Diffusers | 1 / 18

VVKR
Swirl ceiling diffuser with adjustable deflectors

Ordering codes Description


VVKR is a swirl ceiling diffuser with manually adjustable
VVKR-
air guiding deflectors. It enables us to adjust
A the airflow pattern to individual requirements
B of the room at any time. Ideal to use in shopping halls,
Type C
receptions, or offices. The diffuser is suited for both cool
Round front plate R and hot air application, and can be used for extracting air
Square front plate S with or without deflectors. The maximum recommended
installation height is 4 meters. Supply air temperature
Dimensions 300 - 825 can vary from -10K to +10K based on the room air
temperature. The diffuser can be used for large air
Number of deflectors 8 - 92
volume exchanges at high temperature differences ΔT.
Black B The front plate is installed to a plenum box with top
White W
or side entry.
Deflectors without blades (extract air) R

AISI304 Information about accessories for VVKR is available


AISI316 on page 14.
Material / surface finish RALxxx
• PB-VVK - Plenum box
• PB-VVKU - Universal plenum box
Ordering Code example:
VVKR - A - S - 300 × 8 - W - RAL9010
Swirl diffuser with adjustable deflectors, type-A square diffuser face size
300×300 mm with 8 deflectors. Deflectors are painted white (W).

NOTE:
Combinations of diffuser types, dimensions and number of deflectors need
to be based on Fig. 6 (page 3).

Fig. 1: Air flow visualisation at different deflector configurations


(figure left: vertical flow, figure right: horizontal flow)
2 / 18 | Diffusers

Design
Material used

The diffuser can be supplied with a round or square front


plate manufactured from galvanized steel. The surface is
powder painted white RAL9010 as standard, or another
RAL code can be specified. It is also possible
to manufacture a stainless steel AISI304 or AISI316
version, without surface finish.
The deflectors are made from plastic, available in black
or white colour. In the middle of the diffuser there is 1

a pre-punched hole for front plate screw fixing. A screw


with a white decorative cap for its installation is provided
together with a self-adhesive seal, which must be
adhered at the installation site.

figure left: inner swirl, figure right: outer swirl

Fig. 2: Beveled deflectors configuration

1. All deflectors are set to an external helix


2. Half of the deflectors are always configured to the internal, or external
helix, respectively
3. Deflectors of opposite quadrants are set to the internal, or external
helix, respectively

Fig. 5: Different ways of deflectors configuration and airflow direction


Fig. 3: Vertical airflow Fig. 4: Extract airflow with
deflectors
Diffusers | 3 / 18

□A □A □A □A □A □A

VVKR-A-S-XXX-8 VVKR-A-S-XXX-16 VVKR-A-S-XXX-24 VVKR-A-S-XXX-32 VVKR-A-S-XXX-40 VVKR-A-S-XXX-48


VVKR-A

□A □A □A øD øD øD

VVKR-A-S-625-54 VVKR-A-S-800-72 VVKR-A-S-825-80 VVKR-A-R-XXX-8 VVKR-A-R-XXX-16 VVKR-A-R-XXX-24

øD øD øD øD øD øD

VVKR-A-R-XXX-32 VVKR-A-R-XXX-40 VVKR-A-R-XXX-48 VVKR-A-R-625-54 VVKR-A-R-800-72 VVKR-A-R-825-80

□A □A □A □A □A

VVKR-B-S-XXX-8 VVKR-B-S-XXX-16 VVKR-B-S-XXX-24 VVKR-B-S-XXX-40 VVKR-B-S-XXX-64


VVKR-B

øD øD øD øD øD

VVKR-B-R-XXX-8 VVKR-B-R-XXX-16 VVKR-B-R-XXX-24 VVKR-B-R-XXX-40 VVKR-B-R-XXX-64


VVKR-C

□A □A □A □A □A

VVKR-C-S-XXX-8 VVKR-C-S-XXX-16 VVKR-C-S-XXX-36 VVKR-C-S-XXX-48 VVKR-C-S-825-92

Fig. 6: Diffuser types and shapes

NOTE: The front plate sizes (XXX) for different diffuser types and number of nozzles are available in Tab. 4 on page 4.
4 / 18 | Diffusers

Dimensions
□A øD Free area
Size
(mm) With Without
Type Size × Number of deflectors
300 296 298 deflectors deflectors

400 396 398 (m2)


500 496 498 300×8, 400×8, 500×8, 600×8, 625×8 0,00814 0,01714

600 596 598 400×16, 500×16, 600×16, 625×16 0,01628 0,03427

625 621 623 500×24, 600×24, 625×24 0,02443 0,05141

800 796 798 600×32, 625×32 0,03257 0,06854

825 821 823 A 600×40, 625×40 0,04071 0,08568

600×48, 625×48 0,04885 0,10282


Tab. 1: Diffuser dimensions
625×54 0,05496 0,11567

825×80 0,08142 0,17136

800×72 0,08575 0,17706


Number of deflectors
Size 300×8, 400×8, 500×8, 600×8, 625×8 0,00814 0,01714
8 16 24 32 40 48 54 64 72 80
400×16, 500×16, 600×16, 625×16 0,02044 0,04188
300 0,5
B 500×24, 600×24, 625×24 0,02858 0,05902
400 0,9 0,9
600×40, 625×40 0,04487 0,09329
500 1,4 1,4 1,3
800×64, 825×64 0,07761 0,15992
600 2,7 2,0 1,9 1,9 2,3 1,8
300×8, 400×8, 500×8, 600×8, 625×8 0,01022 0,02094
625 2,8 2,2 2,1 2,1 2,5 2,6 2,5
400×16, 500×16, 600×16, 625×16 0,02044 0,04188
800 4,2 4,3
C 500×36, 600×36, 625×36 0,04288 0,08853
825 4,4 4,6
600×48, 625×48 0,05717 0,11804

Tab. 2: Weight for round diffusers (kg) 825×92 0,11235 0,23131

Tab. 4: Free area

Number of deflectors
Size
8 16 24 32 36 40 48 54 64 72 80 92
300 0,7

400 1,2 1,1

500 1,9 1,8 1,7 1,6

600 2,6 2,6 2,5 2,5 2,4 2,5 2,4

625 2,8 2,8 2,8 2,7 2,6 2,7 2,6 2,6

800 4,5 4,5 4,1

825 4,7 4,8 4,4

Tab. 3: Weight for square diffusers (kg)


Diffusers | 5 / 18

Number of deflectors
Diffuser size
8 16 24 32 36 40 48 54 64 72 80 92
300 Plenum box size

400

500

600

625

400

500

600

625

500

600

625

600

625

500

600

625

600

625

600

625

625

800

825

800

825

825
300 •
400 • • •
500 • • • • • • •
600 • • • • • • • • • • • • • •
625 • • • • • • • • • • • • • • • • • • • • • •
800 • •
825 • • • •
Tab. 5: Overview of possible plenum box and diffuser combinations Legend

NOTES:
For square diffusers VVKR-A or VVKR-B it is possible to use both round
and square plenum boxes.
• - Recommended plenum box size for diffuser
with number of deflectors
For round diffusers it is only possible to use round plenum boxes.
For diffusers VVKR-C it is only possible to use square plenum boxes.

Quick selection
1000
qv (m3 • h-1)

500

0
300×8 400×16 500×24 600×32 600×40 600×48 625×54 800×72
400×8 500×16 625×24 625×32 625×40 625×48 825×80
500×8 600×16
600×8 625×16
625×8

Tab. 6: Quick selection table for VVKR-A for air supply via a plenum box with horizontal connection

1000 1000
qv (m • h )
qv (m3 • h-1)

-1

500 500
3

0 0
300×8 400×16 500×24 600×40 800×64 300×8 400×16 500×36 600×48 825×92
400×8 500×16 600×24 825×64 400×8 500×16 600×36 625×48
500×8 600×16 625×24 500×8 600×16 625×36
600×8 625×16 600×8 625×16
625×8 625×8

Tab. 7: Quick selection table for VVKR-B for air supply via a plenum box Tab. 8: Quick selection table for VVKR-C for air supply via a plenum box
with horizontal connection with horizontal connection
6 / 18 | Diffusers

Technical parameters
Terminology Legend

qV (m3/h) - Air flow volume per 1 diffuser


Y (m) - Horizontal distance to the wall
H (m) - Room height
Lt A, B Lt
H1 (m) - Distance from the ceiling to the occupied zone
Y H0 (m) - Occupied zone
qV; ΔT0 qV; ΔT0 - Throw distance: by the wall - Lt = H1 + Y
Lt (m)
between diffusers - Lt = H1 + A/2
VLt; ΔTL VLt , VH1 (m/s) - Air velocity at throw distance Lt
∆T0 - Temperate difference between the supply
(K)
and room air

H1
∆TL - Difference between the airflow core and room
(K)
H

VH1, ΔTL VLt; ΔTL air temperature


∆pt (Pa) - Pressure drop

H0 = 1,8 m
LW dB(A) - Sound power level
- Distance between diffusers by length and by width
A, B (m) of the room (A = distance between columns,
B = distance between rows)
Fig. 7: Airflow inside the room
Diffusers | 7 / 18

Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone

VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
HV H V H V H1 = 0,9 1,2 1,6 2 (m)
200 H 120
100

(m = 1
V 80

3 •
qv
60 50

h 0
0,40

-1 )
100

8
5

15
Pressure drop ΔPt (Pa)
50
40 4
Pressure drop ΔPt (Pa)

70 0,30

0
40

10
45
30 0,25

0
50

70
35 )

VH1 (m • s-1)
40
(A 0,20

54
20
30 dB
35

30 15 L W 0,15
25
30

20
(A

10
20
dB

0,10
25

10 8
W
L
20

7 6

5 4
0,05
3
50 70 100 150 200 250 350 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv qv (m3 • h-1) Distance A or B (m)
(m3 • h-1)

VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H V HV H V H V H1 = 0,9 1,2 1,6 2 (m)
100 120
100
80
50

80
60 60

(m = 4 0
45

3 •
q v 30
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

40

h 0
-1 )
40

3
50

25 0
40

30 0,60

VH1 (m • s-1)

20 0
0
45

30

15
20 0,50
35

40

0,40
15
)

35
(A

20
(A
dB
30

dB
30

0,30
10
W

15 0,25
L

W
L
25

8
25

0,20
20

6
10
0,15
20

4
5 3
150 200 250 300 400 500 600 720 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - A - 500 × 24, 600 × 24, 625 × 24 VVKR - A - 500 × 24, 600 × 24, 625 × 24 VVKR - A - 500 × 24, 600 × 24, 625 × 24
H V H V HV HV H1 = 0,9 1,2 1,6 2 (m)
100 120
100

(m = 4
3 •
qv
70 80

h
-1 )
60 0,40
50
30
50

50
0
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

0,30
50

40
20
45

0
15

0,25
45

30 30
0
VH1 (m • s-1)
40

0,20
40

20
20 0,15
35

35

15
(A

)
(A
dB

dB
30
30

10
W
L

0,10
W
L
25

8
25

10
6
20
20

4
0,05
5 3
150 200 300 400 500 700 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - A - 600 × 32 , 625 × 32 VVKR - A - 600 × 32, 625 × 32 VVKR - A - 600 × 32, 625 × 32
H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
100 H 60
Pressure drop ΔPt (Pa)

V
Pressure drop ΔPt (Pa)

(m = 65

70
50

40
3 •
q V 00

50 50
45

30
h
-1 )
VH1 (m • s-1)

0,60
45
40 0

0
40

20
30
0

30 0,50
40
20
A)
35

15
0,40
0
(
dB

20
35
30

10
W
L

0,30
25

30 ) 8
(A 0,25
10 dB 6
20

25 LW 0,20
4
20 0,15
5 3
300 400 600 800 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
8 / 18 | Diffusers

Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone

VVKR - A - 600 × 40 VVKR - A - 600 × 40 VVKR - A - 600 × 40


H V H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
100
H 80

(m = 80
100 V 60

q v 650
3 •
Pressure drop ΔPt (Pa)

h
-1 )
70 40

50 0
50

0
40 0
50
Pressure drop ΔPt (Pa)

0
30

VH1 (m • s-1)
50

30
45 0,60

45
20
0,50
40

40
30

A)
15
0,40

(
35

dB
20 35
10

W
30
)

L
30 0,30
(A 8
dB

25
0,25
10 25 LW 6

20
0,20
20 4
15 3 0,15
5 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
300 400 600 800 1000 1200
qv qv (m3 • h-1) Distance A or B (m)
(m3 • h-1)

VVKR - A - 600 × 48, 625 × 48 VVKR - A - 600 × 48, 625 × 48 VVKR - A - 600 × 48, 625 × 48
H V H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
100
V 80

(m = 0
3 •
qv
100 60

h 0
-1 )
55

95
70
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

70 40

55
50 0,80

0
50 50

40
30

VH1 (m • s-1)
45

0
0,60
45

20
30 40 0,50
)
40

15
(A

35 ) 0,40
(A
dB

20
35

dB 10
30
W

0,30
L

LW
30

8
10 25 6 0,20
25

20
0,15
20

4
5 3
300 400 500 700 1000 1500 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - A - 625 × 54 VVKR - A - 625 × 54 VVKR - A - 625 × 54


H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 V 120
55 100

(m 14
80
H qv

3 •
100 60 =
h 0
-1 )
10

V
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

70 0
00

40
70 0
60

50
0

50
50

30 0,80
VH1 (m • s-1)

45
45

20 0,60
30
40
)
(A
40

15
0,50
dB

20 35
35

10 0,40
L

30 ( A)
30

8
dB
10 25 L 6
25

W
0,30
20 0,25
20

4
5 3 0,20
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m • h )
3 -1 qv (m • h )
3 -1 Distance A or B (m)

VVKR - A - 825 × 80, 800 × 72 VVKR - A - 825 × 80, 800 × 72 VVKR - A - 825 × 80, 800 × 72
H V H=V H=V H1 = 1,2 1,6 2 2,5 (m)
200 120
100
(m

H 80
qv 1

3 •
= 40

100 V 60
h
1

-1 )
60 0
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

70 40
55
10
00

50 30
50 0,60
VH1 (m • s-1)
50

70 0
60
0

30 45 20 0,50
45

)
(A

15
40 0,40
40

dB

20
35 A) 10
W
35

(
dB 8 0,30
30
30

LW
10 6 0,25
25
25

20 4 0,20
20

5 3
600 800 1000 1500 2000 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
Diffusers | 9 / 18

Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone

VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
HV H V H V H1 = 0,9 1,2 1,6 2 (m)
200 H 120
100
V

(m = 18
80

qv
3 •
60 50

h 0
0,40

-1 )
100
5

50

Pressure drop ΔPt (Pa)


4

15
Pressure drop ΔPt (Pa)

70 40 0,30

0
40

10
45
50 30 0,25

0
70
35 )
40
(A

VH1 (m • s-1)
20 0,20

54
30 dB
35

30 L
15 W 0,15
25
30

20
(A

10
dB

20
25

10 8 0,10
W
L
20

7 6
5 4
0,05
50 70 100 150 200 250 350 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H H V HV H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H 60
100
V
50
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

80 40
45

(m = 45
30
50

60

VH1 (m • s-1)

3 •
0,60

qv
40

20

h
-1 )
45

0,50
35

40

30
15
)

0
(A

0
0,40
40

30

dB

20
30
10

15
0
)
W
25

A 0,30
35

0
20 d B( 8
0,25
20

LW 6
30

15 0,20
4
25

10 3 0,15
150 200 250 300 400 500 600 700 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m • h ) 3 -1 qv (m • h )
3 -1 Distance A or B (m)

VVKR - B - 500 × 24, 600 × 24, 625 × 24 VVKR - B - 500 × 24, 600 × 24, 625 × 24 VVKR - B - 500 × 24, 600 × 24, 625 × 24
H V H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
100
80
H
100 60
V
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

50

70 40
50
(m = 5
45

50 30
3 •
q v 450
VH1 (m • s-1)
40

45 0,60
h
-1 )

20
00

30 0,50
40
30
35

15
0
20
)
30

20 0,40
(A

35
0
dB

) 10
(A
25

30 dB 8 0,30
W
L
20

10 LW 6 0,25
25
0,20
20 4
5 3 0,15
150 200 250 300 400 500 600 700 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - B - 600 × 40 VVKR - B - 600 × 40 VVKR - B - 600 × 40


H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H
(m = 90

100 60
q v 00
3 •

V
h
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)

70
-1 )

40
7

50
50

0
50

50 30
0
40
VH1 (m • s-1)

45 0,60
45

20
30 40 0,50
40

)
(A

15
35 0,40
dB
35

20
10
W

30
L
30

) 8 0,30
(A
25 dB
25

10 6 0,25
LW
20
20

0,20
4
5 3 0,15
300 400 500 600 700 800 1000 1200 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
10 / 18 | Diffusers

Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone

VVKR - B - 800 × 64, 825 × 64 VVKR - B - 800 × 64, 825 × 64 VVKR - B - 800 × 64, 825 × 64
H H=V H=V H1 = 1,2 1,6 2 2,5 (m)
200 120
55 100
V
80
100 60
H

Pressure drop ΔPt (Pa)


Pressure drop ΔPt (Pa)

70

(m 160
V 40

qv
3 •
=
50 50 30 0,60

50

h 0
VH1 (m • s-1)

14 00

-1 )
12 00
00
45

10 0
0,50

45
20

90 0
30
40

70 0
(A
15

40
0,40

dB

60
20
35

35
10

W
L
30 ) 8 0,30

30
(A
10 25 dB 6 0,25

25
LW
20 4 0,20

20
5 3
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
H V H V H V H V H1 = 0,9 1,2 1,6 2 (m)
100 120
100
80 80
45

60
60 50
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

40 45

(m = 30
40

qv
3 •
40 30 40 0,60

VH1 (m • s-1)

h
-1 )
20
35 0,50
35

20

0
)

0
30

15
(A
15 30 dB 0,40

0
)
(A
30

dB

25 LW
20 10 0,30
W
L

8 20 0,25
25

15 6
0,20
20

4
10 3 0,15
150 200 250 300 400 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv Distance A or B (m)
(m3 • h-1)

VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H H V HV H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H 60
100
V
50
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

80 40
45

30
50

60
(m = 4
VH1 (m • s-1)

0,60
40

3 •
qv

20
45

h
35

40 0,50
-1 )
30

15
50
A)

0
(

0,40
40

30

dB

30
20

10
15
0

)
W
25

(A
35

0,30
0

8
20 dB
0,25
20

LW 6
30

15
0,20
4
25

10 3 0,15
150 200 250 300 400 500 600 700 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m • h ) 3 -1 qv (m • h )
3 -1 Distance A or B (m)

VVKR - C - 500 × 36, 600 × 36, 625 × 36 VVKR - C - 500 × 36, 600 × 36, 625 × 36 VVKR - C - 500 × 36, 600 × 36, 625 × 36
H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H
(m = 90

100 60
qv
3 •

V
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

70
-1 )

40
70

50
50

0
0
50

50 30
0
40
VH1 (m • s-1)

45 0,60
45

20
30 40 0,50
40

)
(A

15
35 0,40
dB
35

20
10
W

30
L
30

0,30
( A) 8
25 dB
25

10 6 0,25
LW
20 0,20
20

4
5 3 0,15
300 400 500 600 700 800 1000 1200 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
Diffusers | 11 / 18

Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone

VVKR - C - 600 × 48, 625 × 48 VVKR - C - 600 × 48, 625 × 48 VVKR - C - 600 × 48, 625 × 48
H V H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
55 100

(m = 14
80

qv
H

3 •
100 60

h 0
-1 )
10
V
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

0
70

00
40

70 0
60
50

0
50

50
30 0,80

VH1 (m • s-1)
45

45
30 20 0,60
40

)
(A
40
15
0,50

dB
20 35

35

W
10 0,40

L
)
30 A
B(

30
8
d
10 25 LW 6

25
0,30
20 0,25

20
4
5 3 0,20
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

VVKR - C - 825 × 92 VVKR - C - 825 × 92 VVKR - C - 825 × 92


H V H V H=V H=V H1 = 1,2 1,6 2 2,5 (m)
100 120
100
80
70

(m = 16 0
60

q v 140

3 •
50

h 0
-1 )
Pressure drop ΔPt (Pa)

Pressure drop ΔPt (Pa)

50 40

10

0
0,60

00
30
50

70
VH1 (m • s-1)
45

0
0,50
45
20
30
0,40
40

15
)
40

(A
dB

35

20 10 0,30
W

)
L

(A

8
35

30

dB

6 0,25
25

0,20
L
30

4
20
25

10 3
500 700 800 1000 1500 2000 2500 3000 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)

Temperature differential
Temperature differential

0,5
0,4 NOTES:
0,3 1. When installing under a continuous ceiling, the values VH1 and ΔTL / ΔT0
Temperature differential ΔTL / (ΔT0)

0,20 need to be multiplied by the coefficient 0,7


Number of deflectors

0,15 2. The diagrams for the air flow throw and velocity are only applicable for
0,10 installation where A = B
92
80
0,05 48 Legend
0,04 40
0,03
36
0,02 32 H - Horizontal (side) connection
24
16 V - Vertical (top) connection
0,01 8 - Control damper opened
0,8 1 1,5 2 3 4 5
- Control damper 45°
Distance Lt (m)
12 / 18 | Diffusers

Swirl Diffuser VVKR Calculation and Design Example


Given parameters:

Room dimensions:
Width: 18,0 m
Length: 24,0 m
Height: 3,65 m
Air exchange in the room: i = 12 times
Room temperature: T = 24 °C
Temperature differential between the room air temperature and the supply air temperature ΔT0 = -8 K
Average air flow velocity between two diffusers at distance H1, vH1 < 0,2 m•s-1
Requested sound power level LWA < 30 dB(A)

Requested parameters:

1. QV - supply air flow volume into the room


2. qV - supply air flow volume into one VVKR
3. VVKR type

Solution:

1. We determine the supply air volume for the room 24 m long, 18 m wide and 3.65 m high with a plasterboard
ceiling. QV = 24 × 18 × 3,65 × 1 = 24 m × 18 m × 3,65 m × 12 = 18922 m3 • h-1
2. Architect’s definition for this particular case is that the minimim distance from a vertical wall is 3 m (Y = 3 m).
Then the remaining area for VVKR distribution is 12 × 18 m. If the axial distance between end diffusers
at a transverse direction is 12 m and the distance between rows is B = 3 m, then the number of rows is 5 and if the
axial distance between end diffusers at a longitudinal direction is 18 m and the distance between columns is A = 3
m, then the number of columns is 7.
We calculate the supply air flow volume into one VVKR
qV = QV / number of rows (B) × number of columns (A) = 18922 / (5 × 7) = 540 m3 • h-1
3. Based on Tab. 6 we determine a preliminary size design for q V = 540 m3 • h-1, which is VVKR-A-S-600×40

Calculation of the amount of pressure drop, sound power level and effective velocity
for a swirl diffuser
Given parameters:

VVKR-A-S-600×40
Air supply into box - horizontally
Measurable air flow volume q V = 540 m3 • h-1
Free area at dimensions 600 × 40 AV = 0,0409 m2
(from Tab. 4)

Requested parameters:

1. LWA
2. Δpt

Solution:

Based on page 13 (Diagram 1) for an open damper in VVKR-A-S-600×40, where q V = 540 m3 • h-1 we get:

1. diffuser pressure drop: Δpt = 22 Pa

2. sound power level: LWA = 29 dB(A)


Diffusers | 13 / 18

Calculation of vH1 and ΔTL for a swirl diffuser at basic deflector configuration
Flow length between the occupied zone and the ceiling H1 = H - H0 (Obr. 7)
H1 = 3,65 - 1,8 = 1,85 m
Distance between two anemostats A=B=3m

Diagram 2 for VVKR-A-600×40 with a horizontal connection, at qv = 540 m3 • h-1, A = 3 m and distance H1 = 1,85 m shows:
1. vH1 = 0,18 m • s-1

Diagram 3 shows the temperature differential ΔTL / ΔT0 for VVKR-A-S-600×40,


at distance Lt = A/2 + H1 = 1,5 + 1,85 = 3,35 m is:
2. ΔTL / ΔT0 = 0,06
ΔTL = ΔT0 × 0,06 = -8 × 0,06 = -0,48 K

NOTE: In the calculation, it is important to use a lower Lt amount, i.e. the worst case scenario (by a wall or between two diffusers).

Conclusion:
The requests in the example will be fulfilled by anemostat
VVKR - A - S - 600 × 40 in the amount of 35 pieces

with the PB - VVK - S - 600 - S - H plenum box in the amount of 35 pieces,


distributed according to the example solution

VVKR - A - 600 × 40
H V H1 = 0,9 1,2 1,61,85 2 (m)
200 0,5
H 0,4
0,3
Temperature differential ΔTL / (ΔT0)

100 V
(m = 8
qv 0
3 •

0,20
h

70

Number of deflectors
-1 )
65 0

0,15
50
50 0

00
Pressure drop ΔPt (Pa)

40 0

50
VH1 (m • s-1)

30

45 0,60 0,10
30 40 0,50
0,06
92
22 29 80
20 35 0,40 0,05 48
54
0

) 0,04
30 (A 0,30 40
dB 0,03
10 25 LW 0,25 36
0,02 32
20 0,20 24
0,18 16
5 15 0,15 0,01 8
300 400 600 800 1000 1200 0,8 1 1,5 2 3 4 5 6 0,8 1 1,5 2 3 3,35 4 5
qv (m3 • h-1) Distance A or B (m) Distance Lt (m)

Diagram 1: Supply air pressure drop and sound Diagram 2: Air flow throw and air flow velocity, Diagram 3: Temperature differential
power level, VVKR - A - 600 × 40 VVKR - A - 600 × 40
14 / 18 | Diffusers

Accessories
PB-VVK
Plenum box

The PB-VVK is produced in 2 types of shapes round


(PB-VVK-R) or square (PB-VVK-S), with a horizontal
or a vertical connection and with internal or external
insulation. The plenum box is made of galvanized sheet
as a standard.

There are 2 types of connection:

• D1: a simple spigot without a seal, with a damper


• D2: a pressed spigot with a seal including the Zeus
damper (damper information available on page 15)

Ordering codes

PB-VVK-
6 3 2

Plenum box face round R


Plenum box face square S

Dimensions 300 - 825

Supply with mesh screen S


Extract without mesh screen E

Horizontal connection (from the side) H


Vertical connection (from the top) V 1

5 4
Untight spigot with a damper 1 D1
Pressed tight spigot with the Zeus damper 1 D2
Product parts description:
With internal insulation, 14 mm 2 I2
J 1. Spigot
With external insulation 2

2. Casing

3. Hanging bracket
Ordering codes example:
4. Bridge with a rivet nut for connection to a diffuser
PB-VVK - S - 300 - S - H - I2
5. Mesh screen with a rivet nut for connection
Square plenum box with nominal dimension 300, supply with mesh screen,
horizontal connection (from the side), spigot type D1, internal insulation. 6. Damper

1. If the spigot type is not entered in the ordering code, type “D1“ will be Fig. 8: Product PB-VVK
supplied by default. It is not possible to order the Zeus damper for the
product PB-VVK-R with horizontal connection. Plenum boxes with a verti-
cal spigot D2 are supplied without a mesh screen.
2. In case the insulation type is not entered in the ordering code, the product
PB-VVK will be supplied without insulation.
Diffusers | 15 / 18

ød Plenum box selection diagram


50

15

50
PB-VVK-R (for round diffusers) PB-VVK-S (for square diffusers)

ød
Top Side Top Side
H1

H2
connection connection connection connection

77
D1 D2 D1 D1 D2 D1 D2
øD øD
Mesh screen • — • • — • •
øD + 11 øD + 11
Internal insulation I2 • • • • • • •

Fig. 9: Main dimensions of the PB-VVK-R External insulation J • • • • • • •

H1 H2 m
øD ød
Size (horiz.) (vert.) horiz. vert. Legend
(mm) (kg)
D1 - Untight socket with a sheet-metal control damper
300-160 275 250 200 158 2,29 1,97 D2 - Pressed tight socket with a Zeus damper
xxxx - Defined selection option
400-200 364 290 200 198 3,34 2,82
• - Option to add a position to the selection
500-200 470 290 200 198 4,68 3,91 — - Not possible to add a position to the selection

600-200 575 290 300 198 6,21 6,31

600-250 575 340 300 248 6,68 6,23

625-200 595 290 300 198 6,52 6,92

625-250 595 340 300 248 7,00 6,55


The Zeus damper
800-315 775 405 300 313 11,35 10,46 The Zeus control damper contains impulse tubes
825-315 795 405 300 313 11,83 10,88 for measuring differential pressure using a portable
measuring device. It can be adjusted manually using
Tab. 9: Main dimensions of the PB-VVK-R a cable gearing.

ød
50

ød
20
A + 24
ød
2
HH1

H1

□A
B

□A □A
NOTE: In case of using PB-VVK-R with horizontal connection it is not
□A ++ 24
□A 24 □A + 24
A possible to use the Zeus damper.

A + 24
Fig. 10: Main dimensions of PB-VVK-S

H1 H2 m
A×A ød B
Size (horiz.) (vert.) horiz. vert.
(mm) (kg)
300-160 266×266 240 200 158 2,58 2,39

400-160 366×366 240 200 158 3,62 3,43

400-200 366×366 280 200 198 3,98 3,65

500-200 466×466 280 200 198 5,27 4,74


62
600-200 566×566 280 300 198 6,71 7,19

600-250 566×566 330 300 248 7,42 7,31

625-200 591×591 280 300 198 7,11 7,63

625-250
Tab. 591×591
10: Hlavné rozmery330
produktu300 248
PB-VVK-S 7,81 7,73

800-315 766×766 400 300 313 13,63 12,03


67
825-315 791×791 400 300 313 14,22 12,61

Tab. 10: Main dimensions of the PB-VVK-S


16 / 18 | Diffusers

PB-VVKU
Universal plenum box

K1

K2 ød1

The PB-VVKU is a universal box which is possible to use


for installation on various types of air terminal devices.

ød1
H
The PB-VVKU is manufactured from galvanized sheet.

60
Upon customer’s request it is possible to apply a powder-
K4
paint RAL surface finish. The box is optimized for use

40
ød2

with both horizontal and vertical connection. When K3 7


in storage, the PB-VVKU provides the advantage of
stacking, thus saving storage space. Fig. 11: Main dimensions of the PB-VVKU

Ordering codes
PB-VVKU- ød1 ød2 K1 K2 K3 K4 H m
Size
(mm) (kg)
Not insulated - horizontal 0H
Not insulated - vertical 0V 300 98 126 250 200 278 292 190 1,95
Insulated - horizontal IH
300 123 247 200 278 292 215 2,20
Layout Insulated - vertical IV 161
300 158 242 185 278 292 250 2,50
Dimensions Nominal Box Size (300 - 625) 400 158 202 340 279 378 392 240 4,10

400 198 334 260 378 392 280 4,50


Plenum Box Connection (100 - 315)
500 158 252 438 375 478 492 250 5,90
Mounting Frame R
500 198 432 356 478 492 290 6,10
Mesh screen S
Connection type Spigot and socket joint U 500 248 432 336 478 492 320 6,50

600 198 535 465 578 592 270 6,70


No Sealing A
Sealing B 600 248 528 442 578 592 320 7,70
Spigot type Sealing and Damper C 317
600 313 500 400 578 592 385 8,90

625 198 560 490 603 617 270 8,70

Ordering codes example: 625 248 553 467 603 617 320 9,10

PB-VVKU - 0H - 300 - 100 - S - B 625 313 402 540 440 603 617 385 9,70

Universal plenum box, not insulated with horizontal supply,


nominal size 300, connection dimension 100, mesh screen, sealed socket. Tab. 11: Main dimensions and weight of the PB-VVKU

NOTE: When using the PB-VVKU plenum box, it is recommended to read


the technical documentation for the product TPI-07.
Diffusers | 17 / 18

Mounting
The VVKR swirl diffuser is most commonly installed Fig. 12 depicts various methods of installing the VVKR
onto a ventilation duct as illustrated on Fig. 12. onto the ceiling. When mounted into a suspended
The mounting consists of installing the plenum box grid ceiling the supply air swirl is expected to be
to the ceiling using draw-bars and mounting the diffuser partially reduced. It is therefore needed to respect the
face onto the plenum box using a centric screw which is minimum distance of the diffuser - at least 150 mm
included in the delivery. from the grid ceiing.

závesné tyče

øD

˃150
h
1. Flush mounted for continuous suspended ceiling 2. Free hanging installation onto ceiling 3. Installation between the ceiling and the
hmin > (3 ~ 5) D suspended grid ceiling

Fig. 12: Examples of mounting


Diffusers | 18 / 18

Diffusers - Related products

VVKN
Swirl diffusers with fixed deflectors

Information about the product is in the technical


documentation TPI-31.

VVT
Swirl diffusers with thermostatic control

Information about the product is in the technical


documentation TPI-41.

10 / 2013
Systemair
TPI-19