Power System Stability:: The Hong Kong Polytechnic University

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

The Hong Kong Polytechnic University Transient Stability

Power System Stability:


• A large power system consists of a number of synchronous machines operating
in synchronism ‐ synchronous generators located at great and small distances
apart and of varied ratings and characteristics have to continuously operate at
the same frequency (electrical speed = pole pairs × mechanical speed).
• It is necessary that they should maintain synchronism despite the ever present
disturbances induced by nature and by man ‐ load changes, switching actions,
faults and so on.
• When the system is subject to some form of disturbance, there is a tendency for
the system to develop forces to bring it to a normal or stable condition. The
ability of a system to reach a normal or stable condition after being disturbed is
call stability.
• Synchronous stability may be divided into two main categories depending upon
the magnitude of the disturbance.
1

The Hong Kong Polytechnic University Transient Stability

Small‐Signal (or small‐disturbance) Stability:


‐ The ability of power system to maintain synchronism under small disturbances
‐ Such disturbances occur continually on the system because of small variations in the
load and generation

Transient stability
‐ The ability of the power system to maintain synchronism when subjected to a severe
transient disturbance
‐ The resulting system response involves large excursions of generator rotor angles
‐ Stability depends on both the initial conditions and the severity of the disturbance
‐ The post‐disturbance steady state operation differs from that prior to the disturbance

‐The system is designed and operated so as to be stable for a selected set of


contingencies
‐ Those contingencies are selected based on the severity and the occurrence probability
(usually different type short circuits occurred on transmission facilities and assumed to
be cleared with the operation of the appropriate circuit breakers)
2

1
The Hong Kong Polytechnic University Transient Stability

Swing Equation

d m
J  Tm  Te
dt
d m
 m
dt

J     : moment of inertia (generator + turbine), kgm2 Representation of machine rotor
ωm : angular velocity of the rotor, rad/s
m : angular displacement of the rotor (wrt stationary axis), rad
Tm : mechanical torque, Nm
Te : electromagnetic torque, Nm
t     : time, s

 m  s t   m
ωs : synchronous speed of the machine, rad/s
m : angular displacement of the rotor (from synchronously rotating  reference axis), rad

d m d d 2 m
 sm  m  J  Tm  Te
dt dt dt 2
3

The Hong Kong Polytechnic University Transient Stability

d 2 m Pm : Mechanical input power input to the machine, W
J m  Pm  Pe Pe : Electrical power output of the machine, W
dt 2
* Rotational losses in mechanical system and armature |I2|R losses are neglected.
M  J m
Inertia constant :                    ,   Joule‐second per mechanical radian 
d 2 m
M  Pm  Pe
dt 2
As ωm does not differ significantly from ωsm , M can be considered as constant.

Inertia constant H:
1 J sm
2
stored kinetic energy in megajoules at synchronous speed
H 
2 S Base machine MVA rating

d 2 m 2 H d 2 m P P
M  Pm  Pe  m  e  Pm  Pe
dt 2 sm dt 2 S Base S Base

P m and P e are in per unit
4

2
The Hong Kong Polytechnic University Transient Stability

2 H d 2
 P m  Pe Swing Equation
s dt 2

ωs and  are in electrical units

When one common MVA (Ssys)is used for a power system consisting many synchronous 
machines, the related inertia constant for jth machine becomes
S j mach
H j  sys  H j  mach
S sys

The Hong Kong Polytechnic University Transient Stability

 E  EB 
Pe    sin   Pmax sin 
 XT 

Single machine ‐ infinite bus system 

Equivalent circuit
Power angle relationship

2 H d 2
 P m  P max sin 
s dt 2

Reduced equivalent circuit 6

3
The Hong Kong Polytechnic University Transient Stability
Consider a step change in Pm
2 H d 2
 Pm  Pe
s dt 2

2
d  d 2 s P m  P e d 

 
2
dt dt H dt
d  d 

2

s P m  P e d  
dt  dt  H dt
Speed deviation (d  /dt) is initially zero and changes due to the 
disturbance. It become zero after some time after  the disturbance 
(stable operation)
m

s P m  P e d 
dδ  0


 H dt
0

Energy gained during acceleration is directly proportional to area A1


m
d

0
 P m
dt

 P e dδ  area A1

Energy lost during deceleration is directly proportional to area A2


m
d
  P m
dt

 P e dδ  area A2
Response to a step change in mechanical power input  0 7

The Hong Kong Polytechnic University Transient Stability

P  Pmax sin 

P  P
 0
|
   Pmax cos0    SP 
 

synchronizing power coefficient

2H d
2
   
0
 Pm   Pe  Pe 
s
2
dt
2 H d 
2

  Pmax cos  0    0
s
2
dt
d 
2
s S P
2
   0
dt 2H

The angular frequency of the undamped oscillations is given by

s S P
n  elec rad / s
2H 8

Explanation:  The equation "d2x/dt2 +  wn2x  =  0"  has  the  general  solution  Acos(wnt)  +  Bsin(wnt)  with 
constants  A  and  B  determined  by  the  initial  conditions.  The  solution  when  plotted  is  an  undamped 
sinusoid of angular frequency wn. 

4
The Hong Kong Polytechnic University Transient Stability

Single machine ‐ infinite bus system
(second line is open at infinite bus end) 

area A1  area A2

area A3  area A4

Power ‐ Angle curves
9

The Hong Kong Polytechnic University Transient Stability
Critical Clearing Time

Single machine ‐ infinite bus system
(second line is open at infinite bus end)  
Power ‐ Angle curve showing critical angle
 cr
d
area A1  P m  P m  cr   0 
 0
dt
 max
area A2   P max sin   P m  ddt  P max  cos  max  cos  cr   P m  max   cr 
cr

  cr  cos 1  P m P max   max   0   cos  max   cos 1 sin  0   2 0   cos  0 


 

s P m 4H
 cr  tcr2   0  tcr   cr   0 
4H s P m
10

5
The Hong Kong Polytechnic University Transient Stability

Single machine ‐ infinite bus system Equivalent circuit

Power ‐ Angle curve showing critical angle

cos cr 
P
m 
Pmax max  0   r2 cos max  r1 cos 0
r2  r1

Response to a fault cleared in  Response to a fault cleared in 
tc1 seconds (stable case) tc2 seconds (unstable case) 11

The Hong Kong Polytechnic University Transient Stability

Factors influencing transient stability
‐ How heavily the generator is loaded
‐ The generator output during the fault (This depends on fault location and type)
‐ The fault clearing time
‐ The post‐fault  transmission system reactance
‐ The generator reactance
‐ The generator inertia
‐ The internal voltage magnitude
‐ The infinite bus voltage magnitude

12

6
The Hong Kong Polytechnic University Transient Stability

Factors influencing transient stability
‐ How heavily the generator is loaded
‐ The generator output during the fault (This depends on fault location and type)
‐ The fault clearing time
‐ The post‐fault  transmission system reactance
‐ The generator reactance
‐ The generator inertia
‐ The internal voltage magnitude
‐ The infinite bus voltage magnitude

13

The Hong Kong Polytechnic University Transient Stability

Example:
Vt  1.05 pu
HT
LT
Trans. CB1 j0.3 CB2 Classical model parameters of the equivalent machine 
(expressed in per‐unit on 2000 MVA, 24 kV base):
SM F1
CB3 j0.2 CB4
j0.075
‐ Xd’= 0.3 pu, 
Inf. Bus
4 x 500 MVA
F2 F4 F3 ‐ Inertia constant, H = 4 s
EB  1 pu
P = 1.8 pu
System single-line diagram, equivalent circuit
and data in per unit (1000 MVA and 24 kV)

j X total
1. Find the parameters of the reduced equivalent
circuit of the system for small‐signal and transient
 
stability analysis (use per‐unit system on 2000 EI  i 1 0 0
MVA base).

Reduced Equivalent Circuit


14

7
The Hong Kong Polytechnic University Transient Stability

After changing base power from 1000 MVA to 2000 MVA:


P = 0.9 j0.6
j0.3
Total inductance:
j0.15
j0.4
X total  (0.3 + 0.15 + 0.6//0.4) = 0.69 pu
EI  i Vt   t EB 0

Power delivered by the generator:


EB Vt
P sin  t , X   0.15  0.6 / /0.4   0.39 pu   t  0.34 rad  19.5 deg
X
j0.69
Output current of the generator:

I  Vt  EB  jX  0.9000 + j0.0267 pu 1.1615 32.320  


1 0 0

 EI  Vt  jX d I  0.9816 + j 6261 pu =1.1615 32.320


Reduced Equivalent Circuit
15

The Hong Kong Polytechnic University Transient Stability

2. Draw the power‐angle curve and show the operating point.

Power-angle equation:

EI EB
P sin  i  Pmax sin  i  1.6834 sin  i
X Total

P (pu)
Pmax sinδ
1.5

1 Pm = 0.9 pu

0.5 0 = 32.32

0
0 50 100 150
 (deg)
16

8
The Hong Kong Polytechnic University Transient Stability

3. Determine the frequency of machine rotor oscillations when it is subjected to a small


temporary electrical disturbance.

17

The Hong Kong Polytechnic University Transient Stability

4. Consider the fault at F1. The fault will be cleared with the operation of the circuit‐breakers
CB‐1 and CB‐2.
‐ Draw the power‐angle curves for pre‐fault and post‐fault conditions on the same graph. Show
the critical clearing angle cr determined by the equal area criterion on that graph.
‐ Calculate the critical clearing angle (cr) and the critical clearing time (tcr).
j0.69

EI  i
 
1 0 0 Prefault:
Pe  1.6834sin i
j 0.45
j0.3

During Fault:
EI  i 00
Pe  0
j0.85
Postfault:
EI  i
 
1 0 0
Pe  1.3665sin i

18

9
The Hong Kong Polytechnic University Transient Stability

19

The Hong Kong Polytechnic University Transient Stability

5. Consider the fault at F2. The fault will be cleared with the operation of the circuit‐breakers
CB‐3 and CB‐4.
‐ Draw the power‐angle curves for pre‐fault and post‐fault conditions on the same graph. Show
the critical clearing angle cr determined by the equal area criterion on that graph.
‐ Calculate the critical clearing angle (cr) and the critical clearing time (tcr).
j0.69

 
1 0 0 Prefault:
EI  i
Pe  1.6834sin i
j 0.45
j0.3
During Fault:
EI  i 00
Pe  0

j1.05
Postfault:

EI  i
 
1 0 0 Pe  1.1062sin i

20

10
The Hong Kong Polytechnic University Transient Stability

21

The Hong Kong Polytechnic University Transient Stability

6. Consider the fault at F3. The fault will be cleared with the operation of the circuit‐breakers
CB‐3 and CB‐4.

The critical clearing angle (cr) and the critical clearing time (tcr) are same with the fault F2.

Prefault:
Pe  1.6834sin i

During Fault:
Pe  0

Postfault:
Pe  1.1062sin i

22

11
The Hong Kong Polytechnic University Transient Stability

7. Consider the fault at F3. The fault will be cleared with the operation of the circuit‐breakers
CB‐3 and CB‐4.
‐ Draw the power‐angle curves for pre‐fault and post‐fault conditions on the same graph. Show
the critical clearing angle cr determined by the equal area criterion on that graph.
‐ Calculate the critical clearing angle (cr) and the critical clearing time (tcr).
j0.6
During Fault:
j0.45

j0.2 j0.2
E I  i EB 0

j2.4
j0.45 j0.6


 
EI  i 1 0 0
E I  i j0.2 j0.2 EB 0

j2.4
Pe  0.484sin i
E I  i j0.8 j1.067 j0.2 EB 0

23

The Hong Kong Polytechnic University Transient Stability
j0.69
Prefault:
 
E I  i 1 0 P  1.6834sin 
0
e i

j2.4

 
During Fault:
E I  i 1 0 0
Pe  0.484sin i

j1.05

  Postfault:
E I  i 1 0 0
Pe  1.1062sin i

r1  0.2875 & r2  0.6571


  Pm Pmax  max
   0   r2 cos  max
  r1 cos  0 
 cr  cos1    0.8465 rad  48.5 deg
  r2  r1  
24

12
The Hong Kong Polytechnic University Transient Stability

8. Suppose that the line is Vt  1.05 pu


HT
compensated with series capacitor LT
Trans. j0.15 jXc j0.15
(compensation degree = 50%).
SM
Calculate the critical clearing angle j0.2
(cr) and the critical clearing time 4 x 500 MVA
j0.075 Inf. Bus
F2
(tcr) for the fault F2. EB  1 pu
P = 1.8 pu
j0.62

  Prefault:
E I  i 1 0 0
Pe  1.8693sin i
j0.45

00 During Fault:
E I  i
Pe  0
j0.75
Postfault:
 
E I  i 1 0 0
Pe  1.5488sin i
25

The Hong Kong Polytechnic University Transient Stability

26

13
The Hong Kong Polytechnic University Transient Stability

27

The Hong Kong Polytechnic University Transient Stability

28

14
The Hong Kong Polytechnic University Transient Stability

29

The Hong Kong Polytechnic University Transient Stability

30

15
The Hong Kong Polytechnic University Transient Stability

31

The Hong Kong Polytechnic University Transient Stability

440 fault at F2 at t = 1 s
t = 10 ms

420
m (rad/s)

t = 100 ms
400 c

t = 90 ms
380 c

360 440 fault at F4 at t = 1 s


0 1 2 3 4 t = 10 ms
t (s)
420
m (rad/s)

t = 150 ms
400 c

t = 140 ms
380 c

360
0 1 2 3 4
t (s)
32

16
The Hong Kong Polytechnic University Transient Stability

33

The Hong Kong Polytechnic University Transient Stability

34

17
The Hong Kong Polytechnic University Transient Stability

35

The Hong Kong Polytechnic University Transient Stability

3 x 210 MW 300 km 400 kV System


TPP Equivalent
+
100 km 100 km

CB1 CB2
FAULT
F

Synchronous
SM Controls Machine
Step-up
Transformer
Single machine - infinite bus system
AVR+Gov
‐exst1 1 2
SM
‐pss1a +30
‐ieeesgo

‐ Conventional thermal power plant


‐ Fault is applied at t = 1s
AVR+Gov
‐exst1 1 2
SM 400 kV Bus

‐ Fault is cleared at t = 1.275 s


‐pss1a +30
‐ieeesgo

AVR+Gov
1 2
‐ Critical clearing time for the constant excitation
and constant mechanical input scenario
‐exst1
SM
‐pss1a +30
‐ieeesgo

TPP subcircuit
36

18
The Hong Kong Polytechnic University Transient Stability

Impact of Excitation System

Constant Excitation
DC Excitation System (slow response, low gain, low ceiling voltage)
δ (deg)

Static Excitation System with Power System Stabilizer (PSS)

Static Excitation System (fast response, high gain, high ceiling voltage)

Time (s) 37

The Hong Kong Polytechnic University Transient Stability

Impact of Excitation System


ω (pu)

Constant Excitation
DC Excitation System
Static Excitation System with PSS
Static Excitation System

Time (s)
38

19
The Hong Kong Polytechnic University Transient Stability

The change in electrical torque of a synchronous machine following a perturbation


can be resolved into tow components:

Te  TS   TD 
synchronizing damping torque 
torque coefficient coefficient

‐ Lack of sufficient synchronizing torque results in instability through an aperiodic drift


in rotor angle
‐ Lack of sufficient damping torque results in oscillatory instability
‐ Excitation system
‐ Improves synchronizing torque coefficient
‐ Reduces damping torque coefficient
‐ Power System Stabilizer (PSS) usage is essential in modern (fast response & high gain)
excitation systems for desired damping torque coefficient.
39

The Hong Kong Polytechnic University Transient Stability

‐ Generator (with constant field voltage) connected radially to a large power system 

Instability due to insufficient synchronizing torque 
40

20
The Hong Kong Polytechnic University Transient Stability

‐ Generator (with excitation control) connected radially to a large power system 

Instability due to insufficient damping torque  41

The Hong Kong Polytechnic University Transient Stability

42

21
The Hong Kong Polytechnic University Transient Stability

Impact of Governor Control

Generator with Constant Mechanical Input


‐ Fault is applied at t = 1s
Generator with Speed Governor
‐ Fault is cleared at t = 1.36 s
‐ Critical clearing time for
static excitation (with PSS)
δ (deg)

scenario

Time (s)
43

The Hong Kong Polytechnic University Transient Stability

Generator with Constant Mechanical Input


Generator with Speed Governor

Generator with Constant Mechanical Input


ω (pu)

Generator with Speed Governor

Time (s)
44

22
The Hong Kong Polytechnic University Transient Stability

Impact of Synchronous Machine Controls on Critical Clearing Time

Scenario Excitation System Governor Control tcr (ms)


1 Constant Excitation Voltage ‐ 275
2 DC Excitation System ‐ 295
3 DC Excitation System + 300
4 Static Excitation System (with PSS) ‐ 360
5 Static Excitation System (with PSS) + 370

45

Explanation:   “+” => with governor control,  
“‐” => without governor control (i.e. constant mechanical power input). 

The Hong Kong Polytechnic University Transient Stability

3 x 210 MW
300 km 400 kV System
HPP Equivalent
+
100 km 100 km

CB1 CB2
FAULT
F

Synchronous
SM Controls Machine
Step-up
Transformer
Single machine - infinite bus system
Exc+Gov
‐exst1 1 2
SM
‐pss1a +30
‐ieeeg3

‐ Hydro power plant


Exc+Gov
‐exst1
SM
1 2
400 kV Bus
‐ Fault is applied at t = 1s
‐ Fault is cleared at t = 1.385 s
‐pss1a +30
‐ieeeg3

Exc+Gov
1 2
‐ Static excitation system (with PSS)
‐ Critical clearing time for the constant
‐exst1
SM
‐pss1a +30

mechanical input scenario


‐ieeeg3

HPP subcircuit
46

23
The Hong Kong Polytechnic University Transient Stability

Generator with Governor Control

Generator with Constant Mechanical Input


ω (pu)

Generator with Governor Control

Generator with Constant Mechanical Input

Time (s)
47

The Hong Kong Polytechnic University Transient Stability

Recall special characteristics of hydraulic turbine
For a step change in gate opening, the initial value theorem
gives
1 1  Tw s
 P m (0)  lim s  s  2
s 1  0.5 Tw s

the final value theorem gives

1 1  Tw s
 P m ()  lim s 0 s 1
s 1  0.5 Tw s

the complete time response is given by

 2 Tw t
 P m (t )  1  3e  G Change in turbine mechanical power 
  following a unit step change in gate position

48

24
The Hong Kong Polytechnic University Transient Stability

Negative Impact on First Swing Stability!


tcr reduces to 0.38 s with governor control

Hydraulic turbine response to a step change and a ramp change in gate position (gate opening reduced 
0.1 pu), with initial values of head, power, velocity, and gate position equal to 1 pu (Tw = 1.0s)
49

25
THE HONG KONG POLYTECHNIC UNIVERSITY
Department of Electrical Engineering

EE4031 Power Systems


Tutorial on Transient Stability

1. A three-phase fault is applied at P as shown in Fig.1 with reactances given on a common


system base. The generator is delivering 1.0 pu power at the instant preceding the fault.
a) By calculation, find the critical clearing angle for clearing the fault with
simultaneous opening of the breakers 1 and 2.
b) Plot the power-angle curves and show the equality of the accelerating and
decelerating areas.
c) Suggest a method to improve the transient stability of this system and explain briefly
how the method works.

Fig.1

2. A 50Hz generator with a reactance of 0.3 pu has an inertia constant H = 5. It delivers


power of 0.8 pu to an infinite bus through a transmission network with transfer reactance
of 0.2 pu. The internal voltage of the generator and the voltage of the infinite bus are
maintained at 1.05 pu and 1 pu, respectively.
a) Determine the load angle of the generator.
b) Determine the steady-state stability limit.
c) Determine the synchronizing power coefficient.
d) Due to a fault on the transmission network, the transfer reactance is suddenly
doubled. Plot the swing curve of the generator for the first 0.2 s after the fault using
a time step of 0.05 s.

3. A generator operating at 50 Hz with an inertia constant H of 5 sec delivers half-load (i.e.


Po = 0.5 pu) to an infinite bus of voltage 1.0 pu through a transmission link with total
reactance XL of 0.4 pu. The internal voltage E and reactance XG of the generator is 1.5 pu
and 0.8 pu, respectively.
a) Find the power angle Go and the steady-state stability limit Pmax.
b) A three-phase fault occurs at the generator terminal, find the critical clearing angle
Gcr and the corresponding critical clearing time tcr.

EE4031, KWCn, 23 Apr 2010 1


4. A generator with 0.2 pu reactance is connected to a busbar via a transformer having a
reactance of 0.15 pu. The busbar is then connected to a large power system by a double-
circuit line, each circuit of which has a reactance of 1.2 pu. The voltages at both the
generator terminal and the large power system is 1.0 pu. The generator has an inertia
constant of 5 sec and delivers 0.9 pu real power to the large power system.
B

a) Find the internal voltage and the power angle of the generator.
b) Due to malfunction of a relay, one of the circuits in the double circuit line was
tripped suddenly and then reclosed after 0.2 sec. Calculate the power angle of the
generator when the tripped circuit was reclosed, hence plot its value for the next 0.1
sec using time steps of 0.05 sec.

5. Fig.5 shows a synchronous generator connected to an infinite bus via a double circuit
line with reactances and voltages given on a common system base. A transient three-
phase fault occurs at the mid-point of one of the lines. At the instant preceding the fault,
the generator is delivering a steady-state power Pg = 1.0 pu.
a) Determine the pre-fault steady-state rotor angle Go of the generator.
b) The fault is first isolated by switching out the faulty line when the rotor angle
increases to G1 = 90o, and is subsequently cleared by the time when the line is
reclosed at rotor angle G2 = 120o. Apply the equal area criterion, and determine the
transient stability of the post-fault system.

Fig.5

6. A 50Hz generator with a reactance of 0.25 pu delivers a steady-state power of 0.8 pu


over a transmission system to an infinite busbar. The steady-state voltages at both the
generator terminal and the infinite bus are 1.0 pu. The generator has an inertia constant H
of 5 sec, and the effective transfer reactance of the transmission system is 0.4 pu.
a) Find the internal voltage and the power angle of the generator.
b) A solid three phase fault occurs in the transmission system and is subsequently
cleared after 0.15 sec. The effective transfer reactances of the transmission system
during and after the fault are 1.0 and 0.6 pu, respectively. Plot the power angle of the
generator for the first 0.1 sec after the fault using time steps of 0.05 sec, and hence
determine the power angle and power output of the generator after the fault has been
cleared for 0.1 sec.

EE4031, KWCn, 23 Apr 2010 2


EE4031 Power Systems
Tutorial on Transient Stability

1. a) The total transmission reactance:

X pre 0.2  0.4 // 0.4  0.05 0.45 pu X post 0.2  0.4  0.05 0.65 pu
The maximum power output:
EV 1.2 8 EV 1.2 24
Pmax pu Pmax 2 pu
X pre 0.45 3 X post 0.65 13
and their ratio
Pmax 2 24 /13 9
r2
Pmax 8/3 13
The initial rotor angle
3
Pmax sin G o 1 o Go sin 1 0.3844 rad
8
The maximum rotor angle
13
Pmax 2 sin G m 1 o Gm sin 1 2.5692 rad
24
The critical clearing angle

ª (G  G o ) sin G o  r2 cos G m º
G cr cos 1 « m » 1.2209 rad 69.95o
¬ r2 ¼

b) power-angle curves

c) Install a “braking resistor” close to the generator terminals, the amount of energy
available to accelerate the rotor can then be significantly reduced, and hence the system
stability can be improved.

EE4031, KWCn, 23 Apr 2010 3


2. a) X pre 0.3  0.2 0.5 pu
EV 1.05
Pmax 2.1 pu
X pre 0.5
Po 0.8
Po Pmax sin G o o G o sin -1 sin -1 22.39 o
Pmax 2.1

b) Stability limit Pmax 2.1 pu

c)
Ps Pmax cos G o 2.1cos 22.39o 1.94 pu/rad

H 5 1
M s 2 /deg
d) 180 f 180 u 50 1800
X post 0.3  0.4 0.7 pu
EV +t 2
t (s) Pmax Pe Pmax sin G Pa 0.8  Pe Pa +G G (deg)
X M
0- 2.1 0.8 0   
0+ 1.5 0.5714 0.2286   
0avg   0.1143 0.51 0.51 22.90
0.05 1.5 0.5837 0.2163 0.97 1.48 24.38
0.10 1.5 0.6192 0.1808 0.81 2.29 26.67
0.15 1.5 0.6733 0.1267 0.57 2.86 29.53
0.20 1.5 0.7393 0.0607 0.27 3.13 32.66
+t 2
where +G ( n ) +G ( n 1)  Pa and G ( n ) G ( n1) +G ( n )
M (n)

34

32

30
Rotor (deg)

28

26

24

22
0 0.05 0.1 0.15 0.2
Time (s)

EE4031, KWCn, 23 Apr 2010 4


3. a) The total transmission reactance:
X 0.8  0.4 1.2 pu
The maximum power output:
EV 1.5 u 1.0
Pmax 1.25 pu
X 1.2
Steady-state output:
0.5
Po Pmax sin G o 0.5 pu Ÿ Go sin 1 23.58q 0.4115 rad
1.25

b) Fault-on:
Pmax1
Pmax1 0 Ÿ r1 0
Pmax
Post-fault:
Pmax 2
Pmax 2 Pmax Ÿ r2 1
Pmax
The maximum rotor angle:
G m S  G o 2.7301 rad
The critical clearing angle:
ª (G  G o ) sin G o  r2 cos G m º
G cr
cos 1 « m » 1.5599 rad 89.375
o

¬ r2 ¼
Considering the corresponding critical clearing time:
S u f u Po 2 S u 50 u 0.5 2
G cr u tcr  G o u tcr  0.4115 1.5599 rad
2uH 2u5
Ÿ tcr 0.3824 sec

4. a) Let Gt be the terminal voltage angle relative the infinite bus.


1u1
sin G t 0.9 Ÿ G t 42.454q
0.15  1.2 / 2
Vt  Vb 1‘42.454q  1‘0q
Terminal current I 0.9  j 0.35 pu
j 0.75 j 0.75
Generator internal voltage:
E Vb  IX 1  (0.9  j 0.35)( j 0.95) 0.668  j 0.855 1.085‘52q

H 5 1 2 1.2
b) M s / deg X pre 0.2  0.15  0.95 pu
180 f 180 u 50 1800 2
X fault 0.2  0.15  1.2 1.55 pu X post X pre

EE4031, KWCn, 23 Apr 2010 5


t ¨t Pe (pu) Pa (pu) Į (o/s2) ¨Ȧ (o/s) Ȧ (o/s) ¨į (o) į (o)
0– 0.9 0
0+ 0.5516 0.3484
0avg 0.05 0.1742 313.56 15.68 15.68 0.78 52.78
0.05 0.05 0.5575 0.3425 616.58 30.83 46.51 2.33 55.11
0.10 0.05 0.5742 0.3258 586.48 29.32 75.83 3.79 58.90
0.15 0.05 0.5994 0.3006 541.09 27.05 102.88 5.14 64.05
0.2– 0.6294 0.2706
0.2+ 1.0269 -0.1269
0.2avg 0.05 0.0718 129.32 6.47 109.35 5.47 69.51
0.25 0.05 1.0699 -0.1699 -305.77 -15.29 94.06 4.70 74.22
0.3 0.05 1.0990 -0.1990 -358.28 -17.91 76.15 3.81 78.02

EV EV Pa( n )
where Pe( n ) sin G ( n ) , Pa( n ) Pm  Pe( n ) 0.9  sin G ( n ) , D ( n 1)
X (n) X (n) M
'Z ( n 1) D a( n 1) 't , Z ( n 1) Z ( n )  'Z ( n 1)
'G ( n 1) Z ( n 1) 't , G ( n 1) G ( n )  'G ( n 1)

5. a) Pre-fault transmission reactance X 0 j 0.9  j 0.4 // ( j 0.2  j 0.2) j1.1


EaVb 1.8 u 1
Pre-fault power output P0 sin G 0 sin G 0 1 Ÿ G0 37.67q
X0 1.1
0.9 u 0.4  0.4 u 0.2  0.2 u 0.9
b) Fault-on transmission reactance X 1 j j 3.1
0.2
EaVb 1.8 u 1
Ÿ P1 sin G sin G 0.5806sin G
X1 3.1
Fault-off transmission reactance X 2 j 0.9  j 0.4 j1.3
EaVb 1.8 u 1
Ÿ P2 sin G sin G 1.3846sin G
X2 1.3
Post-fault transmission reactance = pre-fault transmission reactance = j1.1
EaVb 1.8 u 1
Ÿ P3 sin G sin G 1.6364sin G
X0 1.1
Total accelerating area
G1 90q
Aa ³G 0
( P0  P1 )d G ³37.67q
1  0.5806sin G d G 0.454

Total decelerating area


G2 G3
Ad ³G 1
( P2  P0 )d G  ³ ( P3  P0 )d G
G2
q
180q37.67q
³90q 1.3846sin G  1 dG  ³120q 1.6364sin G  1 dG
120
0.256

Based on the equal area criterion, the system is transient unstable as the allowable
decelerating area is less the acceleration are, i.e. Aa ! Ad

EE4031, KWCn, 23 Apr 2010 6


6. a) Let Gt be the terminal voltage angle relative the infinite bus.
1u1
sin G t 0.8 Ÿ G t 18.663q
0.4
Vt  Vb 1‘18.663q  1‘0q
Terminal current I 0.8  j 0.131 pu
j 0.4 j 0.4
Generator internal voltage:
E Vb  ǿX 1  (0.8  j 0.131)( j 0.25  j 0.4) 0.915  j 0.52 1.052‘29.62q

H 5 1 2
b) M s / deg X pre 0.25  0.4 0.65 pu
180 f 180 u 50 1800
X fault 0.25  1.0 1.25 pu X post 0.25  0.6 0.85 pu

t ¨t Pe (pu) Pa (pu) Į (o/s2) ¨Ȧ (o/s) Ȧ (o/s) ¨į (o) į (o )


0– 0.8 0 29.62
0+ 0.416 0.384
0avg 0.05 0.192 345.64 17.28 17.28 0.86 30.49
0.05 0.05 0.427 0.373 671.43 33.57 50.85 2.54 33.03
0.10 0.05 0.4587 0.3413 614.27 30.71 81.57 4.08 37.11
0.15– 0.5078 0.2922
0.15+ 0.7467 0.0533
0.15avg 0.05 0.1728 310.99 15.55 97.11 4.86 41.96
0.2 0.05 0.8276 -0.0276 -49.62 -2.48 94.63 4.73 46.70

EV EV Pa( n )
where Pe( n ) (n)
sin G ( n ) , Pa( n ) Pm  Pe( n ) 0.8  (n)
sin G ( n ) , D (n)
X X M
'Z ( n 1) D a( n ) 't , Z ( n 1) Z ( n )  'Z ( n 1)
'G ( n 1) Z ( n 1) 't , G ( n 1) G ( n )  'G ( n 1)

After fault cleared for 0.1 sec (i.e. t = 0.25 sec):


Power angle = 46.7o
Power output = 0.9 pu

EE4031, KWCn, 23 Apr 2010 7

You might also like