PART 1
1.0 INTRODUCTION
This Guide conveys the objectives and vision for the Midfield Concourse and provides each
Tenant with guidelines on how to approach the fit out of their premises so as to be
sympathetic with the ambience and safety standards of the Midfield Concourse. In this
context, all Tenants will be required to meet high standards for design and quality of fit-out,
as well as comply with all relevant constraints. The objective of this document is to set out
the unique design requirements and limitations to be followed by Tenants taking up and
fitting out premises located in the Midfield Concourse building.
Each Tenant shall follow and conform to all obligations defined herein, as well as all rules,
regulations and requirements that the Landlord may promulgate relative to the design and
construction of the Tenant areas. In the event of conflict between this document and the
Airport Authority Hong Kong document entitled ‘Tenant Fit-Out Handbook’, the Tenant shall
seek the advice of the Airport Authority Hong Kong prior to commencing works. The
Airport Authority Hong Kong reserves the right to request the Tenant to carry out
rectification works, at his own cost, for any part of the fit out works which is deemed to
contravene the requirements of this guide and which does not have prior agreement with
the Landlord.
The contents herein do not relieve the Tenant of the obligation to verify the as built
conditions on site and the location of Landlord and Tenant services that run within and
serve the Tenant’s unit. In addition to the requirements stated herein, each Tenant shall be
responsible for compliance with all Statutory Requirements, Codes of Practice, the Fire
Safety Strategy for the Midfield Concourse, requirements of utility companies and all Airport
Authority Hong Kong procedure’s applicable to the design and construction of the Midfield
Concourse works. The Tenant shall be responsible for the submission of all designs to the
relevant bodies to obtain approvals and consents prior to commencing the works.
This Guide should be read in conjunction with other documentation produced to inform
Tenants of the constraints affecting Tenant fit-out design.
Items (1) to (4) above will be issued to the Tenant. All other documents will be made
available, upon request, for inspection in the offices of the Landlord.
1.3 Abbreviations
Unless otherwise stated, the abbreviations use in this guide shall have the following
meaning:
The retail, F&B units and CIP lounges are optimized for the Departures passenger flows
through the MFC. Retail, F&B units and CIP lounges are mainly located in the Departures
Concourse on Level 6 and 7. 2 CIP lounges are also located on Level 5 with direct,
dedicated access from Level 6. Refer to Appendix Fig A.2.1 – A.4.1.
Departing Passengers
Passengers are required to pass through Security & Immigrations check point in Terminal 1
or 2 before taking the APM at East hall to the MFC.
Transferring Passengers
Depending on the location of their onward flight, transferring passengers may be processed
either at the MFC or Terminal 1. Passengers who are transferring from Terminal 1 shall
follow the same route as arrival passengers. Passengers who are transferring within the
MFC shall go through transfer security on Level 5 and re-circulate to the Departures
Concourse for their next flight.
Members of staff may access the building using the APM or airside vehicles. Dedicated
doors with access control are provided for staff to directly access departures, arrivals, retail
/ F&B storage and loading areas. Within the building, circulation is similar to passenger
circulation in front of house areas, but members of staff may also gain access to back of
house areas through doors with access control. A staff channel is provided in the Level 5
Transfer Security area allowing staff movement from Departures to Arrivals.
The building is designed to be operationally and energy efficient, with a distinct identity.
Some specific objectives manifest in the resolved MFC design are:
Retail units are located along the primary circulation in the central node area and along the
north and south concourses on Level 6. This arrangement is supplemented with F&B
outlets, and CIP lounges on Level 7 in the central node to draw interest and create key
focal points of activity.
The retail layout is designed to optimize the frontage length and maximize the number of
shops provided. The shop fronts generate interest when viewed upon passenger arrival
from the central departures escalators and lifts, and from within the north and south arms of
the concourse
Dedicated F&B outlets are located next to the eastern exterior glazing on Level 6.
Open type units which may be used for exhibition or F&B purposes. Two open type units in
the central node, and one open type unit in each concourse. These units are equipped with
provisions for light refreshment or cafeteria use, they are positioned to provide service to
the majority of passengers passing through the MFC.
The flexible planning and services provisions on Level 7 allow the four quadrants to be
used for F&B and CIP Lounges. The two eastern quadrants are primarily intended for F&B
usage, the southwestern quadrant is intended for CIP lounges, and the northwestern
quadrant is intended for a food court.
Plans showing the general disposition of retail, F&B and CIP lounge spaces of different
types throughout the building are shown in Appendix Fig. A.1.1 – A.4.1.The materials have
been selected to provide a relaxing ambience and promote a pleasant shopping and dining
experience, thereby encouraging increased dwell time.
The floor finish of the circulation spaces is polished homogenous floor tiles set on a
modular grid. Accented highlights are integrated into the floor pattern.
Bulkheads over shops on the Level 6 feature metallic champagne bronze colored aluminum
clad surfaces and nosing. The shopfront of the node units feature a front-illuminated,
PART 2
continuous white (RAL 9016) backpainted and acid etched glass downstand; while the
concourse units feature continuous grey (RAL 7012) backpainted laminated glass
downstand with integrated shopfront identity signage, refer to section 3.2.9. Tenants are
not permitted to alter the retail bulkhead in anyway without the permission of the
Landlord.For bulkhead details refer to the Appendix Fig. A.5 and A.6.
3.1 Ge n e ra l De s ig n Is s u e s
The following sub-section is generally applicable to all front of house types of tenancies
within the MFC directly accessible by passengers. These include retail, F&B and CIP
lounges. Plans showing the general disposition of retail, F&B and CIP lounge spaces of
different types throughout the building are shown in the Appendix, Fig A.1.1 – A.4. Tenants
shall achieve BEAM Plus Interiors Gold rating for all fitout works.
The following general design principles of MFC should be considered by the front of house
Tenants within their design concept:
• Contribution of the Tenant's high quality design proposal and standard to the Midfield
Concourse’s excellent ambience and identity;
• Optimized operational efficiency and development of incremental and impulse sales;
• Tenants are expected to produce designs which incorporates their individual corporate
brand identity, contributing presence whilst remaining compatible with the public areas;
• Front of house tenancies shall be seen as integral with the design of MFC Landlord
area and thereby complement the overall architectural theme.
Cooking is not permitted in any area except in enclosed kitchens with 2 hour fire rated
enclosures.
Fixtures and fittings within the tenancy shall be selected to achieve Class 1 Surface Spread
of Flame under BS 476 Part 7 or equivalent.
Specialist products used for the above purpose shall be tested and certified in accordance
with relevant British Standard requirements and shall also be capable of satisfying the
requirements of BD/FSD with respect to Class 1 Surface Spread of Flame when used in
conjunction with the proposed materials of construction.
The following areas within MFC have extended travel distances greater than those
stipulated under Buildings Department’s Code of Practice for Fire Safety in Buildings, 2011:
PART 3
1. Level 5 – Arrivals Level;
2. Level 6 – Departures Concourse Level;
3. Level 7 – Mezzanine Level
The extended travel distances have been allowed subject to the following inherent features
that contribute to fire safety:
Tenants are responsible for these criteria to be reasonably satisfied within the tenancies
and these shall be criteria used by the Landlord in considering the Tenant’s submitted
designs.
The interior of each tenancy must be of a standard equal to the shopfront / frontage design
and surrounding environment and also be suitable for the product / services on offer.
Tenants are encouraged to maintain the clear legible nature of the passenger spaces in
their store theme and planning. The interior of the tenancies shall be designed with equal
attention to detail as the shopfront displays. If a Tenant has a brand or corporate image,
this should be carried through from the shopfront signage into the interior of the tenancy.
Tenants shall be responsible for floor finishes within their premises. The flooring shall be
left by the Landlord with a clean ‘as cast’ concrete slab finish for application of screed by
the Tenant. In most cases the existing slab has a smooth finish and the Tenant should
take steps to ensure an adequate bonding of the screed with the structural concrete slab.
The tenant should use a high performance screed with a proprietary screed additive to
achieve the required bonding and not by the scabbling of the existing concrete. The tenant
is responsible for the supply and installation of their own floor finish; this shall be subject to
prior approval from the Landlord.
The total available depth for the provision of Tenant screed and floor finish measured from
the concrete floor slab to the FFL provided by the Landlord adjacent to the tenancy varies
with building structure tolerances, but is typically in the region of 100mm. Raised slabs to
accommodate lift overruns are present inside units 6MC 005 and 6MC 207, at these
locations the total available depth over the raised slabs is approximately 50mm.
No raising of floor finishes above public area finished floor level is permitted within retail
areas without the Landlord's prior approval.
Generally, floor surfaces are subject to heavy wear and tear through circulation of
passengers. Materials specified for the common area are chosen for their durability, ease
of cleaning and maintenance without causing undue disruption to the operation of the MFC.
Tenants shall follow these principles in the selection of their floor finishes.
PART 3
Floor finishes or anti-slip coating applied to the floor finishes shall achieve dynamic
coefficient of friction (DCOF) of minimum 0.60 or above in both dry and wet conditions on
the floor surface upon completion of the floor finishes works; and a minimum DCOF of 0.40
shall be maintained for at least 12 months under normal wear and tear conditions.
If anti-slip coatings are used, the tenant shall submit the material literature of the anti-slip
coating for the Landlord’s approval.
Testing instrument:
Methodology:
1. Position the self propelling device Tortus on the surface for the test;
2. Drive the Tortus across the surface;
3. Use a leather shoe to the reel of the Tortus for measuring the surface in dry condition;
4. Use (Four S) rubber shoe to the reel of the Tortus for measuring the surface in wet
condition.
Adjacent floor finishes and interfaces shall be finished flush to minimize tripping hazards.
Tenants are not permitted to remove, replace or in any way alter the Landlord’s common
area floor finishes. Tenants shall respect the demise line and the Tenants proposed floor
finishes shall abut with the Landlord finishes.
Tenants shall be responsible to replace defective floor finishes and maintain a smooth floor
level within the Tenant area.
Wherever screeding precedes partition installation, screed angles forming the edge of the
screed area adjacent to dry-lined walls may be omitted. Where screeding follows partition
installation, the screed angle shall be installed. All fire-rated walls are to be installed prior to
screeding.
All floor finishes shall not emit toxic fumes when exposed to fire.
Tenants shall ensure that the noise levels resulting from the operation of any plant,
equipment and any activities within the tenancy area will not cause nuisance to other
Tenants, interfere with airport operational requirements or cause disturbance to passengers.
Tenants shall pay particular attention in their fit-out design to all potential noise generating
sources within their tenancy and incorporate devices such as silencers, isolation, insulation
etc., in order to prevent the transfer of noise and/or vibration to adjacent spaces.
Where a noise complaint is filed against the Tenant, a recognized acoustic consultant shall
be employed by the Landlord to determine if noise from the Tenant have exceeded the
noise criteria. The noise criterion of NC40 shall be adopted; all measurements shall be
conducted with an IEC type 1 sound level meter and shall satisfy standard acoustical
PART 3
practices.
3.1.7 Security
Doors to the rear of tenancies, where they occur, shall be fitted by the Landlord with
ironmongery. To facilitate evacuation in the event of an incident the ironmongery shall
always allow egress from the tenancy.
Some inter-tenancy walls on Level 6 include open mesh above designated Tenant ceiling
level to the soffit above. The Tenant may provide additional security, however provision for
passage of smoke must be maintained.
Burglar alarms devices may be installed by Tenants but they shall not be of audible type.
The flashing component of the burglar alarm must not be installed at any location visible by
passengers.
CCTV and access control can be made available to Tenants within the Tenant area subject
to approval by the Landlord.(See section 8.6.4 for CCTV details) Face detection device
shall not be used.
Operation, maintenance and repair of security shutter is the tenant’s own responsibility.
(see 3.2.3 for shutter details)
Tenants are required to maintain visibility of EXIT signs provided by the Landlord within
their tenancy. Tenants shall install additional LED illuminated EXIT or directional signs as
required to ensure compliance with the current Codes of Practices of the Fire Services
Department and Buildings Department, or where sight lines to those provided by the
Landlord are blocked.
EXIT signs provided by the Landlord within tenancies shall be the subject of routine
inspection and maintenance to be undertaken by the Landlord. Such inspections shall also
include Exit Signs installed by the Tenant but in this case any required maintenance arising
shall be the Tenants responsibility.
Unit enclosure and inter-tenancy walls are generally of dry wall, blockwork or concrete
construction provided by the Landlord. The tenant is not allowed to hang cabinets or
shelves or other heavy pictures, frames, signages or furniture off such partitions. Any new
PART 3
internal walls provided by the Tenant shall be designed to allow the passage of smoke
above the ceiling level.
The Tenant shall provide final finishes and any additional cladding required to existing
tenancy walls and columns. Tenants shall install all walls and partitions within the tenancy
boundary.
Blockwork and concrete walls exposed to public view must be rendered, painted or clad at
the Tenant’s cost. Electrical distribution must be concealed from view, either within the wall
cavity or behind cladding.
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 3 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 3- 5
Steel posts are contained within some tenancies. They are coated with fire retardant paint,
which shall not be compromised in any way. The steel columns may be clad or concealed
within walls but no fixings to the steel columns shall be permitted.
The Tenant, upon completion of the license/lease agreement, shall make good to the
original condition the Landlord’s wall finishes and any modifications he has made to
Landlord’s shell and core.
All glass partitions, screens, or light-boxes, within the region of 500mm setback from
demise line or along the demise line to the public, shall either withstand, or be protected
from, impact by passengers, baggage or trolleys, etc. Where light boxes, glazed screens,
or any other types of walls border public areas, they are to be designed as protective
barriers in accordance with BS 6180 Table 2(f). This gives the following load cases
(separately applied): -
• Horizontal uniformly distributed load of 3.0kN/m applied 1100mm above FFL in case
of those structures located in an area with expected crowd load or level difference;
or horizontal uniformly distributed load of 0.75kN/m applied 1100mm above FFL for
structures located elsewhere;
• Horizontal pressure of 1.0kPa for infill panels or 1.5kPa for glass panels; and a point
load of 1.0kN applied to any part of the infill panel or 1.5kN applied to any part of a
glass panel.
These figures are slightly in excess of those figures quoted in the Buildings (Construction)
Regulations but are considered more appropriate for this situation.
Deflection limits of span/250 for double end supported members and span/150 for
cantilevered members apply for the above loadings separately applied.
Tenants are required to show conclusive proof of safety in terms of impact and abrasion
resistance in accordance with BS 6206:1981(1994), BS 6262-4:1994, BS EN 12150, and
BS EN ISO 12543 where safety, tempered and heat soaked glass has been specified.
All full height glazing utilizing clear glass shall be permanently marked to indicate the
presence of glass, for example, by using dots or bands at eye level (1.5m above FFL). The
Tenant may refer to UK Building Regulations Part K Manifestation for general guidance on
such design. All signs and/or logos on glass are subject to the Landlord's approval.
PART 3
Protective barriers or satin stainless steel buffer rails with a diameter of 50mm should be
added where required to meet the above objectives. The tenant is advised to take
consideration of the height, size and maneuvering of luggage trolleys and to provide extra
protective rails as required.
The Tenant is to ensure the integrity of all fire rated walls, columns and steel posts that
border or are located within his Tenancy. No wall mounted cabinets or the like are
permitted to be fixed to fire rated walls or columns, including steel columns. No chasing of
fire rated walls shall be permitted.
The Tenant shall not make alterations which will reduce, change or eliminate the character
of fire protective structures, panels or barriers.
Tenants should note that construction tolerance for concrete structural elements of the
main building frame is nominally plus or minus 25mm. Tenants are advised to take site
measurements prior to the preparation of detail design drawings.
In the event of a Tenant occupying two or more adjoining tenancies the inter-tenancy wall
may be demolished. Upon completion of the license/lease agreement such walls and
associated mesh for smoke passage shall be reinstated by the Tenant.
The Tenant shall develop their design bearing in mind that upon completion of the
license/lease agreement, they shall make good to original condition all modifications made
to Landlord’s services, structure, shell and core, finishes, flooring, walling, shutters and
components/assemblies forming part of the premises at handover.
Tenants are required to design and install ceilings, wall cladding and cabinetry such that
they allow access by Landlord to Landlord’s services located in the ceiling void above the
Tenants ceiling and at any other locations in walls and floors (minimum panel size to be no
less than 450x450mm). The Tenant should refer to the M&E drawings available from the
Landlord for the extrent of the Landlord services and also arrange to visit the site at regular
intervals through the Tenant design development process to verify exact ‘as installed’
Landlord services arrangement and their locations.
Access panels and the like shall be provided for access to cable containments, valves,
switches, fire dampers, cleaning eyes and other electrical and mechanical equipment
requiring maintenance. Access panels shall be limited in size and weight to facilitate safe
PART 3
handling by one person. Tenants shall submit details of their access panels, intended for
installation as part of their drawing submission for approval by the Landlord.
Tenants’ finishes and light fittings should not block Landlord building services or access
panels.
Tenants shall inform the Landlord of the location, size and weight of any safe or heavy
equipment within Tenant area. Prior approval from the Landlord is required before
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 3 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 3- 7
installation, as well as removal, of any heavy equipment. In case of intended specific heavy
objects, furniture or equipment such as safe, vault, stone sculpture or filing cabinets, load
spreader, tenant shall submit properly designed and certified proposal by a Registered
Structural Engineer for the Landlord’s approval. Refer to Section 10.2 for design loadings,
and structural loading report available separately from the Landlord.
Ceilings provided by the Tenant shall comply with the fire engineering and smoke control
requirements. Ceilings shall have a minimum 30% free area of the total ceiling area;
openings in the ceilings shall be evenly distributed. Where perforated ceiling tiles are used
the holes shall not be less than 4mm diameter. Perforations and openings in the ceiling
shall not be blocked by acoustic backing, debris or other materials that will inhibit the free
passage of smoke through the ceiling. The minimum free area for smoke venting shall be
maintained during tenant fit out and course of tenancy. The Tenant shall keep
600mmclearance for smoke extraction outlets from cabins, racks or other obstacles.
Tenant’s ceiling panels shall be evenly distributed within the retail unit to evenly obscure the
soffit or cabin roof above. Any E&M services (such as diffuser, grille, light fitting, sprinkler
head, detector speaker) or decorations installed on the ceilings shall not reduce the
minimum 30% open ceiling area. All ceiling layouts shall be subject to the Landlord’s
approval.
All materials used in or above the suspended ceiling shall be Non-combustible under BS
476 Part 8 or equivalent. Paint finishes shall be Class 1 Surface Spread of Flame under
BS 476 Part 7 or equivalent. All wirings above the ceiling shall be low smoke emission type
and installed in metal ducting, conduit or trunking. Tenant ceiling shall in no case be lower
than 2.5m above FFL and not higher than 4.5m above FFL.
The Tenant shall extend the existing upper level sprinkler system to provide lower layer
sprinkler installation at the suspended ceiling level. All sprinklers shall be fast response
sprinklers (RTI ≤ 50m 0.5s0.5 and operating temperature of 68oC), to control fire growth at
source and mitigate the risk of fire spread. Under no circumstances would concealed type
sprinklers be considered.
It is essential that perforations in any ceiling tile system do not compromise the buildup of
heat at the sprinkler head and therefore extend the activation time beyond that which would
be expected for a solid ceiling. Any heat sink plate fitted to the sprinklers shall not reduce
the minimum 30% open ceiling area.
Equipment within the ceiling void shall be supported from a suitable suspension system
independent of the ceiling. Fixing methods and loading of suspension structure should
observe structural loading limitations. All slab fixing methods, types and locations must be
PART 3
approved by the Landlord prior to construction. No drilling, anchorage, or self tapping fixing
method for ceiling shopfront and floor finishes should have impact on the structural stability,
reinforcement, or concrete integrity.
Security grilles installed above inter-tenancy walls within the ceiling void shall not be
modified or obstructed by materials or items that will inhibit the free passage of smoke.
Tenants shall note that the slabs and beams of the soffit above the Level 5 and Level 6
node are of reinforced concrete construction while that of Level 6 cabin and Level 7 are
steel framed, with cement/steel fire resistant board lining construction.
Refer to Appendix Fig A.1.1 - A.4.1 for the location of retail and F&B units.
Refer to Appendix Fig A.5 & A.6 for typical Level 6 unit elevation and section.
As a primary element of the overall design and ambience of the retail and F&B areas, the
Landlord requires great emphasis to be paid to the merchandising of the shopfront.
Tenants are encouraged to propose creative and inventive shopfronts, designed in
accordance with these guidelines, and maintain their self identity.
Tenants shall make use of environmental friendly and energy saving light fixtures wherever
possible.
Retail and F&B units are intended to maintain an open shopfront approach to permit free
movement and access. Free standing shelving in retail cabin units shall not exceed 1.5m
high.
Shelving, counter or display units in open type exhibition and F&B units shall not exceed
1.3m high. Unit’s branding and signage shall not exceed 2.4m in height, and shall not
obstruct views to any wayfinding signage.
The Landlord provides manually operated, horizontal sliding and folding security shutters to
the open shopfronts of the cabin units as part of the base provision. These are not fire
rated but are part of the make up air requirements associated with smoke extraction
systems.
Shutters are made up of white (RAL 9016) powder coated, extruded aluminum links, with
polycarbonate vision panels and openings for make-up air as required. Security shutters
are lightweight to enable shutter operation with ease.
Security shutters are contained fully within the tenancy area, including shutter housing and
guide rails. Tenants shall adopt the shutters within the tenancy area and shall be solely
responsible for their operation and maintenance. In the event that a shutter requires partial
or complete replacement at any time, then such work shall be undertaken by the tenant at
PART 3
his own cost. Replacement shutters shall match in performance and appearance, those
they are intended to replace. No other means shall be used by the tenant to secure his
premise at the shopfront.
The stability, integrity and the normal operation of the shutter must remain unaffected and
openings must not be blocked whether units are closed or open or during testing and
operation of the smoke extraction system within the building. The Tenant shall keep
600mm horizontal clearance for the security shutter to prevent blocking the makeup air
outlets at the shop entrance during the shop closure hours.
Where perforated ceiling panels are to be installed, backings or linings are permitted
provided that gaps are left between panels to achieve 30% free area or otherwise these
would compromise the free area requirements for tenancy in retail areas. Where Tenants
wish to use an acoustic absorber at high level, they should consider an absorptive lining
applied to parts of the soffit or other appropriate surfaces.
The shop demise line for all retail areas on Concourse Level is defined as the maximum
extent to which display/merchandise can be placed. Retail units are considered high fire
risk areas. Shop interiors and open type units are controlled by an active fire protection
system of fast response sprinklers at both cabin ceiling level and concourse ceiling level,
plus dynamic smoke extraction system in the cabins and static smoke extraction in the
concourse roof. No objects shall be placed outside or across demise and shutter lines.
The interior design of the units should take into consideration the fire engineering principles
of specific commercial areas (For more information, please refer to Chapter 9: Fire
Engineering).
Colour and materials to all exposed wall, floor, ceiling finishes, furniture and fitting shall
complement aesthetically and qualitatively, enhancing the environment of the passenger
areas. The designated size and format of storage area, offices, changing rooms should be
in accordance with the requirements of the MFC Fire Engineering Report and related fire
engineering principles approved by Buildings Department.
Tenants shall adopt an open display concept where passengers are encouraged to "feel
and touch" the merchandise. Shop design layout should therefore encourage impulse
buying and reflect the need for efficiency, ease of browsing and speed of transaction, as
well as high operational efficiency.
Open shopfront concepts are encouraged throughout MFC to increase ease of passenger
flow and visibility. Shelving/Merchandise should be arranged in a disciplined order and aisle
widths must be adequate with at least 900 mm for passengers with baggage and disabled
persons in wheelchairs.
If partition walls or tall obstructions are to be constructed, statutory requirements for means
of escape shall be maintained as per the Landlord’s approved General Building Plans. Exit
routes and access panels for fire dampers shall not be blocked and additional illuminated
PART 3
directional or exit signs shall be provided by Tenants to suit the particular layout to comply
with the current Codes of Practices of the FSD and BD.
Lighting is an integral ingredient of the retail and F&B environment and general ambience
of the MFC. General building illumination installed by the Landlord will provide adequate
background lighting for safe and comfortable passenger circulation within the building.
Tenants shall ensure there is no glare from their fittings to the public areas nor to any
adjacent Airport signage. Tenants shall not use exposed bulbs or tubes within shops facing
public areas.
Lighting within the first 1.5m depth of the shopfront shall be designed as specific display
zone lighting to enhance the presentation of merchandise and provide contrast to the
lighting level in the passenger area.
The MFC is operational 24 hours; however, not all Tenant units in the premises are
expected to follow the same policy. It is the Landlord's policy to maintain even illumination
across retail shopfront during off-peak hours, and as such the shopfront lighting within the
display zone shall remain on during shop closure hours. The tenant shall provide, within the
tenancy, separate switching to the lighting in the display zone.
• The lighting design shall fulfil the requirements as set out in the latest Building Energy
Code (BEC) issued by EMSD. LED lighting shall be adopted wherever possible. For
other types of lamps, the latest technology with higher energy efficiency shall be
adopted. All lamps with the luminous efficacy less than 60 are not allowed except by
the approval of Authority. (Refer to 8.7.8)
• Light sources selected shall have colour rendering index of 85 or better.
• No exposed or coloured lamps shall be permitted unless approved by the Landlord.
• No flashing strobe, spinner or chase type lighting shall be permitted.
• Except for Light fittings within showcases, light fittings shall be installed at a level not
lower than 2.3m above the finished floor levels.
• Where LED lighting is used in the shopfront display, lamps must be completely
shielded.
• Pendant light fittings, luminous ceilings, chandeliers, wall brackets or glitter strips may
be used only if approved by the Landlord.
• Recessed downlight fittings shall have specular or semi-specular aluminum reflectors,
or other low brightness shielding devices.
• Surface or pendant mounted track and track light fittings may be used.
• All internally illuminated showcases and display cases must be adequately ventilated
and suitable illumination shall be installed to provide contrast against the background
lighting level.
• Self contained interior emergency lighting and illuminated EXIT / directional signs shall
be installed as required by FSD and BD.
• Lighting levels must be designed to avoid an unacceptable level of glare from all
publicly accessible viewpoints.
• Special care shall be taken for the lighting design in tenancies which have visual
PART 3
access to the Apron and daylight, to avoid causing glare to users of the operational
airfield.
Temporary lighting has been provided by the Landlord in each tenancy. The Tenant may
remove this temporary lighting during the fit-out period and make his own provisions for
permanent self-contained emergency lighting and EXIT signs, according to statutory
requirements, and to suit the fit-out planning arrangements. All temporary lighting shall be
reinstated at the end of tenancy periods.
Tenants are encouraged to design a bright shopfront to at least 1000 lux (on major vertical
faces at eyelevel). Shopfronts below 500 lux will not be permitted.
Lux levels within Tenant area should be maintained at not less than 400 lux and the light
fittings should be equipped with light dimmers.
The shop front signage of the Level 6 cabin units are provided by the Landlord; the front
facing media and lighting fitting in the Signage shall be supplied and installed by the Tenant.
The light fitting shall be LED lighting.
Tenants shall typically not be permitted to remove and replace the Landlord’s sign casings.
Tenants who wish to replace the Landlord’s sign casings may only do so if their alternative
design is deemed by Landlord to enhance the overall concept of the building and make the
retail space more interesting and lively. Only alternative designs that bring real dynamism
to the project will be considered by Landlord.
Electrical supply for the sign shall be provided and maintained by the Tenant. The Tenant
shall adopt the sign with the premise and shall be responsible for all aspects of its
maintenance including cleaning and lamp replacement.
Tenants shall be responsible for the design of the graphics and media to be installed in the
shop front signs. Size of sign graphics must be in proportion with the sign area provided.
All of the shop front sign face shall be covered by media, without gaps or joints. The Tenant
shall submit designs to the Landlord for review.
No other shop front signage will be permitted. No signage or posters shall be taped to the
walls within the Tenant’s unit. Only the Tenants approved store or business name (as
stated in the Lease and License agreement) and logo may appear on the shop front signs.
No advertising slogans, brand names or product names shall be permitted on the shop
front signs, nor any part of the Hong Kong International Airport common areas, without
Landlord approval.
The name, stamps or decals of manufacturers, installers or maintainers of signage shall not
be visible to the public.
PART 3
Floor signs, such as inserts into floor paving, etc, shall be permitted within the Tenants
lease line, but shall be subject to approval by the Landlord.
The Tenant is responsible for the design and material of the Tenant’s front facing signage
media. The signage media sub-assembly shall be designed to be fitted to the Landlord’s
signage casing, and shall not project or protrude beyond the casing. Tenants who wish to
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 3 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 3 - 12
install signage that exceeds the size of, or require modification to the specified signage
casing dimension is subject to Landlord’s approval. The tenant may select any appropriate
material and finish for the signage, yet the signage should not cause any undesirable
effects (e.g. glare, unexpected reflection etc) to the environment and other users of the
building. The tenant may also vary the extent of illumination of the signage media (e.g. as a
fully lit sign or selective lit sign where only symbols or lettering is lit). The material selected
shall be durable and be able to withstand the rigors of regular cleaning and maintenance.
Tenants are responsible for gaining approvals and consents from the relevant statutory
authorities prior to operation. The Tenant shall ensure the design, layout, and finish
conforms to all applicable statutory and license regulations. The Tenant shall be
responsible to obtain the required license before operation.
Cooking shall not be permitted in open serveries or open F&B units. Food may be
displayed and kept warm by electric reheating appliances only. No gas or flammable liquid
shall be permitted in these areas.
The Tenant shall maintain a level of lighting in excess of 400 lux at counter height in all
serveries facing public areas during opening hours.
Kitchens shall be enclosed within 2 hour fire rated enclosures. The boundary walls between
kitchen and F&B related seating areas are provided by the Landlord. Tenants are expected
to retain these walls as the boundary between cooking and other operations unless the
need for change is compelling. Any such change shall be fully pre-justified by the Tenant
and subject to Landlord’s approval. Changes to the location of any of these enclosing walls
will involve an Alterations and Additions submission by the tenant to, and approval from BD
and FSD, except as discussed below.
In the special circumstances that apply leading up to the initial opening of MFC, Tenants
who have an interest in exploring the viability of relocating these walls should discuss their
proposals with the Landlord to see if the need for separate A&A submission can be avoided.
The Landlord accepts no obligation in this regard and each shall be considered on a case
by case basis.
PART 3
3.3.5 Kitchen and Servery Waterproofing Membrane
The Tenant shall be responsible for the provision of a high performance waterproof
membrane on top of the concrete slab or landlord’s pre-laid screed prior to the application
of screed and finishes. The membrane shall comply with the following:
The membrane shall cover the entire area of the kitchen and servery and any other
parts of the tenancy where there is risk of flooding, liquid spillage, or where the
flooring is expected to be wet washed.
The membrane shall return vertically to a height of 100mm above finished floor level at
walls and other abutments and shall be effectively sealed around all penetrations.
The tenant shall be liable for any damage caused to the Landlord’s or other tenant’s
property, by leakage from the tenant’s area.
The Tenant shall arrange to undertake a water flood test (Refer to Appendix E) that will be
jointly inspected with the Landlord. The area of the test will be bunded and subject to
50mm head of standing water for at least 24 hours. A fluorescent dye will be added to the
water for purpose of tracing any leaks. Any costs arising from damage caused by leaking
water during testing shall be borne by the Tenant.
Enclosed F&B units shall have an individual grease trap and drainage point per unit
provided by Landlord as part of the base provision. Tenants shall be solely responsible for
their maintenance, cleaning and application for WPCO license.
The tenant shall be responsible for all floor finishes in F&B units, and the foodcourt. This
shall include areas within and outside of the cabins.
The Tenant may raise the height of the floor finish within kitchen and servery areas to
accommodate hydraulic services, floor gullies and drains. All gullies shall be covered with a
stainless steel grate. Tenants shall use a lightweight screed as a substrate to the final floor
finish. Floor finishes in the kitchen and servery areas should be non-slip and non-porous.
This applies to forward stores within Tenant units, i.e. stores created within the main
Tenant areas to which public have access as opposed to centrally located general stores.
Any serving bar and forward store containing alcohol not fully enclosed within a 2Hr FRP
enclosure will have to be constructed from non-combustible materials. The quantity of
alcohol stored shall not exceed 12,500 litres in the aggregate when packed in individual
receptacles not exceeding a capacity of 5 litres. The space for storage or consumption shall
be fully protected throughout by automatic sprinkler installations. This requirement is inline
with Hong Kong Fire Services Department’s Fire Protection Notice No. 4, Dangerous
Goods General.
PART 3
3.3.8 Confinement of Cooking Operations
All cooking areas are required to be enclosed by a 2 hour fire rated construction. The
Tenant has to ensure that the design, layout, and finish of the kitchen and the cooking
areas conform to all applicable statutory and licensing regulations. The Tenant is
responsible to gain approvals and license from the statutory authorities prior to operation.
In situations where the Tenant wishes to open up part of the kitchen area to public view as
in the case of some fast food operations, a 2-hour fire-rated shutter shall be installed at the
Tenant's expense. Such a change will require an A&A submission by the tenant to, and
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 3 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 3 - 14
approval from BD and FSD. Cooking is not permitted in serveries or in areas of the building
under the main roof assigned for F&B or related seating.
Each kitchen hood shall be equipped with a FSD approved Automatic Restaurant Fire
Suppression System to protect the associated cooking appliances, hoods and ductwork
against fire. The provision of the system is regardless of the size of the hood and of the
type of fuel being used for the cooking appliances which the exhaust hood serves. The
Automatic Restaurant Fire Suppression System shall be of the pre-engineered liquid agent,
cartridge operated type with a fixed nozzle agent distribution network, capable of automatic
detection and actuation and manual actuation. It shall be listed with Underwriter’s
Laboratories Inc. (UL300) and comply with the Codes of NFPA10, NFPA17, NFPA17A &
NFPA96. The system shall be capable of automatically shutting off the electric supply to the
concerned cooking appliances and providing audible fire alarm upon actuation of the fire
suppression system. The Tenant shall incorporate cleansing facilities / area within the
kitchen for the purpose of cleasing reusable utensils and cutlery etc.
No tables, seating or other furniture shall be placed outside or across demise and shutter
lines, or in such a manner that will obstruct or potentially jeopardize any escape routes.
Tenants shall provide evidence that any upholstery used for seating complies with the
flammability standards stipulated in FSD Circular Letter No 1/2000 and fully fire retarded in
accordance with British Standard BS 5852 (all ignition sources). Tenants shall not erect
any walls or other obstructions higher than 1.3m in seating areas where these may obstruct
any potential views from or across the seating area. All seating arrangements shall be
subject to Landlord’s approval.
lobbies. The lounge spaces are enclosed within 2 hour fire rated walls, separated from
other Level 5 spaces and accommodation. External glazing is provided along the
western frontage of these spaces, with views out to the airport. The The Landlord has
not provided any partitions or enclosures within the spaces, therefore the tenant shall
be responsible to design and erect enclosures to contain any enclosed private or back
of house spaces the tenant wishes to create. The southern CIP Lounge space external
glazed wall incorporates openable windows and can be designed as sleeping
accommodation if required.
As one of the primary elements of the overall design and ambience of the concourse, the
Landlord requires great emphasis to be paid to the design of the lounge frontage and
enclosure. Tenants are encouraged to propose elegant and timeless designs, in
accordance with these guidelines, whilst maintaining their self identity and customer
comfort.
The aesthetics, material and design of the CIP Lounge enclosure shall be complimentary
with the Authority’s design and environmental intent for the MFC. The following guiding
principles, dimensions and modules shall be observed in the Tenant’s design:
• The Level 7 spaces are designed to be open in nature and the Tenant may erect a
perimeter enclosure along the demise line to enhance the privacy within the CIP
Lounge. Any Tenant enclosure shall be glazed / perforate as far as possible to maintain
the sense of openness as originally intended. The enclosure shall be designed to neatly
interface with the Landlord’s 1300mm high balustrade. Where a perforate design is
used, the perforation must not be less than 50% of the screen’s surface area.
• The Landlord’s 1300mm high balustrade shall not be modified and may be adopted by
the Tenant as a low level lounge enclosure. Should the tenant wish to enhance the
privacy of the Lounge spaces, an additional glazed / perforate screen may be erected
behind the balustrade, with a 600mm wide, continuous clear space between the screen
and the inner edge of the 60mm diameter balustrade handrail, the top of which is at
1100mm above finished floor level. The clear space is intended to facilitate cleaning of
the Tenant’s screen and Landlord balustrade. The clear space may be reduced to
150mm if the screen only covers the area above the balustrade, with intermittent
structural supports below which allow reasonable access to the Landlord balustrade.
See figure A.5 for details of the L7 balustrade.
• Where the Landlord’s 1300m high, sloping balustrade is used as the Lounge enclosure
only; no furniture shall be placed within 900mm to the balustrade for safety reasons.
The 900mm dimension shall be measured from the inner edge of the 60mm diameter
PART 3
handrail, the top of which is at 1100mm above finished floor level.
• The Level 7 balustrade typically uses 2.4m wide panels in the linear sections, which are
aligned with the retail bulkhead metal cladding modules below. The modular dimension
and setting out of the CIP lounge enclosure / screening panels, modules and supporting
members shall be in harmony with this dimensionally, at 2.4m wide or 1.2m wide. The
modules shall be aligned with the balustrade modules as far as possible.
• The MFC horizontal planning / cladding master datum are arranged from finished floor
level and spaced at 500mm centres (i.e. at 500 / 1000 / 1500 / 2000 / 2500mm etc.
above finished floor level). The overall height of the enclosure or screen shall be inline
with this datum and not exceeding 2.5m. Any horizontal modules shall be multiples of
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 3 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 3 - 16
500mm in height, with joints aligned with the master datum. No elements of the
enclosure or interior fitting out shall exceed 2500mm above finished floor level unless
otherwise approved by the Landlord.
• The Tenant’s branding and signage maybe constructed within the Tenancy, behind the
glazed enclosure or integrated with the enclosure. The height of the tenant’s signage
shall not exceed 1m, and where signage band is used, its position shall be aligned to
the horizontal master datum.
• Where the Landlord’s 1300m high, sloping balustrade is used as the Lounge enclosure
only; no furniture shall be placed within 900mm to the balustrade for safety reasons.
The 900mm dimension shall be measured from the inner edge of the 60mm diameter
handrail, the top of which is at 1100mm above finished floor level.
The interior design of the units should take into consideration the fire engineering principles
of specific commercial areas (For more information, please refer to Chapter 9: Fire
Engineering).
Colour and materials to all exposed wall, floor, ceiling finishes, furniture and fitting shall
complement aesthetically and qualitatively. The interior design shall be comfort orientated
yet reflect the need for efficiency.
Space planning and furniture shall be considered, and widths of circulation areas must be
adequate with an absolute minimum of 900 mm for passage of a single passenger with
baggage or disabled persons in wheelchairs.
Within the Level 7 units, the height of any partitions erected within the open area of the
lounge shall not exceed 2.5m. The use of translucent materials such as acid etched glass
to maintain visual lightness is encouraged.
If partition walls or tall obstructions are to be constructed, statutory requirements for means
of escape shall be maintained as per the Landlord’s approved General Building Plans. Exit
routes shall not be blocked and additional illuminated directional or exit signs shall be
provided by Tenants to suit the particular layout to comply with the current Codes of
Practices of the FSD and BD.
The designated size and format of storage area, offices, changing rooms should be in
accordance with the requirements of the MFC Fire Engineering Report and related fire
engineering principles approved by Buildings Department.
Tenant may install free standing / floor or wall mounted light fittings in open areas of the
Level 7 lounges. The height of these fittings shall not exceed 2.5m AFFL.
Temporary lighting has been provided by the Landlord in each tenancy. The Tenant may
remove this temporary lighting during the fit-out period and make his own provisions for
permanent self-contained emergency lighting and EXIT signs, according to statutory
requirements, and to suit the fit-out planning arrangements. All temporary lighting shall be
reinstated at the end of tenancy periods.
Tenants shall ensure that their interior design and fit out complies with Hong Kong
regulations, and are responsible for gaining approvals and consents from the relevant
statutory authorities prior to operation. The Tenant shall ensure the design, layout, and
finish conforms to all applicable statutory and license regulations. The Tenant shall be
responsible to obtain the required license before operation.
Cooking shall not be permitted in the open CIP lounge areas. Food may be displayed and
kept warm by electric reheating appliances only. Use of gas or flammable liquid shall not
be permitted in these areas.
tenant shall be responsible for extension of the air conditioning supply / return air system as
required to maintain the space’s cooling performance.
3.4.6 Level 5 CIP Lounges – Kitchen Envelope and Other Internal Enclosures
For CIP Lounges on Level 5, any kitchens and non-open areas shall be enclosed within 2
hour fire rated compartments. The boundary walls between kitchen and the CIP lounge
areas, and any other enclosures within the spaces shall be provided by the tenant, and
shall be subject to the Landlord’s approval. Changes to the internal usage and layout of
these spaces will involve an A&A submission by the tenant to, and approval from BD and
FSD.
The Tenant shall be responsible for the provision of a high performance waterproof
membrane on top of the concrete slab prior to the application of screed in all kitchens,
toilets, showers and wet areas. The membrane shall comply with the following:
The membrane shall cover the entire area of the kitchen and servery and any other
parts of the tenancy where there is risk of flooding, liquid spillage, or where the
flooring is expected to be wet washed.
The membrane shall return vertically to a height of 100mm above finished floor level at
walls and other abutments and shall be effectively sealed around all penetrations.
The tenant shall be liable for any damage caused to the Landlord’s or other tenant’s
property, by leakage from the tenant’s area.
The Tenant shall arrange to undertake a water flood test that will be jointly inspected with
the Landlord. The area of the test will be bunded and subject to 50mm head of standing
water for at least 24 hours. A fluorescent dye will be added to the water for purpose of
tracing any leaks. Any costs arising from damage caused by leaking water during testing
shall be borne by the Tenant.
CIP Lounge units shall have individual grease trap and drainage point per unit provided by
the Landlord as part of the base provision. Tenants shall be solely responsible for their
maintenance, cleaning and application for WPCO license.
The Tenant may raise the height of the floor finish within kitchen and servery areas to
accommodate hydraulic services, floor gullies and drains. All gullies shall be covered with a
stainless steel grate. Tenants shall use a lightweight screed as a substrate to the final floor
finish. Floor finishes in the kitchen and servery areas should be non-slip and non-porous.
This applies to forward stores within Tenant units, i.e. stores created within the main
Tenant areas to which public have access as opposed to centrally located general stores.
Any serving bar and forward store containing alcohol not fully enclosed within a 2Hr FRP
enclosure will have to be constructed from non-combustible materials. The quantity of
alcohol stored shall not exceed 12,500 litres in the aggregate when packed in individual
receptacles not exceeding a capacity of 5 litres. The space for storage or consumption shall
be fully protected throughout by automatic sprinkler installations. This requirement is inline
with Hong Kong Fire Services Department’s Fire Protection Notice No. 4, Dangerous
Goods General.
All cooking areas are required to be enclosed by a 2 hour fire rated compartment. The
Tenant has to ensure that the design, layout, and finish of the kitchen and the cooking
areas conform to all applicable statutory and licensing regulations. The Tenant is
responsible to gain approvals and license from the statutory authorities prior to operation.
In situations where the Tenant wishes to open up part of the kitchen area to public view as
in the case of some fast food operations, a 2-hour fire-rated shutter shall be installed at the
Tenant's expense. Such a change will in general require an Alterations and Additions
submission by the tenant to, and approval from BD and FSD. Cooking is not permitted in
serveries or in areas of the building under the main roof assigned for CIP lounges or related
seating.
Each kitchen hood shall be equipped with a FSD approved Automatic Restaurant Fire
Suppression System to protect the associated cooking appliances, hoods and ductwork
against fire. The provision of the system is regardless of the size of the hood and of the
type of fuel being used for the cooking appliances which the exhaust hood serves. The
Automatic Restaurant Fire Suppression System shall be of the pre-engineered liquid agent,
cartridge operated type with a fixed nozzle agent distribution network, capable of automatic
detection and actuation and manual actuation. It shall be listed with Underwriter’s
Laboratories Inc. (UL300) and confirmed to the Codes of NFPA10, NFPA17, NFPA17A &
NFPA96. The system shall be capable of automatically shutting off the electric supply to the
concerned cooking appliances and providing audible fire alarm upon actuation of the fire
suppression system.
No tables, seating or other furniture shall be placed outside or across demise or shutter
lines, or in such a manner that will obstruct or potentially jeopardize any escape routes or
fire compartment enclosures such as fire shutters.
PART 3
The Tenant shall provide evidence that any upholstery used for seating complies with the
flammability standards stipulated in FSD Circular Letter No 1/2000 and fully fire retarded in
accordance with British Standard BS 5852 (all ignition sources). All seating arrangements
shall be subject to Landlord’s approval.
4.1 General
Retail storage areas are centrally located on Level 4 in the node area, within a short
distance from the loading / unloading docks and goods lifts. They are easily accessed
through the goods lifts from Levels 6 and 7.
The Retail stores are to be fitted out and finished by the Tenant.
Storage areas are individually contained within 2 hour fire rated compartments. The
Landlord has made chilled water feed provisions for Tenants to install their own air
conditioning system. All internal shelving and racking shall be supplied by the tenant and
the design and layout of which must comply with LPC rules for automatic sprinklers.
Cabinets, shelves, furniture or heavy installations are not allowed to be mounted to or hung
off the Landlord’s walls. Tenants wishing to change the layout within the storage area, such
as erecting solid partitions shall ensure the fire protection facilities are not compromised
and that all statutory requirements are complied with. Such proposals shall be submitted to
the Landlord for approval.
Service lifts L-122, L126, L134, L135 and L138 and Jumbo service lift L-125 shall be used
as part of the goods delivery route. The capacity and net car size are as follows:
Lift No. Capacity Net Car Width Net Car Depth Net Car Height
(kg) (mm) (mm) (mm)
L-122 2,500 1,800 2,600 2,300
L-125 8,600 2,400 6,000 2,300
L-126 2,500 1,800 2,600 2,300
L-134 2,500 1,800 2,600 2,300
L-135 2,500 1,800 2,600 2,300
L-138 2,500 1,800 2,600 2,300
The following applies to goods stored in locations other than the formal designated stores
referred to above:
Storage of goods within the Tenant’s space shall comply with statutory requirements
PART 4
and be subjected to approval by BD and FSD.
Electrical Supply
Essential Lighting
Chilled water supply
Primary air supply
TDF (selected units only)
For specific details of service provision for each store refer to the Tenant M&E Schedule for
the unit in question.
PART 4
The Landlord shall hand over the premises to tenants with certain basic builders works and
E&M provisions described below, which tenant is expected to retain, utilize or adapt
according to guidelines below during the course of necessary fitting out of the interior.
5.1.1 Procedures: The tenant should refer to the Tenant Fit-out Handbook for procedures of
submitting fitting-out proposals for landlord’s approval
5.1.2 Compliance: The tenant’s designer is responsible for observing the relevant codes and
regulations on means of escape and fire rated construction in the layout and construction.
5.1.3 Alterations: In the case of tenant’s proposed alterations of landlord’s basic provision due
to specific need, the tenant shall submit to the Landlord for approval, and be subject to
various other considerations such as code compliance, technical feasibility, building
management and design matters. Due to the limited size and extent of each office and
ramp premise, the Landlord does not anticipate any alteration of landlords structural
elements by the tenant, such as creation of floor voids, services openings on structural
walls, alteration of inter-tenancy walls, or addition of plant equipment in the Landlord’s
areas.
5.1.4 Walls: Walls enclosing the premises are full height reinforced concrete structural walls, or
block work walls (either fire rated or non fire rated) erected by the landlord.
No chasing into such walls to accommodate tenant’s wires / conduits is allowed. No fixing
of furniture or shelves and no hanging of shelves or substantial features are allowed onto
such walls. Lightweight items such as decoration and painting may only be hanged or fixed
to the walls if the loading, hanging or fixing method is unlikely going to cause permanent,
irreparable damage to the wall . The tenant should erect his own furring sub-frame in case
decorative wall panels are intended or ensure all shelves / cabinets all self standing on
floors.
5.1.5 Doors: All doors of BOH offices are painted timber fire rated doors. They are not allowed to
be altered or damaged or replaced. Nevertheless, tenant may propose the application of
finishes on such doors provided that the tenant’s door specialist contractor demonstrates
that such applied finishes neither damages the original finishes or compromises the fire
rating of the existing doors.
5.1.6 Ceiling, Floor and Wall Finishes: Ceilings, flooring and wall finishes withing the tenant
PART 5
area shall be provided by the tenant.
5.1.7 Ironmongery: All doors have been fitted with locks operable by keys on the outside and
openable by simple turn on the inside. The tenant may propose that these doors be fitted
with tenant’s own locking mechanisms without damaging the doors. Escape doors shall
always be openable from the inside without the use of keys. All electrical locks shall be
released automatically in the event of power failure or actuation of fire alarm in accordance
with current codes of practice.
5.1.8 Heavy Loading: The standard office floor can withstand live loads of 5kN/m2 plus 1.5kN/m2
for partition loads. In case of intended specific heavy objects, furniture or equipment such
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 5 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 5-2
as safe, vault, stone sculpture or filing cabinets etc., the tenant shall submit proposal of
load spreader, properly designed and certified by a Registered Structural Engineer for the
Landlord’s approval.
5.1.9 Reinstatement: The Tenant shall develop their design bearing in mind that they are
responsible for the maintenance of all newly installed items, including all fixtures, fittings
and systems during the term of the licence/lease agreement. Upon completion of the
license / lease agreement, they shall make good to original condition all modifications made
to Landlord’s services, structure, shell and core, finishes, flooring, walling, shutters and
components/assemblies forming part of the premises at handover.
Storage areas have concrete floors with epoxy paint finish in grey (RAL 7038). Walls and
soffit are painted. Storage areas are individually contained within 2 hour fire rated
compartments. The Landlord can make provisions for Tenants to install their own air
conditioning system upon request. All internal shelving and racking shall be supplied by the
tenant and the design and layout of which must comply with LPC rules for automatic
sprinklers. Cabinets, shelves, furniture or heavy installations are not allowed to be mounted
to or hung off the Landlord’s walls. Tenants wishing to change the layout within the storage
area, such as erecting solid partitions shall ensure the fire protection facilities are not
compromised and that all statutory requirements are complied with. Such proposals shall
be submitted to the Landlord for approval.
Service lifts L-122, L126, L134, L135 and L138 and Jumbo service lift L-125 shall be used
as part of the goods delivery route. The capacity and net car size are as follows:
Lift No. Capacity Net Car Width Net Car Depth Net Car Height
(kg) (mm) (mm) (mm)
L-122 2,500 1,800 2,600 2,300
L-125 8,600 2,400 6,000 2,300
PART 5
L-126 2,500 1,800 2,600 2,300
L-134 2,500 1,800 2,600 2,300
L-135 2,500 1,800 2,600 2,300
L-138 2,500 1,800 2,600 2,300
The following applies to goods stored in locations other than the formal designated stores
referred to above:
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 5 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 5-3
Storage of goods within the Tenant’s space shall comply with statutory requirements
and be subjected to approval by BD and FSD.
For specific details of service provision for each store unit, please refer to the Tenant M&E
Schedule for the unit in question.
PART 5
6.1 General
Goods Delivery Routes are the routes through the building, taken when delivering goods to
the retail, F&B, CIP lounge and office areas. Depending on the destination of the delivery,
goods will be transported by authorized airside vehicles and unloaded at one of the
loading/unloading bays situated at the northern or southern sides of the Node or Wings of
the building on the apron level.
Refuse Disposal Routes are the routes of passage for refuse transfer from retail, food &
beverage, lounge and office areas to Refuse Rooms. Depending on the location of the units,
tenants shall transfer refuse to the designated Refuse Room at the Node or Concourses of
the building. Tenants shall be responsible for segregating their refuse into different waste
streams as advised by the Landlord and provide sufficient refuse storage space for each
waste stream within their units before transferring to the Refuse Room in MFC.
During goods and refuse transfer, tenants shall comply with all health and safety
regulations and delivery operations shall be carried out within the Back-of-House Area to
avoid conflict with the passengers and other building users. For tenancies where the
carrying in and out of goods and refuse transfer is only possible through public circulation
areas, the transfer will be restricted to off-peak periods as determined by the Authority.
The requirements of relevant Airport Circulars as may be issued from time to time and
standing Terminal Operation Procedures Manual shall be observed and complied with.
Only material handling equipment with plastic wheels such as goods trolleys and roll cages
are allowed to be used within MFC to reduce damage to the flooring.
Refuse produced by tenants shall be segregated and stored within their units, Tenants are
responsible for transferring and disposing segregated refuse into the appropriate
containers by waste stream within designated Refuse Rooms. Tenants shall use the
containers within the Refuse Rooms properly to maintain cleanliness and avoid damage.
PART 6
Locations of Refuse Rooms for different units at various levels of the building are specified
in Appendix Fig B.1. Refuse is stored in the Refuse Rooms until it is emptied by specialist
refuse disposal contractor.
Tenant storage rooms within the MFC are available upon arrangement with the Landlord.
Refer to Appendix Fig A.1 – A1.4 & B.1 for the location of the Loading/Unloading Bays,
Refuse Rooms and Tenant’s Storage.
There are a total of six standard lifts within the MFC. This includes five standard goods lifts
and one oversized goods lift, all dedicated to Back-of-House functions including goods
delivery and refuse transfer. Back-of-House lifts are not for passenger use and shall be
access controlled.
The five standard goods lifts used as part of the goods delivery/refuse transfer routes are
numbered L122, L125, L126, L134, L135 and L138 The capacity and net car size are
summarized in the table below.
Lift No. Capacity (kg) Net Car Width Net Car Depth Net car Height
(mm) (mm)
L122 2500 1800 2600 2300
L125 8600 2400 6000 2300
L126 2500 1800 2600 2300
L134 2500 1800 2600 2300
L135 2500 1800 2600 2300
L138 2500 1800 2600 2300
Certain corridors within MFC are dedicated to Back-of-House functions, including goods
delivery and refuse disposal. These corridors are not for passenger use.
Tenants shall keep the corridors clear at all times and shall not leave any goods and
material handling equipment along the corridors.
Any transportation of cooked food via the Back-of-House corridors shall be made within
completely self-sealed containers as quickly as possible to avoid risk of contamination.
Goods delivery and refuse disposal routes are illustrated graphically. Refer to Appendix Fig
B.1.
PART 6
ATMs are to be located at Level 6 retail area, beneath the escalators serving Level 7.
Provision of a 1650mm frontal opening x 2100mm deep opening in the Landlord’s wall
cladding system beneath the escalator truss is provided. Tenant shall provide side cladding
and front cladding to coordinate with the ATM machine housing dimensions. The detailed
design of the ATM cladding by the Tenant shall be subject to approval by the Landlord.
Advertising and other identification graphics and signs shall be neatly incorporated into the
cladding to provide an integral and coherent design; coordinating with and complementing
the Landlord’s interior designs. Access panels within the Tenant’s cladding, if required,
shall be carefully designed. The Tenant’s cladding shall be coordinated with the escalator
truss cladding to ensure a neat interface but allowing for deflection of the truss by 40mm
vertically.
Use of plants potted in self-contained planter boxes to enhance Tenant areas is permitted,
provided that these are of species without any parts that are toxic, disperse pollens or
attract insects. Silk, other artificial, or dried plants, except plastic plants, within lease/license
areas are allowed subject to approval of satisfactory cleaning techniques and frequency.
The Landlord has pre-determined pay phone sites within the MFC. Pay phones may be
free-standing or wall mounted. Suitable Landlord structures have been provided in each
site to receive Tenant's fittings and equipment. All support structures are mild steel framed,
and clad with polyester powdered coated steel panels. Each structure is divided into the
following zones: skirting; main body including telephone attachment zone, and information
panel (capable of incorporating two A4 size notice); and signage zone housing illuminated
telephone sign. The Landlord shall provide within the satin stainless steel triangular
telephone attachment housing telephone line and electrical cabling for connection to
Tenant's equipment.
PART 7
8.1 Ge n e ra l
The following building services provisions will be made available by Landlord for Tenant’s
use.
Systems Provisions
• Tenant’s Distribution Frame (TDF) for voice and data services
• FIDS Connection (Application to AAHK Required)
• Cable trunking into the Tenant area
• Building Management Systems (BMS) monitoring and control status for Landlord E&M
provisions
The actual termination points shall be determined on site prior to the commencement of the
design.
PART 8
The Tenant will be responsible for the complete design and fit out of the building services
within the agreed tenancy. All mechanical and electrical services detailed designs shall be
submitted to the Landlord for approval prior to commencement of work. The Landlord's
building services passing through the tenancy shall not be modified or interfered with in any
way and it will be the responsibility of the Tenant to carry out as-fitted surveys of the
existing installations so that the design and implementation of the fit out works does not
interfere with the Landlord's building services and maintains adequate access for
maintenance by the AAHK maintenance contractors. (e.g. permanent fixtures should not be
located in the access path and non-permanent fixtures shall be movable to allow
maintenance equipment e.g. ladders or working platform for personnel to reach the
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8- 2
The Tenant shall design the building services fit out works within the maximum provisions
provided. However, where prior agreement as been reached to modify the base provisions
such works will normally be undertaken by the Landlord at the Tenant's cost. The Tenant
shall also be responsible for returning the systems back to their original configuration.
The Tenant shall be entirely responsible for obtaining all relevant authority approvals.
All equipment proposed by the Tenant shall comply with the latest version of the AAHK
General Materials and Workmanship specification. All designs, equipment and materials
will be subject to the Landlord's approval.
The Tenant will be required to submit details of his proposed design team and design team
members to ensure the fit out design is carried out by a responsible and competent
engineer familiar with the AAHK requirements.
8.2.1 General
The Tenant shall be responsible for the design and installation of the final mechanical
services provisions to suit the individual needs. No part of the Tenants fit out works shall
adversely impact the operation and maintenance access to the existing Landlords
mechanical services provisions. It is noted that some tenancy areas open to the public
concourse shall be able to benefit from the existing concourse air conditioning systems.
All associated services shall be concealed within the ceiling spaces of tenancies.
The smoke management systems for the MFC are described in Section 9. The Tenant
shall not modify any part of the smoke management systems and shall design and install
the fit-out works to ensure that the operation and maintenance requirements of the system
are not adversely impacted.
The following design conditions shall be used as the basis for the mechanical services
provisions:
Mechanical Ventilation:
Minimum outside air supply:
Offices 10 l/s per person minimum
Retails Units: 8 l/s per person minimum
F&B Units: 10 l/s per person minimum
CIP Lounge: 10 l/s per person minimum
CIP Washroom / Shower facilities 30 air changes per hour (ACH)
Kitchens (minimum) 60 ACH (3.5m ceiling height)
A supply of pretreated outside air shall be made available as indicated in Table 8.2.1:
Note 1: For areas not covered in Table 8.2.1, the Tenant shall confirm the availability of the
pretreated air supply with the Landlord.
Note 2: The data supplied above is for reference only and the Tenant shall be responsible
for ascertaining the actual supply temperature and available static pressure on site.
Notification of the request for the activation of the pretreated air supply shall be supported
by evidence that the complete duct systems as been tested for leakage and is free of all
debris and contaminates.
The landlord shall provide a chilled water supply to the Tenant as indicated in Table 8.2.2.
It shall be supplied at a design flow temperature of about 6.0 deg C. The Tenants shall
ensure that the chilled water temperature does not exceed 12.0 deg C at the return
connection to the Landlords chilled water main. The design chilled water supply/return
differential pressure at the Landlord/Tenant interface is 100 kPa.
The chilled water connection to the Landlords supply is complete with an isolation gate
valve, on the supply, and isolation/double regulating valve, on the return, terminated inside
tenant area. The motorized isolation valve shall remain under the control of the Landlord.
The Tenant shall provide an approved flow limiting device to restrict the chilled water flow
rate to the maximum available water-flow provided for each of the Tenants connections.
In addition the Tenant shall provide an approved strainer's on the return side of each heat
exchanger/coiling coil connected to the system and universal test points or similar on each
PART 8
side of each exchanger/coiling coil.
Modification of existing chilled water system, as requested by the Tenant, shall be designed
and installed by Landlord, at the Tenant’s cost.
Note 1: For areas not covered in Table 8.2.2, the Tenant shall confirm the availability of the
chilled water supply with the Landlord.
Note 2: The data supplied above is for reference only and the Tenant shall be responsible
PART 8
for ascertaining the actual temperature and available differential pressure on site.
Before connecting the Tenants chilled water supply to the Landlords provision, the Tenant
shall provide at least 5 working days advance notice shall be given to the Landlord to check
the layout is in accordance with the drawings. The Tenants shall submit separate
applications for the provision of a temporary connection (for testing purposes) and a
permanent application once testing has been completed.
Notification of the request for the activation of the permanent chilled water system shall be
supported by evidence that the complete systems has been hydraulically tested and is free
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8- 6
from all leakage and that the complete system has been flushed clean and chemically
treated to remove all debris and contaminates from the system. The Tenant shall produce
independent test records to demonstrate that the system has been flushed and has been
de-contaminated.
Upon activation of the permanent chilled water supply, the Tenant shall submit details of
the final balancing records. The Landlord reserves the right to witness the balancing of the
systems to ensure that the maximum design flow rates, pressure differentials and
temperature differentials are in accordance with the above design criteria.
Any additional chilled water capacity required by the Tenant requiring an increase in supply
flow and return pipework to their unit shall be designed and installed by Landlord at
Tenant’s cost. Tenant shall submit the calculation details to substantiate the demand load
and obtain approval from the Landlord.
The Tenant shall arrange all air cooling plant so as to allow condensate water to efficiently
drain to condensate drain points provided by the Landlord. The Tenant shall not be allowed
to relocate the condensate drain points and shall, as required, provide additional
condensate pumping facilities as necessary.
The landlord shall provide a central kitchen exhaust system (except for CIP Lounges and
the Staff Canteen which are provided with dedicated kitchen exhaust system with constant
speed control) comprising kitchen exhaust fans, make up air fans, main ductwork,
connections to external louvres and electrostatic precipitator. Individual kitchen exhaust
and make up air ducts, branching off from main ducts, are provided to each F&B unit. The
kitchen exhaust systems are controlled by variable frequency drives which may be adjusted
by the Landlord to suit individual tenancy requirements. The Tenant shall provide the final
duct additional balancing facilities or booster fans as required.
Note 1: The data supplied above is for reference only and the Tenant shall be responsible
for ascertaining the actual flow rate and available static pressure on site.
The Tenant shall be responsible for all associated submissions to the EPD and FEHD with
respect to the final design of the complete kitchen exhaust system.
The Landlord shall provide the toilet exhaust and general exhaust for the tenants (selected
units only) comprising exhaust fans, main ductwork and connections. These exhaust
systems are controlled by constant speed drives.
Air handling units - tested and rated in accordance with ARI 430 or equivalent;
Fan coil units - 700 L s-1 and below to be tested in accordance with ASHRAE 79 and rated
in accordance with ARI 440; above 700 L s-1 to be tested and rated in accordance with ARI
430 or equivalent;
Fans -tested in accordance with ASHRAE 51 (general) ASHRAE 68 (noise) and rated in
accordance with ARI 670 or equivalent;
Chilled water and condensate pipework - copper to be to BS 2871 Part 1 Table or steel to
BS 1387 medium;
Insulation - chilled water and condensate drain pipework: Closed Cell Elastomeric
Insulation or equivalent;
The Tenant, upon completion of the lease/licence agreement, shall make good to original
condition the Landlord’s Mechanical services.
The voltage drop between the main LV switchboard and the Tenant’s point of supply may
be assumed to be 3% of system voltage. A time delay of 15 to 20 seconds is expected for
the switchover. The prospective short circuit current at the tenancy area distribution board
feeding the Tenant’s point of supply is stated on the Landlord’s drawings. The earth fault
loop impedance at the Tenant’s point of supply shall be ascertained by the tenant / licensee
by measurement. The Tenant shall provide their own surge protection devices to protect
their own electronic equipment/installation.
In the event of loss of incoming power supply and/or essential services elsewhere in the
building, the Tenant’s power supplies may be switched off automatically.
A limited Essential power supply may be made available to the tenant/licensee upon
request subject to critical airport related operational need. The following conditions will
apply:
• The Tenant shall provide and install load shedding equipment to the approval of the
Landlord in order to ensure that the Tenant’s installation operates within the limits of
the essential power supply made available.
• The supply, installation, and termination of the essential power cable between the
Tenant’s distribution board and the Tenant’s point of supply, and the supply, installation,
and termination of other necessary apparatus shall be carried out by the Landlord. All
costs including the ongoing energy consumption involved shall be borne by the Tenant.
8.3.4 Metering
The tenant is required to negotiate and bear all costs associated with the provision of the
Tenant’s electrical metering by CLP Power Limited. (CLP). A metering board or cubicle is
provided by the Landlord within the Landlord’s electrical room or cupboards for the
mounting of CLP’s metering equipment.
Permission for the installation of an underfloor cable containment system which extends to
the common Landlord areas that affect Landlord’s applied floor finishes may be granted
upon request to the Landlord. All works in the lifting of such floor finishes and screeds, the
supply and installation of the cable containment system, the relaying and making good of
the floor surface finish, and the future reinstatement of the floor at the termination of the
tenancy within Landlord areas, shall be carried out by the Landlord. All costs involved shall
be borne by the Tenant.
The installation shall be designed, installed and tested in accordance with the requirements
of the Code of Practice for Electricity (Wiring) Regulations issued by EMSD and the current
edition of BS7671 Requirements for Electrical Installations, also known as the IEE
Regulations, including any amendments. In addition the installation shall satisfy the
requirements of both China Light and Power’s Supply Rules, prescriptive Building Energy
Code (BECs) and the Electricity Supply Ordinance.
The electrical installation shall be carried out to a high standard of workmanship using
Government registered electrical workers of appropriate grades of proven ability. Workman
shall be supervised at all times. Residual current devices shall be installed to protect all
small power socket outlets. Earth fault protection relay with adjustable setting for sensitivity
and time delay shall be included at the main power supply of the tenant’s distribution board
to provide protection discrimination setting.
Mechanical protection in the form of steel wire armour, or steel / LSOH conduit / trunking
shall be provided for all cabling within the tenancy area. All cables, cable trunking,
distribution boards, etc, shall be clearly labelled in order to identify the services provided
and distinguish it from the Landlord services. The labelling system employed will be subject
to approval by the Landlord.
Particular attention shall be paid to the earth bonding of all extraneous metalwork,
especially display cabinets, food preparation tables, sinks, cool rooms, etc. Installation
shall not extend into or pass through Landlord’s areas or the area of any other tenants. For
the purpose of protective earthing, a separate circuit protective conductor shall be run with
every sub-circuit. The use of cable armouring or steel conduit / trunking as the sole means
of providing a circuit protective conductor shall not be acceptable.
Shop front signage and shop front lighting shall be kept illuminated at all times by power
fed from the tenant’s power source. Emergency lighting for tenant fit out works complying
PART 8
with FSD statutory requirements shall be provided by the Tenant.
All electrical installation works installed by the Tenant shall be dismantled and removed
upon returning the premises to the Landlord with the exception of the following:
• Landlord’s original electrical provision such as main isolators, switches and auto-
changeover switch;
• Main distribution board mounted securely on the wall with appropriate miniature circuit
breakers and other accessories installed for power supply to temporary lighting, exit
signs and security shutters;
• Temporary emergency light fittings securely fastened or suspended from the soffit;
• All electrical accessories associated with power provision to the above items including
cables, trunking, cable tray, earth bonding, etc.
The incoming Tenant is deemed to have carried out his own testing and commissioning to
the above items to ensure that they are in good working order and complying with all
electrical rules, should he wish to take over the same.
The Tenant will remove Landlord’s temporary lighting during his fit out and make his own
provision for emergency lighting, according to statutory requirements and to suit his design.
The Landlord’s temporary fittings shall be returned to the Landlord in good order.
The following Fire Services Systems are installed within the Midfield Concourse:
Sprinkler System;
Hydrant / Hosereel System;
Fire Alarm and Detection System
Tenancy areas are protected by a sprinkler system complying with BS EN12845:2003 and
FSD Circular Letter No. 3/2006 for Automatic Sprinkler installations. The hazard class is
Ordinary Hazard Group 3 and all sprinkler heads in Midfield including the tenancy areas are
fast response type. Prior to occupancy, tenant space is provided by the Landlord with a
PART 8
layer of sprinklers at high level providing general coverage of the area. Any works to
sprinkler systems undertaken in specific relation to the tenants fit-out shall employ medium
grade galvanized iron pipework to BS 1387 / ISO 65 with fittings to BS EN10241:2000.
Tenants shall maintain the integrity of Landlord’s fire services. Landlord sprinklers within
tenant spaces shall not be blocked, or de-activated.
Any additional sprinklers and the modification of the existing sprinklers, required by
Tenants shall be designed by the Tenant, installed by the Landlord at the Tenant’s cost and
submitted to Fire Services Department by a Registered Fire Service Contractors (The
Registered FS Contractor should be selected from the list of AA’s pre-qualified FS
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8 - 11
Contractors). All sprinkler layouts shall be submitted to the Landlord for review. Sprinkler
layouts shall achieve the “Review with no objection” status before commencement of work.
Connection of the second layer of sprinklers to the main system, including the work permit
application, drain off the existing system, isolation of the zone subsidiary valve, connection,
re-energization of the system including re-filling the system shall be done by Landlord at
Tenant’s cost. The tenant shall give at least 5 working days to the Landlord for the Landlord
to check the sprinkler layout is in accordance with the drawings and conduct testing before
the Tenant seals up any ceilings. The time and date for connecting the second layer of
sprinklers shall be subject to the discretion of the Landlord.
The second layer of sprinklers including the modification of the 1st layer of sprinkler, if so
required, shall be to the current FSD requirements. The AA’s pre-qualified FS contractors
are responsible for the submission of all statutory forms i.e. FS 314A, FS 251 to FSD to
cover all the changes to the fire services installation at Tenant’s cost.
All areas of The Midfield Concourse are equipped with hydrants and hosereels in
accordance with FSD requirements. This provides coverage to the unoccupied Tenant
space. Additional hydrants and hosereels extended from blanked T-off's on the hydrant
mains may be required to meet FSD requirements due to the addition of tenancy
partitioning. Hydrant pipe work shall be the same material as sprinkler pipe work. Any
modification and addition to the existing hydrant / hose reel system shall be designed by
the Tenant and installed by the Landlord at the Tenant’s cost. AAHK’s pre-qualified FS
contractors are responsible for the submission of all statutory forms i.e. FS 314A, FS 251 to
FSD to cover all the changes to the fire services installation at Tenant’s cost.
The building is provided with a digital addressable intelligent fire alarm and detection
system complying with BS 5839 -1:2002 + A2:2008 and FSD Circular Letter No. 1/2009 and
3/2010. Addressable loop wiring is provided within compartmentalized trunking at all
Tenancy boundaries for connection of the Tenant's fire alarm and detection systems.
Where additional fire alarm and detection systems are required by the Tenant, such
systems shall be connected into the Landlord's addressable loop system to provide an
automatic general fire alarm signal upon activation of the Tenant’s fire alarm system.
Modification of existing automatic fire alarm system and detection system, including the
relocation of existing detectors/visual fire alarm/audible fire alarm, additional
detectors/visual fire alarm/audible fire alarm and fire signals, upgrading and re-
programming the master fire alarm panel and workstations to pick up the additional signals,
PART 8
as requested by the Tenant shall be designed by the Tenant and installed by the Landlord,
at the Tenant’s cost.
The Tenant, upon completion of the lease/licence agreement, shall make good to original
condition the Landlord’s fire services.
8.5.1 General
Not all the above occur in all tenant areas. Tenants should refer to the Landlord Service
Schedule related to their unit(s) for precise details. Landlord's provisions of these services
are on the basis that Tenants are permitted to provide facilities requiring such connections
in restricted areas known as `hydraulic zones'. Tenant's services are not permitted to pass
through other tenancies without prior approval from the Landlord.
Any additional plumbing and drainage required by Tenants to their shops including the
modification of the existing services and the connection to the main systems shall be
designed and installed by the Tenant at their own cost. Maintenance of the additional
plumbing and drainage systems shall be by the Tenant.
Before connecting the plumbing and drainage to the main systems, 5 working days
advance notice shall be given to the Landlord to check that the layout is in accordance with
the drawings. Testing shall be carried out to the Landlord’s satisfaction. The time and date
for connecting to the main systems shall be subject to the discretion of the Landlord.
Main grey water drains are located within the hydraulic zones of the tenancy areas with
capped branch connections and are for the purposes of drainage of waste fitments. All
tenant drainage pipework and fittings shall be socketless cast iron and comply to BSEN 877
with internal epoxy coating and external anti-oxidant protective primer for pipes from 50mm
to 150mm diameter. Pipework from 32mm and 40mm diameter and the associated fittings
shall be UPVC to BSEN 1329-1. Where the UPVC passes through fire rated wall or floor,
fire collar shall be provided at tenants cost.
PART 8
8.5.3 Soil Water Drainage
Main soil water drains are located within the hydraulic zones of the tenancy areas with
capped branch connections and are for the purposes of drainage of tenancy soil waste. All
soil water drainage pipework shall of the same material as the grey water drainage
pipework.
Independent greasy stacks are located in service risers adjacent to designated kitchen
areas, with capped branch connections terminated within the tenancy area. Floor drains are
also provided within the tenancy area and connected to the independent greasy stacks.
Both floor drain and capped off greasy waste pipework are for the purposes of drainage
from the kitchen greasy waste drainage. Dedicated grease traps for kitchen areas are
provided by the landlord for each F&B outside tenancy areas. All greasy water drainage
pipework shall be of the same material as for grey water drainage pipework. Each tenant
shall provide and install a grease tank prior to connection to the capped off greasy waste
pipework; the design of the grease tank shall be submitted to AA for approval. The floor
drain cover grating must be intact at all times. Each tenant shall be responsible for the
operation, cleaning and maintenance aspects of their greasy waste system, grease tanks
and the grease traps.
Vent pipes are provided to all grease traps and connected to the Landlord’s adjacent main
vent point. Venting of all soil water drainage pipework shall be provided by the Tenant and
connected to the Landlord's main. All vent pipework shall be socketless cast iron pipe to
BSEN 877 with internal epoxy coating and external anti-oxidant protective primer.
Potable water supplies within the Midfield Concourse consist of a pressurized piping
network feeding all service risers from water storage tanks and distributed throughout the
building. Valved and capped branches from service riser are fed to hydraulic wet zones
within tenant areas. Potable water supply pressure at the Landlord / Tenant interface is 200
kPa.
Tenants are required to submit their plumbing layout to Water Authority for approval. All
plumbing installations shall be conducted by licensed plumber in accordance with the Water
Authority requirements. All submission and approval processes including WSD water meter
installations shall be done by the Tenant’s licensed plumber. All WSD meters shall be
located in the Landlord’s water meter room and installed at 300-1500mm AFFL in
accordance with WSD requirements. Potable water pipework shall be copper to BS EN
1057 R250 in half hard condition. Associated fittings shall comply with BS EN 1254 Part 1 &
2 and shall be non-dezincifiable. Silver brazing filler material to BS EN 1044 shall be used
on all capillary joints on potable water supply.
Cleansing water is provided for the purpose of water supply to the kitchen’s hydrovent
system. Cleansing water supplies within the Midfield Concourse consist of a pressurized
piping network feeding all service risers from water storage tanks and distributed
PART 8
throughout the building. Valved and capped branches from service riser are fed to hydraulic
wet zones within tenant areas.
Tenants are required to submit their plumbing layout to Water Authority for approval. All
plumbing installations shall be conducted by licensed plumber in accordance with the Water
Authority requirements. All submission and approval processes including WSD water meter
installations shall be done by the Tenant’s licensed plumber. All WSD meters shall be
located in the Landlord’s water meter room and installed at 300-1500mm AFFL in
accordance with WSD requirements. Cleansing water pipework shall be of the same
material as the potable water pipework.
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8 - 14
Flushing water supply is provided to tenancy toilet areas. Flushing water supplies within the
Midfield Concourse consist of a pressurized piping network feeding all service risers from
water storage tanks and distributed throughout the building. Valved and capped branches
from service riser are fed to hydraulic wet zones within tenant areas. Tenants are
responsible for the future connection of the capped off points.
Flushing water pipes from 20mm to 63mm diameter shall be of MDPE pipes PE80 to BS
6730. Pipework for 90mm diameter and above shall be of PE pipes PE100 to WIS4-32-13
and automatic electofusion fittings to WIS4-32-14.
Town gas supply is provided to the tenancy kitchen areas. Town gas pipework branched off
from the main and connects to the tenancy areas capped off with individual stop valve.
Town gas pipework shall be carbon steel to BS EN 10216-1 and BS EN 10217 Part 1 with
minimum pipe thickness of 5.6mm. Carbon steel butt weld fittings shall comply with BS
1965 Part 1 and BS EN 10253-1 and shall be jointed by welding. Pipework and fittings shall
be coated with minimum one layer of external epoxy primer.
Tenants are responsible for the connection for interlocking with the associated kitchen
exhaust fans within the tenancy areas such that when all the kitchen exhaust fans in the
same group are off, the corresponding town gas stop valve shall close. Tenants are
responsible for applying individual town gas meter from the Gas Company and provide the
pipework and fittings to the town gas kitchenware. Installation of town gas pipework shall
comply with the requirements of the Gas Safety Authority and code of practices issued by
the Gas Company.
The Tenant, upon completion of the lease/licence agreement, shall make good to original
condition the Landlord’s hydraulic services.
8.6.1 General
Tenants shall address all queries related to Systems works affecting or related to their
premises to the Authority’s Representative appointed under the Works Schedule. The
Tenant Fit-out Handbook contains details of the relevant contact details.
PART 8
8.6.2 Controls Interface with Building Management System (BMS)
1. Mechanical Building Management System (MBMS). The MBMS system is used for the
monitoring and control of the MVAC installations only.
2. General Building Management System (GBMS) – The GBMS system is used for the
monitoring and control of all other building services plant and equipment which is not
covered by the MBMS system
Unless otherwise stated herein or specified in the Tenancy Agreement, the Tenants shall
provide independent control of individual plant and equipment required under the fit-out
design. Where the Tenant is required to interface with one or both of the Landlord's BMS
system/s, the design and installation shall be strictly comply with BMS interface standards
regarding hardware, software and protocol.
A zoned public address system is installed in all public areas but not in tenant areas. Retail,
F&B and CIP lounge areas are provided with a Public Address zone feed within the tenant
space. Other tenants who require access to this public address system shall discuss their
requirements with the Landlord. In order not to confuse and alarm passengers alarm bells
and buzzers of Tenant’s security systems are not allowed to emit any sound. Therefore
Tenant’s security alarm systems are only permitted to emit visual signals, e.g. flashing
lights.
8.6.4 Security
Access control and CCTV systems are installed throughout the Midfield Concourse for
security and general surveillance. Access control is provided enabling the use of a single
access card to gain zoned access to public areas.
This system can be made available to Tenants within the Tenant area subject to approval
by the Landlord. Access control is a common system for the whole of the airport including
T1, T2, SkyPier, Midfield Concourse and ancillary buildings in airfield, and not solely for the
Midfield Concourse. CCTV system within the tenancy area is for surveillance coverage only
and face detection device is not allowed in order not to contravene the Privacy Ordinance.
PART 8
The WIDS provides current flight information on a web-based environment over the Internet.
Two types of services are available for subscription by tenants. The first type is for display
only with auto-scroll feature. The second type is called BBIF with a set of predefined reports
for viewing on-screen, printed as PDF file or exported to CSV file. The subscribers have to
acquire their own hardware. Tenants requiring this shall discuss their requirements with the
Landlord.
All tenancy areas are provided by the Landlord with a Tenant Distribution Frame (TDF)
using ANSI/TIA/EIA standard 25- pair Category 5E UTP cable. Where there is subdivision
of large tenant area, then Tenant Termination Frames (TTF) are provided to serve the
individual tenants if needed. These frames will provide data and voice connectivity back to
the Landlord’s designated Communications Rooms or Communications Closets.
Where optic fibre is required to be connected to other areas outside the tenancy, this can
be made available via the nearest Communications Rooms or Communications Closets
designated by Landlord. Tenants requiring this shall discuss their requirements with the
Landlord.
Tenants may obtain registration forms to facilitate the application / approval process from
the Authority’s Representative. The registration form clarifies the submission / processing
procedure.
Tenants requiring the services shall prepare to further discuss their requirements with the
Landlord.
PART 8
8.7.4 Trunk Mobile Radio
The airport is currently served by a site wide radio system operating at 800 MHz. If required,
the Tenant will need to make a written application for access to the system. The design and
installation of the extension of the Trunk Radio System will be carried out by the Landlord
and paid for by the Tenant.
The MFC Master Clock System provides a synchronized time source across the whole
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8 - 17
airport. Connection to the Master Clock System can be made available for Tenants in the
form of a digital signal, subject to review and approval by the Landlord. If required the
Tenant will need to make a written application for a connection point. The application shall
include the proposed format of the signal and any special requests. The design and
installation of the extension of the MFC Master Clock System will be carried out by the
Landlord and paid for by the Tenant.
A television distribution system is available throughout the MFC and provides both local
territory and satellite channels. The MATV system is a standard subscription service
provided by the Landlord to Tenants. Tenants requiring the service shall discuss their
requirements with the Landlord by making a written application to the Landlord with the
quantity of MATV outlets required and the exact locations of those outlets. The design and
installation of the MATV outlets will be carried out by the Landlord and paid for by the
Tenants plus a monthly subscription charge.
8.7.7 Lighting
General Lighting
Shop lighting is an integral ingredient of the retail environment and general ambience of
thespace. Tenants shall ensure there is no glare from their fittings to the public areas nor to
adjacent Airport signage. Tenants are not permitted to use exposed bulbs or tubes within
shops facing public areas.
The lighting design shall fulfil the requirements as set out in the latest Building Energy Code
(BEC) issued by EMSD. LED lighting shall be adopted wherever possible. For other types of
lamps, the latest technology with higher energy efficiency shall be adopted. For instance,
using LED T5 fluorescent tubes instead of T8 tubes. All lamps with luminous efficacy less
than 60 are not allowed except by approval of the Authority.
The Tenant is responsible for providing lighting in two different zones: Display Lighting and
Interior Lighting. The Display Lighting Zone (shopfront window zone) is the area extending
1.5m inward from the tenant boundary. The Interior Lighting Zone shall comprise of all other
areas of the tenant‟s premises which are open to public view.
Dimmers should be provided on all light fittings (Display Lighting and Interior Lighting) in
case the specified lux level is exceeded to reduce the light output accordingly.
Display Lighting
The first 1.5m display zone must be separately switched to a lighting level in excess of 800
PART 8
lux so that it may remain on during off peak/out of work hours when the shop unit lighting is
switched off. The circuits shall be connected to a timer control such that the exact operating
hours of the display lighting can be adjusted as agreed with the Authority. Provision shall
also be made within the shopfront window zone for specific display lighting to enhance the
presentation of merchandise and to provide a contrast against the lighting level within the
public area. Light sources shall be selected which have a colour rendering index of 85 or
better. No exposed or coloured lamps shall be permitted unless approved by the Authority.
No flashing strobe, spinner, or chase type lighting shall be used. High intensity discharge
(HID) lamps (i.e., mercury vapour, sodium or metal halide) which do not meet the colour
rendering criteria, shall not be used except as approved by the Authority. Where fluorescent
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 8 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 8 - 18
lighting is used in the storefront display, the lamps must be completely shielded. Pendant
light fittings, luminous ceilings, chandeliers, wall brackets or glitter strips may be used only if
the Tenant has established an identity or theme approved by the Authority.
Interior Lighting
All light fittings shall be of the low brightness type. All light sources, i.e., directional fittings,
downlights, track light, soffit lights, etc, or indirect fittings in coves, etc, must be shielded
from view. Fluorescent fittings shall have low brightness parabolic diffusers, metal
paralume-type. No lensed fittings shall be used except in storage or other "back of house"
areas away from public view. Recessed downlights shall have specular or semi-specular
aluminium reflectors, or other low brightness shielding devices. No surface or pendant
mounted track or track light fittings may be used. All internally illuminated showcases and
display cases must be adequately ventilated and suitable illumination shall be provided to
contrast against the background lighting level.
Minimum illumination within the tenancy, behind the display zone, shall be 400 lux. Lighting
levels must be designed so as to avoid glare from all viewpoints. Special care has to be
taken.
PART 8
The design and operations of the Midfield Concourse has been approved on the basis of a
combination of prescriptive measures (as typically described in the FSD Code of Practice
for Minimum Fire Service Installations) and through performance based Fire Engineering.
The minimum requirements for all fire related works are covered in the Midfield Concourse
Fire Engineering Report (FER) and these requirements shall be adhered to at all times.
The FER has stated that the retail units / exhibition areas have designed to allow adequate
flexibility to cover the following businesses:
In addition to the base fire protection systems provided, Tenants shall be required to
ensure that the quantity of goods (i.e. liquor) and fire fighting appliances (i.e.; fire
extinguishers) are in compliance with FSD requirements.
The full extent of the base building provisions for each of the Tenancy areas is covered in
Section 8 of this Tenancy Fit-out Guide. In summary, these include:
• Upper layer automatic fire sprinkler system employing fast response sprinklers
PART 9
• Visual fire alarm
• Emergency lighting
Provisions for smoke extraction from above the retail unit have been made from the central
smoke management systems. A common unobstructed smoke reservoir above the ceiling
shall be maintained to allow the smoke extraction system to efficiently extract smoke as
required.
9.3.2 Kitchens
Kitchens for F&B will be enclosed by 2 hour fire resisting walls and ceilings. The kitchens
shall be fully sprinklered and automatic fire shutters shall be provided at openings such as
kitchen serving hatches. Smoke extraction will not be provided.
All retail units are required to accommodate provision in the shop front for an adequate flow
of make-up air for the correct operation of the smoke management systems. This make-up
air is required to replace air withdrawn from the unit when the smoke extraction system is
activated. The make-up air should be admitted to the Tenant area and should be available
at all times. Should the Tenant wish to enclose any part of their tenancy unit with glass or
other solid material then the design of the enclosing elements must provide for the
continuous make-up air requirements.
PART 9
Tenant/licensees are required to include in their proposals all information related to the
structural design of the fit out works. Information shall include, but not be limited to the
following:
• Setting out and construction details of all partitions, canopies, ceilings, plinths and/or
bases;
• Details of methods of fixing to the concrete and steel structure;
• Materials used together with details of the materials density, thermal properties,
acoustic properties and fire rating properties;
• Design of all supporting frames.
• All items of equipment with an operational and/or static weight of more than 200 kg
giving setting out details and fixing details;
• Details of any permanent lifting equipment and/or equipment fixing, giving setting out
details, fixing details and maximum SWL;
• The setting out and maximum load capacity of all tenants fixtures including but not
limited to display cabinets, counters, storage racks, compactor units and other like
equipment and giving setting out details and fixing details;
• Details of any proposed modifications to the permanent structure including, but not
limited to, floor and wall penetrations, steel framing, cladding systems, fire protection
systems etc. A detailed description of how such modifications shall be carried out
together with mitigation measures to prevent disruption to passengers, airport
operations and/or other Tenants.
• Design calculation for all structural works. The AAHK reserves the right to request
additional calculations to support the design intent of the fit out works.
• Copies of all Statutory Submissions, together with approvals letters and consents to
carry out the works as necessary.
• Design calculations prepared by a qualified engineer for all structural works. The AAHK
reserves the right to request additional calculations to support the design intent of the
fitout works.
10.2 Loadings
The maximum design loadings allowed in the Tenant areas, resulting from the intended use
of any space, shall not exceed the design live loads and superimposed dead loads as set
out in Appendix D.
PART 10
It is expected that tenants’ partitions will be of dry wall construction (metal stud /
plasterboard) and most configurations of dry wall partitions will fall within the 100kg/m2
allowance.
The incorporation of concrete plinths and/or other supports shall be accounted in the overall
loading assessment to ensure the above criterion is met.
Tenants should note in particular that no loading may be imposed on the roof without the
express written agreement of AAHK.
The Tenant shall be responsible for the all such vibration isolation treatment to ensure that
no part of the Tenants equipment and/or operations will transmit excessive vibration to the
base structure. All equipment and/or operations which are likely to set up vibration
transmission into the base structure will be subject to Landlord approval. The Landlord
reserves the right to request the Tenant to remove/isolate/discontinue any equipment
and/or operations which are found to cause adverse structural vibrations creating
disturbance to other users.
All loading requirements must be within the allowances described in Section 10.2, including
but not limited to ceilings fixtures, building services, lifting hooks, monorails or hi beams.
The Tenant shall note the fire rating and percentage openness ratio of the completed
ceiling shall not exceed the minimum requirements of the FSS.
All loading requirements must be within the allowances described in Section 10.2, including
but not limited to kitchen equipment, building services, storage and refuse areas.
10.6.1 Concrete
The type, size, location and embedment of all masonry anchors used in the fixing of all
items are to be clearly shown on the tenants working drawings. Use of these anchors will
be subject to the consent of the Landlord. Calculations and testing results demonstrating
that the capacity of the fixings is adequate are to be submitted to the landlord for review.
Guidelines for the slabs are provided. For all other elements, reinforcement should always
be located with a cover meter prior to drilling. No cutting or drilling through the
reinforcement is permitted.
The Tenant/licensee shall have regard to the following requirements when proposing the
type and location of masonry anchors:
PART 10
Generally, the best location for making fixings to the underside of the floor is into the sides
of the ribs or beams. In all beams and ribs, fixings can be drilled into the side faces in the
zones shown. Fixing may also be achieved by drilling into the underside of the rib on its
centre line.
Fixing into the top of the slab can be achieved in slab, rib or beam zones. In the 150mm
thick slabs, only anchors requiring holes less than 90mm deep will be permissible. In the
beam and rib zones reinforcement congestion will make the installation of masonry anchors
difficult. Details should be proposed which allow for congestion in these areas and allow for
HONG KONG INTERNATIONAL AIRPORT November 2014 Version -
File Ref.: MFC TDG Issue No 4 - Section 10 Issue No.: 4
HONG KONG AIRPORT AUTHORITY 10 - 3
some flexibility for variation in the actual position of reinforcement compared to that shown
on the drawings. Reinforcement is to be located with a cover meter prior to drilling into
these zones.
10.6.3 Steelwork
Fixings to support steelwork installed by Tenants shall be welded fixings. For other fixings
not requiring drilling or cutting of the support steelwork the tenant shall ensure that these
fixings do not degrade the corrosion protection or fire protection systems of the steelwork.
Where either of these systems is accidentally damaged by the fixing, the Landlord's
contractor shall repair damage at the Tenant's cost.
All fixings shall be compatible with the support steelwork and shall not allow bi-metallic
corrosion.
The following rules are provided as a guideline only to the Tenant. All holes required by the
Tenant are subject to the approval of the Landlord. No cutting by the tenant shall be carried
out until after approval is obtained.
Fixings to non-structural elements such as homogeneous floor tiles and glazing structures
are not permitted. Any fixings to blockwork are required to adhere to manufacturer's
specifications.
Notwithstanding any other rules, penetrations of maximum dimension 300mm square are
permissible anywhere within the slab panels. Any two such holes must be separated by not
less than 3 times their maximum dimension, measured between centrelines. For the
purposes of this rule, any two or more- holes that fit within a 300 mm zone can be
considered as a single hole.
It is not anticipated that small floor penetrations within the zones between ribs will be
coordinated onto the structural drawings. However penetrations of this size, which occur
through the beams, must be coordinated and are subject to the approval of the Landlord.
Penetrations on both sides of the rib are acceptable if the remaining widths of slab
connected to the beam at any rib cross section are not less than 950mm.
Except for very small penetrations all penetrations in panels immediately adjacent to
movement joints over ribs should be referred to the Landlord for review.
10.10 Walls
No generalized rules are available for the position of post-formed holes in walls. This is
because the structural functions of the walls vary greatly around the building. All proposals
will require detailed review by the Landlord.
Kitchen areas will be permitted to have a raised finished floor level in excess of the typical
100mm above structural slab level in order to accommodate drainage services. Any raised
floor levels will have to be formed using a lightweight screed in order that the superimposed
dead load does not exceed the permitted levels. Typically allowance for superimposed
dead load varies in each area. It is a combination of services and finishes loadings, of
which 0.6KPa has been allowed for services. The combined floor loading of Tenant’s
partitions and any floor finishes will not be permitted to exceed the permitted superimposed
dead load. Tenants are required to submit all proposals for approval by the Landlord. The
Tenant is responsible to submit their proposal to Buildings Department under the Minor
Works Control System.
Tenants shall inform the Landlord of the location, size and weight of any safe or heavy
equipment within the Tenant area. Prior approval from the landlord is required before
installation as well as removal of any heavy equipment.
Heavy loads must not bear on either an independent structure or partition adjacent to any
demise wall. Tenants must seek approval from the Landlord to provide access of heavy
equipment across public areas. In situations where additional support is required and
approved by the Landlord, such provisions and their removal shall be made at the Tenant's
own cost.
PART 10
11.0 Construction
11.1 Hoardings
Hoarding in compliance with current Hong Kong Building Regulations and Codes of
Practices of the Labours Department on Site Safety shall be provided during fit-out by
Tenant. The hoarding shall include a combination key locked door. In general, Tenant may
erect a 2.4m high hoarding (or other height as may be specified by AA from time to time) to
separate the shop during renovation from the Landlord’s public area, along a line 600mm to
1m in front of the Tenant’s shutter line or unit demise line. Corners of the hoarding shall be
radiused if possible. The top of the hoarding or any gaps between hoarding and the
bulkhead above shall be closed off with white (RAL9016) canvas to prevent dust dispersion.
The hoarding shall not block or interfere with adjacent tenant’s shopfront, signage or
shutter. Hoarding layout, design, structural calculation and details shall be submitted for
the Landlord’s approval.
Hoardings shall be of all metal construction or a combination of metal frame and painted
plasterboard and shall be white in base colour on the public side. The hoarding shall be
sturdy, plumb, and aligned. Materials used for hoarding construction shall be new and
maintained in excellent condition throughout the execution of the works. Any damage
occurring to the external finishes shall be made good as it occurs.
Hoardings shall be extensively covered with Graphic film and suitable printed graphics to a
layout/composition to be agreed with the Landlord. If no graphics is proposed, the hoarding
shall be painted white (RAL9016). Where necessary for operational reasons space shall be
allowed on the hoardings for the fixing of temporary direction and other operationally
related signage by the Landlord.
Any materials or finishes damaged by the Tenant during his fit-out works shall be made
good by the Landlord’s Contractor at the Tenant’s cost.
The Tenant should notify the Landlord the proposed working hours and should keep
construction noise level to NC40 during opening hours of retail and F&B units and avoid
interference with other building occupants. Noisy operations or those that lead to significant
structure borne vibration given rise to nuisance shall be undertaken at specific times during
the night as approved by the Landlord. Tenant shall also prevent the escape of dust, smoke
PART 11
and smell (from welding, paint, adhesive or other chemicals for construction).
The Landlord provides a basic tenancy shell and services for the tenancies.
The Tenant shall be responsible for all facets of the tenancy fit-out including the design,
authority approvals and installation of the works. The fit-out shall be at the Tenants cost
and to the approval of the Landlord.
The Tenant’s design shall be subject to all relevant statutory submissions and approvals.
Where alterations to the architecture, structure and/or services of the base building are
required due to the design of the tenancy, subject to the approval of the proposed alteration
by the Landlord, the works will be designed and undertaken by the Landlord at the Tenant’s
cost.
PART 11
12.0 Advertising
The advertising locations are focused in the most prominent locations with the intention of
achieving maximum visual prominence to travelers. In order to maintain consistency within
the MFC, the Authority regulates the design and standardized the sizes of all advertising
displays. All advertising media shall be professionally designed, fabricated and installed.
Advertising proposals are subject to the Authority’s approval. The Authority reserves the
right to remove any advertising which is in conflict with, or is considered detrimental to the
operation or clarity of the directional signage system.
Besides the primary function of distributing conditioned air to the concourse area, the MFC
binnacles are designed to accomodate advertising lightboxes and LCD display screens.
The display frontage area of the is controlled by the by the modular dimension of the
binnacle cladding, which is 2.4m wide by 2.0m high (nominal). The Tenant may install
suitable lightboxes or LCD display screens with glass cover which fully covers the frontage,
and which remain flush with the surrounding binnacle cladding. The type of lightbox
envisaged by the Authority utilizes flexible vinyl media mounted using a tension system,
however the tenant shall ensure that their proposed system can be adapted to fit rigid
plastic, glass or aluminium facing. The Authority will provide fused spur power points and
single mode optical fibre data point within the binnacle opening.
There are selected sites for advertising display on various wall surfaces throughout the
MFC, which are set within the glazed or polyester powder coated metal wall cladding
panels. Most of the spaces reserved are either based on multiples of the 1.2m or 1.8m
wide modular cladding system, or standard 12-sheet size. The Tenant may install suitable
lightboxes or LCD display screens with glass cover which fully covers the frontage, and
which remain flush with the surrounding binnacle cladding. The Authority will provide fused
PART 12
spur power points and single mode optical fibre data point within the cladding opening.
The Authority will provide a series of 70” LCD display screens at the corner junctions
between the gate corridor and main corridor on L5 Arrivals Concourse. These are
integrated into the wall cladding and are splayed to face the passengers walking along the
main corridor.
The aesthetics, material and sizes of all free standing advertising displays shall be
complimentary with the Authority’s design and environmental intent for the MFC. The
proposed designs shall be durable and easy to maintain.
The display lightbox casing / structure shall be clad in aluminium or steel, with a polyester
powder coated finish in RAL 7012 (standard dark grey hue used in MFC). The lightbox
shall be sturdily supported by internal steel posts. Lightboxes may be single- or double-
sided, with hinged and lockable glass doors to protect the media and to facilitate good
access for replacement of graphics media and maintenance. For single-sided displays, the
blanking rear panel shall be in the same cladding material, finish and colour as the lightbox
casing. Tenants must ensure the design of the lightbox and spacing of light fittings provide
even lighting to the graphics media. LED luminaires shall be used, and energy efficiency
shall be considered. Sufficient ventilation shall be incorporated in the design and where
necessary shall be fan assisted for heat dissipation. The fan units shall not emit any
audible noise in the ambient environment of the concourse.
The Authority will provide steel base plates with integrated fused spur power points,
located locally within the floor finish. The Tenant shall be responsible for the design, supply
and installation of the advertising light boxes in accordance with the Authority’s guidelines.
12.2 L1 AP M S ta tio n
High level, large format static light boxes are installed along the central glass-clad walls in
the APM station Departures and Arrival Platforms.
12.3 L4 AP V S ta tio n
Large and medium format static light boxes have been integrated into the metal wall
cladding in both lounges.
12.4 L5 Arriva l Co n c o u rs e
Large format static light boxes are installed along each of the corridors leading from the
western gates towards the main north-south arrivals corridor. A large and an extra-large
PART 12
format static light boxes are installed at the ends of the main corridors in both the north and
south concourse wings and faces passengers as they approach the node. Dynamic
advertising can be displayed on the monitors installed at the corner junctions between the
gate corridor and main corridor. These are integrated into the wall cladding and are
splayed to face the passengers walking along the main corridor.
12.5 L6 De p a rtu re Co n c o u rs e
The advertising devices are incorporated in the services binnacles located along the
concourse wings. The binnacles near the node have been fitted with dynamic advertising
LCD display screens. The binnacles further away from the node are fitted with medium
format static light boxes. Sites for clocks are also integrated with the binnacle units.
PART 12
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX B
APPENDIX B
APPENDIX B
APPENDIX B
Aluminium security shutter assembly (horizontal) [M6] shall be Dynamic Way DW-Type Crystal
Folding Shutter or Chung Tai Aluminium folding shutter or equal, horizontal manual sliding and
APPENDIX B
folding shutters typically installed in all open shop fronts of retail and food and beverage units in the
building. Shutters shall be stored in drywall housings within each unit. For use in longer shop-fronts,
the shutter shall be divided into shorter runs, to allow opening and closing operation to be performed
by 1 person. Type [M6] shall be as follows:
Shutter slats: Nominally 250mm wide slats. Typical slats shall be assembled from extruded
aluminium 6063 alloy profiles with polyester powder coated finish forming window openings. Slats to
be interlocked using extruded aluminium hinging profiles to form a continuous shutter. Window
openings in slats shall be nominally 200mm wide and full height, with one intermediate aluminium
extrusion support profile. Lowest portion of each slat shall be designed to provide make up air for
smoke extraction by incoporating perforated alumium panels, with slot openings not larger than
95mm (L) x 11mm (H).
Side bars: Satin stainless steel side bars shall be installed at both ends of each shutter run,
incorporating stainless steel floor and ceiling bolt locking devices, operable from outside the
unit. Bolts shall be engaged into satin stainless steel floor sockets.
Window inserts: Transparent polycarbonate (PC) slat inserts shall be installed in all slats.
The PC inserts shall be ultra-violet resistant and made of nominally 200mm wide x 3mm
thick PC sheet.
Suspension rod and guide rollers: fixed to alternate slats, including slats immediately
adjacent to side bars. Roller shall be designed and constructed to minimize the probability of
jams in operation, taking into account anticipated debris and dust build-up.
Overhead Track: Nominal 60mm high x 60mm wide concealed GMS profile.
An aggregate free area of 3.2m² shall be provided by the shutters installed in the shop front
of each of the following groups of retail and food and beverage units:
Group 3: 6MC 100, 6MC 101, 6MC 102 and 6MC 103.
Group 4: 6MC 150, 6MC 151, 6MC 152 and 6MC 153.
APPENDIX B
Units 102, 14/F. , Hung Tai Industrial Building
37-39 Hung To Road, Kwun Tong, Kowloon,
Hong Kong
Ph: (852) 2401 3721
Midfield Concourse
Landlord
Retail Bulkhead Landlord Landlord Landlord Landlord
(Note 2)
Tenant Tenant
Tenancy Ceiling Tenant Tenant Tenant
(Note 3) (Note 1)
Tenant Tenant
Kitchen Serveries / Counters Tenant Tenant Tenant
(Note 3) (Note 1)
Tenant Tenant
Tenant services within Tenancy Tenant Tenant Tenant
(Note 3) (Note 1)
APPENDIX C
Smoke Extraction System Landlord Landlord Landlord Landlord Landlord
Note 1: The Tenant shall be responsible for the associated costs to return the tenancy unit back to its original
arrangement on the termination of the Tenancy. The Landlord reserves the right to contra charge the Tenant
for any modification required to return the basic shell and services to their original arrangement on the
termination of the Tenancy.
Note 2: The Tenant shall be responsible for the maintenance and replacement of lighting and associated lamps in
the shop front bulkhead signage.
Note 3: The Tenant shall submit all design proposals for approval by Landlord.
APPENDIX D
Note: For Level 7 cabin roofs, the tenant’s ceiling and service loading shall be 0.2kPa.
APPENDIX D
APPENDIX E
underneath the water test
location if needed;
APPENDIX E
8 TSD will inform affected TSD will notify the following: TSD
Departments, tenants and Duty - RAD
Team the actual time when - T1D or T2LD
Tenant start to fill the area with - Issue Work Notification to IAC,
water, once TSD is satisfied Duty Team and FT Team
with the Tenant preparation
works;
APPENDIX E
hours unless otherwise advise
by TSD;
12 TSD should be present when Tenant /TSD
Tenant start to fill up the area
with water and a general
inspection will be carried out to
ensure there is no immediate
leakage. Once TSD is satisfied
there is no immediate leakage,
the monitoring will be the
responsibility of the Tenant;
APPENDIX E
standby in case the
waterproofing has failed.
APPENDIX E
19 Tenant is responsible to protect Tenant
the waterproofing layer, after
the completion of the test?
Should TSD believe the
waterproofing layer is
subsequently damaged, TSD
may request Tenant to
demonstrate the integrity of the
waterproofing;