FXD IEC60870-5-101 Protocol Test Report

Test Report of FXD

IEC60870-5-101 Communication

The Proprietary right of this this document is on Eaton Cooper Electronic


Technologies (Shanghai) Co., Ltd and the copying and distribution of this
document to a third party without the agreement of the proprietary is prohibited.
FXD IEC60870-5-101 Protocol Test Report

CLASSIFICATION Performance Test

APPARATUS Recloser Controller

DESIGNATION FXD

APPLIED STANDARD IEC 60870-5-104

MANUFACTURER Eaton Cooper Electronic Technologies (Shanghai)


Co., Ltd.

TESTER ZhouWei, LiuQianQian

DATE OF TESTS March,20,2014~May,15,2014

DATE OF ISSUE May,16,2014

TEST RESULT The IEC 60870-5-101 protocol communication


function was tested internally and the result was
satisfactory.

This test report on the IEC 60870-5-101 protocol communication function is performed following
company’s specification standard.
FXD IEC60870-5-101 Protocol Test Report

1 Scope

The test of IEC 60870-5-104 protocol communication of FXD is performed based on


Eaton Cooper Electronic Technologies’(ShangHai) Co., Ltd’s quality process and the
IEC 60870-5-104 standard spec.

2 Test Procedure and Information

The test is conducted with Triange MicroWorks company tool and test related
information is as below:
Device under Test: FXD
Test Tool: Test Harness
Date of Test: 3/20/2014
Tester: Zhou Wei and Liu Qianqian
Test Reference:
IEC 60870-5-101: Telecontrol equipment and systems,Part 5-101. Conformance test
cases for the IEC 60870-5-101 Companion Standard.

3 Test Result

The IEC 60870-5-104 protocol communication function was tested internally and the
result was satisfactory.

4 Test List and Test Result


FXD IEC60870-5-101 Protocol Test Report

4.1 Overview lists of the test result:


Table 1 Test List and Result(1/14)

Record the conformance test procedure result for Assignm Common Cause of
Transmis Address field of Information
each of the supported configuration parameter Station type Transmission speed ent class address transmiss
sion type the link object address
values on the right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is originator address)
One(1) octets for COT field(2nd octet
is originator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure
passed for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test
Cases.
N.A: indicates that configuration

in controlled

in monitor
in controlled

in monitor
value is not supported by the
device.

Maximum length L(control direction) N.A √ - - - - - - - - - - - - - - - - - -


Frame length
Maximum length L(monitor direction) N.A √ - - - - - - - - - - - - - - - - - -
Physical layer Byte frame N.A √ - - - - - - - - - - - - - - - - - -
FT1.2 Frame Layout N.A √ - - - - - - - - - - - - - - - - - -
Byte lag N.A √ - - - - - - - - - - - - - - - - - -
Verification Control Field N.A √ - - - - - - - - - - - - - - - - - -
of Link level Unbalanced Transmission Procedure N.A √ - - - - - - - - - - - - - - - - - -
Balanced Transmission Procedure N.A √ - - - - - - - - - - - - - - - - - -
Time Out interval N.A √ - - - - - - - - - - - - - - - - - -
FXD IEC60870-5-101 Protocol Test Report

Table 2 Test List and Result(2/14)

Record the conformance test procedure result for Assignm Common Cause of
Transmis Address field of Information
each of the supported configuration parameter Station type Transmission speed ent class address transmiss
sion type the link object address
values on the right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed
for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test
Cases.

in controlled

in monitor
N.A: indicates that configuration

in controlled

in monitor
value is not supported by the device.

Verification Type Identification N.A √ - - - - - - - - - - - - - - - - - -


of data unit Variable Structure Qualifier N.A √ - - - - - - - - - - - - - - - - - -
identifier Cause of Transmission N.A √ - - - - - - - - - - - - - - - - - -
ASDU 1 Single-point information N.A √ - - - - - - - - - - - - - - - - - -
ASDU 2 Single-point information with N.A N.A - - - - - - - - - - - - - - - - - -
Timetag
ASDU 3 Double-point Information N.A √ - - - - - - - - - - - - - - - - - -
ASDU 4 Double-point Information with N.A N.A - - - - - - - - - - - - - - - - - -
Timetag
Verification ASDU 5 Step-position Information N.A N.A - - - - - - - - - - - - - - - - - -
of ASDUs ASDU 6 Step-position Information With N.A N.A - - - - - - - - - - - - - - - - - -
Timetag
ASDU 7 Bitstring of 32 bit N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 8 Bitsring of 32 bit with Timetag N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 9 Measured value, normalized value N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 10 Measured value, normalized Value N.A N.A - - - - - - - - - - - - - - - - - -
with Timetag
FXD IEC60870-5-101 Protocol Test Report

Table 3 Test List and Result(3/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value

in controlled

in monitor
in controlled

in monitor
is not supported by the device.

ASDU 11 Measured value, scaled value N.A √ - - - - - - - - - - - - - - - - - -


ASDU 12 Measured value, scaled value With N.A N.A - - - - - - - - - - - - - - - - - -
Timetag
ASDU 13 Measured value, short floating Point N.A √ - - - - - - - - - - - - - - - - - -
number with Timetag
ASDU 14 Measured value, short floating Point N.A N.A - - - - - - - - - - - - - - - - - -
number with Timetag
ASDU 15 integrated Totals N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 16 integrated Totals with Timetag N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 17 Event of protection equipment With N.A N.A - - - - - - - - - - - - - - - - - -
Timetag
ASDU 18 Packed start events of Protection N.A N.A - - - - - - - - - - - - - - - - - -
equipment with Timetag
ASDU 19 Packed output circuit information of N.A N.A - - - - - - - - - - - - - - - - - -
Protection equipment with Timetag
ASDU 20 Packet single-point information With N.A N.A - - - - - - - - - - - - - - - - - -
status change detection
FXD IEC60870-5-101 Protocol Test Report

Table 4 Test List and Result(4/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value

in controlled

in monitor
in controlled

in monitor
is not supported by the device.

ASDU 21 Measured value, normalized N.A N.A - - - - - - - - - - - - - - - - - -


value without quality descriptor
ASDU 30 Single-point Information with N.A √ - - - - - - - - - - - - - - - - - -
Timetag CP56Time2a
ASDU 31 Double-point Information N.A √ - - - - - - - - - - - - - - - - - -
with Timetag CP56Time2a
ASDU 32 Step-position Information N.A N.A - - - - - - - - - - - - - - - - - -
with Timetag CP56Time2a
ASDU 33 Bitstring of 32 bit with N.A N.A - - - - - - - - - - - - - - - - - -
Timetag CP56Time2a
ASDU 34 Measured value, normalized N.A N.A - - - - - - - - - - - - - - - - - -
value with Timetag CP56Time2a
ASDU 35 Measured value, scaled value N.A √ - - - - - - - - - - - - - - - - - -
with Timetag CP56Time2a
ASDU 36 Measured value, short floating point N.A √ - - - - - - - - - - - - - - - - - -
number with Timetag CP56Time2a
ASDU 37 Integrated totals with Timetag N.A N.A - - - - - - - - - - - - - - - - - -
CP56Time2a
ASDU 38 Event of protection equipment N.A N.A - - - - - - - - - - - - - - - - - -
FXD IEC60870-5-101 Protocol Test Report

with Timetag CP56Time2a

Table 5 Test List and Result(5/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value

in controlled

in monitor
in controlled

in monitor
is not supported by the device.

ASDU 39 Packed start events of Protection N.A N.A - - - - - - - - - - - - - - - - - -


equipment with Timetag
CP56Time2a
ASDU 40 Packed output circuit information N.A N.A - - - - - - - - - - - - - - - - - -
of Protection equipment with Timetag
CP56Time2a
ASDU 45 Single Command N.A √ - - - - - - - - - - - - - - - - - -
ASDU 46 Double Command N.A √ - - - - - - - - - - - - - - - - - -
ASDU 47 Regulating step Command N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 48 Set point Command, normalized value N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 49 Set point Command, scaled value N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 50 Set point Command, short Floating N.A N.A - - - - - - - - - - - - - - - - - -
point value
ASDU 51 Bitstring of 32 bits N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 70 End of initialization N.A √ - - - - - - - - - - - - - - - - - -
ASDU 100 Interrogation N.A √ - - - - - - - - - - - - - - - - - -
FXD IEC60870-5-101 Protocol Test Report

ASDU 101 Counter Interrogation command N.A N.A - - - - - - - - - - - - - - - - - -


ASDU 102 Read command N.A N.A - - - - - - - - - - - - - - - - - -

Table 6 Test List and Result(6/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value

in controlled

in monitor
in controlled

in monitor
is not supported by the device.

ASDU 103 Clock synchronisation command N.A √ - - - - - - - - - - - - - - - - - -


ASDU 104 Test command N.A √ - - - - - - - - - - - - - - - - - -
ASDU 105 Reset process command N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 106 Delay acquisition command N.A √ - - - - - - - - - - - - - - - - - -
ASDU 110 Parameter of measured value, N.A N.A - - - - - - - - - - - - - - - - - -
normalized value
ASDU 111 Parameter of measured values, N.A N.A - - - - - - - - - - - - - - - - - -
scaled value
ASDU 112 Parameter of measured value, N.A N.A - - - - - - - - - - - - - - - - - -
Short floating point number
ASDU 104 Test command N.A √ - - - - - - - - - - - - - - - - - -
ASDU 120 File ready N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 121 Section ready N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 122 Call directory, select file, call N.A N.A - - - - - - - - - - - - - - - - - -
File, call section
FXD IEC60870-5-101 Protocol Test Report

ASDU 123 Last section. Last segment N.A N.A - - - - - - - - - - - - - - - - - -


ASDU 124 ACK file, ACK section N.A N.A - - - - - - - - - - - - - - - - - -
ASDU 125 Segment N.A N.A - - - - - - - - - - - - - - - - - -

Table 7 Test List and Result(7/14)

Record the conformance test procedure result Assignm Common Cause of


Transmis Address field of Information
for each of the supported configuration Station type Transmission speed ent class address transmiss
sion type the link object address
parameter values on the right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure
passed for that configuration
value.
FAIL: indicates the test procedure
failed for at least one of the test
Cases.

in controlled

in monitor
N.A: indicates that configuration

in controlled

in monitor
value is not supported by the
device.

ASDU 126 Directory N.A N.A - - - - - - - - - - - - - - - - - -


Frame Count Bit N.A √ - - - - - - - - - - - - - - - - - -
Invalid Checksum N.A √ - - - - - - - - - - - - - - - - - -
Link Layer
Time Out Interval N.A √ - - - - - - - - - - - - - - - - - -
Address Field N.A √ - - - - - - - - - - - - - - - - - -
Data Unit Type identification N.A √ - - - - - - - - - - - - - - - - - -
Cause Of Transmission N.A √ - - - - - - - - - - - - - - - - - -
identifier
Common Address of ASDU N.A √ - - - - - - - - - - - - - - - - - -
Information N.A √ - - - - - - - - - - - - - - - - - -
Object Address
object address
Initialisation of the controlling station in √ N.A √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Station unbalanced transmission systems:(re- A A
)boot
FXD IEC60870-5-101 Protocol Test Report

Initialisation Local initialization of the controlled N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √


function(unbala Station in unbalanced transmission A A
nced systems) Systems:(re-)boot

Table 8 Test List and Result(8/14)

Record the conformance test procedure result for Assignm Common Cause of
Transmis Address field of Information
each of the supported configuration parameter Station type Transmission speed ent class address transmiss
sion type the link object address
values on the right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure
passed for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test
Cases.
N.A: indicates that configuration

in controlled

in monitor
in controlled

in monitor
value is not supported by the
device.

Remote initialization of the Controlled N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.


Station in unbalanced transmission Systems A A A A A A A A A A A A A A A A A A
Re-establishing a broken link between the N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
controlling and the Controlled Station in A A
unbalanced transmission Systems
Compatibility With Other Test Cases N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Data Data acquisition by polling in Unbalanced N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
acquisition by Transmission systems Sequential A A
polling Procedure
function(unbal COM Compatibility With Other Test Cases N.A
FXD IEC60870-5-101 Protocol Test Report

anced
systems)
Initialisation of the controlling station In √ N.A √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Station
balanced transmission systems: (re-)boot A A
Local initialization of the controlled Station N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Initialisation
in Balanced Transmission A A
function
systems :(re-)boot
(balanced
Remote initialization of the Controlled N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
systems)
station in Balanced Transmission systems A A A A A A A A A A A A A A A A A A

Table 9 Test List and Result(9/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value
in controlled

in monitor
in controlled

in monitor
is not supported by the device.

Re-establishing a broken link between the N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √


Controlling and the controlled station in Balanced A A
transmission systems
Compatibility with other test cases N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Periodic check of all redundant connections N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Redund
A A A A A A A A A A A A A A A A A A
ant link
Both lines are fully Initialized, on both lines test N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
FXD IEC60870-5-101 Protocol Test Report

Function of link are transmitled. On A A A A A A A A A A A A A A A A A A


primaryAnswered with ACK, on secondary
answered with N.ACK
Switch over it established by sending a command N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
(GI, Test command)on the secondary line. From A A A A A A A A A A A A A A A A A A
then On test functions of link on secondary are
answered With ACK and on primary with
N.ACK
Switchback is performed accordingly N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
A A A A A A A A A A A A A A A A A A
Cyclic Cyclic data transmission and background Scan- N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
data sequential procedure A A
transmis
sion N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Compatibility with other test cases
function A A

Table 10 Test List and Result(10/14)

Record the conformance test procedure result for Assignm Common Cause of
Transmis Address field of Information
each of the supported configuration parameter values Station type Transmission speed ent class address transmiss
sion type the link object address
on the right 2 of ASDU ion

Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed
for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test Cases.
N.A: indicates that configuration value
in controlled

in monitor
in controlled

in monitor
is not supported by the device.

N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Data Data acquisition through Read sequential
A A A A A A A A A A A A A A A A A A
acquisition Procedure
through read
N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
function Compatibility with other test cases
A A A A A A A A A A A A A A A A A A
Acquisition Acquisition of events - sequential Procedure N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
of events A A
FXD IEC60870-5-101 Protocol Test Report

fuction Compatibility with other test cases N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √


A A
Outstation Interrogation – one logical Remote N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Unit(LRU)available in the Controlled station A A
Outstation Interrogation –more than one logical N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Remote Unit(LRU)available in the Controlled A A A A A A A A A A A A A A A A A A
General
station
Interrogatio
Re-activate a running outstation Interrogation- N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
n function
option 1:the running GI continues A A A A A A A A A A A A A A A A A A
Re-activate a running outstation Interrogation- N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
option 2:the running GI is Stopped and the A A A A A A A A A A A A A A A A A A
second GI is started

Table 11 Test List and Result(11/14)

Record the conformance test procedure result for each Assignm Common Cause of
Transmis Address field of Information
of the supported configuration parameter values on the Station type Transmission speed ent class address transmiss
sion type the link object address
right 2 of ASDU ion
Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed for
that configuration value.
FAIL: indicates the test procedure failed
for at least one of the test Cases.
N.A: indicates that configuration value
in controlled

in monitor
in controlled

is not supported by the device. in monitor

Re-activate a running outstation Interrogation N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √


option 3: the running GI Continues and after A A
activation termination (COT=10)the second GI is
started(option 3 can be described as undesirable
behavior)
FXD IEC60870-5-101 Protocol Test Report

Deactivate a running outstation Interrogation N.A N.A N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.


A A A A A A A A A A A A A A A A A A
Compatibility with other test cases N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Clock synchronization – sequential Procedure N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Clock synchronization - Change the clock N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Compatibility with other test cases N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Comma
A A
nd
Select and Execute N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
transmis
A A
sion
Select and Deactivation N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
function
A A
Direct Execute N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
A A
Select with Negative confirmation by Controlled N.A √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
station(Abort) A A

Table 12 Test List and Result(12/14)

Record the conformance test procedure result for Assignm Common Cause of
Station Transmis Address field of Information
each of the supported configuration parameter Transmission speed ent class address transmiss
type sion type the link object address
values on the right 2 of ASDU ion
Controlled station test (Master)

Controlled station test (Slave)

direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed
for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test
Cases.
in controlled

in monitor
N.A: indicates that configuration
in controlled

in monitor

value is not supported by the device.

Select with Negative Execute confirmation N. √ √ √ √ √ √ √ N.A √ √ √ N. √ √ √ √ √ √ √


By controlled station If execute is received A A
After configured delay in the controlling
Station
FXD IEC60870-5-101 Protocol Test Report

Direct execute with negative confirmation By N. √ √ √ √ √ √ √ N.A √ √ √ N. √ √ √ √ √ √ √


controlled station A A
Test for all supported ASDU’s N. √ √ √ √ √ √ √ N.A √ √ √ N. √ √ √ √ √ √ √
A A
Compatibility with other test cases N. √ √ √ √ √ √ √ N.A √ √ √ N. √ √ √ √ √ √ √
A A
Transmission Mode A-Local freeze with spontaneous N. N. N. N. N. N. N. N. N.A N. N. N. N. N. N. N. N. N. N. N.
of integrated Interrogation A A A A A A A A A A A A A A A A A A A
totals Mode B-Local freeze with counter N. N. N. N. N. N. N. N. N.A N. N. N. N. N. N. N. N. N. N. N.
(telecounting) Interrogation A A A A A A A A A A A A A A A A A A A
function Mode C-Remote Initiated freeze with counter N. N. N. N. N. N. N. N. N.A N. N. N. N. N. N. N. N. N. N. N.
Interrogation A A A A A A A A A A A A A A A A A A A
Mode D-Remote Initiated freeze with N. N. N. N. N. N. N. N. N.A N. N. N. N. N. N. N. N. N. N. N.
Spontaneous transmission A A A A A A A A A A A A A A A A A A A
Compatibility with other test cases N. N. N. N. N. N. N. N. N.A N. N. N. N. N. N. N. N. N. N. N.
A A A A A A A A A A A A A A A A A A A

Table 13 Test List and Result(13/14)

Record the conformance test procedure result for each Assignm Common Cause of
Station Transmis Address field of Information
of the supported configuration parameter values on Transmission speed ent class address transmiss
type sion type the link object address
the right 2 of ASDU ion
Controlled station test (Master)

Controlled station test (Slave)


direction
Max Transmission speed
direction
Min Transmission speed
direction
Max Transmission speed
direction
Min Transmission speed

Unbalanced transmission

Balanced transmission

field(balanced only)
Zero(0) octet for address

One(1) octet for address field

Two(2) octet for address field

messages
Standard assignment of class 2
messages
Special assignment of class 2
ASDU(CASDU)
One(1) octet for Common Address of
ASDU(CASDU)
Two(2) octet for Common Address of
Address(structured or unstructured)
One(1) octet for Information Object
Address(structured or unstructured)
Two(2) octet for Information Object
Address(structured or unstructured)
Three(3) octet for Information Object
is origiN.Ator address)
One(1) octets for COT field(2nd octet
is origiN.Ator address)
Two(2) octets for COT field(2nd octet
√: indicates the test procedure passed
for that configuration value.
FAIL: indicates the test procedure
failed for at least one of the test Cases.
N.A: indicates that configuration value
in controlled

in monitor
in controlled

in monitor

is not supported by the device.

Parameter Load and activate parameter N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.


FXD IEC60870-5-101 Protocol Test Report

loading A A A A A A A A A A A A A A A A A A A A
function Load and activate parameter with Negative N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Confirmation by controlled station A A A A A A A A A A A A A A A A A A A A
Compatibility with other test cases N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
A A A A A A A A A A A A A A A A A A A A
Test procedure – sequential N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Test
procedure A A A
procedure
Compatibility with other test cases N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
function
A A A
File transfer procedure(monitor direction) N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Sequential procedure A A A A A A A A A A A A A A A A A A A A
File transfer
File transfer procedure(control direction) N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
procedure
Sequential procedure A A A A A A A A A A A A A A A A A A A A
function
Compatibility with other test cases N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
A A A A A A A A A A A A A A A A A A A A
Delay acquisition procedure Sequential N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Delay
Procedure A A A
acquisition
Compatibility with other test cases N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
procedure
A A A
Out of service behavior N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
AdditioN.Al A A A
Conformance Miscellaneous N. √ √ √ √ √ √ √ N. √ √ √ N. √ √ √ √ √ √ √
Test A A A
Procedures N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N. N.
Time invalid
A A A A A A A A A A A A A A A A A A A A
Table 14 Test List and Result(14/14)

Record the conformance test procedure result for Assignm Common Cause of
Station Transmis Address field of Information
each of the supported configuration parameter Transmission speed ent class address transmiss
type sion type the link object address
values on the right 2 of ASDU ion
Two(2) octets for COT field(2nd octet
N.

N.

N.
A

A

is origiN.Ator address)
One(1) octets for COT field(2nd octet
N.

N.

N.
A

A

is origiN.Ator address)
Three(3) octet for Information Object
N.

N.

N.
A

A

Address(structured or unstructured)
Two(2) octet for Information Object
N.

N.

N.
A

A

Address(structured or unstructured)
One(1) octet for Information Object
N.

N.

N.
A

A

Address(structured or unstructured)
Two(2) octet for Common Address of
N.

N.

N.
A

A

ASDU(CASDU)
One(1) octet for Common Address of
N.

N.

N.
A

A

ASDU(CASDU)
Special assignment of class 2
N.

N.

N.

N.

N.

N.
A

messages
Standard assignment of class 2
N.

N.

N.
A

A

messages
N.

N.

N.

Two(2) octet for address field


A

A

N.

N.

N.

One(1) octet for address field


A

A

Zero(0) octet for address


N.

N.

N.

N.

N.

N.
A

field(balanced only)
N.

N.

N.

Balanced transmission
A

A


FXD IEC60870-5-101 Protocol Test Report

N.

N.

N.

Unbalanced transmission
A

A

Min Transmission speed in monitor


N.

N.

N.
A

A

direction
Max Transmission speed in monitor
N.

N.

N.
A

A

direction
Min Transmission speed in controlled
N.

N.

N.
A

A

direction
Max Transmission speed in controlled
N.

N.

N.
A

A

direction
N.

N.

N.

Controlled station test (Slave)


A

A


N.

N.

N.

N.

N.

N.
Controlled station test (Master)
A

A
√: indicates the test procedure passed

value is not supported by the device.


FAIL: indicates the test procedure

N.A: indicates that configuration


failed for at least one of the test

Compatibility with other test cases

Compatibility with other test cases


for that configuration value.

Negative tests

Function:

Function:

Function:
Cases.

Test Procedures
PIXIT related
Conformance
Conformance
Procedures
Negative
FXD IEC60870-5-101 Protocol Test Report

4.2 Detailed Data Point test result:

FUNCTION TEST RTU RECLOSER


MARK COOPER
TYPE FXD Controller
PROTOCOL IEC60870-5-101
A: indicate this item is available for the test report.
N.A: indicate this item is not applicable for the test report.
√: indicate the result of this item is passed.
-: indicate this item is empty.
Address TEST
FUNCTION
Offset A/N.A VALUES(0/1) RESULT
A. TElE STATUS - BIN
BINARY INPUT
0 RecloserClosed A INVALID/CLSOED √
1 RecloserOpen A INVALID/OPEN √
2 ControlIsLockedOut A INVALID/LOCKOUT √
3 AnyControlSystemAlarm A NORMAL/ALARM √
4 AboveMiniTrip A NORMAL/ALARM √
5 SupervisoryOff A ON/OFF √
6 NonReclosing A OFF/ON √
7 GroundTripBlocked A UNBLOCKED/BLOCKED √
8 SefBlocked A UNBLOCKED/BLOCKED √
9 CLPUBlocked A UNBLOCKED/BLOCKED √
10 PhaseTripBlocked A UNBLOCKED/BLOCKED √
11 NormalProfileSelected A INVALID/NORMAL √
12 AlterProfile1Selected A INVALID/ALT#1 √
13 AlterProfile2Selected A INVALID/ALT#2 √
14 AlterProfile3Selected A INVALID/ALT#3 √
15 HotLineTag A OFF/ON √
16 PhaseAVoltagePresent A NO PRESENT/PRESENT √
17 PhaseBVoltagePresent A NO PRESENT/PRESENT √
18 PhaseCVoltagePresent A NO PRESENT/PRESENT √
19 Reserve N.A - -
20 BatteryTestActive A IN.ACTIVE/ACTIVE √
21 NoACPowerPresent A NO PRESENT/PRESENT √
22 BatteryAlarm A NORMAL/ALARM √
23 PhaseAFaultTrip A NORMAL/ALARM √
24 PhaseBFaultTrip A NORMAL/ALARM √
25 PhaseCFaultTrip A NORMAL/ALARM √
FXD IEC60870-5-101 Protocol Test Report

26 GroundFalutTrip A NORMAL/ALARM √
27 SefTrip A NORMAL/ALARM √
28 Reserve N.A - -
29 Reserve N.A - -
30 Reserve N.A - -
31 RemoteHLTLockON A OFF/ON √
32 LocalHLTLockON A OFF/ON √
33 ControlCircuitInterrupted A OFF/ON √
34 Reserve N.A - -
35 VoltageTripBlocked A UNBLOCKED/BLOCKED √
36 FrequencyTripBlocked A UNBLOCKED/BLOCKED √
37 TestPointActived A IN.ACTIVE/ACTIVE √
38 ControlDoorOpened A OPEN/CLSOE √
39 Yellow Handle On A OFF/ON √
40 PhaseOvercurrentAlarm A NORMAL/ALARM √
41 GroundOvercurrentAlarm A NORMAL/ALARM √
42 NegtiveSequenceOvercurrentAlarm A NORMAL/ALARM √
43 OverVoltageAlarm A NORMAL/ALARM √
44 UnderVoltageAlarm A NORMAL/ALARM √
45 HCT Trip Status A NORMAL/ALARM √
46 IO1 In Status A NORMAL/ALARM √
47 IO2 In Status A NORMAL/ALARM √
48 IO1 Out Status A NORMAL/ALARM √
49 IO2 Out Status A NORMAL/ALARM √
B. TElE STATUS - DOUBLE BIT INPUT
0 SwitchStatus A INVALID/OPEN/CLOSE √
1 SupervisoryStatus A INVALID/ON/OFF √
C. TELE CONTROL - SINGLE COMMANDS
0 CLoseMechanism A - √
1 TripMechanism A - √
2 BlockReclosing A - √
3 BlockGroundTrip A - √
4 BlockSEF A - √
5 BlockCLPU A - √
6 BlockPhaseTrip A - √
7 ProfileNormal A - √
8 ProfileAlt1 A - √
9 ProfileAlt2 A - √
10 ProfileAlt3 A - √
FXD IEC60870-5-101 Protocol Test Report

11 ResetTarget A - √
12 Reserve N.A - -
13 ResetAlarms A - √
14 TestBattery A - √
15 HLTSet A - √
16 HLTReset A - √
17 ResetEnergyMeters A - √
18 BlockVoltageTrip A - √
19 BlockFreqTrip A - √
20 TripAll A - √
21 CloseALL A - √
22 TestPoint A - √
23 ClearAboveMinTrip A - √
D. TELE CONTROL - DOUBLE COMMANDS
0 OperateSwitch A - √
1 SupervisoryStateSwitch A - √
E. TELE METERING
0 A Phase Primary Current Magnitude A DECIMAL √
1 B Phase Primary Current Magnitude A DECIMAL √
2 C Phase Primary Current Magnitude A DECIMAL √
3 3I0 Primary Current Magnitude A DECIMAL √
4 A Phase Primary Voltage Magnitude A DECIMAL √
5 B Phase Primary Voltage Magnitude A DECIMAL √
6 C Phase Primary Voltage Magnitude A DECIMAL √
7 A Phase Power Factor A DECIMAL √
8 B Phase Power Factor A DECIMAL √
9 C Phase Power Factor A DECIMAL √
10 A Phase Primary Apparent Power A DECIMAL √
11 B Phase Primary Apparent Power A DECIMAL √
12 C Phase Primary Apparent Power A DECIMAL √
13 A Phase Primary Real Power A DECIMAL √
14 B Phase Primary Real Power A DECIMAL √
15 C Phase Primary Real Power A DECIMAL √
16 A Phase Primary Reactive Power A DECIMAL √
17 B Phase Primary Reactive Power A DECIMAL √
18 C Phase Primary Reactive Power A DECIMAL √
19 Line Frequency A DECIMAL √
20 Reserve N.A - -
21 Battery Voltage A DECIMAL √
FXD IEC60870-5-101 Protocol Test Report

22 A Phase Line Voltage Magnitude A DECIMAL √


23 B Phase Line Voltage Magnitude A DECIMAL √
24 C Phase Line Voltage Magnitude A DECIMAL √
25 A Phase Fault Current A DECIMAL √
26 B Phase Fault Current A DECIMAL √
27 C Phase Fault Current A DECIMAL √
28 SEF Fault Current A DECIMAL √
F. COUNTER
0 ProtectTripCounter A DECIMAL √
1 ManualTripCounter A DECIMAL √
2 OperationsTripCounter A DECIMAL √
FXD IEC60870-5-101 Protocol Test Report

Tested by:

Date: May,16,2014

Checked by:

Date: May,16,2014

Approved by:

Date: May,16,2014