VVKR
Swirl ceiling diffuser with adjustable deflectors
NOTE:
Combinations of diffuser types, dimensions and number of deflectors need
to be based on Fig. 6 (page 3).
Design
Material used
□A □A □A □A □A □A
□A □A □A øD øD øD
øD øD øD øD øD øD
□A □A □A □A □A
øD øD øD øD øD
□A □A □A □A □A
NOTE: The front plate sizes (XXX) for different diffuser types and number of nozzles are available in Tab. 4 on page 4.
4 / 18 | Diffusers
Dimensions
□A øD Free area
Size
(mm) With Without
Type Size × Number of deflectors
300 296 298 deflectors deflectors
Number of deflectors
Size
8 16 24 32 36 40 48 54 64 72 80 92
300 0,7
Number of deflectors
Diffuser size
8 16 24 32 36 40 48 54 64 72 80 92
300 Plenum box size
400
500
600
625
400
500
600
625
500
600
625
600
625
500
600
625
600
625
600
625
625
800
825
800
825
825
300 •
400 • • •
500 • • • • • • •
600 • • • • • • • • • • • • • •
625 • • • • • • • • • • • • • • • • • • • • • •
800 • •
825 • • • •
Tab. 5: Overview of possible plenum box and diffuser combinations Legend
NOTES:
For square diffusers VVKR-A or VVKR-B it is possible to use both round
and square plenum boxes.
• - Recommended plenum box size for diffuser
with number of deflectors
For round diffusers it is only possible to use round plenum boxes.
For diffusers VVKR-C it is only possible to use square plenum boxes.
Quick selection
1000
qv (m3 • h-1)
500
0
300×8 400×16 500×24 600×32 600×40 600×48 625×54 800×72
400×8 500×16 625×24 625×32 625×40 625×48 825×80
500×8 600×16
600×8 625×16
625×8
Tab. 6: Quick selection table for VVKR-A for air supply via a plenum box with horizontal connection
1000 1000
qv (m • h )
qv (m3 • h-1)
-1
500 500
3
0 0
300×8 400×16 500×24 600×40 800×64 300×8 400×16 500×36 600×48 825×92
400×8 500×16 600×24 825×64 400×8 500×16 600×36 625×48
500×8 600×16 625×24 500×8 600×16 625×36
600×8 625×16 600×8 625×16
625×8 625×8
Tab. 7: Quick selection table for VVKR-B for air supply via a plenum box Tab. 8: Quick selection table for VVKR-C for air supply via a plenum box
with horizontal connection with horizontal connection
6 / 18 | Diffusers
Technical parameters
Terminology Legend
H1
∆TL - Difference between the airflow core and room
(K)
H
H0 = 1,8 m
LW dB(A) - Sound power level
- Distance between diffusers by length and by width
A, B (m) of the room (A = distance between columns,
B = distance between rows)
Fig. 7: Airflow inside the room
Diffusers | 7 / 18
Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone
VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - A - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
HV H V H V H1 = 0,9 1,2 1,6 2 (m)
200 H 120
100
(m = 1
V 80
3 •
qv
60 50
h 0
0,40
-1 )
100
8
5
15
Pressure drop ΔPt (Pa)
50
40 4
Pressure drop ΔPt (Pa)
70 0,30
0
40
10
45
30 0,25
0
50
70
35 )
VH1 (m • s-1)
40
(A 0,20
54
20
30 dB
35
30 15 L W 0,15
25
30
20
(A
10
20
dB
0,10
25
10 8
W
L
20
7 6
5 4
0,05
3
50 70 100 150 200 250 350 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv qv (m3 • h-1) Distance A or B (m)
(m3 • h-1)
VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - A - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H V HV H V H V H1 = 0,9 1,2 1,6 2 (m)
100 120
100
80
50
80
60 60
(m = 4 0
45
3 •
q v 30
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
40
h 0
-1 )
40
3
50
25 0
40
30 0,60
VH1 (m • s-1)
20 0
0
45
30
15
20 0,50
35
40
0,40
15
)
35
(A
20
(A
dB
30
dB
30
0,30
10
W
15 0,25
L
W
L
25
8
25
0,20
20
6
10
0,15
20
4
5 3
150 200 250 300 400 500 600 720 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
VVKR - A - 500 × 24, 600 × 24, 625 × 24 VVKR - A - 500 × 24, 600 × 24, 625 × 24 VVKR - A - 500 × 24, 600 × 24, 625 × 24
H V H V HV HV H1 = 0,9 1,2 1,6 2 (m)
100 120
100
(m = 4
3 •
qv
70 80
h
-1 )
60 0,40
50
30
50
50
0
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
0,30
50
40
20
45
0
15
0,25
45
30 30
0
VH1 (m • s-1)
40
0,20
40
20
20 0,15
35
35
15
(A
)
(A
dB
dB
30
30
10
W
L
0,10
W
L
25
8
25
10
6
20
20
4
0,05
5 3
150 200 300 400 500 700 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
VVKR - A - 600 × 32 , 625 × 32 VVKR - A - 600 × 32, 625 × 32 VVKR - A - 600 × 32, 625 × 32
H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
100 H 60
Pressure drop ΔPt (Pa)
V
Pressure drop ΔPt (Pa)
(m = 65
70
50
40
3 •
q V 00
50 50
45
30
h
-1 )
VH1 (m • s-1)
0,60
45
40 0
0
40
20
30
0
30 0,50
40
20
A)
35
15
0,40
0
(
dB
20
35
30
10
W
L
0,30
25
30 ) 8
(A 0,25
10 dB 6
20
25 LW 0,20
4
20 0,15
5 3
300 400 600 800 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
8 / 18 | Diffusers
Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone
(m = 80
100 V 60
q v 650
3 •
Pressure drop ΔPt (Pa)
h
-1 )
70 40
50 0
50
0
40 0
50
Pressure drop ΔPt (Pa)
0
30
VH1 (m • s-1)
50
30
45 0,60
45
20
0,50
40
40
30
A)
15
0,40
(
35
dB
20 35
10
W
30
)
L
30 0,30
(A 8
dB
25
0,25
10 25 LW 6
20
0,20
20 4
15 3 0,15
5 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
300 400 600 800 1000 1200
qv qv (m3 • h-1) Distance A or B (m)
(m3 • h-1)
VVKR - A - 600 × 48, 625 × 48 VVKR - A - 600 × 48, 625 × 48 VVKR - A - 600 × 48, 625 × 48
H V H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
100
V 80
(m = 0
3 •
qv
100 60
h 0
-1 )
55
95
70
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
70 40
55
50 0,80
0
50 50
40
30
VH1 (m • s-1)
45
0
0,60
45
20
30 40 0,50
)
40
15
(A
35 ) 0,40
(A
dB
20
35
dB 10
30
W
0,30
L
LW
30
8
10 25 6 0,20
25
20
0,15
20
4
5 3
300 400 500 700 1000 1500 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
(m 14
80
H qv
3 •
100 60 =
h 0
-1 )
10
V
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
70 0
00
40
70 0
60
50
0
50
50
30 0,80
VH1 (m • s-1)
45
45
20 0,60
30
40
)
(A
40
15
0,50
dB
20 35
35
10 0,40
L
30 ( A)
30
8
dB
10 25 L 6
25
W
0,30
20 0,25
20
4
5 3 0,20
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m • h )
3 -1 qv (m • h )
3 -1 Distance A or B (m)
VVKR - A - 825 × 80, 800 × 72 VVKR - A - 825 × 80, 800 × 72 VVKR - A - 825 × 80, 800 × 72
H V H=V H=V H1 = 1,2 1,6 2 2,5 (m)
200 120
100
(m
H 80
qv 1
3 •
= 40
100 V 60
h
1
-1 )
60 0
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
70 40
55
10
00
50 30
50 0,60
VH1 (m • s-1)
50
70 0
60
0
30 45 20 0,50
45
)
(A
15
40 0,40
40
dB
20
35 A) 10
W
35
(
dB 8 0,30
30
30
LW
10 6 0,25
25
25
20 4 0,20
20
5 3
600 800 1000 1500 2000 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
Diffusers | 9 / 18
Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone
VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - B - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
HV H V H V H1 = 0,9 1,2 1,6 2 (m)
200 H 120
100
V
(m = 18
80
qv
3 •
60 50
h 0
0,40
-1 )
100
5
50
15
Pressure drop ΔPt (Pa)
70 40 0,30
0
40
10
45
50 30 0,25
0
70
35 )
40
(A
VH1 (m • s-1)
20 0,20
54
30 dB
35
30 L
15 W 0,15
25
30
20
(A
10
dB
20
25
10 8 0,10
W
L
20
7 6
5 4
0,05
50 70 100 150 200 250 350 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - B - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H H V HV H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H 60
100
V
50
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
80 40
45
(m = 45
30
50
60
VH1 (m • s-1)
3 •
0,60
qv
40
20
h
-1 )
45
0,50
35
40
30
15
)
0
(A
0
0,40
40
30
dB
20
30
10
15
0
)
W
25
A 0,30
35
0
20 d B( 8
0,25
20
LW 6
30
15 0,20
4
25
10 3 0,15
150 200 250 300 400 500 600 700 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m • h ) 3 -1 qv (m • h )
3 -1 Distance A or B (m)
VVKR - B - 500 × 24, 600 × 24, 625 × 24 VVKR - B - 500 × 24, 600 × 24, 625 × 24 VVKR - B - 500 × 24, 600 × 24, 625 × 24
H V H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
100
80
H
100 60
V
Pressure drop ΔPt (Pa)
50
70 40
50
(m = 5
45
50 30
3 •
q v 450
VH1 (m • s-1)
40
45 0,60
h
-1 )
20
00
30 0,50
40
30
35
15
0
20
)
30
20 0,40
(A
35
0
dB
) 10
(A
25
30 dB 8 0,30
W
L
20
10 LW 6 0,25
25
0,20
20 4
5 3 0,15
150 200 250 300 400 500 600 700 1000 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
100 60
q v 00
3 •
V
h
Pressure drop ΔPt (Pa)
Pressure drop ΔPt (Pa)
70
-1 )
40
7
50
50
0
50
50 30
0
40
VH1 (m • s-1)
45 0,60
45
20
30 40 0,50
40
)
(A
15
35 0,40
dB
35
20
10
W
30
L
30
) 8 0,30
(A
25 dB
25
10 6 0,25
LW
20
20
0,20
4
5 3 0,15
300 400 500 600 700 800 1000 1200 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
10 / 18 | Diffusers
Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone
VVKR - B - 800 × 64, 825 × 64 VVKR - B - 800 × 64, 825 × 64 VVKR - B - 800 × 64, 825 × 64
H H=V H=V H1 = 1,2 1,6 2 2,5 (m)
200 120
55 100
V
80
100 60
H
70
(m 160
V 40
qv
3 •
=
50 50 30 0,60
50
h 0
VH1 (m • s-1)
14 00
-1 )
12 00
00
45
10 0
0,50
45
20
90 0
30
40
70 0
(A
15
40
0,40
dB
60
20
35
35
10
W
L
30 ) 8 0,30
30
(A
10 25 dB 6 0,25
25
LW
20 4 0,20
20
5 3
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8 VVKR - C - 300 × 8, 400 × 8, 500 × 8, 600 × 8, 625 × 8
H V H V H V H V H1 = 0,9 1,2 1,6 2 (m)
100 120
100
80 80
45
60
60 50
Pressure drop ΔPt (Pa)
40 45
(m = 30
40
qv
3 •
40 30 40 0,60
VH1 (m • s-1)
h
-1 )
20
35 0,50
35
20
0
)
0
30
15
(A
15 30 dB 0,40
0
)
(A
30
dB
25 LW
20 10 0,30
W
L
8 20 0,25
25
15 6
0,20
20
4
10 3 0,15
150 200 250 300 400 500 200 400 600 1000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv Distance A or B (m)
(m3 • h-1)
VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16 VVKR - C - 400 × 16, 500 × 16, 600 × 16, 625 × 16
H H V HV H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H 60
100
V
50
Pressure drop ΔPt (Pa)
80 40
45
30
50
60
(m = 4
VH1 (m • s-1)
0,60
40
3 •
qv
20
45
h
35
40 0,50
-1 )
30
15
50
A)
0
(
0,40
40
30
dB
30
20
10
15
0
)
W
25
(A
35
0,30
0
8
20 dB
0,25
20
LW 6
30
15
0,20
4
25
10 3 0,15
150 200 250 300 400 500 600 700 200 400 600 1000 2000 0,8 1 1,5 2 3 4 5 6
qv (m • h ) 3 -1 qv (m • h )
3 -1 Distance A or B (m)
VVKR - C - 500 × 36, 600 × 36, 625 × 36 VVKR - C - 500 × 36, 600 × 36, 625 × 36 VVKR - C - 500 × 36, 600 × 36, 625 × 36
H H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
V 100
80
H
(m = 90
100 60
qv
3 •
V
Pressure drop ΔPt (Pa)
70
-1 )
40
70
50
50
0
0
50
50 30
0
40
VH1 (m • s-1)
45 0,60
45
20
30 40 0,50
40
)
(A
15
35 0,40
dB
35
20
10
W
30
L
30
0,30
( A) 8
25 dB
25
10 6 0,25
LW
20 0,20
20
4
5 3 0,15
300 400 500 600 700 800 1000 1200 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
Diffusers | 11 / 18
Pressure drop & sound Pressure drop & sound Air flow velocity in the
power level of the supply air power level of the extract air occupied zone
VVKR - C - 600 × 48, 625 × 48 VVKR - C - 600 × 48, 625 × 48 VVKR - C - 600 × 48, 625 × 48
H V H=V H=V H1 = 0,9 1,2 1,6 2 (m)
200 120
55 100
(m = 14
80
qv
H
3 •
100 60
h 0
-1 )
10
V
Pressure drop ΔPt (Pa)
0
70
00
40
70 0
60
50
0
50
50
30 0,80
VH1 (m • s-1)
45
45
30 20 0,60
40
)
(A
40
15
0,50
dB
20 35
35
W
10 0,40
L
)
30 A
B(
30
8
d
10 25 LW 6
25
0,30
20 0,25
20
4
5 3 0,20
300 400 500 700 800 1000 1500 200 400 600 1000 2000 5000 0,8 1 1,5 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
(m = 16 0
60
q v 140
3 •
50
h 0
-1 )
Pressure drop ΔPt (Pa)
50 40
10
0
0,60
00
30
50
70
VH1 (m • s-1)
45
0
0,50
45
20
30
0,40
40
15
)
40
(A
dB
35
20 10 0,30
W
)
L
(A
8
35
30
dB
6 0,25
25
0,20
L
30
4
20
25
10 3
500 700 800 1000 1500 2000 2500 3000 200 400 600 1000 2000 5000 1,6 2 3 4 5 6
qv (m3 • h-1) qv (m3 • h-1) Distance A or B (m)
Temperature differential
Temperature differential
0,5
0,4 NOTES:
0,3 1. When installing under a continuous ceiling, the values VH1 and ΔTL / ΔT0
Temperature differential ΔTL / (ΔT0)
0,15 2. The diagrams for the air flow throw and velocity are only applicable for
0,10 installation where A = B
92
80
0,05 48 Legend
0,04 40
0,03
36
0,02 32 H - Horizontal (side) connection
24
16 V - Vertical (top) connection
0,01 8 - Control damper opened
0,8 1 1,5 2 3 4 5
- Control damper 45°
Distance Lt (m)
12 / 18 | Diffusers
Room dimensions:
Width: 18,0 m
Length: 24,0 m
Height: 3,65 m
Air exchange in the room: i = 12 times
Room temperature: T = 24 °C
Temperature differential between the room air temperature and the supply air temperature ΔT0 = -8 K
Average air flow velocity between two diffusers at distance H1, vH1 < 0,2 m•s-1
Requested sound power level LWA < 30 dB(A)
Requested parameters:
Solution:
1. We determine the supply air volume for the room 24 m long, 18 m wide and 3.65 m high with a plasterboard
ceiling. QV = 24 × 18 × 3,65 × 1 = 24 m × 18 m × 3,65 m × 12 = 18922 m3 • h-1
2. Architect’s definition for this particular case is that the minimim distance from a vertical wall is 3 m (Y = 3 m).
Then the remaining area for VVKR distribution is 12 × 18 m. If the axial distance between end diffusers
at a transverse direction is 12 m and the distance between rows is B = 3 m, then the number of rows is 5 and if the
axial distance between end diffusers at a longitudinal direction is 18 m and the distance between columns is A = 3
m, then the number of columns is 7.
We calculate the supply air flow volume into one VVKR
qV = QV / number of rows (B) × number of columns (A) = 18922 / (5 × 7) = 540 m3 • h-1
3. Based on Tab. 6 we determine a preliminary size design for q V = 540 m3 • h-1, which is VVKR-A-S-600×40
Calculation of the amount of pressure drop, sound power level and effective velocity
for a swirl diffuser
Given parameters:
VVKR-A-S-600×40
Air supply into box - horizontally
Measurable air flow volume q V = 540 m3 • h-1
Free area at dimensions 600 × 40 AV = 0,0409 m2
(from Tab. 4)
Requested parameters:
1. LWA
2. Δpt
Solution:
Based on page 13 (Diagram 1) for an open damper in VVKR-A-S-600×40, where q V = 540 m3 • h-1 we get:
Calculation of vH1 and ΔTL for a swirl diffuser at basic deflector configuration
Flow length between the occupied zone and the ceiling H1 = H - H0 (Obr. 7)
H1 = 3,65 - 1,8 = 1,85 m
Distance between two anemostats A=B=3m
Diagram 2 for VVKR-A-600×40 with a horizontal connection, at qv = 540 m3 • h-1, A = 3 m and distance H1 = 1,85 m shows:
1. vH1 = 0,18 m • s-1
NOTE: In the calculation, it is important to use a lower Lt amount, i.e. the worst case scenario (by a wall or between two diffusers).
Conclusion:
The requests in the example will be fulfilled by anemostat
VVKR - A - S - 600 × 40 in the amount of 35 pieces
VVKR - A - 600 × 40
H V H1 = 0,9 1,2 1,61,85 2 (m)
200 0,5
H 0,4
0,3
Temperature differential ΔTL / (ΔT0)
100 V
(m = 8
qv 0
3 •
0,20
h
70
Number of deflectors
-1 )
65 0
0,15
50
50 0
00
Pressure drop ΔPt (Pa)
40 0
50
VH1 (m • s-1)
30
45 0,60 0,10
30 40 0,50
0,06
92
22 29 80
20 35 0,40 0,05 48
54
0
) 0,04
30 (A 0,30 40
dB 0,03
10 25 LW 0,25 36
0,02 32
20 0,20 24
0,18 16
5 15 0,15 0,01 8
300 400 600 800 1000 1200 0,8 1 1,5 2 3 4 5 6 0,8 1 1,5 2 3 3,35 4 5
qv (m3 • h-1) Distance A or B (m) Distance Lt (m)
Diagram 1: Supply air pressure drop and sound Diagram 2: Air flow throw and air flow velocity, Diagram 3: Temperature differential
power level, VVKR - A - 600 × 40 VVKR - A - 600 × 40
14 / 18 | Diffusers
Accessories
PB-VVK
Plenum box
Ordering codes
PB-VVK-
6 3 2
5 4
Untight spigot with a damper 1 D1
Pressed tight spigot with the Zeus damper 1 D2
Product parts description:
With internal insulation, 14 mm 2 I2
J 1. Spigot
With external insulation 2
2. Casing
3. Hanging bracket
Ordering codes example:
4. Bridge with a rivet nut for connection to a diffuser
PB-VVK - S - 300 - S - H - I2
5. Mesh screen with a rivet nut for connection
Square plenum box with nominal dimension 300, supply with mesh screen,
horizontal connection (from the side), spigot type D1, internal insulation. 6. Damper
1. If the spigot type is not entered in the ordering code, type “D1“ will be Fig. 8: Product PB-VVK
supplied by default. It is not possible to order the Zeus damper for the
product PB-VVK-R with horizontal connection. Plenum boxes with a verti-
cal spigot D2 are supplied without a mesh screen.
2. In case the insulation type is not entered in the ordering code, the product
PB-VVK will be supplied without insulation.
Diffusers | 15 / 18
15
50
PB-VVK-R (for round diffusers) PB-VVK-S (for square diffusers)
ød
Top Side Top Side
H1
H2
connection connection connection connection
77
D1 D2 D1 D1 D2 D1 D2
øD øD
Mesh screen • — • • — • •
øD + 11 øD + 11
Internal insulation I2 • • • • • • •
H1 H2 m
øD ød
Size (horiz.) (vert.) horiz. vert. Legend
(mm) (kg)
D1 - Untight socket with a sheet-metal control damper
300-160 275 250 200 158 2,29 1,97 D2 - Pressed tight socket with a Zeus damper
xxxx - Defined selection option
400-200 364 290 200 198 3,34 2,82
• - Option to add a position to the selection
500-200 470 290 200 198 4,68 3,91 — - Not possible to add a position to the selection
ød
50
ød
20
A + 24
ød
2
HH1
H1
□A
B
□A □A
NOTE: In case of using PB-VVK-R with horizontal connection it is not
□A ++ 24
□A 24 □A + 24
A possible to use the Zeus damper.
A + 24
Fig. 10: Main dimensions of PB-VVK-S
H1 H2 m
A×A ød B
Size (horiz.) (vert.) horiz. vert.
(mm) (kg)
300-160 266×266 240 200 158 2,58 2,39
625-250
Tab. 591×591
10: Hlavné rozmery330
produktu300 248
PB-VVK-S 7,81 7,73
PB-VVKU
Universal plenum box
K1
K2 ød1
ød1
H
The PB-VVKU is manufactured from galvanized sheet.
60
Upon customer’s request it is possible to apply a powder-
K4
paint RAL surface finish. The box is optimized for use
40
ød2
Ordering codes
PB-VVKU- ød1 ød2 K1 K2 K3 K4 H m
Size
(mm) (kg)
Not insulated - horizontal 0H
Not insulated - vertical 0V 300 98 126 250 200 278 292 190 1,95
Insulated - horizontal IH
300 123 247 200 278 292 215 2,20
Layout Insulated - vertical IV 161
300 158 242 185 278 292 250 2,50
Dimensions Nominal Box Size (300 - 625) 400 158 202 340 279 378 392 240 4,10
Ordering codes example: 625 248 553 467 603 617 320 9,10
PB-VVKU - 0H - 300 - 100 - S - B 625 313 402 540 440 603 617 385 9,70
Mounting
The VVKR swirl diffuser is most commonly installed Fig. 12 depicts various methods of installing the VVKR
onto a ventilation duct as illustrated on Fig. 12. onto the ceiling. When mounted into a suspended
The mounting consists of installing the plenum box grid ceiling the supply air swirl is expected to be
to the ceiling using draw-bars and mounting the diffuser partially reduced. It is therefore needed to respect the
face onto the plenum box using a centric screw which is minimum distance of the diffuser - at least 150 mm
included in the delivery. from the grid ceiing.
závesné tyče
øD
˃150
h
1. Flush mounted for continuous suspended ceiling 2. Free hanging installation onto ceiling 3. Installation between the ceiling and the
hmin > (3 ~ 5) D suspended grid ceiling
VVKN
Swirl diffusers with fixed deflectors
VVT
Swirl diffusers with thermostatic control
10 / 2013
Systemair
TPI-19