TPG Relays ABB Distance

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 7

Technical Specification

Technical Particular and


Guarantee
Distance Protection Relays

No Description Unit Required Proposed & Guarantee


1 Manufacturer REL650(A11)

2 Type of Designation Digital Numerical

3 Input

AC Voltage V 110-120 rms, phase - phase 100 - 120 rms, phase - phase

AC Current A 1 and 5 (able to accommodate 1A and 5A in one 1 and 5 (able to accommodate 1A and 5A in one device)
device)
Freq Hz 50 50

4 Aux Supply V min 110 Vdc ( -15 s/d +10% ) 48 - 125 Vdc ( 38 - 150 Vdc )

5 Relays Characteristic

Setting Zone - 4 zone (phase - phase / phase ground) 5 Zone ( phase - phase/ phase ground )

Setting Group - min 2 ( two ) Group 4 Setting Group

Reach Characteristic

Phase - Phase - Mho and Quad Mho - Quad or combined

Phase - Ground - Dyn. Mho or Quad or reactance Mho - Quad or combined

Forward Reach Zone ohm 0.1 ohm - 200 ohm 0.005 - 3000 0hm

Reverse Reach Zone ohm 0.1 ohm - 200 ohm 0.005 - 3000 0hm

Zero Sequence Compensation (kn or ohm Used for all zone Yes
Ko)
Angel Characteristic deg Min 48 - 80 deg in 1 step 0 - 90° in step 0.01°
Measuring Accuracy % ± 5% ± 5%

Sensitivity % <10% In 2% In

Typical Operating time ms ≤30 30

Maximum Operating time ms <40, at 80% reach setting 30 at 85% reach setting

SIR - 1<SIR<30 0.5<SIR<30

Scheme - Basic, PUTT,POTT + WI, Blocking Basic, PUTT,POTT + WI, Blocking

Tripping Scheme - Single and Three pahse Tripping Single and Three pahse Tripping

Time Setting

Zone 1 ms 0 - 2000 ms, with step 10 ms 0 - 60000 with step 1 ms

Zone 2 ms min. 100 - 2500 0 - 60000 with step 1 ms

Zone 3 ms min. 100 - 3500 0 - 60000 with step 1 ms

Time Signalling Channel ms min. 0 - 80 in step 1 ms 0 - 60000 with step 1 ms

Timer Accuracy max ± 5% with SIR less than 30

Auto Reclose

Dead Time SPAR sec 0.1 - 2 in 0.1 sec step 0 - 60 s, step 1 ms

Dead Time TPAR sec 0.1 - 30 in 0.1 sec step 0 - 60 s, step 1 ms

Reclaim time sec 5 - 100 in 0.1 sec step 0 - 6000 s, step 10 ms

Synchro Check

Voltage Diff % 5 - 20 % of rating in 1% steps or 70-100 V in 1V step 2 - 50 % Un with step 1 %

Phase Diff deg 5 - 30 deg in 2.5 deg step 5 - 90 deg, step 1 deg

Freq Slip sec 0 -1 sec in 0.5 sec step 0 - 60 sec, step 1 ms

LL/DB and DL/LB Enable Yes

Minimum Features

PSB - Enabled Enabled


CT Supervisi for disatance Enabled Enabled

Out of Step Enabled Enabled

SOTF - Enabled Enabled

Self Diagnostic - Enabled Enabled

VTS - Enabled Enabled

Watch Dog - Enabled Enabled

Block for relays Failure - Enabled Enabled

output Contact Rating

Rated Voltage Vdc min 125 250 Vdc

Continuous A >3 5

Make and Carry A >15 30 A for 0.5 sec

MMI - keypad and comm. Port with PC (Built in) keypad and comm. Port with PC (Built in)

6 Disturbance and Event Recorder

Number of record - The last 3 record in ring buffer 100 record in ring buffer

Analog Input - min 4 voltage and 4 current 40 analog input

Trigger Analog Signal - Trip signal and analog input change Trip signal and analog input change

Trigger Event Signal - internal and external Trigger internal and external Trigger

Sampling Rate - min 12 ample per cycle min 12 ample per cycle

Recording Duration sec min 2.5 sec 3.4 sec for all input triggerred

Format File - COMTRADE IEC 60255 - 24 COMTRADE IEC 60255 - 24

7 Communication

Protocol - IEC61850 and modbus or IEC61950 and IEC103 or IEC61850


Iec61
Interface - RS232, RS485, USB RS485

Communication Type - serial RJ45


Data Transfer Speed bit/s min 1200 1200 - 19200 bit/sec

Communication Port - front or rear or both Both

Communication Media - Shielded or Fiber optic Shielded or Fiber optic

8 Performace Test

Type Test Submitted Submitted

Routine Test Submitted Submitted

Acceptance Test Test by user ok

RTDS withness by User+J75 ok

Operation Performance Existing Yes

9 High Voltage Withstand - Min complied with IEC60255-5: Min complied with IEC60255-5:

1997 / ANSI C37.90-1989 1997 / ANSI C37.90-2005

Dielectric Withstand - 2 kV rms for 1 minute between all 2 kV rms for 1 minute between all

case terminal connected together case terminal connected together

and case earth and case earth

2 kV rms for 1 minute between all 2 kV rms for 1 minute between all

case terminal independent circuit case terminal independent circuit

with terminal on each indepent with terminal on each indepent

circuit connected together circuit connected together

High Voltage Impuls IEC60255-5:1977, three positive IEC60255-5:1977, three positive

and three negative impulse of 5 kV and three negative impulse of 5 kV

peak, 1.25/50 ps, 0.5 J between all peak, 1.25/50 ps, 0.5 J between all

terminal and terminal to case earth terminal and terminal to case earth

10 Electrical Environment Strength Min complied with IEC60266-11: Min complied with IEC60266-11:

DC Supply Interuption 1979 1979


The unit will withstand a 20 ms The unit will withstand a 50 ms

Interruption in the aux supply, in its Interruption in the aux supply, in its

quiescent State, w/o deenergizing quiescent State, w/o deenergizing

IEC 60225-11:1979 IEC 60225-11:1979

Withstand 12% DC Ripple on Supply Withstand 15% DC Ripple on Supply

Supply Fast Transient withstand IEC 60255-22-4:1992 1 ANSI C37.90.1 IEC 60255-22-4:1992 1 ANSI C37.90.1

4 kV, 2.5 kHZ Applied Directly to Aux Supply 4 kV, 2.5 kHZ Applied Directly to Aux Supply

4 kV, 2.5 kHZ Applied Directly to Input 4 kV, 2.5 kHZ Applied Directly to Input

Radio interference withstand IEC 60255-22-3:1992/ANSI C37.90.2 IEC 60255-22-3/ANSI C37.90.2 : 2004

25Mhz - 1000Mhz, zero and 100% sq wave 80Mhz - 1000Mhz, zero and 100% sq wave

Modulated Modulated

Field Strength 0f 35 V/m Field Strength 0f 20 V/m

Surge Withstand IEC 60255-22-1/ANSI C37.90.1:1989 IEC 60255-22-1/ANSI C37.90.1: 2012

4kV fast transient and 2.5 kV oscilatory app. 4kV fast transient and 2.5 kV oscilatory app.

directly across each output contact, optically directly across each output contact, optically

isolated input and power supply circuit isolated input and power supply circuit

Electromagnetic Compatibility Complaint Complaint

11 Atmospheric environtment Minimum complied with Minimum complied with

Operation Temp 10 - 50 deg C ( IEC 60255-6:1988 -25 to 55 deg C) 10 - 50 deg C ( IEC 60255-6:1988 -25 to 55 deg C)

Humidity 90(IEC 60068-2-3:1969 56 days at 93% RH 90(IEC 60068-2-3:1969 56 days at 93% RH

and +40 deg C) IEC 60529:1989 and +40 deg C) IEC 60529:1989

Enclosure Protection IEC 60529:1989 IEC 60529:1989

IP 52 Protection ( front panel ) againts dust IP 52 Protection ( front panel ) againts dust

and dripping water at 15deg vertical and dripping water at 15deg vertical
12 Mechanical Strength Minimum Complied with Minimum Complied with

Vibration IEC 60255-21-1:1996 IEC 60255-21-1:1996

Response class 2 Response class 1

Endurance Class 2 Endurance Class 1

IEC 60255-21-2:1995 IEC 60255-21-2

Shock Response class 2 Shock Response class 1

Shock Withstand class1 Shock Withstand class1

Seismic IEC 60255-21-3:1995 IEC 60255-21-3: Class 2

13 Directional Earth Fault Enable Enable

Sensitivity < 10% In 1% of In at I ≤ In

Range Setting

Time for backup trip

Teleprotection Scheme Basic, Blocking and POTT Basic, Blocking and POTT

Characteristic time curve inverse, definite or both Both

Have phase selection ability for single pole AR A must Yes

Trip mode Single and 3 Pole Yes

14 Licensed Software setting Included Included

15 Time Sinchronization IRIG-B and Ethernet Yes

16 Cable connection Included Included

17 Training included ( Class room and Site ) included

18 Default Setting and Logic Enabled Enabled

19 Guarantee 18 month after operation Yes

20 Manual Book ( soft and hard Submited Submited

copy) and enclosed with ori


certificate of routine test

21 Accessories Test Block (MMLG or matching with MMLB) Yes

You might also like