD1090 EHD2090 EHD3090
100 EHD1100 EHD2100 EHD3100
Maximum 600 Vac Maximum, 250 Vdc 277 Vac Maximum, 125 Vdc 600 Vac Maximum, 250 Vdc
Continuous 65 kAIC @ 277 Vac 65 kAIC @ 480 Vac 100 kAIC @ 480 Vac
Ampere
Rating Type HFD Type FDC Current Limiting
@ 40°C 1-Pole 2-Pole 3-Pole 4-Pole 2-Pole 3-Pole 4-Pole
CATALOG NUMBERS (Includes Terminals on Load End Only)
15 HFD1015 HFD2015 HFD3015 HFD4015 FDC2015 FDC3015 FDC4015
20 HFD1020 HFD2020 HFD3020 HFD4020 FDC2020 FDC3020 FDC4020
25 HFD1025 HFD2025 HFD3025 HFD4025 FDC2025 FDC3025 FDC4025
30 HFD1030 HFD2030 HFD3030 HFD4030 FDC2030 FDC3030 FDC4030
35 HFD1035 HFD2035 HFD3035 HFD4035 FDC2035 FDC3035 FDC4035
40 HFD1040 HFD2040 HFD3040 HFD4040 FDC2040 FDC3040 FDC4040
45 HFD1045 HFD2045 HFD3045 HFD4045 FDC2045 FDC3045 FDC4045
50 HFD1050 HFD2050 HFD3050 HFD4050 FDC2050 FDC3050 FDC4050
60 HFD1060 HFD2060 HFD3060 HFD4060 FDC2060 FDC3060 FDC4060
70 HFD1070 HFD3070 HFD3070 HFD4070 FDC2070 FDC3070 FDC4070
80 HFD1080 HFD2080 HFD3080 HFD4080 FDC2080 FDC3080 FDC4080
90 HFD1090 HFD2090 HFD3090 HFD4090 FDC2090 FDC3090 FDC4090
100 HFD1100 HFD2100 HFD3100 HFD4100 FDC2100 FDC3100 FDC4100
110 HFD1110 HFD2110 HFD3110 HFD4110 FDC2110 FDC3110 FDC4110
125 HFD1125 HFD2125 HFD3125 HFD4125 FDC2125 FDC3125 FDC4125
150 HFD1150 HFD2150 HFD3150 HFD4150 FDC2150 FDC3150 FDC4150
175 — HFD2175 HFD3175 HFD4175 FDC2175 FDC3175 FDC4175
200 — HFD2200 HFD3200 HFD4200 FDC2200 FDC3200 FDC4200
225 — HFD2225 HFD3225 HFD4225 FDC2225 FDC3225 FDC4225
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 5
October 1997
Series C®
Mailed to: E, D, C/29-100A, 31-400A,
31-500A
Molded Case
Circuit Breakers
F-Frame
10-225 Amperes
MOLDED CASE SWITCHES CIRCUIT BREAKERS FOR DC
APPLICATIONS
Molded case switches are used as compact Molded Case Switch High Magnetic
switches in applications requiring high Trip Setting These UL listed Dc Molded Case Circuit
current switching capabilities. Molded case Frame Rating Trip Tolerance Breakers are for use in the ungrounded bat-
switches are constructed of circuit breaker Setting (Amps) (Percent) tery supply circuits of UPS systems providing
components and are of the high instanta- continuous, reliable Ac power to computer
EHD, FD 100 2400 ±20
neous automatic type. Molded case switches EHD, FD 150 2400 ±20 controlled applications such as financial
are listed in accordance with Underwriters FD 225 2400 ±20 transactions and telecommunications.
Laboratories, Inc., Standard UL1087.
Maxi- High Interrupting Capacity
Maximum 480 Vac Maximum, 250 Vdc 600 Vac Maximum, 250 Vdc mum 35 kAIC @ 600 Vdc
Continuous Complete Circuit Breaker Complete Circuit Breaker Contin-
Ampere uous
with Load Side Terminals Only with Load Side Terminals Only Complete Circuit Breaker
Rating Ampere
@ 40°C CATALOG NUMBERS with Line and Load Side Terminals
Rating
2-Pole @ 40°C CATALOG NUMBERS
100 EHD2100K FD2100K 1-Pole 2-Pole 3-Pole
150 — FD2150K 15 HFDDC1015L HFDDC2015L HFDDC3015L
225 — FD2225K 20 HFDDC1020L HFDDC2020L HFDDC3020L
3-Pole 25 HFDDC1025L HFDDC2025L HFDDC3025L
30 HFDDC1030L HFDDC2030L HFDDC3030L
100 EHD3100K FD3100K
150 — FD3150K 35 HFDDC1035L HFDDC2035L HFDDC3035L
225 — FD3225K 40 HFDDC1040L HFDDC2040L HFDDC3040L
4-Pole 45 HFDDC1045L HFDDC2045L HFDDC3045L
100 — FD4100K 50 HFDDC1050L HFDDC2050L HFDDC3050L
150 — FD4150K
225 — FD4225K 60 HFDDC1060L HFDDC2060L HFDDC3060L
70 HFDDC1070L HFDDC2070L HFDDC3070L
80 HFDDC1080L HFDDC2080L HFDDC3080L
90 HFDDC1090L HFDDC2090L HFDDC3090L
LOAD
LOAD
Selection Data
29-120F
Page 6
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 7
Westinghouse
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Termination
Accessories
LINE AND LOAD TERMINALS
Line and load terminals provide wire specified, F-frame circuit breakers are fac- terminals (same as standard load-end ter-
connnecting capabilities for specific ranges tory equipped with load terminals only. minals) are required, add suffix L to the
of continuous current ratings and wire circuit breaker catalog number. When non-
types. Except as noted, terminals comply Ordering Information standard or optional line and/or load termi-
with Underwriters Laboratories, Inc., Stan- F-frame circuit breakers and molded case nals are required, order by style number.
dard UL486A or UL486B. Unless otherwise switches have load terminals only as stan- Specify if factory installation required.
dard equipment. When standard line-end
Collar
Screw Collar
Nut
Clip
Collar
Conductor
Collar
Washer
Washer
Conductor
Screw Screw
Assemble collar on top of conductor as Collar slides onto conductor and is held in Assemble collar on top of conductor as
shown. Tighten securely with screw and position by a screw and lockwasher. shown. Tighten securely with screw and
washer. washer. Terminal shield must be used with
this collar.
The keeper nut slides onto the line or load Imperial Thread
conductor of the circuit breaker and acts as No. of Description Type of STYLE
a threaded adapter for the conductor to Poles Mounting NUMBERS
accept a ring terminal or other bolt-on 1 .164-32 x 3.188 Individual 624B375G01
connector. The keeper nut is available with inch Pan-Head
English and metric thread sizes. Screws and Steel Screws, Group (one set of 624B375G02
Lockwashers, hardware for two
washers are supplied by customer. (Field and Clamps circuit breakers)
installation only.) Listed per UL File E7819. For use with steel or stainless steel➀ termi-
nals only. 2 .164-32 x 1.5 Individual 4218B80G01
inch Pan-Head
Ordering Information Steel Screws
Ordering Information and
Thread Type Thread Size CATALOG NUMBERS Package of 12. Priced individually. Lockwashers
Package of 12 3,4 .164-32 x 1.5 Individual BMH1
CATALOG NUMBER
(Priced Individually) inch Pan-Head
FCWTK Steel Screws
Imperial 10-32 KPR1A and
Metric M-5 KPR1AM Lockwashers
Metric Thread
MULTI WIRE CONNECTORS No. of Description Type of STYLE
Poles Mounting NUMBERS
Multi Wire Lug Kits include mounting hard- 1 M4 - 0.7 x Individual 4218B80G09
80 mm Pan-
ware, insulators and tin-plated aluminum Head Steel Group (one set of 4218B80G10
connectors to replace three mechanical Screws, Lock- hardware for two
load lugs. UL listed for copper only as used washers, circuit breakers)
on the load side (OFF) end. and Clamps
2 M4 - 0.7 x Individual 4218B80G11
38 mm Pan-
Ordering Information Head Steel
Package of 3. Screws and
Lockwashers
Maximum KIT Wires Wire Pressure
Amperes CATALOG Per Size Screw 3,4 M4 - 0.7 x Individual BMH1M
NUMBERS Terminal Range Torque 38 mm Pan-
Field-installed multi wire connectors for the AWG Cu (lb/in) Head Steel
load side (OFF) end terminals. They are Screws and
225 3TA150F3K 3 #14-2 70 Lockwashers
used to distribute the load from the circuit
225 3TA150F6K 6 #14-6 25
breaker to multiple devices without the use
of separate distribution terminal blocks.
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 9
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Termination
Accessories
TERMINAL SHIELDS TERMINAL END COVERS INTERPHASE BARRIERS
The terminal shield provides protection The terminal end covers are designed for The interphase barriers provide additional
against accidental contact with live line ter- use in motor control center applications electrical clearance between circuit breaker
minations. Terminal shields are formed where, because of confined spaces, line poles for special termination applications.
from high dielectric insulating material and side conductors are normally custom fitted. The barriers are high dielectric insulating
fasten over the front terminal access open- The molded end covers are made of high plates that are installed in the molded slots
ings. Small holes in the shields provide dielectric glass-polyester and slide over the between the terminals. Interphase barriers
limited access to the terminals for tighten- line ends of the circuit breaker. Close fitting are listed per UL File E7819. (Field installa-
ing connectors. Terminal shields are listed conductor openings are molded into the tion only.)
per UL File E7819. (Field installation only.) end covers. The end cover and circuit
breaker case fit together to form terminal Ordering Information
Ordering Information compartments that isolate discharged ioniz- The interphase barrier is available for
The terminal shield is available for line ter- ing gases during circuit breaker tripping. extended insulation between circuit breaker
minal areas in 1-, 2-, 3- and 4-pole circuit Terminal end covers are available with two poles. Specify quantity when ordering.
breakers. Special terminal shields are also conductor opening diameters, 0.25 and 0.41
available for use when an electrical (sole- inch, and are listed per UL File E7819. (Field CATALOG NUMBER
noid) operator is mounted on the circuit installation only.)
IPB1 (Package of 2 barriers)
breaker. The standard style number by pole
for each terminal shield (shown in table Ordering Information
below) is for a package of 10. Special termi- The terminal end cover is available for 3-
nal shields are packaged individually. pole circuit breakers only. Two conductor
opening sizes are available. Specify quan-
Number STYLE NUMBERS tity (one per circuit breaker) when ordering.
of Poles Standard Special
(Package of 10) Conductor Opening CATALOG
(Priced Individually) Diameter (Inches) NUMBERS
1 625B229G06 .......... 0.25 (6.35 mm) TEC1
2 625B229G07 .......... 0.41 (10.41 mm) TEC2
3 625B229G08 4210B95G01
4 625B229G09 4210B95G02
Selection Data
29-120F
Page 10
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 11
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Accessories
GENERAL INFORMATION
All internal accessories are of the plug-in
type and are listed for field installation
under UL File E64983.➀ Internal accessories
for sealed circuit breakers are listed under
UL File E7819 for factory installation only.
The available plug-in accessories include
the following:
Different combinations of accessories can be supplied, depending on the types of accessories and the number of poles in the circuit breaker.
Reference 1-Pole 2-Pole 3-Pole 4-Pole
Termination Accessories Page Ctr. Lt. Rt. Lt. Ctr. Rt. Lt. Ctr. Rt. Neu.
Internal Accessories
Alarm Lockout Switch (Make Only) 13 ■
Alarm Lockout (Make/Break) 13 ■ ❏ ❏ ■
Alarm Lockout (2Make/2Break) 13 ■ ❏ ❏ ■
Auxiliary Switch (1A, 1B) 14 ■ ■ ■ ■ ■
Auxiliary Switch (2A, 2B) 14 ■ ■ ■ ■ ■
Auxiliary Switch/Alarm Lockout 14 ■ ❏ ❏ ■
Shunt Trip–Standard 15 ■ ■ ■ ■ ■
Shunt Trip–Low Energy 16 ■ ■ ■ ■
Undervoltage Release Mechanism 17 ■ ■ ■ ■
External Accessories
Non-Padlockable Handle Block 19 ■ ■ ■ ■
Snap On Padlockable Handle Lock Hasp 19 ■ ■ ■ ■
Padlockable Handle Lock Hasp 19 ■ ❏ ❏ ❏ ❏
Cylinder Lock 20 ■
Key Interlock Kit 20 ■ ❏ ❏ ❏ ❏
Sliding Bar Interlock–Requires 2 Breakers 20 ●
Walking Beam Interlock–Requires 2 Breakers 21 ● ●
Electrical (Solenoid) Operator 21 ● ●
IQ Energy Sentinel 22 ● ●
LFD Current Limiter 22 ●
Plug-In Adapters 22 ● ● ●
Rear Connecting Studs 23 ● ● ● ●
Panelboard Connecting Straps 23 ● ● ● ●
Handle Mechanism 25-28 ●
Door Hardware/Accessories 27 ● ●
FiveMarine
ParkwayApplication
Center 29 ● ● ● ●
Pittsburgh,
■ Pennsylvania,
Applicable in indicated U.S.A. 15220
pole position ● Accessory available/Modification available ❏ May be mounted on left or right pole – not both
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220 Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 13
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Internal
Accessories
ALARM (SIGNAL)/LOCKOUT SWITCH
Electrical Rating Data➀➁
Make
Maximum Frequency Maximum Dielectric
Voltage Current Withstand
Break Amps Voltage
Multi-Pole Circuit Breakers
600 50/60 Hz 6 2500
125 dc 0.5➂ 2200
250 dc 0.25➂ 2200
Single-Pole Circuit Breakers
125/250 50/60 Hz 6➂ 2000
28 dc 3➂ 2000
28 dc 5➃ 2000
Ordering Information
Auxiliary Switch
Number of Mounting Factory Mounted Field Mounted
Contacts Location
Connection Type and Location Field Installation Kits➄
The auxiliary switch provides circuit breaker a and b (Pole)
18-Inch Pigtail Leads Terminal Pigtail Terminal
contact status information by monitoring Block Leads Block
the position of the molded cross bar which
Same Rear➅ Opposite Same
contains the moving contact arms. The
Side Side Side
auxiliary switch is used for remote indica-
tion and interlock system verification, and CATALOG NUMBERS CATALOG NUMBERS
consists of one or two SPDT switches 1 Left➁ A1X1LA A1X1LB A1X1LC A1X1LT A1X1PK A1X1LTK
housed in a plug-in module. Each SPDT E1X1LA➆ E1X1LB➆ E1X1LC➆ ...... E1X1PK ......
switch has one “a” and one “b” contact. Right or A1X1RA A1X1RB A1X1RC A1X1RT A1X1PK A1X1RTK
Neutral E1X1RA➆ E1X1RB➆ E1X1RC➆ ...... ...... ......
When the circuit breaker contacts are open,
the “a” contact is open and the “b” contact 2 Left ➁ A2X1LA A2X1LB . . . . . . A2X1LT A2X1LPK A2X1LTK
is closed. E2X1LA➆ E2X1LB➆ . . . . . . ...... E2X1LPK ......
Right or A2X1RA A2X1RB . . . . . . A2X1RT A2X1RPK A2X1RTK
Neutral E2X1RA➆ E2X1RB➆ . . . . . . ...... E2X1RPK ......
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 15
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Internal
Accessories
SHUNT TRIP
Electrical Rating Data➀➁➂
ST 50/60 Hz Dc
c Supply Minimum VA Supply Minimum VA
Voltage Operating Voltage Operating
Voltage Voltage
12 6.75 75 12 9 400
24 300 24
48 36 92 48 36 100
60 140 60 160
110 480
120 570
127 640
208 156 180 110 165 55
220 200 120 66
240 240 125 71
380 610 127 72
The shunt trip provides remote controlled 415 300 130 220 . . . 110
tripping of the circuit breaker. The shunt 440 330 250 . . . 140
trip consists of an intermittent rated sole- 480 380 ... . . . ...
noid with a tripping plunger and a cutoff 525 450 ... . . . ...
switch mounted in a plug-in module. The 550 530 ... . . . ...
600 590 ... . . . ...
120 Vac shunt trip is marked, “suitable for
700 ... . . . ...
use with ground fault protection devices.”
Ordering Information
Select shunt trip catalog number for the voltage within the indicated voltage range. Shunt
trip coils are designed to be applied at specific Ac or Dc voltages within the voltage range
shown. Electrical ratings are also shown on applicable circuit breaker accessory nameplates.
Shunt Trip
Voltage Rating Factory Mounted Field Mounted
(Ac Freq = 50/60 Hz)
Connection Type and Location Field Installation Kits➃
18-Inch Pigtail Leads➄ Terminal Pigtail Terminal
Block Leads Block
Same Rear➅ Opposite Same
Side Side Side
CATALOG NUMBERS CATALOG NUMBERS
Left-Pole Mounting Ac/Dc Ratings
12-24 Vac or Vdc SNT1LA03 SNT1LB03 SNT1LC03 SNT1LT03 SNT1LP03K SNT1LT03K
48-127 Vac or 48-60 Vdc➆ SNT1LA08 SNT1LB08 SNT1LC08 SNT1LT08 SNT1LP08K SNT1LT08K
208-380 Vac or 110-127 Vdc SNT1LA12 SNT1LB12 SNT1LC12 SNT1LT12 SNT1LP12K SNT1LT12K
415-600 Vac or 220-250 Vdc SNT1LA18 SNT1LB18 SNT1LC18 SNT1LT18 SNT1LP18K SNT1LT18K
Right- or Neutral-Pole Mounting Ac/Dc Ratings➇
9-24 Vac or Vdc SNT1RA03 SNT1RB03 SNT1RC03 SNT1RT03 SNT1RP03K SNT1RT03K
➀ Average unlatching time: 6 milliseconds.
48-127 Vac or 48-60 Vdc➆ SNT1RA08 SNT1RB08 SNT1RC08 SNT1RT08 SNT1RP08K SNT1RT08K
➁ Average circuit breaker contact total
208-380 Vac or 110-127 Vdc SNT1RA12 SNT1RB12 SNT1RC12 SNT1RT12 SNT1RP12K SNT1RT12K
opening time: 18 milliseconds.
415-600 Vac or 220-250 Vdc SNT1RA18 SNT1RB18 SNT1RC18 SNT1RT18 SNT1RP18K SNT1RT18K
➂ Endurance: 6000 electrical operations
plus 4000 mechanical operations.
➃ Not listed with Underwriters Laboratories, Inc.,
for field installation.
➄ Pigtail wire size: No. 18 AWG (0.82 mm2).
➅ Standard pigtail lead exit location.
➆ 120 Vac marked suitable for ground fault
protection devices.
➇ Standard mounting location.
Selection Data
29-120F
Page 16
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 17
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Internal
Accessories
UNDERVOLTAGE RELEASE MECHANISM
Electrical Rating Data➀
50/60 Hz Dc
UV
Supply Dropout Pickup VA Supply Dropout Pickup VA
Voltage Voltage Voltage Voltage Voltage Voltage
Min. Max. Max. Min. Max. Max.
12 4.2 6.3 7.6 1.3 12 4.2 8.4 10.2 2.8
2.5
24 8.4 16.8 20.4 1.4 24 8.4 16.8 20.4 1.6
48 21 33.6 40.8 1.2 48 21 33.6 40.8 1.3
60 1.9 60 2.0
110 44.5 77 93.5 1.3 110 44.5 77 93.5 1.5
120 1.5 120 1.7
127 1.7 125 1.9
The undervoltage release mechanism
208 84 145.6 176.8 2.2 220 87.5 154 187 2.6
monitors a voltage (typically a line voltage) 220 2.4 250 3.4
and trips the circuit breaker when the volt- 240 2.9 ... ... ... ... ...
age falls to between 70 and 35 percent of
380 168 266 323 2.9 ... ... ... ... ...
the solenoid coil rating. 415 3.5 ... ... ... ... ...
440 3.9 ... ... ... ... ...
The undervoltage release mechanism con-
480 4.6
sists of a continuous rated solenoid with a
plunger and tripping lever mounted in a 525 210 367 446 4.3 ... ... ... ... ...
550 4.8 ... ... ... ... ...
plug-in module. The tab on the tripping 600 5.8 ... ... ... ... ...
lever resets the undervoltage release
mechanism when normal voltage has been
restored and the circuit breaker handle is
moved to the reset (or OFF) position. With
less than pickup voltage applied to the
undervoltage release mechanism, the cir-
cuit breaker contacts will not touch when a
closing operation is attempted.
NOTE: Undervoltage release mechanism
accessories are not designed for,
and should not be used as, circuit
interlocks.
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 19
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
External
Accessories
NON-PADLOCKABLE HANDLE BLOCK SNAP ON PADLOCKABLE HANDLE PADLOCKABLE HANDLE LOCK HASP
LOCK HASP
The nonlockable handle block secures the The snap on padlockable handle lock allows The padlockable handle lock hasp allows
circuit breaker handle in either the ON or the handle to be locked in the OFF or ON the handle to be locked in the ON or OFF
OFF position. (Trip-free operation allows position. (Trip-free operation allows the position. (Trip-free operation allows the
the circuit breaker to trip when the handle circuit breaker to trip when the handle lock circuit breaker to trip when the handle lock
block holds the circuit breaker handle in the holds the circuit breaker handle in the ON holds the circuit breaker handle in the ON
ON position.) The device is positioned over position.) This device was designed for use position.) The hasp mounts on the circuit
the circuit breaker handle and secured by a on the 1-pole circuit breaker, but may be breaker cover within the trimline. The cover
setscrew to deter accidental operation of used on 1-, 2-, 3-, and 4-pole styles. The is predrilled on both sides of the operating
the circuit breaker handle. Listed per UL handle lock snaps onto the escutcheon area handle so that the hasp can be mounted on
File E7819. (Field installation only.) of the handle with an optional retaining either side of the handle. The hasp will
screw for added secureness. The handle accommodate up to three padlocks with
1
Ordering Information lock will accommodate one padlock with a ⁄4 inch (6 mm) shackles. Listed per UL File
1
⁄4 inch (6 mm) shackle. Listed per UL File E7819. (Field installation only.)
CATALOG NUMBER
E7819. (Field installation only.)
LKD1 The padlockable handle lock can be
Ordering Information mounted on either side of the operating
handle. One per circuit breaker. (Field
CATALOG NUMBER
installation only.)
PHL1
Ordering Information
CATALOG NUMBER
2-, 3-, 4-pole breakers PLK1
Selection Data
29-120F
Page 20
➤➤
The cylinder lock internally blocks the trip The key interlock is used to externally lock The sliding bar interlock provides mechani-
bar in the tripped position to prevent the the circuit breaker handle in the OFF posi- cal interlocking between two adjacent 3-
circuit breaker from being switched to ON. tion. When the key interlock is locked, an pole circuit breakers. It is installed on the
The cylinder lock is factory installed in the extended deadbolt blocks movement of the enclosure cover between the circuit break-
circuit breaker cover. Other internally circuit breaker handle. Uniquely coded keys ers. When the sliding bar interlock handle is
mounted accessories cannot be installed in are removable only with the deadbolt moved from one side to the other, a bar
the same pole as the cylinder lock. (Factory extended. Each coded key controls a group extends to alternately block movement of
installation only.) of circuit breakers for a given specific cus- the circuit breaker handles and prevents
tomer installation. both circuit breakers from being switched to
The cylinder lock is factory installed in the ON at the same time. Sliding bar interlocks
left pole only of the circuit breaker cover. The key interlock assembly is Underwriters are not UL listed. (Field installation only.)
Internal accessories cannot be installed in Laboratories, Inc., listed for field installation
the same pole as the cylinder lock. under UL file E7819 and consists of a Ordering Information
mounting kit and a purchaser supplied The sliding bar interlock is available for
Ordering Information deadbolt lock. The mounting kit comprises mounting between two adjacent 3-pole
a mounting plate, which is secured to the circuit breakers with circuit breakers
CATALOG NUMBER
circuit breaker cover in either the left- or centerline spacing at 43⁄16 inches and enclo-
Order by description right-pole position, key interlock mounting sure front panel thickness of 1⁄8 or 3⁄16 inch.
screws, and a wire seal. Specific mounting (For field installation only.)
kits are required for individual key interlock
types. CATALOG NUMBER
SBK1
Ordering Information
Key interlock mounting kits are for field
installation only. Select mounting kit cata-
log numbers to match type of lock used.
Key interlocks are supplied by customer.
Square D SF None
Federal Pioneer VF 3/ 8 inch
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 21
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
External
Accessories
WALKING BEAM INTERLOCK ELECTRICAL (SOLENOID) OPERATOR
Electrical Rating Data➁
Voltage Freq. Inrush Maximum Fuse➂
EO
Current Operating Amps
Amps Time
120➃ 50/60 10 5 cycles 3
240➃ Hz Ac 5 (80 ms) 2
120➄ Dc 14 5 cycles 3-5
240➄ Dc 8 (80 ms) 2-3
Ordering Information
Voltage Freq. Terminal Block 18-Inch
Pigtail Lead
CATALOG NUMBERS
The walking beam interlock provides 120 Ac EOP1T07 EOP1P07
mechanical interlocking between two adja- 240 EOP1T11 EOP1P11
cent circuit breakers of the same pole con- 120 Dc EOP1T07DC EOP1P07DC
figuration. The walking beam interlock The electrical (solenoid) operator➀ is a sin- 240 EOP1T11DC EOP1P11DC
mounts on a bracket behind and between gle solenoid mechanism that enables local
the circuit breakers. A plunger on each end and remote circuit breaker ON, OFF, and
of the beam is inserted through an access reset switching. The electrical operator is
hole in the back plate and base of each cir- mounted on the circuit breaker cover within
cuit breaker. The walking beam interlock the trimline of the circuit breaker. The elec-
prevents both circuit breakers from being trical operator uses a unique bistable latch
switched ON at the same time. If a walking that allows the device to operate using one
beam interlock is installed, the wiring solenoid. The accessory provides high-
troughs in the back of the circuit breaker speed switching with a maximum operating
case are blocked by the plungers and can- time of 5 cycles (80 ms) making it suitable
not be used for cross wiring. Factory modi- for generator synchronizing applications.
fied circuit breakers are required for this
application. UL File E3816. Means are provided for remote electrical
operation and for local manual operation.
Ordering Information A special slide includes provisions for
The walking beam interlock is available for padlocking the circuit breaker handle in the
mounting between two adjacent circuit OFF position. The slide will accept three
breakers spaced 1⁄4 inch apart and having padlock shackles with a maximum diameter
the same pole configuration. The two circuit of 1⁄4 inch (6 mm) each. An interlock electri-
breakers must be factory modified to accept cally disconnects the solenoid when the
the walking beam interlock assembly (suit- electrical operator cover is removed. The
able for use with either 2-, 3-, or 4-pole cir- above table provides electrical rating data
cuit breakers). With properly modified for the electrical (solenoid) operator.
circuit breakers, the walking beam interlock
is suitable for field installation. Order circuit The electrical (solenoid) operator is Under-
breakers of the type and rating required writers Laboratories, Inc., listed as a circuit
modified for field installation of the walking breaker accessory under UL File E64983.
beam interlock.
CATALOG NUMBER
WBL1
The IQ Energy Sentinel is a highly accurate, The LFD current limiter is an accessory that
microprocessor-based, breaker-mounted bolts to the load end of a standard FDB or
device designed to monitor power and FD thermal-magnetic circuit breaker, pro-
energy readings. It represents an alternative viding 200,000A interrupting capacity at up
to watt meters, watt-hour meters, and watt to 600 Vac. LFD current limiters for thermal-
demand meters. Key advantages include magnetic circuit breakers are listed with Plug-in adapters simplify installation and
savings in space, lower installation costs, Underwriters Laboratories, Inc., under File front removal of circuit breakers. Individual
and remote monitoring capability. E47239. line and load plug-in adapters are available
for rear connection applications on 2-, 3-,
The IQ Energy Sentinel mounts on the load Ordering Information and 4-pole circuit breakers. Common
side of a Westinghouse Series C F-frame Circuit Breaker Rating Amps➀ CATALOG mounting plates for line- and load-end
(150 Amp) circuit breaker. It can be applied NUMBERS adapters are available. The plug-in adapters
on three-phase, four-wire systems, or 15-70 LFD3070R are rated 100A or 150/160A. Plug-in adapt-
single-phase, three-wire systems with volt- 80-160 LFD3150R ers are component recognized through
age connected through phases A and C. 150A per UL File E56845. (Field installation
only.)
For more information see Descriptive
Bulletin 8178. Ordering Information
Plug-in adapters are available for 2-, 3-, and
4-pole circuit breaker configurations. One
plug-in adapter is used for each terminal
end (line or load); specify quantity when
ordering. A one-piece steel mounting plate
is available at no charge when ordered with
line and load plug-in adapters. (Field instal-
lations only.)
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 23
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
External
Accessories
REAR CONNECTING STUDS PANELBOARD CONNECTING STRAPS
Rear connecting studs are available in sev-
eral sizes to accommodate specific fixed-
mounted circuit breaker applications. The
rear connecting studs are rated 100A or
150A.
Ordering Information
Each rear connecting stud assembly con-
sists of one stud and one tube. Select alter-
nate long and short stud assemblies for
circuit breakers with more than one pole to
maintain proper clearances between poles.
One assembly is required for line-end and
one for load-end of each pole. Tubes must
be ordered separately. Connecting studs are Panelboard connecting straps are used to
available only with imperial thread sizes. connect the circuit breaker terminals to the
panelboard bus. The panelboard connecting
straps are available in two types with 50A,
E 100A, and 150 ratings: outside pole and
B center pole.
Mounting Panel
The panelboard connecting strips are avail-
able in two sizes to meet the needs of most
“F” Thread standard panelboard applications. The
Breaker Mounting panelboard connecting straps are listed by
Surface
panelboard bus spacing. Style numbers for
special mounting brackets for CDP panel-
board installations are also included.
1
A C
316
4 D Ordering Information
Refer to panelboard manufacturer for
Stud STUD Panel Thickness Tube Length TUBE Dimensions compatibility.
Ampere STYLE (Inches) (Inches) STYLE (Inches)
Rating NUMBER A B C NUMBER D E F Panelboard Connecting Straps
For 15A to 100A Circuit Breakers Bus Contin- Pole Connector Type
100A Short 451D874G01 1 11⁄16 . . . . 32B9446H20 . . . . 35 ⁄8 5
⁄16 - 18 Spacing uous Center Outside
100A Short 451D874G01 11 16
⁄ to 15⁄16 1 3 ⁄8 . . . . 32B9446H21 . . . . (Inches) Current
3 Rating STYLE NUMBERS
100A Short 451D874G01 ⁄8 to 5⁄8 111⁄⁄16 . . . . 32B9446H22 . . . .
100A Short 451D874G01 1
⁄4 to 5⁄16 2 . . . . 32B9446H23 . . . . (Amperes)
100A Long 451D874G02 1 . . . . 37⁄16 32B9446H24 6 1 ⁄8 . . . . 53⁄4-Inch Deep Box, 600 Vac Max
100A Long 451D874G02 11 16⁄to 15⁄16 . . . . 3 3 ⁄4 32B9446H25 . . . . 23⁄4 50 673B142G02 673B142G09
3
100A Long 451D874G02 ⁄8 to 5⁄8 . . . . 41⁄16 32B9446H26 . . . . 23⁄4 100 673B142G02 673B142G10
100A Long 451D874G02 1⁄4 to 5⁄ 16 . . . . 4 3 ⁄8 32B9446H27 . . . . 23⁄4 150 673B142G04 673B142G03
For 110A to 150A Circuit Breakers 31⁄2 50 1253C72G01 1253C72G03
150A Short 374D883G01 1 11⁄16 . . . . 374D883H06 . . . . 4 1 ⁄4 7
⁄16 - 14 31⁄2 100 1253C73G03 1253C73G06
150A Short 374D883G01 11
⁄16 to 15⁄16 1 3 ⁄8 . . . . 374D883H07 . . . . 31⁄2 150 1253C73G01 1253C73G05
150A Short 374D883G01 38
⁄ to 5⁄8 111⁄16 . . . . 374D883H08 . . . .
1
150A Short 374D883G01 ⁄4 to 5⁄16 2 . . . . 374D883H09 . . . . Mounting Bracket
150A Long 374D883G02 1 . . . . 37⁄16 374D883H10 7 1 ⁄2 . . . .
11 16 STYLE NUMBERS
150A Long 374D883G02 ⁄ to 15⁄16 . . . . 3 3 ⁄4 374D883H11 . . . .
150A Long 374D883G02 3
⁄8 to 5⁄8 . . . . 41⁄16 374D883H12 . . . . 2-Pole 3-Pole
1
150A Long 374D883G02 ⁄4 to 5⁄16 . . . . 4 3 ⁄8 374D883H13 . . . . 624B600H02 624B600H01
Selection Data
29-120F
Page 24
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 25
October 1997
Mailed to: E, D, C/29-100A, 31-400A,
31-500A
Series C®
F-Frame
External
Accessories
FLEX SHAFT™ HANDLE MECHANISM
Ordering Information
Catalog Number includes complete assem-
bly consisting of handle, flexible shaft,
operating mechanism, and door interlock
hardware to fit industry standard flange
cutout.
The Westinghouse general purpose Rotary To meet the various enclosure depths, four Accessories
handle mechanisms are suitable for use with variable depth shafts are offered (6 inch, 12 As an option, an auxiliary switch is offered
NEMA 1, 3R, 4, and 12 fabricated enclosures. inch, 16 inch, and 24 inch). Each shaft so that the control panel builder may elec-
They are designed for use with Series C includes a support brace to ensure proper trically indicate the status of the breaker.
F-Frame Circuit Breakers, Molded Case alignment. In addition, the 16 inch and 24 This accessory would be mounted on the
Switches, and Motor Circuit Protectors inch extra long shafts include an adjustable mechanism and comes with 24-inch pigtail
(HMCP). support bracket. leads.
Required for a standard application are the The standard mechanism located on the Microswitch
operating handle, shaft, and mechanism. breaker does include means for internally (Includes 24-inch Pigtail leads)
locking the breaker in the “OFF” position
with up to 3 padlocks each with a maximum STYLE NUMBER
The operating handle has been designed
to meet NFPA 79 requirements. It may be diameter of .312 inch. 5108A61G01
mounted in either the horizontal or the
vertical direction. The handle was ergonomi- NEMA 4/4X handles are similar to standard
cally designed with extra clearance for a handles except they include an internal
“gloved hand” to operate. It may be neoprene gasket. NEMA 4/4X handle style
padlocked in the OFF position utilizing number is 6648C22G03. Due to gasketing Refer to Technical Data 29-121 or Catalog
3 padlocks. effect between the handle and the housing, 26-000 for replacement type Vari-depth and
the handle may not indicate a tripped AMT handle mechanisms.
The standard label on the operating handle position.
indicates ON/Tripped/OFF/Reset.
UL File E64893
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 27
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
External
Accessories
TYPE SM SAFETY HANDLE DOOR HARDWARE Accessories
MECHANISM➀
Door Hardware listed in this section may be Dress Nameplates: Required
used with Types SM and AMT handle to meet automotive specifi-
mechanisms. cations. Mounts from inside
enclosure and covers oper-
Three choices of door hardware and an ating mechanism mounting
auxiliary handle are offered to provide the bolts; makes mechanism
best latching scheme for individual needs. non-removable when enclo-
The door hardware is designed with a sure door is closed.
provision for padlocking, and a coin-proof STYLE NUMBER
slot that requires the use of a tool to open
373D260G05
the door.
Ordering Information
For use with NEMA 1 Enclosure Catalog
CATALOG NUMBER
SMCU150FD
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997
Selection Data
29-120F
Page 29
October 1997
Mailed to: E, D, C/29-100A, 31-400A, Series C®
31-500A
F-Frame
Modifications
Order by description.
Refer to Cutler-Hammer for pricing.
Cutler-Hammer
Five Parkway Center
Pittsburgh, Pennsylvania, U.S.A. 15220
Printed in U.S.A.
October 1997