Produced on 13/11/2020 with Xpress Selection V9.0.1 - database DIL 16.0.

Project name INFINIUM GREEN


Project address Peru
Reference LIMA
Client name IDP
Revision GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Type Model Name Qty Description
Outdoor unit RHXYQ14ATL 1 Heat pump VRV IV 220V(TL)LA
Indoor unit FXAQ32AVM 6 VRV A(AVM) - Unidad montada en pared
FXAQ50AVM 3 VRV A(AVM) - Unidad montada en pared
FXDQ50NDVE 1 VRV D(PDVE) - Unidad delgada de conducto montada en techo
Branch unit KHRP26A22T 6 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 2 Refnet branch piping kit
Centralized DTA116A51+SVMPC1 1 (DTA116A51)Home Automation Interface Adaptor with SVMPC1 - External power supply may
controller be required depending on the model
Option or add- BRC2E61 10 Simplified Remote Controller
on
Refrigerant R410A 8.9kg Extra refrigerant charge
Copper pipe Piping ¼" 63.0m Soft copper pipe
Piping ⅜" 32.2m Soft copper pipe
Piping ½" 79.6m Soft copper pipe
Piping ⅝" 24.6m Soft copper pipe
Piping ¾" 5.8m Hard copper pipe
Piping ⅞" 1.8m Hard copper pipe
Piping 1" 16.6m Hard copper pipe

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 2
2.2. VRV - 1 - RHXYQ14ATL
Capacity data at conditions and connection ratio (111%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
UE - 1 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 2 FXAQ50AVM 24.0 / 17.0 n/a 16549 n/a 12857 6.0 11.7 530
UE - 3 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 4 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 5 FXAQ50AVM 24.0 / 17.0 n/a 16549 n/a 12857 6.0 11.7 530
UE - 6 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 7 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 8 FXAQ32AVM 24.0 / 17.0 n/a 10748 n/a 8087 6.0 12.2 346
UE - 9 FXAQ50AVM 24.0 / 17.0 n/a 16549 n/a 12857 6.0 11.7 530
UE - 10 FXDQ50NDVE 24.0 / 17.0 n/a 16549 n/a 12233 6.0 10.0 441

Required cooling capacity towards the outdoor unit: 130686BTU/h.


Required heating capacity towards the outdoor unit: 167877BTU/h.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
UE - 1 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 2 35.5-41 220V 1ph 0.7 1050×290×269 15
UE - 3 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 4 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 5 35.5-41 220V 1ph 0.7 1050×290×269 15
UE - 6 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 7 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 8 28.5-37.5 220V 1ph 0.6 795×290×266 12
UE - 9 35.5-41 220V 1ph 0.7 1050×290×269 15
UE - 10 27-33 220V 1ph 1.3 900×200×620 28

Outdoor unit placed 6.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 3
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
EER EER at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
COP COP at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 4
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC EER (*) Tmp H HC Rq HC COP (*)
% °C BTU/h BTU/h BTU/h/W °C BTU/h BTU/h W/W
VRV - 1 RHXYQ14ATL ▼ 111 30.0 120998 (-7.4%) 130686 15 17.0 / 11.0 167081 (-0.5%) 167877 4.5

(*) The EER and COP values are calculated at nominal conditions: nominal temperatures, 100% connection ratio
and without considering pipe length corrections.

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
VRV - 1 RHXYQ14ATL 44.4 R410A 6.9 8.9

Name Model PS MCA WxHxD Wght


A mm kg
VRV - 1 RHXYQ14ATL 220V 3ph 55 1240×1657×765 285

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 5
3.2.1. VRV - 1 - RHXYQ14ATL

Model Type Model Name Qty Description


Outdoor unit RHXYQ14ATL 1 Heat pump VRV IV 220V(TL)LA
Indoor unit FXAQ32AVM 6 VRV A(AVM) - Unidad montada en pared
FXAQ50AVM 3 VRV A(AVM) - Unidad montada en pared
FXDQ50NDVE 1 VRV D(PDVE) - Unidad delgada de conducto montada en techo
Branch unit KHRP26A22T 6 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 2 Refnet branch piping kit
Option or add-on BRC2E61 10 Simplified Remote Controller
Refrigerant R410A 8.9kg Extra refrigerant charge
Copper pipe Piping ¼" 63.0m Soft copper pipe
Piping ⅜" 32.2m Soft copper pipe
Piping ½" 79.6m Soft copper pipe
Piping ⅝" 24.6m Soft copper pipe
Piping ¾" 5.8m Hard copper pipe
Piping ⅞" 1.8m Hard copper pipe
Piping 1" 16.6m Hard copper pipe

Standard factory refrigerant charge (5m actual piping length) = 6.9kg


Extra refrigerant charge = 16.6m(ø½") × 0.12 + 63.0m(ø¼") × 0.022 + 32.2m(ø⅜") × 0.059 + A + B = 8.9kg
A [ CR 111%, actual length 41.9m ] = 0.0kg
B [ 14HP ] = 3.6kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 6
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping VRV - 1


VRV - 1
RHXYQ14ATL

12.0m 6.0m
½"×1" ¼"×½"
KHRP26A72T

UE - 1
FXAQ32AVM
4.6m 8.6m 12.0m
½"×1" ⅜"×⅝" ¼"×½"
KHRP26A72T KHRP26A22T

UE - 4
FXAQ32AVM
0.8m 4.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

UE - 5
FXAQ50AVM
8.9m 1.5m
⅜"×⅝" ¼"×½"
KHRP26A22T

UE - 6
FXAQ32AVM
7.0m
¼"×½"

UE - 7
FXAQ32AVM
1.8m 1.5m
⅜"×⅞" ¼"×½"
KHRP26A33T

UE - 2
FXAQ50AVM
5.8m 7.0m
⅜"×¾" ¼"×½"
KHRP26A22T

UE - 3
FXAQ32AVM
2.0m 12.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

UE - 10
FXDQ50NDVE
4.3m 4.0m
⅜"×⅝" ¼"×½"
KHRP26A22T

UE - 8
FXAQ32AVM
8.0m
¼"×½"

UE - 9
FXAQ50AVM

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 7
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring VRV - 1


to centralized controller
P1,P2
VRV - 1 UE - 1 BRC2E61
RHXYQ14ATL FXAQ32AVM
OUT F1,F2 IN F1,F2 F1,F2
L1,L2,L3 55A 3ph L, N 0.6A 1ph
P1,P2
UE - 4 BRC2E61
FXAQ32AVM
F1,F2
L, N 0.6A 1ph
P1,P2
UE - 5 BRC2E61
FXAQ50AVM
F1,F2
L, N 0.7A 1ph
P1,P2
UE - 6 BRC2E61
FXAQ32AVM
F1,F2
L, N 0.6A 1ph
P1,P2
UE - 7 BRC2E61
FXAQ32AVM
F1,F2
L, N 0.6A 1ph
P1,P2
UE - 2 BRC2E61
FXAQ50AVM
F1,F2
L, N 0.7A 1ph
P1,P2
UE - 3 BRC2E61
FXAQ32AVM
F1,F2
L, N 0.6A 1ph
P1,P2
UE - 10 BRC2E61
FXDQ50NDVE
F1,F2
L, N 1.3A 1ph
P1,P2
UE - 8 BRC2E61
FXAQ32AVM
F1,F2
L, N 0.6A 1ph
P1,P2
UE - 9 BRC2E61
FXAQ50AVM
F1,F2
L, N 0.7A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 8
6. Device Options

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 9
7. Centralized Controllers
7.1. Concept

Control Groups Specific Controller Models

Control group 1
Automatización en casa
VRV - 1 (10) # outdoors 1
# indoors 10 # controllers 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 10
7.2. Control group 1

VRV - 1 (10)
RHXYQ14ATL OUT F1,F2

Automatización en casa
DTA116A51+SVMPC1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 11

You might also like