Professional Documents
Culture Documents
01 MEM40105 Multiple Choice Assignment PDF
01 MEM40105 Multiple Choice Assignment PDF
Name _______________________________________________________
Date _______________________________________________________
FOUNDATION
1 1 Metric and imperial tube have the same OD. TRUE FALSE
PRINCIPLES
FOUNDATION
1 2 1 kPa is equal to 0.145 psi 4.015 psi 2.2046 psi
PRINCIPLES
FOUNDATION
1 3 Density units are lb/ft lb/ft2 lb/ft3
PRINCIPLES
FOUNDATION
1 4 1 kPa is equal to 0.145 "H2O 4.015 "H2O 2.2046 "H2O
PRINCIPLES
FOUNDATION
1 5 Metric and imperial pipe have the same OD. TRUE FALSE
PRINCIPLES
FOUNDATION
1 6 The SI Prefix kilo means 0.001 1 1000
PRINCIPLES
False, there is no
FOUNDATION True, Australia is a True, the government
1 8 In Australia, all industrial plants use only metric units. defined rules for all
PRINCIPLES metric country. makes them.
industrial plants.
FOUNDATION National Pipe Thread (NPT) and British Standard Pipe (BSP)
1 9 TRUE FALSE
PRINCIPLES are the same thing.
FOUNDATION
1 11 The abbreviation for International System of Units is ISU IS SI
PRINCIPLES
Y??? = ylower +
Y??? = ylower (yupper - Y??? = ylower + (xwant -
FOUNDATION ((xwant - xlower) /
1 12 The formula for interpolation is ylower) + ((xwant - xlower) (xupper - xlower )
PRINCIPLES (xupper - xlower ))
xlower) / (xupper - xlower )) (yupper - ylower)
(yupper - ylower)
FOUNDATION
1 15 The formula p = m / V is the same as m=p/V V=pm m=pV
PRINCIPLES
FOUNDATION 3 3 3
1 19 The density of air 0 C and 101.325 kPa .99 kg/m 1 kg/m 1.293 kg/m
PRINCIPLES
FOUNDATION 3
1 21 The density of water at 15 C is 998 kg/m3 999 kg/m3 1000 kg/m
PRINCIPLES
FOUNDATION
1 22 The formula for density is P=m/V p=m/V p=mV
PRINCIPLES
FOUNDATION
1 23 Understanding pressure useful for an instrument technician. TRUE FALSE
PRINCIPLES
FOUNDATION
1 24 Density is dependant on temperature. TRUE FALSE
PRINCIPLES
FOUNDATION
1 25 Relative density is density specific gravity gravity
PRINCIPLES
FOUNDATION
1 26 A gas with a SG = 1.5 will rise to the ceiling sink to the floor SG cannot be > 1
PRINCIPLES
FOUNDATION There is a gas release at work. The deadly gas has a SG = 2. out via the roof
1 28 out via the ground exit makes no difference
PRINCIPLES It is the same distance to escape. Should I go exit
FOUNDATION
1 30 A liquid with a SG = 1.5 will float on water not float on water SG cannot be > 1
PRINCIPLES
FOUNDATION
1 31 Force is not related to pressure. TRUE FALSE
PRINCIPLES
FOUNDATION
1 32 The acceleration of gravity is 0.98 m/s² 9.8 m/s² 98 m/s²
PRINCIPLES
FOUNDATION
1 33 Weight and Force are the same thing. TRUE FALSE
PRINCIPLES
FOUNDATION
1 34 The metric unit for weight is the gram newton kilogram
PRINCIPLES
FOUNDATION
1 35 Pounds can be either a unit of force or a unit of mass. TRUE FALSE
PRINCIPLES
FOUNDATION Absolute pressure is zero referenced against a perfect gauge pressure plus gauge pressure plus
1 36 gauge pressure
PRINCIPLES vacuum, so it is equal to atmospheric pressure absolute pressure
FOUNDATION
1 37 kPaa is a typo atmospheric absolute
PRINCIPLES
FOUNDATION
1 41 Atmospheric pressure increases with decreasing altitude. TRUE FALSE
PRINCIPLES
FOUNDATION
1 42 Atmospheric pressure is also called barometric pressure. TRUE FALSE
PRINCIPLES
FOUNDATION
1 44 Vacuum is always measured from atmospheric pressure. TRUE FALSE
PRINCIPLES
FOUNDATION
1 46 The most common type of pressure measurement is gauge differential absolute
PRINCIPLES
pressure will be
pressure will be the pressure will be the
FOUNDATION If there are two tanks with the same height and fluid, but one different and the
1 48 same but the weight same and the weight
PRINCIPLES tank has twice the volume the weight will be
will be different will be the same
different
FOUNDATION
1 49 The static pressure formula is P=w A P=A/w P=w/A
PRINCIPLES
FOUNDATION
1 51 The hydrostatic pressure formula is P=phg p=phg P=ph/g
PRINCIPLES
FOUNDATION
1 55 Thermal energy can always be measured in a fluid. TRUE FALSE
PRINCIPLES
FOUNDATION
1 56 Heat energy is not thermal energy. TRUE FALSE
PRINCIPLES
FOUNDATION
1 58 Heat and temperature are not the same thing TRUE FALSE
PRINCIPLES
FOUNDATION
2 60 All companies use the ISA symbology. TRUE FALSE
PRINCIPLES
FOUNDATION The control system graphics display is usually laid out to Process Flow
2 61 P&ID Layout Drawings
PRINCIPLES represent the Diagram
FOUNDATION
2 62 A company may have several P&ID Legend Sheets. TRUE FALSE
PRINCIPLES
FOUNDATION
2 63 The primary purpose of a P&ID is to show terminations instruments process connection
PRINCIPLES
FOUNDATION Maintaining the instrument records and drawings is the maintenance and
2 64 maintenance engineering
PRINCIPLES responsibility of which department engineering
FOUNDATION
2 67 A control valve always has a 'C' for the middle letter. TRUE FALSE
PRINCIPLES
FOUNDATION
2 69 A diamond on a P&ID always means the same thing. TRUE FALSE
PRINCIPLES
FOUNDATION
2 71 An instrument bubble with no line means control room panel rear field
PRINCIPLES
FOUNDATION
2 72 An instrument bubble with a box means instrument control system interlock
PRINCIPLES
FOUNDATION
2 73 Most plants use single loop controllers. TRUE FALSE
PRINCIPLES
FOUNDATION
2 75 An instrument bubble with a solid line means control room panel rear field
PRINCIPLES
FOUNDATION
2 77 A dashed signal line means electronic data pneumatic
PRINCIPLES
FOUNDATION
2 78 A dashed with circles signal line means electronic data pneumatic
PRINCIPLES
FOUNDATION
2 79 A computation symbol is usually located top left middle top right
PRINCIPLES
FOUNDATION
2 81 The plant area is shown in an instrument bubble. TRUE FALSE
PRINCIPLES
FOUNDATION
2 82 A solid signal line with parallel slashes means electronic data pneumatic
PRINCIPLES
FOUNDATION
2 83 An instrument bubble with a dashed line means control room panel rear field
PRINCIPLES
FOUNDATION The instrument data sheet must show the full tag number
2 85 TRUE FALSE
PRINCIPLES including the area.
FOUNDATION
2 88 The data sheet can have one or more instruments per sheet. TRUE FALSE
PRINCIPLES
FOUNDATION
2 89 The instrument data sheet will have calibration. TRUE FALSE
PRINCIPLES
FOUNDATION The instrument data sheet does not have to state the line
2 90 TRUE FALSE
PRINCIPLES number or equipment number.
FOUNDATION An instrument data sheet is used to identify information about instrument and
2 92 instrument process
PRINCIPLES the process
FOUNDATION
2 95 Some plants may not use loop diagrams. TRUE FALSE
PRINCIPLES
FOUNDATION
2 96 The I/O schedule only lists connected instruments. TRUE FALSE
PRINCIPLES
FOUNDATION A plant will always have only one system for instrument
2 98 TRUE FALSE
PRINCIPLES records.
FOUNDATION
2 100 The I/O schedule lists all available points. TRUE FALSE
PRINCIPLES
FOUNDATION
2 102 The rack drawing will show cables in and out of the rack. TRUE FALSE
PRINCIPLES
FOUNDATION
2 104 On a loop diagram, the control system are located on the left middle right
PRINCIPLES
FOUNDATION
2 106 Instrument information is duplicated in many documents. TRUE FALSE
PRINCIPLES
FOUNDATION
2 107 On a loop diagram, the field instrument/s are located on the left middle right
PRINCIPLES
FOUNDATION
2 108 The primary purpose of a loop diagrams is to show terminations instruments process connection
PRINCIPLES
FOUNDATION The instrument junction box drawing will show cables in and
2 109 TRUE FALSE
PRINCIPLES out of the box.
FOUNDATION
2 111 Some plant have an instrument power schedule. TRUE FALSE
PRINCIPLES
FOUNDATION The instrument cable schedule will list all cables associated
2 112 TRUE FALSE
PRINCIPLES with an instrument including element and power cables.
FOUNDATION
2 115 If a valve requires a defined fail action, it is shown on a P&ID. TRUE FALSE
PRINCIPLES
FOUNDATION
2 116 Some P&IDs use a generic valve symbol. TRUE FALSE
PRINCIPLES
FOUNDATION
2 117 A P&ID may have different symbols for type of actuators. TRUE FALSE
PRINCIPLES
FOUNDATION
2 118 To prevent backflow use a control valve on/off valve one way valve
PRINCIPLES
FOUNDATION
2 119 To control flow use a control valve on/off valve one way valve
PRINCIPLES
FOUNDATION Instruments are small and do not have much impact on the
3 122 TRUE FALSE
PRINCIPLES running of the plant.
FOUNDATION
3 129 All instruments are directly connected to a process line. TRUE FALSE
PRINCIPLES
FOUNDATION I'm a contractor; the plant work permit system does not apply
3 135 TRUE FALSE
PRINCIPLES to me.
FOUNDATION
3 136 Most instrument work requires a hot work permit. TRUE FALSE
PRINCIPLES
FOUNDATION
4 138 A display of 30 to 45C is suppressed zero elevated zero zero suppression
PRINCIPLES
FOUNDATION
4 143 Span is URL - LRL LRL - URL URL + LRL
PRINCIPLES
FOUNDATION If the tank level was actually 45%, and the transmitter output
4 147 precision resolution accuracy
PRINCIPLES was 45%. This is
FOUNDATION
4 148 A display of -40 to 100C is suppressed zero elevated zero zero suppression
PRINCIPLES
FOUNDATION
4 150 The National Measurement Institute (NMI) is located in UK Australia USA
PRINCIPLES
FOUNDATION
4 151 In statics, errors are multiplied are additive are subtractive
PRINCIPLES
FOUNDATION
4 152 Precision means repeatable correct precise
PRINCIPLES
FOUNDATION
4 153 Increased resolution means increased accuracy repeatability readability
PRINCIPLES
FOUNDATION
4 155 Accuracy means repeatable correct precise
PRINCIPLES
FOUNDATION
4 156 Calibration can improve accuracy. TRUE FALSE
PRINCIPLES
FOUNDATION If you have remote seal, then there maybe zero suppression
4 158 TRUE FALSE
PRINCIPLES or elevation.
FOUNDATION With a corrosive fluid, the same material should be used for
4 160 TRUE FALSE
PRINCIPLES the diaphragm and the body.
FOUNDATION The good fill fluid for high vacuum and high temperature Syltherm XLT
4 162 DC705 Silicone Neobee M20
PRINCIPLES applications is Silicone
FOUNDATION
4 163 Silicon is inert and is OK for all process fluids. TRUE FALSE
PRINCIPLES
FOUNDATION
4 166 The ambient temperature will not effect a transmitter. TRUE FALSE
PRINCIPLES
FOUNDATION
4 170 All errors are stated in a product data sheet. TRUE FALSE
PRINCIPLES
FOUNDATION
4 171 The vibration effect can be calibrated out. TRUE FALSE
PRINCIPLES
FOUNDATION
4 172 The instrument parts in contract with process fluid are called wet leg wetted part liquid part
PRINCIPLES
FOUNDATION
4 173 The best selection for range is near the minimum span mid range upper range limit
PRINCIPLES
FOUNDATION A high velocity flow through the small bore of an orifice plate
4 174 pitting galvanic erosion
PRINCIPLES may cause what type of corrosion
FOUNDATION
4 176 The power supply effect can be calibrated out. TRUE FALSE
PRINCIPLES
FOUNDATION The line pressure effect span error can be calibrated out of
4 180 TRUE FALSE
PRINCIPLES some instruments.
FOUNDATION
4 181 All measurements require the same accuracy. TRUE FALSE
PRINCIPLES
FOUNDATION The line pressure effect zero error can be calibrated out of
4 183 TRUE FALSE
PRINCIPLES some instruments.
FOUNDATION The reason the calibrated LRL is negative could be because vacuum or remote
4 185 vacuum remote seals
PRINCIPLES of seals
FOUNDATION
4 189 The most destructive form of corrosion is pitting galvanic erosion
PRINCIPLES
FOUNDATION 316 SST and 316L SST are all the same thing just written
4 190 TRUE FALSE
PRINCIPLES differently.
FOUNDATION Most data sheets will have just one type of instrument error
4 193 TRUE FALSE
PRINCIPLES specified.
FOUNDATION
4 199 Which diaphragm material is best for liquid natural gas 316L SST Hastelloy C Monel
PRINCIPLES
FOUNDATION
4 203 Which instrument output has just a digital signal 4-20 mA HART fieldbus
PRINCIPLES
measuring below
FOUNDATION The reason 4-20 mA is used is because a value of 3 mA measuring below
4 204 instrument fault calibrated range or
PRINCIPLES means calibrated range
instrument fault
FOUNDATION 18 AWG or
4 205 What type of cable is typically used in instrumentation twisted shielded pair shielded pair
PRINCIPLES 1.5mm2
FOUNDATION
4 216 The paper work is just as important as the actual calibration. TRUE FALSE
PRINCIPLES
FOUNDATION
4 227 It is always best to calibrate in the field. TRUE FALSE
PRINCIPLES
FOUNDATION The control systems range displayed will always provide the
4 231 TRUE FALSE
PRINCIPLES range for calibrating the field instrument.
FOUNDATION The piping designer will always provide the correct process
5 233 TRUE FALSE
PRINCIPLES connection required by instrumentation.
FOUNDATION
5 238 A mistake will be found before a plant starts full operation. TRUE FALSE
PRINCIPLES
FOUNDATION A root cause analysis will have people who know the facts of
5 243 TRUE FALSE
PRINCIPLES the problem.
FOUNDATION
5 246 Usually, I should cut back the ground shield. TRUE FALSE
PRINCIPLES
FOUNDATION
5 247 The purpose of root cause analysis is to find the fault cause solution
PRINCIPLES
FOUNDATION
5 248 The fault found is usually the fault reported. TRUE FALSE
PRINCIPLES
FOUNDATION You should only use the look and tug method as a last resort
5 251 TRUE FALSE
PRINCIPLES to find the fault.
FOUNDATION
5 252 I should use the same fault finding approach for any fault. TRUE FALSE
PRINCIPLES
FOUNDATION
5 253 Asking questions is the good way to find the fault. TRUE FALSE
PRINCIPLES
FOUNDATION If a solution does not allow the plant to run, a better solution is
5 254 TRUE FALSE
PRINCIPLES required.
FOUNDATION
5 256 I may irritate people if I ask questions. TRUE FALSE
PRINCIPLES
FOUNDATION
5 258 The purpose of fault finding is to find the fault cause solution
PRINCIPLES
FOUNDATION
5 259 All operators will have the same perception. TRUE FALSE
PRINCIPLES
FOUNDATION
5 260 Asking questions only tells me where the fault is. TRUE FALSE
PRINCIPLES
FOUNDATION
5 261 Asking questions allows me to eliminate possible causes. TRUE FALSE
PRINCIPLES
FOUNDATION
5 262 The most powerful tool in your toolbox should be your documents communicator brain
PRINCIPLES
XMITTER & When reading a water type manometer, read the meniscus at
1 265 bottom centre top
VALVES the
XMITTER &
1 266 The American platinum 100 ohm RTD coefficient is 0.00362 0.00385 0.00392
VALVES
XMITTER &
1 268 A RTD temperature transmitter is commonly mounted on the assembly remote junction box
VALVES
XMITTER &
1 270 Which instrument cannot accurately measure 1 kPa? bourdon tube manometer draft range DP
VALVES
XMITTER &
1 271 The normal pH range is 0-14 0-16 0-18
VALVES
XMITTER & A simple local control sump pump system for level most likely
1 272 DP ultrasonic float
VALVES has a
XMITTER &
1 273 A instrument technician should be able to calculate orifice plate bore control valve sizing tank level
VALVES
XMITTER & A tank is 10 metres high and the SG=1. What is the
1 275 9.8 kPA 98 kPA 980 kPA
VALVES calibration range?
XMITTER & The most common industrial temperature sensor for 1000 C
1 276 RDT RTD TC
VALVES would be
XMITTER &
1 277 For a pH measurement, what value is pure water or neutral? 5 7 9
VALVES
XMITTER &
1 278 Ammonia and borax are more acidic neutral caustic
VALVES
XMITTER &
1 279 Thermocouples are not reliable. TRUE FALSE
VALVES
XMITTER & If the process fluid density changes, a DP level transmitter will
1 281 TRUE FALSE
VALVES need recalibration.
XMITTER &
1 283 Beer and orange juice are more acidic neutral caustic
VALVES
XMITTER & When is it a good choice to use radar or ultra sonic over DP fluid density fluid density changes
1 284 corrosive
VALVES for level? changes or corrosive
XMITTER &
1 285 A safety pressure gauge should be blow out front blow out top blow out back
VALVES
XMITTER &
1 286 The most common RTD is 2 wire 3 wire 4 wire
VALVES
XMITTER &
1 287 What type of flow measurement is nonlinear? magmeter coriolis DP
VALVES
XMITTER & With a bare metal thermocouple it is easy to figure out what
1 288 TRUE FALSE
VALVES type it is.
XMITTER & What is the better choice for level measurement of a settling
1 289 DP ultrasonic float
VALVES pond?
XMITTER & Open tank level measurement by DP needs how many tank
1 290 1 2 4
VALVES connections?
XMITTER & A instrument over pressured by 25% of maximum design be damaged and
1 291 be OK leak or explode
VALVES pressure may need replacement
XMITTER & A tank is 100 inches high and the SG=1. What is the
1 292 0-10 "H2O 0-100 "H2O 0-1000 "H2O
VALVES calibration range?
XMITTER &
1 298 The IEC/DIN platinum 100 ohm RTD coefficient is 0.00362 0.00385 0.00392
VALVES
XMITTER &
1 299 A pneumatic local temperature controller most likely has a RTD TC filled system
VALVES
XMITTER & The most common industrial temperature sensor for 100 C
1 300 RDT RTD TC
VALVES would be
XMITTER &
1 301 A high water tank for level most likely has a DP ultrasonic float
VALVES
XMITTER & Bimetal strip is not used any more for temperature
1 303 TRUE FALSE
VALVES measurement.
XMITTER & A instrument over pressured by 200% of maximum design be damaged and
1 306 be OK leak or explode
VALVES pressure most likely will need replacement
XMITTER & Inline analytic elements must be removed from the line when
1 309 TRUE FALSE
VALVES doing a line flush.
XMITTER &
2 311 Australian Standards are often copies of ISO Standards. TRUE FALSE
VALVES
XMITTER &
2 313 How many instrumentation related Standards are there? <50 50 to 100 >100
VALVES
Company Policy,
Organisation Code, Company
XMITTER & In Australia, select the correct order of power with the highest Code,
2 316 Standard, Company Policy, Organisation
VALVES first and the lowest last from a company view point. Organisation
Policy, Code Standard
Standard
XMITTER & Regulations typically contain the actual rules that must be
2 317 TRUE FALSE
VALVES followed.
XMITTER &
2 319 Australian Standards are often copies of American Standards. TRUE FALSE
VALVES
XMITTER &
2 320 You can download a copy of an Australia Standard for free? TRUE FALSE
VALVES
XMITTER & In Australia, select the correct order of power with the highest Regulation, Code, Standard, Regulation, Regulation,
2 321
VALVES first and the lowest last from a legal view point. Standard Code Standard, Code
XMITTER &
3 322 It is OK to swap a 6mm and a 1/4" tube fittings. TRUE FALSE
VALVES
XMITTER &
3 323 Cl 1, Div 1, Gr B, C, D is an example of Australian IEC American
VALVES
XMITTER &
3 325 Instrumentation cable does not have to be twisted. TRUE FALSE
VALVES
XMITTER &
3 326 NEMA rating for enclosure protection is which standard? IEC Australian American
VALVES
XMITTER & What criteria is used to determine hazardous area hazardous flammable probability, type,
3 327
VALVES classification? material concentrations temperature
XMITTER &
3 329 The drain wire should be cut and taped at the instrument junction box rack room
VALVES
XMITTER &
3 330 What is the best method to shown area ratings? a list signs drawing
VALVES
XMITTER &
3 331 AUS Ex 1234XEx d IIC T6 (Ta=60C) IP66 is an example of Australian IEC American
VALVES
XMITTER & During a flushing, there could be pipe slag, welding rods, dirt,
3 332 TRUE FALSE
VALVES and pop cans flowing in a pipeline.
XMITTER &
3 334 Australian pipe ID is different then American pipe ID. TRUE FALSE
VALVES
XMITTER & The most common reason for erratic signal in the construction defective
3 335 no power loose wiring
VALVES phase is instrument
Degrees of Protection
XMITTER & Intellectual
3 336 The IP Code represents? Ingress Protection Provided By
VALVES Property
Enclosures
Degrees of Protection
XMITTER & Intellectual
3 337 The IP means? Ingress Protection Provided By
VALVES Property
Enclosures
XMITTER &
3 338 Instrument air is commonly 500 kPa or 60 psig 700 kPa or 80 psig 1000 kPa or 100 psig
VALVES
XMITTER &
3 340 The most instrument testing occurs during which phase Start-up Commissioning Precommissioning
VALVES
XMITTER &
3 342 IEC hazardous area protection type which is more common? Ex o Ex d Ex m
VALVES
XMITTER &
3 343 Intrinsic safety systems are commonly used with motors. TRUE FALSE
VALVES
XMITTER &
3 345 A common instrument enclosure rating is IP66 or NEMA 4X. TRUE FALSE
VALVES
XMITTER &
3 347 Intrinsic safety cable will have what colour of sheath? blue red yellow
VALVES
XMITTER &
3 349 DN means diameter normal diameter nominal nominal size
VALVES
XMITTER &
3 351 You can convert from IP to NEMA. TRUE FALSE
VALVES
XMITTER &
3 354 PN means pressure normal pressure nominal nominal pressure
VALVES
XMITTER &
3 355 You can convert from NEMA to IP. TRUE FALSE
VALVES
XMITTER & During normal operation, the valve should be in the open
4 356 ATO FO NO
VALVES position.
XMITTER & On a large line, a bypass control valve may be used for fine
4 357 TRUE FALSE
VALVES control.
XMITTER & What is the difference between a manual valve and a control
4 358 limit switches actuator travel stops
VALVES valve?
XMITTER &
4 360 Which valve is rotary? globe needle ball
VALVES
XMITTER &
4 361 Gate valves make good control valves. TRUE FALSE
VALVES
XMITTER & What type of actuator cannot normally take full instrument air
4 362 piston double acting diaphragm
VALVES pressure?
XMITTER &
4 363 Check valves make good control valves. TRUE FALSE
VALVES
XMITTER & When air pressure drops below required minimum, the valve
4 365 ATC FC NC
VALVES is automatically closed usually by a spring.
XMITTER & A control valve needs tight shut off, able to throttle flow, and
4 366 TRUE FALSE
VALVES actuation.
XMITTER &
4 367 What type of actuator typically uses a 4-way solenoid valve? piston electric diaphragm
VALVES
XMITTER &
4 368 Air pressure is required to open the valve. ATO FO NO
VALVES
XMITTER &
4 370 Air pressure must be applied to close the valve. ATC FC NC
VALVES
XMITTER & For two small chemical injection control valves using ratio
4 371 equal percentage linear square root
VALVES control, which control valve characteristic would be better?
XMITTER &
4 372 Which valve is suitable for large flows? globe needle ball
VALVES
XMITTER & You can select the pressure drop you want across a control
4 375 TRUE FALSE
VALVES valve in an existing system.
XMITTER &
4 378 It cannot damage a piping system if control valves slam shut. TRUE FALSE
VALVES
XMITTER &
4 379 Which actuator has pressure applied to two ports? diaphragm double acting piston
VALVES
XMITTER &
4 380 Which valve is suitable for fine control on a small line? globe needle ball
VALVES
XMITTER & The location of a control valve will not affect the pressure drop
4 381 TRUE FALSE
VALVES but it will affect the DP allowed without cavitation.
XMITTER & Opening and closing a valves numerous times may dislodged
4 382 TRUE FALSE
VALVES gunk from a valve.
XMITTER & With a control valve assembly, what components require valve, actuator and
4 383 valve valve and actuator
VALVES sizing? quick release
XMITTER &
4 385 Which valve is not as similar as the other two? ball butterfly plug
VALVES
XMITTER &
4 386 Which one is not a common control valve characteristic? equal percentage linear square root
VALVES
XMITTER & When air pressure drops below required minimum, the valve
4 387 ATO FO NO
VALVES automatically opened usually by a spring.
XMITTER & When designing a new system, you can select a pump that
4 388 TRUE FALSE
VALVES would have a low pressure drop across the control valve.
XMITTER &
4 390 To reduce water hammer, it is best to open a control valve fast slowly does not matter
VALVES
XMITTER &
4 392 What type of actuator typically uses a 3-way solenoid valve? piston double acting diaphragm
VALVES
XMITTER &
4 393 Diaphragm valves are very common in industrial plants. TRUE FALSE
VALVES
XMITTER & Extra care must be taken when disassembling spring return
4 395 TRUE FALSE
VALVES actuators to prevent injury.
XMITTER & The control valve does not determine the pressure drop; the
4 396 TRUE FALSE
VALVES control valve will absorb the excess pressure in the system.
XMITTER &
4 397 Which actuator is more common? electric pneumatic hydraulic
VALVES
XMITTER &
4 398 Which valve is suitable and cost more on a DN 200 line? globe needle ball
VALVES
XMITTER &
4 399 A pneumatic signal travels at the speed of light sound wave
VALVES
XMITTER & If a pneumatic signal tubing run is longer than the maximum
4 400 use larger tubing volume booster P/I
VALVES recommended length, what should be used?
XMITTER & During normal operation, the valve should be in the closed
4 401 ATC FC NC
VALVES position.
XMITTER &
5 402 Turbulent flow has a Re of < 2000 >2000 and < 4000 > 4000
VALVES
XMITTER &
5 404 All magmeters should have a grounding strap. TRUE FALSE
VALVES
XMITTER &
5 405 Which one is not a valid velocity equation? v=q/A v = w / (A p) v= w/Ap
VALVES
XMITTER &
5 406 A orifice plate with a high beta has a ??? bore size. small average large
VALVES
XMITTER & A orifice plate with a low beta has a ??? permanent pressure
5 407 low average high
VALVES drop.
XMITTER & Viscosity is a measurement of the resistance of a fluid to flow external force is
5 408 steady state flow up conditions
VALVES when applied
XMITTER &
5 409 A wet leg is used for liquids. TRUE FALSE
VALVES
XMITTER &
5 410 Laminar flow has a Re of < 2000 >2000 and < 4000 > 4000
VALVES
XMITTER & For a liquid DP flow, the transmitter should be installed ???
5 411 below same height above
VALVES the line.
XMITTER &
5 412 It is always OK to install a flow element on a vertical pipe. TRUE FALSE
VALVES
XMITTER &
5 413 Magmeters are good for measuring non-conducting fluids. TRUE FALSE
VALVES
XMITTER &
5 414 High velocity does not increase risk of erosion. TRUE FALSE
VALVES
XMITTER &
5 415 Magmeters are good for measuring liquid gas steam
VALVES
XMITTER & For a steam DP flow, the transmitter should be installed ???
5 416 below same height above
VALVES the line.
XMITTER & A orifice plate with a high beta has a ??? permanent
5 417 low average high
VALVES pressure drop.
XMITTER & For a gas, the kinematic viscosity will ??? with higher
5 419 decrease same increase
VALVES temperature.
XMITTER &
5 420 Kinematic viscosity is the ratio of dynamic viscosity to density. TRUE FALSE
VALVES
XMITTER & As a general rule of thumb for every 250mm of impulse line
5 421 15 C 35 C 55C
VALVES tubing, the process temperature will drop approximately
XMITTER &
5 423 A restriction in a pipe line will cause the velocity to decrease same increase
VALVES
XMITTER & Which one can differential pressure not be used to make a
5 425 flow level viscosity
VALVES measurement?
XMITTER & For a liquid, the kinematic viscosity will ??? with higher
5 426 decrease same increase
VALVES temperature.
XMITTER & Any beta between 0.2 and 0.75 can be used for any line size
5 427 TRUE FALSE
VALVES of orifice plate and still have good readings.
XMITTER &
5 428 Absolute viscosity is the ratio of dynamic viscosity to density. TRUE FALSE
VALVES
XMITTER & If you don't have the required straight run for a flow
5 430 TRUE FALSE
VALVES transmitter, the output may not represent the actual flow.
XMITTER & For a gas DP flow, the transmitter should be installed ??? the
5 431 below same height above
VALVES line.
XMITTER &
5 432 High viscosity liquids offer a low resistance to flow. TRUE FALSE
VALVES
XMITTER & The downstream side of the orifice plate will have the sharp
5 433 TRUE FALSE
VALVES edge.
XMITTER &
5 434 A restriction in a pipe line will cause the pressure to decrease same increase
VALVES
XMITTER & A 3 valve manifold with the equalizing valve is used to prevent
5 435 TRUE FALSE
VALVES over pressuring the DP cell.
XMITTER & Orifice plates are old school and not used any more in a new
5 436 TRUE FALSE
VALVES modern plant.
XMITTER &
5 437 Molasses viscosity is low average high
VALVES
XMITTER & If you don't have the required straight run for a flow
5 438 TRUE FALSE
VALVES transmitter, there will not be an output from the transmitter.
XMITTER &
5 439 Transient flow has a Re of < 2000 >2000 and < 4000 > 4000
VALVES
XMITTER & A blind list will help to ensure the plant is operational for start-
5 440 TRUE FALSE
VALVES up.
XMITTER &
5 441 A wet leg is used for gases that will condensate. TRUE FALSE
VALVES
XMITTER & For a steam DP flow in mass units what measurements are flow, temp, press,
5 442 flow, temp, press flow density
VALVES required? density
XMITTER &
5 444 Velocity is used to size a magmeter. TRUE FALSE
VALVES
XMITTER & For a steam DP flow, the transmitter output will be in mass
5 445 TRUE FALSE
VALVES units.
XMITTER & A 3 valve manifold with the equalizing valve open should have
5 446 0 0.5 1
VALVES a DP transmitter output of
XMITTER &
5 448 Gas viscosity compared to water is lower same higher
VALVES
XMITTER & Velocity is the rate at which a mass moves in a given time
5 449 TRUE FALSE
VALVES interval.
XMITTER &
5 453 With large head losses, it cost less to operate a plant. TRUE FALSE
VALVES
CONTROL & Employees must take reasonable care of the health and
1 455 TRUE FALSE
SIGNAL safety of themselves and others.
CONTROL &
1 456 A hazard is any situation that has harmed may harm will harm
SIGNAL
CONTROL &
1 457 The primary focus of a Major Hazard Facilities is safety of people safety of community safety of property
SIGNAL
CONTROL &
1 458 SOP can be used to obtain an expected range of results. TRUE FALSE
SIGNAL
CONTROL &
1 460 A ice bath is used for temperature measurement calibration cooling
SIGNAL
CONTROL &
1 461 External factors can cause error in the measurement. TRUE FALSE
SIGNAL
CONTROL &
1 462 Before taking corrective actions, validate the measurement. TRUE FALSE
SIGNAL
CONTROL &
4 463 It would have been easy to prevent the Bhopal India disaster? TRUE FALSE
SIGNAL
CONTROL & A instrument technician may manually override an interlock if depends on company
4 465 TRUE FALSE
SIGNAL they let someone know. policy
CONTROL & In the Bhopal India disaster, Union Carbide stated in court
4 466 TRUE FALSE
SIGNAL they had a safe system.
engineering,
CONTROL &
4 467 A hazop will be attended by? engineering maintenance maintenance, and
SIGNAL
operations
CONTROL &
4 469 Cause and Effect Chart may be created by a Hazop. TRUE FALSE
SIGNAL
CONTROL &
4 470 In the Piper Alpha disaster, only one person was responsible. TRUE FALSE
SIGNAL
CONTROL &
4 474 A Hazop may review a Cause and Effect Chart. TRUE FALSE
SIGNAL
CONTROL &
4 475 What is used to link the primary components DCE FIU BUS
SIGNAL
CONTROL &
4 476 A trend is equivalent to a recorder. TRUE FALSE
SIGNAL
CONTROL &
4 477 Alarm priorities are usually colour coded. TRUE FALSE
SIGNAL
CONTROL &
4 478 A typical faceplate is a controller. TRUE FALSE
SIGNAL
CONTROL &
4 479 The parameters are stored in the OIU DCE FIU
SIGNAL
CONTROL & Gas detectors for a F&G are usually connected to the control
4 480 TRUE FALSE
SIGNAL system for alarming and ESD.
CONTROL & A new DCS, PLC, or SCADA system are completely different
4 481 TRUE FALSE
SIGNAL in operation.
CONTROL & Historically, which type of system was designed for analogue
4 482 DCS PLC SCADA
SIGNAL loops?
CONTROL &
4 483 Historically, which type of system was designed to store data? DCS PLC SCADA
SIGNAL
CONTROL & An alarm that is programmable for trip point is typically from
4 484 analogue digital station
SIGNAL what type of source.
CONTROL &
4 486 A plant could have many remote terminal units. TRUE FALSE
SIGNAL
CONTROL &
4 487 Trends are typically shown on a layer called primary secondary tertiary
SIGNAL
recorders,
CONTROL & monitor, keyboard, monitor, recorders,
4 488 The operator interface unit typically has controllers,
SIGNAL mouse controllers
indicators
CONTROL &
4 489 An alarm that is field set is typically from what type of source. analogue digital station
SIGNAL
CONTROL & A new DCS, PLC, or SCADA system basically do the same
4 490 TRUE FALSE
SIGNAL thing now.
CONTROL &
4 491 All instruments must be connected to the primary I/O unit. TRUE FALSE
SIGNAL
CONTROL &
4 493 All process variables will have trends. TRUE FALSE
SIGNAL
CONTROL &
4 495 An alarm is usually just shown on the monitor. TRUE FALSE
SIGNAL
CONTROL &
4 496 Deviation from setpoint is typically shown as a numerical value deviation bar chart
SIGNAL
CONTROL &
4 497 The I/O is connected to the OIU DCE FIU
SIGNAL
CONTROL & A 20 year old DCS, PLC, or SCADA system basically do the
4 498 TRUE FALSE
SIGNAL same thing.
CONTROL &
4 499 The operator uses the OIU DCE FIU
SIGNAL
CONTROL &
4 500 The engineer uses the OIU EIU FIU
SIGNAL
CONTROL &
4 501 A central system that monitors and controls is called a control system PLC SCADA
SIGNAL
CONTROL & What is a generic term for a control system not equipment
4 503 DCS PLC PCS
SIGNAL specific.
CONTROL &
4 505 Most control systems have redundancy. TRUE FALSE
SIGNAL
CONTROL &
4 506 The operator keyboard may have specially designated keys. TRUE FALSE
SIGNAL
CONTROL & A 20 year old DCS, PLC, or SCADA system are completely
4 507 TRUE FALSE
SIGNAL different in operation.
CONTROL &
4 508 A typical faceplate is a recorder. TRUE FALSE
SIGNAL
CONTROL &
4 509 There typically a hierarchical structure for displays TRUE FALSE
SIGNAL
CONTROL &
4 510 Data compression is used in the OIU EIU BUS
SIGNAL
CONTROL &
4 511 Which layer only shows major process lines? primary secondary tertiary
SIGNAL
CONTROL &
4 512 The 'computer brains' is the OIU DCE FIU
SIGNAL
CONTROL &
4 513 Tuning values are called popus parameters objects
SIGNAL
CONTROL &
4 514 A values stored as value-timestamp are a hard soft point
SIGNAL
CONTROL &
4 515 A control key allows interaction with faceplate. TRUE FALSE
SIGNAL
CONTROL &
4 516 A computation done is a control system is called hard soft point
SIGNAL
CONTROL &
4 519 Most control loop tuning is done manually. TRUE FALSE
SIGNAL
CONTROL &
4 520 Most pumps have digital controllers. TRUE FALSE
SIGNAL
CONTROL & It is easy to mess-up a control loop tuning if you have access
4 521 TRUE FALSE
SIGNAL to the tuning parameters.
CONTROL & Most control loop tuning is originally set at typical values for
4 522 TRUE FALSE
SIGNAL the type of loop..
CONTROL &
4 523 Parameters measure the process. TRUE FALSE
SIGNAL
CONTROL &
4 525 Most pumps have analogue controllers. TRUE FALSE
SIGNAL
CONTROL &
4 526 Most variable speed pumps have digital controllers. TRUE FALSE
SIGNAL
CONTROL &
4 527 Parameters are constants. TRUE FALSE
SIGNAL
CONTROL &
4 528 Most control loops are cascade. TRUE FALSE
SIGNAL
CONTROL &
4 530 The process variables measure the process. TRUE FALSE
SIGNAL
CONTROL & When fault finding, you need to determine if the problem is in
4 533 TRUE FALSE
SIGNAL the instrument or the process.
CONTROL & Common plant problems are usually traced to only one
4 534 TRUE FALSE
SIGNAL common source.
CONTROL & A operator coming on shift reports erratic control of loop. The
4 535 TRUE FALSE
SIGNAL problem maybe instrument, tuning, or process.
CONTROL & When fault finding, the smart transmitters will always display
4 536 TRUE FALSE
SIGNAL what is wrong.
CONTROL & When fault finding, always assume it is a problem with the
4 537 TRUE FALSE
SIGNAL instrument.
CONTROL & check, analyse, plan, analyse, act, analyse, plan, act,
4 538 When fault finding, what is the best order
SIGNAL plan, act, check check
# 8 In Australia, all industrial plants use only metric units. False, there is no defined rules for all industrial plants.
# 9 National Pipe Thread (NPT) and British Standard Pipe (BSP) are the same thing. FALSE
# 10 An American company has built an industrial plant in a remote location of the world. What most likely are the units for pressure measurement? imperial
# 12 The formula for interpolation is Y??? = ylower + ((xwant - xlower) / (xupper - xlower )) (yupper - ylower)
# 13 For a 4-20 mA loop, output is calculated by Outputunknown = 4 + ((MVwant - MVlower) / (Span)) (16)
# 14 Interpolation is used to construct a new data point between known data points
# 17 Standard Temperature and Pressure reference does not change and is always the same for every industry. FALSE
# 27 Mercury is used to measure vacuum because the SG is much higher than water
# 28 There is a gas release at work. The deadly gas has a SG = 2. It is the same distance to escape. Should I go out via the roof exit
# 29 The ISA International Standard Atmosphere is defined to 101.325 kPa, 15 C and 0% humidity
# 36 Absolute pressure is zero referenced against a perfect vacuum, so it is equal to gauge pressure plus atmospheric pressure
# 40 There are three containers with different shapes but the same height. the pressure will be the same
# 43 An irregular shaped object will have the same surface pressure regardless of its orientation. FALSE
# 45 A hydraulic lift operation where the two pistons are connected together. The forces are equal to the ratio of the areas of the pistons
# 47 When a solid is pushing on a liquid or gas, the fluid must be confined in a container. TRUE
# 48 If there are two tanks with the same height and fluid, but one tank has twice the volume the pressure will be the same but the weight will be different
# 52 A change in temperature of a fluid normally does not effect the density of the fluid. FALSE
# 53 Temperature is a measurement of how fast the atoms and molecules of a substance are moving. TRUE
# 54 For identical fluids at same temperature, what has to increase to get more heat mass
# 61 The control system graphics display is usually laid out to represent the P&ID
# 64 Maintaining the instrument records and drawings is the responsibility of which department maintenance and engineering
# 66 Why is it important for an instrument technician to understand how to interpretation of drawings, specifications and manuals? perform your job efficiently and
correctly
# 67 A control valve always has a 'C' for the middle letter. FALSE
# 70 What organisation established the use of circles to represent a field transmitter on a P&ID? ISA
# 76 Each instrument tag number is unique and the coding represents service, type, rating, and size. FALSE
# 80 The loop number in an instrument bubble is located in the bottom half. TRUE
# 84 The instrument must be rated greater than the design pressure. TRUE
# 85 The instrument data sheet must show the full tag number including the area. TRUE
# 86 If you have the manufacturer and model number, it is always easy to find details on instrument. FALSE
# 87 The instrument data sheets will be made by the person/organisation responsible for the new installation. TRUE
# 88 The data sheet can have one or more instruments per sheet. TRUE
# 90 The instrument data sheet does not have to state the line number or equipment number. FALSE
# 97 On a loop diagram, it is OK to just show +/- rather then terminal numbers. FALSE
# 98 A plant will always have only one system for instrument records. FALSE
# 99 The manufacturer maintenance manuals are important to do your job correctly. TRUE
# 101 On a loop diagram, the junction box terminations are located in the middle
# 102 The rack drawing will show cables in and out of the rack. FALSE
# 103 As an instrument technician, it is your job to fix the instrument not to waste time on paper work. FALSE
# 104 On a loop diagram, the control system are located on the right
# 105 A master database instrument records system would simplify updating changes to an instrument. TRUE
# 107 On a loop diagram, the field instrument/s are located on the left
# 109 The instrument junction box drawing will show cables in and out of the box. TRUE
# 110 It is the responsibility of the manufacturer to retain old instruction manuals. FALSE
# 113 If I have to make an instrument list of tag numbers, it does not matter if I use a '-' or not. FALSE
# 114 The instrument junction box drawing will show spare terminals. TRUE
# 117 A P&ID may have different symbols for type of actuators. TRUE
# 120 Each pipeline number is unique and the coding represents service, type, rating, and size. TRUE
# 121 Each equipment number is unique and the coding represents service, type, rating, and size. FALSE
# 122 Instruments are small and do not have much impact on the running of the plant. FALSE
# 123 Most instruments connected to a process line or equipment have an isolation valve. TRUE
# 124 Prior to disconnecting an instrument signal line/wiring, the instrument technician should tell the operator
# 125 If an instrument is not directly connected to a process line, you most likely don't need a work permit. FALSE
# 126 Modern instruments are reliable so there is no need to have duplicated instruments for a safety system anymore. FALSE
# 127 If a transmitter is remote mounted, it is OK to just close the isolation valve and remove from service. FALSE
# 128 Which trade usually has a close relationship with the operators? instrument
# 130 During a scheduled plant shutdown, there will most likely be different Work Permit requirements then if the plant is operating. TRUE
# 132 If there is a special instructions tag on an instrument, it means do not operate. FALSE
# 134 It is OK if I don't close off my Work Permit if I plan on finishing the job tomorrow. FALSE
# 135 I'm a contractor; the plant work permit system does not apply to me. FALSE
# 139 Zero suppression is when a pressure transmitter is mounted below the high side process connection
# 140 When selecting an instrument range, the calibrated range may not exceed either the LRL or the URL. TRUE
# 141 Range is only in reference to the instrument specifications and not the calibration. FALSE
# 142 Zero elevation is when a pressure transmitter is mounted above the high side process connection
# 144 The National Measurement Institute sets standards on how to measure. FALSE
# 145 It is OK to have a calibrated span less than the minimum instrument span. FALSE
# 146 The instrument upper range limit can always be found in product data sheet
# 147 If the tank level was actually 45%, and the transmitter output was 45%. This is accuracy
# 149 A transmitter with no accuracy or repeatability can be calibrated to correct both. FALSE
# 154 You can calibrate an instrument to a greater accuracy then the test equipment. FALSE
# 157 As long as my calibrated span is less than the instrument minimum span, it is OK. FALSE
# 158 If you have remote seal, then there maybe zero suppression or elevation. TRUE
# 159 In relationship to calibrated range, it is best to select an instrument range that is near the URL
# 160 With a corrosive fluid, the same material should be used for the diaphragm and the body. FALSE
# 161 Every Rosemount 3051S transmitter has 4-20 mA, HART, and fieldbus and I select in calibration which one is used. FALSE
# 162 The good fill fluid for high vacuum and high temperature applications is DC705 Silicone
# 164 A Rosemount 3051S transmitter with isolating diaphragm code 2 is 316L SST
# 165 All instrument errors are stated in a product data sheet specifications. TRUE
# 167 Any material in contact with the process fluid must be compatible with that fluid. TRUE
# 168 By selecting the correct range of transmitter, I can improve measurement accuracy. TRUE
# 172 The instrument parts in contract with process fluid are called wetted part
# 173 The best selection for range is near the upper range limit
# 174 A high velocity flow through the small bore of an orifice plate may cause what type of corrosion erosion
# 175 What material is best for a pressure transmitter at a sour oilfield drilling rig as per NACE MR0175-2003 Hastelloy C
# 177 A diaphragm rated poor resistance to the process fluid in a Material Selection most likely will have what type of corrosion pitting
# 178 Silicon can cause an explosion if in contact with some process fluids. TRUE
# 179 A process depends on a reliable hydrogen peroxide supply. Which combination is best Flange 316 SST Diaphragm Hastelloy C
# 180 The line pressure effect span error can be calibrated out of some instruments. FALSE
# 182 Modern transmitters are programmable with large turndown ration. There is no need anymore to worry about range selection. FALSE
# 183 The line pressure effect zero error can be calibrated out of some instruments. TRUE
# 184 Two dissimilar metals in contact with a conductive fluid can cause what type of corrosion galvanic
# 185 The reason the calibrated LRL is negative could be because of vacuum or remote seals
# 186 My calibrated range is -400 to 225 "H2O which Rosemount 3051S2C transmitter measurement type code is best D
# 187 My calibrated range is -100 to 225 "H2O which Rosemount 3051S2CD transmitter range code is best 2A
# 190 316 SST and 316L SST are all the same thing just written differently. FALSE
# 192 On a water line, an inline instrument with a different material then the pipe may have what type of corrosion galvanic
# 193 Most data sheets will have just one type of instrument error specified. FALSE
# 194 Every material in a transmitter must be must be compatible with the process fluid. FALSE
# 195 The good fill fluid for cryogenic applications is Syltherm XLT Silicone
# 196 Which Rosemount 3051S transmitter has a high side flange rated for Class 150 3051S2L
# 197 The position the transmitter is mounted in can effect calibration. TRUE
# 199 Which diaphragm material is best for liquid natural gas 316 SST
# 200 Which instrument output has a digital signal on an analogue signal HART
# 202 What type of power supply might an instrument technician not be qualified to modify mains
# 204 The reason 4-20 mA is used is because a value of 3 mA means measuring below calibrated range or instrument fault
# 205 What type of cable is typically used in instrumentation twisted shielded pair
# 206 In most cases, just using a communicator is sufficient for confirming the calibration of a HART pressure transmitter. TRUE
# 208 A communicator or handheld terminal is always required to interface with field instruments. FALSE
# 209 With a Rosemount 375 communicator, you can overcharge the battery pack. FALSE
# 210 With a Rosemount 375 communicator set to event capture all warnings will still work. FALSE
# 211 A communicator or handheld terminal is required to interface with fieldbus instruments. TRUE
# 212 With a Rosemount 375 communicator on a fieldbus segment, you can overload the power supply and lose communication. TRUE
# 213 A communicator or handheld terminal is required to interface with HART instruments. TRUE
# 214 Every plant should have some system of documenting when an instrument was calibrated, by whom, and to what parameters. TRUE
# 216 The paper work is just as important as the actual calibration. TRUE
# 217 The calibration may be done at factory, bench, field, or by a 3rd party. TRUE
# 218 A good instrument technician will use the manufacturer's manual for configuration code confirmation. TRUE
# 219 With the Rosemount 3051S, when doing sensor trim it is OK to use a pressure source with accuracy equal to the transmitter accuracy. FALSE
# 220 A good instrument technician does not need to look at the manufacturer's manual. FALSE
# 221 A good instrument technician can calibrate a smart transmitter with just a screw driver and control over the process. FALSE
# 222 It is OK to adjust the zero trim on a Rosemount 3051S absolute transmitter. FALSE
# 223 If a new or replacement transmitter is installed in the field, then you should check with operations to confirm the control system is displaying the correct value.
TRUE
# 224 A Rosemount 3051S transmitter with a flow turndown > 10:1 on a flow application the square root extraction should be done in the control system
# 226 A Rosemount 3051S transmitter with HART will allow a upper range value greater than the sensor limit. FALSE
# 228 A Rosemount 3051S transmitter can readjust the 4-20 mA points without applying pressure to the transmitter. TRUE
# 229 The Rosemount 3051S manual recommends using a pressure source three times more accurate than the transmitter. TRUE
# 230 If the instrument technician is not provided with the calibration range, they cannot calibrate the instrument. FALSE
# 231 The control systems range displayed will always provide the range for calibrating the field instrument. FALSE
# 232 I'm only responsible to look at a new installation do see if it makes sense. FALSE
# 233 The piping designer will always provide the correct process connection required by instrumentation. FALSE
# 234 It is safe to always trust the instruments and information issued by an engineering firm. FALSE
# 235 A hazop is a multidiscipline meeting that evaluates the process control and safety system of a plant or new design. TRUE
# 236 I'm not responsible to look at an existing installation to see if it makes sense. FALSE
# 237 A hazop meeting will have management from each department. FALSE
# 238 A mistake will be found before a plant starts full operation. FALSE
# 239 A root cause analysis meeting will have the management from each department. FALSE
# 241 Piping designers are required to design as per the plant piping specifications. TRUE
# 242 Engineering and construction companies do make mistakes but there is a process to find them all. FALSE
# 243 A root cause analysis will have people who know the facts of the problem. TRUE
# 245 My communicator will tell me what is wrong. I just need to know how to use it. FALSE
# 249 I should be able to find good information in the manufacturer's maintenance manual to help find the fault. TRUE
# 250 It is best to ask a few questions to eliminate some types of faults and then focus on remaining possible faults. TRUE
# 251 You should only use the look and tug method as a last resort to find the fault. FALSE
# 252 I should use the same fault finding approach for any fault. FALSE
# 253 Asking questions is the good way to find the fault. TRUE
# 254 If a solution does not allow the plant to run, a better solution is required. TRUE
# 255 I should use different fault finding methods depending on if fault is continuous or intermittent. TRUE
# 257 A fault might be caused by the wrong instrument selected for application. TRUE
# 260 Asking questions only tells me where the fault is. FALSE
# 262 The most powerful tool in your toolbox should be your brain
# 264 If the DP level transmitter is mounted above the centreline of the pump, you still measure level at pump C-L? FALSE
# 265 When reading a water type manometer, read the meniscus at the bottom
# 267 Pressurized tank level measurement by DP needs how many tank connections? 2
# 269 Most analytic instruments compare the process sensor to a reference. TRUE
# 272 A simple local control sump pump system for level most likely has a float
# 274 A linear measurement calibrated range is 0-1000. For a MV of 750. A 4-20mA transmitter output would be 16 mA
# 275 A tank is 10 metres high and the SG=1. What is the calibration range? 98 kPA
# 276 The most common industrial temperature sensor for 1000 C would be TC
# 281 If the process fluid density changes, a DP level transmitter will need recalibration. TRUE
# 284 When is it a good choice to use radar or ultra sonic over DP for level? fluid density changes or corrosive
# 288 With a bare metal thermocouple it is easy to figure out what type it is. FALSE
# 289 What is the better choice for level measurement of a settling pond? ultrasonic
# 290 Open tank level measurement by DP needs how many tank connections? 1
# 291 A instrument over pressured by 25% of maximum design pressure may be damaged and need replacement
# 292 A tank is 100 inches high and the SG=1. What is the calibration range? 0-100 "H2O
# 293 Pressurized tank level measurement by DP the top of tank connection should be to the instrument low port
# 294 A bimetal strip is most likely used for temperature measurement in a gauge
# 295 A linear measurement calibrated range is 500-1000. For a MV of 750. A 4-20mA transmitter output would be 12 mA
# 297 A linear measurement calibrated range is 0-1000. The instrument has a accuracy of 1% of calibrated span. What is the +- error of calibrated span? 10
# 299 A pneumatic local temperature controller most likely has a filled system
# 300 The most common industrial temperature sensor for 100 C would be RTD
# 302 What is a good tank position for 100% level? 100mm below bottom of overflow
# 303 Bimetal strip is not used any more for temperature measurement. FALSE
# 304 A instrument over pressured by 5% of maximum design pressure most likely will be OK
# 305 If DP level transmitter is mounted below the centreline of the pump, you still measure level at pump C-L? TRUE
# 306 A instrument over pressured by 200% of maximum design pressure most likely will leak or explode
# 307 A linear measurement calibrated range is 500-1000. The instrument has a accuracy of 1% of calibrated span. What is the +- error of calibrated span. What is the +-
error? 5
# 308 A thermocouple is connected to the transmitter with TC extension wire same type as TC
# 309 Inline analytic elements must be removed from the line when doing a line flush. TRUE
# 310 If the process fluid temperature sufficiently changes, a DP level transmitter will need recalibration. TRUE
# 312 A violation of a Act or Regulation can be punishable by fine, imprisonment, warning, order to cease
# 314 Government of Western Australia has approximately how many regulations that impact employees? >100
# 315 It is very difficult and expensive to get a copy of Australian Regulations and Act? FALSE
# 316 In Australia, select the correct order of power with the highest first and the lowest last from a company view point. Company Policy, Code, Organisation Standard
# 317 Regulations typically contain the actual rules that must be followed. TRUE
# 318 In Australia, it is common to face criminal charges in a court of law for violating a code? FALSE
# 320 You can download a copy of an Australia Standard for free? FALSE
# 321 In Australia, select the correct order of power with the highest first and the lowest last from a legal view point. Regulation, Standard, Code
# 324 Which ASME and PN flanges are the same? PN 20 and ASME 150
# 327 What criteria is used to determine hazardous area classification? probability, type, temperature
# 329 The drain wire should be cut and taped at the instrument
# 332 During a flushing, there could be pipe slag, welding rods, dirt, and pop cans flowing in a pipeline. TRUE
# 335 The most common reason for erratic signal in the construction phase is loose wiring
# 340 The most instrument testing occurs during which phase Precommissioning
# 341 During a flush, which type of control valve is typically removed? globe
# 343 Intrinsic safety systems are commonly used with motors. FALSE
# 346 The purpose of the twisted pair is to reject noise and interference
# 347 Intrinsic safety cable will have what colour of sheath? blue
# 356 During normal operation, the valve should be in the open position. NO
# 358 What is the difference between a manual valve and a control valve? actuator
# 359 Valve packing can usually be tightened to stop packing leakage. TRUE
# 362 What type of actuator cannot normally take full instrument air pressure? diaphragm
# 364 It is OK to stick your hand in a control valve to determine if open or closed. FALSE
# 365 When air pressure drops below required minimum, the valve is automatically closed usually by a spring. FC
# 366 A control valve needs tight shut off, able to throttle flow, and actuation. TRUE
# 367 What type of actuator typically uses a 4-way solenoid valve? piston
# 369 In the event of a plant failure, the control valve is required to fail in the position prior to the failure. This includes any failures from plant air, electrical, or control
system. Fail last can be tricky, depending on the type of valve assembly. FL
# 371 For two small chemical injection control valves using ratio control, which control valve characteristic would be better? linear
# 373 Which valve are usually the same for manual or control? ball, butterfly, rotary plug
# 374 To reduce spare parts, when selecting a replacement control valve you should consider piping spec, preferred vendors, similar application
# 376 When air pressure drops below required minimum the valve position will be unknown. There is no spring to force in any direction. If it is a butterfly valve depending
on position, the fluid flow may open or close the valve. If valve is a ball and already closed, then most likely will stay closed. FI
# 378 It cannot damage a piping system if control valves slam shut. FALSE
# 379 Which actuator has pressure applied to two ports? double acting
# 380 Which valve is suitable for fine control on a small line? needle
# 381 The location of a control valve will not affect the pressure drop but it will affect the DP allowed without cavitation. TRUE
# 382 Opening and closing a valves numerous times may dislodged gunk from a valve. TRUE
# 383 With a control valve assembly, what components require sizing? valve, actuator and quick release
# 384 What is the maximum recommended tubing length for a pneumatic control loop? 60 m
# 386 Which one is not a common control valve characteristic? square root
# 387 When air pressure drops below required minimum, the valve automatically opened usually by a spring. FO
# 388 When designing a new system, you can select a pump that would have a low pressure drop across the control valve. TRUE
# 391 What part of a control valve assembly could be pneumatic, electric motor, solenoid, or hydraulic actuated? actuator
# 392 What type of actuator typically uses a 3-way solenoid valve? diaphragm
# 394 It is easy to size a control valve just plug in values in a free sizing software and it will tell me which valve to buy and it will be the correct choice. FALSE
# 395 Extra care must be taken when disassembling spring return actuators to prevent injury. TRUE
# 396 The control valve does not determine the pressure drop; the control valve will absorb the excess pressure in the system. TRUE
# 398 Which valve is suitable and cost more on a DN 200 line? globe
# 400 If a pneumatic signal tubing run is longer than the maximum recommended length, what should be used? P/I
# 401 During normal operation, the valve should be in the closed position. NC
# 403 A head loss causes a reduction in the amount to pressure available to the system. TRUE
# 406 A orifice plate with a high beta has a ??? bore size. large
# 407 A orifice plate with a low beta has a ??? permanent pressure drop. high
# 408 Viscosity is a measurement of the resistance of a fluid to flow when external force is applied
# 411 For a liquid DP flow, the transmitter should be installed ??? the line. below
# 416 For a steam DP flow, the transmitter should be installed ??? the line. below
# 417 A orifice plate with a high beta has a ??? permanent pressure drop. low
# 418 A calibration DP flow range of 0-1000 and a linear transmitter output at 13 mA. What is the flow? 750
# 419 For a gas, the kinematic viscosity will ??? with higher temperature. increase
# 421 As a general rule of thumb for every 250mm of impulse line tubing, the process temperature will drop approximately 35 C
# 422 Reynolds Number is a dimensionless numerical value used to represent the characteristic of flow in a pipe. TRUE
# 424 A DP flow calibrated range is 0-1000. For a MV of 500. A linear 4-20mA transmitter output would be 8 mA
# 425 Which one can differential pressure not be used to make a measurement? viscosity
# 426 For a liquid, the kinematic viscosity will ??? with higher temperature. decrease
# 427 Any beta between 0.2 and 0.75 can be used for any line size of orifice plate and still have good readings. FALSE
# 430 If you don't have the required straight run for a flow transmitter, the output may not represent the actual flow. TRUE
# 433 The downstream side of the orifice plate will have the sharp edge. FALSE
# 435 A 3 valve manifold with the equalizing valve is used to prevent over pressuring the DP cell. TRUE
# 436 Orifice plates are old school and not used any more in a new modern plant. FALSE
# 438 If you don't have the required straight run for a flow transmitter, there will not be an output from the transmitter. FALSE
# 440 A blind list will help to ensure the plant is operational for start-up. TRUE
# 441 A wet leg is used for gases that will condensate. TRUE
# 442 For a steam DP flow in mass units what measurements are required? flow, temp, press
# 443 A DP flow calibrated range is 500-1000. For a MV of 933. A linear 4-20mA transmitter output would be 16 mA
# 445 For a steam DP flow, the transmitter output will be in mass units. FALSE
# 446 A 3 valve manifold with the equalizing valve open should have a DP transmitter output of 0
# 447 A restriction in a pipe line will not cause a permanent pressure dorp because of recovery factor. FALSE
# 449 Velocity is the rate at which a mass moves in a given time interval. TRUE
# 451 A calibration DP flow range of 0-1000 and a square root transmitter output at 13 mA. What is the flow? 562
# 452 For a DP transmitter, which manifold has vents/drains in the manifold? 5 valve
# 453 With large head losses, it cost less to operate a plant. FALSE
# 454 Hazard training is designed to recognise and assess a potential hazard. TRUE
# 455 Employees must take reasonable care of the health and safety of themselves and others. TRUE
# 459 Calibration is checking the readings of a measuring device against the readings of another measuring device with higher accuracy
# 463 It would have been easy to prevent the Bhopal India disaster? FALSE
# 464 A instrument technician may manually override an interlock, if authorized to do so and the correct company procedures have been followed. TRUE
# 465 A instrument technician may manually override an interlock if they let someone know. FALSE
# 466 In the Bhopal India disaster, Union Carbide stated in court they had a safe system. TRUE
# 468 A HAZOP is a process where the plant design is evaluated using the P&ID and asking a series of “what if” questions. TRUE
# 470 In the Piper Alpha disaster, only one person was responsible. FALSE
# 471 If an interlock is manually overridden and the plant is operating, the plant safety system will no longer functioning as designed. TRUE
# 472 A HAZOP is a process where the plant design is evaluated using the P&ID and asking a series of “why not” questions. FALSE
# 480 Gas detectors for a F&G are usually connected to the control system for alarming and ESD. TRUE
# 481 A new DCS, PLC, or SCADA system are completely different in operation. FALSE
# 482 Historically, which type of system was designed for analogue loops? DCS
# 483 Historically, which type of system was designed to store data? SCADA
# 484 An alarm that is programmable for trip point is typically from what type of source. analogue
# 485 The operator keyboard may be a standard keyboard like at home. TRUE
# 489 An alarm that is field set is typically from what type of source. digital
# 490 A new DCS, PLC, or SCADA system basically do the same thing now. TRUE
# 491 All instruments must be connected to the primary I/O unit. FALSE
# 492 An actual input or output connected to the control system is called hard
# 494 A switch that inhibits or enables access to tuning or engineering functions is typically called a key switch
# 498 A 20 year old DCS, PLC, or SCADA system basically do the same thing. FALSE
# 501 A central system that monitors and controls is called a control system
# 503 What is a generic term for a control system not equipment specific. PCS
# 504 Historically, which type of system is made to represent ladder logic? PLC
# 506 The operator keyboard may have specially designated keys. TRUE
# 517 A instrument tagged with ESD means it is part of Emergency Shutdown System
# 518 The primary components of a control system are OIU, DCE, FIU, BUS
# 521 It is easy to mess-up a control loop tuning if you have access to the tuning parameters. TRUE
# 522 Most control loop tuning is originally set at typical values for the type of loop.. TRUE
# 529 The process variables are controlled or indicated by the control system. TRUE
# 531 Most controllers are automatic and cannot be placed in manual. FALSE
# 533 When fault finding, you need to determine if the problem is in the instrument or the process. TRUE
# 534 Common plant problems are usually traced to only one common source. FALSE
# 535 A operator coming on shift reports erratic control of loop. The problem maybe instrument, tuning, or process. TRUE
# 536 When fault finding, the smart transmitters will always display what is wrong. FALSE
# 537 When fault finding, always assume it is a problem with the instrument. FALSE
# 538 When fault finding, what is the best order analyse, plan, act, check