One-Line Diagram - OLV1 (Load Flow Analysis)

10.5 kA
10.5 kA
13.8 kV
13.8 kV Switch Station
RMU-P1-3
XFMR overloaded
1942 kVA
1923 kVA
81.2 A
82.49% PF 80.5 A
82.53% PF

P1-3 RMU to RMU-P2-1 0 % Vd 0.001 % Vd 4 x Rods (2.5m apart)


0.05 % Vd Substation Grid
RMU-P2-3 to Switchstation

RMU-P2-2 to RMU-P2-3
RMU-P2-1 to RMU-P2-2
RMU-P1-3 CB
0.051 % Vd
1948 kVA 385.8 kVA SS CB
758.2 kVA 1929 kVA
81.5 A 16.1 A
13.8 kV 31.7 A 80.8 A
82.2% PF RMU-P2-1 83.99% PF 99 .95 % 13.8 kV
RMU-P2-2 99 .95 % 81.53% PF
13.8 kV
99.95
% 82.23% PF
RMU-P2-3
1562 kVA 1144 kVA 1171 kVA
65.4 A CB4 CB5 47.9 A CB11
49 A CB12

RMU to TRF-BF5
81.74% PF 82.33% PF CB10

RMU to TFR-BF1
RMU to TFR-BF5

CB6 82.68% PF

RMU to TRF-BF2
RMU to TRF-BF3
RMU to TFR-BF3
0.004 % Vd OVERALL RING
0 % Vd
0 % Vd
0.003 % Vd

0.003 % Vd
TRF-BF1 13.8/0.4 kV 0 % Vd
TRF-BF2 13.8/0.4 kV TRF-BF5 13.8/0.4 kV
1.5 MVA 6 %Z TRF-BF3 TRF-BF6 13.8/0.4 kV
1.5 MVA 6 %Z 13.8/0.4 kV TRF-BF4 13.8/0.4 kV 1.5 MVA 6 %Z
1.5 MVA 6 %Z 1.5 MVA 6 %Z
1.5 MVA 6 %Z
MDB-AP-BF1

MDB-AP-BF2
1495 kVA 920.8 kVA CB13 CB14 CB1 Open
1109 kVA 171.9 kVA CB7 Open 1134 kVA
CB15A Open
0.4 kV

2256 A 1389 CB2

0.4 kV
1653 A 256.2 A CB8 1691 A CB5.
% 84.34% PF 84.13% PF % CB9
95.66 95.66 84.21% PF 84.83% PF % 0.4 kV 0.4 kV
EMDB-S-BF5 96.77
% 84.6% PF 100 %
0.4 kV
574.5 kVA 920.8 kVA MDB-H-BF3 96.82 MDB-H-BF4 Open EMDB-S-BF6
713.1 kVA 420.8 kVA 711.4 kVA 251.4 kVA
<2% V.D4

0.4 kV 936.7 kVA 171.9 kVA


866.8 A 1389 A % 1397 A
Open 96.82 1064 A 627.6 A 1027 A 362.9 A
CB4 (L.S)

256.2 A

CB (L.S) - Cap5 CAP5

CB (L.S).
84.66% PF 84.13% PF

CB (L.S) - Cap2 CAP7


84.09% PF 84.63% PF 84.55% PF Open 84.56% PF 85.01% PF

< 2% V.D
84.83% PF

CB (L.S)
Open
1.94 % Vd

CB3.
< 2% V.D4

CB4.
1.87 % Vd CB4,5,6,7,8 (L.S) 0.4 kV
1x350 kvar
CAP2
0.4 kV

CAP4
CAP1 1.68 % Vd

< 2% V.D2

<2% V.D8
CAP3

<2% V.D2
1x300 kvar 2 % Vd 1.81 % Vd 2.07 % Vd 1.77 % Vd

1x400 kvar
<2% V.D3

1x350 kvar

<2% V.D6
< 2% V.D3

1x400 kvar

<2% V.D
0.4 kV

0.4 kV
1x350 kvar
0.4 kV 1.99 % Vd 0.4 kV
0.4 kV
95 % 0.4 kV .06 % 98.3kV 2%
% SMDB1 93.67
% SMDB3
% SMDB4 SMDB5 SMDB6 SMDB7 94.7
%
0.4 kV 95
% 0.4 kV98 0.4
93.78 SMDB2
0.4 kV kVA 94.82 0.4 kV SMDB10 SMDB9
0.4
563.2
kV kVA 0.4 kV 901.7 0.4 kV kVA
917.4 168.7 kVA 697.9 kVA SMDB8 413.1 kVA 697.6 kVA 247.2 kVA
866.8 A 1389 A 1397 A 256.2 A 1064 A 627.6 A 1027 A 362.9 A
84.84% PF 84.75% PF 84.71% PF 84.71% PF 84.71% PF 84.71% PF 84.74% PF 84.72% PF

< 3% V.D6

< 3% V.D4
< 3% V.D15

< 3% V.D14

< 3% V.D13

< 3% V.D11

< 3% V.D2
< 3% V.D9

< 3% V.D8

< 3% V.D5
1.64 % Vd 2.63 % Vd 3.02 % Vd 3.03 % Vd 2.99 % Vd 2.97 % Vd 2.77 % Vd 2.94 % Vd

Bus8 Bus5
% % %
0.4 kV Bus13 91.04 0.4 kV 91.8 0.4 kV 91.98 0.4 kV 0.4 kV Bus4 % Bus1
95.38
%
0.4 kV Bus9
0.4 kV
95.28
Bus16 553.4 kVA 0.4 kV 871.8 kVA Bus12
4.63 kVA Bus11 888.2 kVA Bus10 163.3 kVA 0.4 kV % 675.8 kVA % 400.2 kVA 677.9 kVA 0.4 kV 239.8 kVA
% 91.71 92.03 0.4
92.14 866.8 A 1382 A 7.3 A 1397 A 256.2 A 1064 A
0.4 kV
kV A
627.6 1027 A 362.9 A
85% PF 85% PF Cable3 85.85% PF 85% PF 85% PF 85% PF 85% PF 85% PF 85% PF
Lump-TRF-BF3 Lump-TRF-BF4

967.2 kVA

Lump-L.S TRF-BF6
Lump-C.W.H,SP (L.S)

244.2 kVA
0.4 kV
2.46 % Vd

690.6 kVA
0.4 kV
Lump-TRF-BF6
917.1 kVA 168.5 kVA

412.8 kVA
Lump-L.S TRF-BF5
698 kVA
Lump-TRF-BF5
4.5 kVA 0.4 kV 0.4 kV 0.4 kV
Lump-TRF-BF1 Lump-Kitchen (L.S) Lump-TRF-BF2 7.3 A
570.6 kVA 264 kVA 902.7 kVA 85% PF
0.4 kV 0.4 kV 0.4 kV
Guard Room
4.71 kVA
0.4 kV

962.9 kVA
1390 A
0.4 kV
Totalization Panel 100 % 84.68% PF
962.9 kVA 0 kVA
1390 A 0A
84.68% PF 0% PF

GCP1

GCP2
1100 kW 1100 kW
Gen1 Gen2

page 1 08:15:25 Nov 10, 2020 Project File: Amaad Business Park Parcel-2