- Sub Station ‘C’

Raw Mill Electrical Room


6.6 kV Switchgear
MCC 200.MC
Thermal Inspection Report
Inspected Equipment Id: Fuse (Red)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 1

Additional
Information

Working
Conditions

Fault Description
64.0°C

AR01 60

55

50
SP02
SP01
45

40.3°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 63.7°C
SP02 59.3°C
AR01 : max 64.1°C
Thermal Inspection Report
Inspected Equipment Id: Fuse (Yellow)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – panel 1

Additional
Information

Working
Conditions

Fault Description
64.0°C

AR01 60

55

50
SP01 SP02

45

40.1°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 62.9°C
SP02 63.0°C
AR01 : max 63.5°C
Thermal Inspection Report
Inspected Equipment Id: Fuse (Blue)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 1

Additional
Information

Working
Conditions

Fault Description
64.4°C

AR01
60

55

50
SP01 SP02

45

40.3°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 63.6°C
SP02 63.4°C
AR01 : max 64.5°C
Thermal Inspection Report
Inspected Equipment Id: Filter Cable Connection

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 4

Additional
Information

Working
Conditions

Fault Description
71.0°C
70

LI01
60

50

LI02
40.1°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
LI01 : max 53.5°C
LI02 : max 53.5°C
Thermal Inspection Report
Inspected Equipment Id: Fuse (Red)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 5

Additional
Information

Working
Conditions

Fault Description
64.1°C

60
AR01

55

50

SP01 SP02
45

40
39.6°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 63.9°C
SP02 60.2°C
AR01 : max 64.1°C
Thermal Inspection Report
Inspected Equipment Id: Fuse (Yellow)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 5

Additional
Information

Working
Conditions

Fault Description
63.0°C

AR01
60

55

SP01 SP02
50

45

40
39.4°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 60.2°C
SP02 60.6°C
AR01 : max 61.7°C
Thermal Inspection Report
Inspected Equipment Id: Fuse (Blue)

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 5

Additional
Information

Working
Conditions

Fault Description
63.6°C

AR01 60

55

50
SP01 SP02

45

40
39.2°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 62.5°C
SP02 62.7°C
AR01 : max 63.8°C
Thermal Inspection Report
Inspected Equipment Id: Filter Cable Connection

Scanned Date: 24th June 2010

Identification
I

Section 224.32

Equipment Mill Fan FC – Panel 8

Additional
Information

Working
Conditions

Fault Description
68.1°C

LI01
60

50

LI02 40
39.2°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
LI01 : max 49.5°C
LI02 : max 47.4°C
Thermal Inspection Report
Inspected Equipment Id: Capacitor - Top

Scanned Date: 24th June 2010

Identification
I

Section 299.31

Equipment EP Fan FC – (+A10)

Additional
Information

Working
Conditions

Fault Description
50.9°C

LI03 LI04 50

45

40

LI01 LI02
36.5°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
LI01 : max 47.8°C
LI02 : max 46.8°C
LI03 : max 46.7°C
LI04 : max 46.3°C
Thermal Inspection Report
Inspected Equipment Id: Capacitor - Middle

Scanned Date: 24th June 2010

Identification
I

Section 299.31

Equipment EP Fan FC – (+A10)

Additional
Information

Working
Conditions

Fault Description
50.9°C
LI01 LI04
50

45

40

LI02 LI03

36.6°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
LI01 : max 46.8°C
LI02 : max 45.2°C
LI03 : max 45.8°C
LI04 : max 45.8°C
Thermal Inspection Report
Inspected Equipment Id: Capacitor - Bottom

Scanned Date: 24th June 2010

Identification
I

Section 299.31

Equipment EP Fan FC – (+A10)

Additional
Information

Working
Conditions

Fault Description
49.2°C

48
LI01 LI02
46

44

42

40

LI04 38
LI03
37.2°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
LI01 : max 44.3°C
LI02 : max 44.0°C
LI03 : max 43.5°C
LI04 : max 43.4°C
Thermal Inspection Report
Inspected Equipment Id: Contactor 1 and 2

Scanned Date: 24th June 2010

Identification
I

Section MCC 200

Equipment Panel (+A18)

Additional
Information

Working
Conditions

Fault Description
127.5°C

120

100

80

SP01SP02SP03 SP04SP05SP06 60

43.0°C

Object parameter Value Recommendation


Emissivity 0.97 No any abnormalities found. Scan in next six month
Label Value
SP01 76.0°C
SP02 77.8°C
SP03 75.4°C
SP04 79.0°C
SP05 83.7°C
SP06 79.9°C
Thermal Inspection Report
Inspected Equipment Id: Capacitor (Contactor 1 & 2)

Scanned Date: 24th June 2010

Identification
I

Section MCC 200

Equipment Panel (+A18)

Additional
Information

Working
Conditions

Fault Description
156.6°C
AR02
AR01
140

120

100

SP02
SP01 80

60

40
38.6°C

Object parameter Value Recommendation


Emissivity 0.97 Higher temperature noted at AR01. Please check for any
Label Value abnormalities and rectify ASAP
SP01 51.9°C
SP02 40.6°C
AR01 : max 164.9°C
AR02 : max 91.1°C
Thermal Inspection Report
Inspected Equipment Id: Fuse 6 and 7

Scanned Date: 24th June 2010

Identification
I

Section MCC 200

Equipment Panel (+18)

Additional
Information

Working Conditions

Fault Description
80.8°C

SP01
SP03

SP02

42.9°C

Object parameter Value Recommendation


Emissivity 0.97 Higher temperature noted at Fuse cable SP02 (Fuse no.7)
Label Value Check for loose connection and for any abnormalities.
ASAP
SP01 78.2°C
SP02 87.9°C
SP03 58.8°C
Thermal Inspection Report
Inspected Equipment Id: Fuse 8 and 9

Scanned Date: 24th June 2010

Identification
I

Section MCC 200

Equipment Panel (+18)

Additional
Information

Working Conditions

Fault Description
79.1°C

SP01
SP02

SP03

39.5°C

Object parameter Value Recommendation


Emissivity 0.97 Higher temperature noted at Fuse cable SP01 and SP02
Label Value (Fuse no.9)
Check for loose connection and for any abnormalities.
SP01 80.3°C ASAP
SP02 84.8°C
SP03 51.0°C
Thermal Inspection Report
Inspected Equipment Id: Contactor 6 and 7

Scanned Date: 24th June 2010

Identification
I

Section MCC 200

Equipment Panel (+18)

Additional
Information

Working Conditions

Fault Description
83.2°C

80

70

60

SP04 SP05SP06 50
SP01SP02SP03

41.5°C

Object parameter Value Recommendation


Emissivity 0.97
No any abnormalities found. Scan in next six month
Label Value
SP01 73.4°C
SP02 76.7°C
SP03 75.5°C
SP04 72.3°C
SP05 75.5°C
SP06 71.3°C

You might also like