OLEX - ZERO SEQUENCE IMPEDANCE

Single Core XLPE/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Stranding Earth size Zero Sequence


Zero Sequence Reactance
size Resistance Trefoil Flat
mm
2
No./mm mm2 Ω/km Ω/km
BDBP17AA001 25 19/1.35 6 10.9 0.100 0.116
BDBP18AA001 35 19/1.53 10 6.59 0.0952 0.110
BDBP19AA001 50 19/1.78 16 4.21 0.0932 0.108
BDBP20AA001 70 19/2.14 25 2.52 0.0899 0.105
BDBP22AA001 95 37/1.78 25 2.43 0.0867 0.102
BDBP23AA001 120 37/2.03 35 1.89 0.0845 0.0997
BDBP24AA001 150 37/2.25 50 1.41 0.0849 0.1001
BDBP25AA001 185 37/2.52 70 0.995 0.0839 0.0992
BDBP26AA001 240 61/2.25 95 0.741 0.0819 0.0972
BDBP27AA001 300 61/2.52 120 0.573 0.0810 0.0963
BDBP28AA001 400 61/2.85 120 0.557 0.0806 0.0958
BDBP30AA001 500 61/3.2 120 0.544 0.0792 0.0945
BDBP32AA001 630 127/2.52 120 0.534 0.0785 0.0937
NOTE: The assumption is that the fault is returning via the earth conductor

Single Core XLPE/PVC 0.6/1kV - Aluminium Conductors

Product Code Conductor Stranding Earth size Zero Sequence


Zero Sequence Reactance
size Resistance Trefoil Flat
mm2 No./mm mm2 Ω/km Ω/km
BDBA17AA001 25 19/1.35 6 11.5 0.100 0.116
BDBA18AA001 35 19/1.53 6 11.1 0.0952 0.110
BDBA19AA001 50 19/1.78 10 6.74 0.0932 0.108
BDBA20AA001 70 19/2.14 10 6.49 0.0899 0.105
BDBA22AA001 95 37/1.78 16 4.13 0.0867 0.102
BDBA23AA001 120 37/2.03 25 2.68 0.0845 0.0997
BDBA24AA001 150 37/2.25 25 2.62 0.0849 0.100
BDBA25AA001 185 37/2.52 35 1.91 0.0839 0.0992
BDBA26AA001 240 61/2.25 50 1.41 0.0819 0.0972
BDBA27AA001 300 61/2.52 70 0.998 0.0810 0.0963
BDBA28AA001 400 61/2.85 95 0.747 0.0806 0.0958
BDBA30AA001 500 61/3.2 95 0.725 0.0792 0.0945
BDBA32AA001 630 127/2.52 120 0.559 0.0785 0.0937
NOTE: The assumption is that the fault is returning via the earth conductor

2C+E PVC/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Size Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
Ω/km Ω/km Ω/km Ω/km Ω/km
2 2
mm mm
DNMP05AA002 1.5 1.5 28.5 49.1 0.223 0.111 0.0743
DNMP07AA002 2.5 2.5 17.6 26.7 0.208 0.103 0.0687
DNMP09AA002 4 2.5 12.1 23.3 0.194 0.103 0.0671
DNMP11AA002 6 2.5 9.93 21.5 0.186 0.0968 0.0637
DNMP13AA002 10 4 6.91 13.3 0.185 0.0909 0.0609
DNMP15AA002 16 6 5.02 8.77 0.182 0.0874 0.0590
DNMP17AA002 25 6 3.71 8.25 0.169 0.0825 0.0555
DNMP18AA002 35 10 2.79 5.02 0.167 0.0797 0.0540
DNMP19AA002 50 16 2.05 3.22 0.165 0.0798 0.0539
DNMP20AA002 70 25 1.41 1.94 0.156 0.0772 0.0516
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.
OLEX - ZERO SEQUENCE IMPEDANCE

3C+E PVC/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Size Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
Ω/km Ω/km Ω/km Ω/km Ω/km
2 2
mm mm
FNMP05AA003 1.5 1.5 33.4 65.4 0.201 0.119 0.0747
FNMP07AA003 2.5 2.5 18.9 35.6 0.201 0.110 0.0711
FNMP09AA003 4 2.5 14.7 32.2 0.190 0.110 0.0697
FNMP11AA003 6 2.5 12.5 30.3 0.181 0.104 0.0661
FNMP13AA003 10 4 8.92 18.8 0.177 0.0983 0.0632
FNMP15AA003 16 6 5.93 12.45 0.173 0.0948 0.0613
FNMP17AA003 25 6 4.92 11.94 0.161 0.0900 0.0577
FNMP18AA003 35 10 3.72 7.21 0.158 0.0872 0.0561
FNMP19AA003 50 16 2.74 4.60 0.154 0.0873 0.0557
FNMP20AA003 70 25 1.75 2.74 0.157 0.0846 0.0550
FNMP22AA003 95 25 1.60 2.66 0.149 0.0840 0.0537
FNMP23AA003 120 35 1.35 2.07 0.148 0.0818 0.0526
FNMP24AA003 150 50 0.974 1.54 0.150 0.0820 0.0531
FNMP25AA003 185 70 0.765 1.084 0.149 0.0819 0.0528
FNMP26AA003 240 95 0.597 0.807 0.148 0.0810 0.0523
FNMP27AA003 300 120 0.480 0.624 0.142 0.0807 0.0515
FNMP28AA003 400 120 0.433 0.608 0.144 0.0803 0.0515
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.

4C+E PVC/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Size Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
mm2 mm2 Ω/km Ω/km Ω/km Ω/km Ω/km
HNMP05AA004 1.5 1.5 33.4 65.4 0.158 0.119 0.0679
HNMP07AA004 2.5 2.5 18.9 35.6 0.144 0.110 0.0624
HNMP09AA004 4 2.5 14.7 32.2 0.136 0.110 0.0607
HNMP11AA004 6 2.5 12.5 30.3 0.129 0.104 0.0577
HNMP13AA004 10 4 8.92 18.8 0.119 0.0983 0.0538
HNMP15AA004 16 6 5.93 12.5 0.0987 0.0948 0.0483
HNMP17AA004 25 6 4.92 11.9 0.0963 0.0900 0.0465
HNMP18AA004 35 10 3.72 7.21 0.0911 0.0872 0.0445
HNMP19AA004 50 16 2.74 4.60 0.0901 0.0873 0.0443
HNMP20AA004 70 25 1.75 2.74 0.0841 0.0846 0.0422
HNMP22AA004 95 25 1.60 2.66 0.0852 0.0840 0.0423
HNMP23AA004 120 35 1.35 2.07 0.0820 0.0818 0.0410
HNMP24AA004 150 50 0.974 1.54 0.0802 0.0820 0.0405
HNMP25AA004 185 70 0.765 1.08 0.0799 0.0819 0.0405
HNMP26AA004 240 95 0.597 0.807 0.0779 0.0810 0.0397
HNMP27AA004 300 120 0.480 0.624 0.0873 0.0807 0.0420
HNMP28AA004 400 120 0.418 0.608 0.0853 0.0803 0.0413
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.
OLEX - ZERO SEQUENCE IMPEDANCE

3C+3E XLPE/PVC/DCT/PVC 0.6/1kV - Copper Conductors - VAROLEX

Product Code Conductor Earth Size Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Resistance(RE+RS) Resistance(RE) Screen Earth Screen//Earth
Ω/km Ω/km Ω/km Ω/km Ω/km
2 2
mm mm
FTDP07AA003 2.5 2.5 27.9 36.9 0.142 0.0993 0.0584
FTDP09AA003 4 1.5 17.2 22.7 0.122 0.0847 0.0501
FTDP11AA003 6 1.5 15.6 20.7 0.121 0.0782 0.0475
FTDP13AA003 10 1.5 14.3 19.1 0.115 0.0677 0.0427
FTDP15AA003 16 2.5 9.14 10.6 0.109 0.0667 0.0414
FTDC17AA003 25 4 5.82 6.62 0.1012 0.0613 0.0382
FTDC18AA003 35 6 4.14 4.47 0.0949 0.0591 0.0364
FTDC19AA003 50 10 2.60 2.76 0.0909 0.0595 0.0359
FTDC20AA003 70 10 2.42 2.60 0.0882 0.0549 0.0338
FTDC22AA003 95 16 1.59 1.67 0.0848 0.0518 0.0322
FTDP23AA003 120 16 1.51 1.62 0.0839 0.0490 0.0309
FTDP24AA003 150 25 1.02 1.06 0.0847 0.0507 0.0317
FTDP25AA003 185 25 0.990 1.03 0.0819 0.0487 0.0305
FTDP26AA003 240 35 0.728 0.745 0.0794 0.0473 0.0297
FTDP27AA003 300 50 0.595 0.605 0.0798 0.0474 0.0297
FTDP28AA003 400 50 0.580 0.589 0.0790 0.0447 0.0286
FTDP30AA003 500 50 0.567 0.575 0.0785 0.0428 0.0277

NOTE: The assumption is that the fault is returning via the earth conductor and the screen.
Values are given for fault return via earth conductor only and screen and earth in parallel.

2C+E XLPE/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
mm2 mm2 Ω/km Ω/km Ω/km Ω/km Ω/km
DTMP07AA002 2.5 2.5 18.2 27.2 0.211 0.105 0.0701
DTMP09AA002 4 2.5 12.6 23.6 0.2079 0.0995 0.0673
DTMP11AA002 6 2.5 10.2 21.7 0.1969 0.0949 0.0640
DTMP13AA002 10 4 7.25 13.4 0.1889 0.0907 0.0613
DTMP15AA002 16 6 5.17 8.84 0.1781 0.0891 0.0594
DTMC17AA002 25 6 3.74 8.30 0.1683 0.0861 0.0570
DTMC18AA002 35 10 2.82 5.05 0.1675 0.0838 0.0559
DTMC19AA002 50 16 2.07 3.25 0.1639 0.0824 0.0548
DTMC20AA002 70 25 0.342 1.95 0.1581 0.0811 0.0536
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.

3C+E XLPE/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
mm2 mm2 Ω/km Ω/km Ω/km Ω/km Ω/km
FTMP07AA003 2.5 2.5 19.5781 36.0467 0.2133 0.1063 0.0710
FTMP09AA003 4 2.5 15.3361 32.4764 0.2029 0.1008 0.0674
FTMP11AA003 6 2.5 12.9966 30.5255 0.1908 0.0962 0.0640
FTMP13AA003 10 4 9.3398 18.8811 0.1833 0.0920 0.0613
FTMP15AA003 16 6 6.8239 12.5221 0.1723 0.0905 0.0593
FTMC17AA003 25 6 4.9540 11.9828 0.1648 0.0875 0.0571
FTMC18AA003 35 10 3.7403 7.2371 0.1617 0.0852 0.0558
FTMC19AA003 50 16 2.7537 4.6217 0.1585 0.0837 0.0548
FTMC20AA003 70 25 1.7651 2.7579 0.1591 0.0824 0.0543
FTMP22AA003 95 25 1.6955 2.8562 0.1500 0.0797 0.0521
FTMP23AA003 120 35 1.3410 2.0767 0.1339 0.0788 0.0496
FTMP24AA003 150 50 1.0147 1.5481 0.1510 0.0796 0.0521
FTMP25AA003 185 70 0.7755 1.0893 0.1488 0.0801 0.0521
FTMP26AA003 240 95 0.6014 0.7903 0.1371 0.0786 0.0499
FTMP27AA003 300 120 0.4909 0.6275 0.1482 0.0780 0.0511
FTMP28AA003 400 120 0.4631 0.6113 0.1441 0.0777 0.0505
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.
OLEX - ZERO SEQUENCE IMPEDANCE

4C+E XLPE/PVC/SWA/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Earth Zero Sequence Zero Sequence Zero Sequence Reactance at 50 Hz
Size Size Resistance(RE+RA) Resistance(RE) Armour Earth Armour//Earth
Ω/km Ω/km Ω/km Ω/km Ω/km
2 2
mm mm
HTMP07AA004 2.5 2.5 18.9 36.0 0.148 0.106 0.0618
HTMP09AA004 4 2.5 14.9 32.5 0.139 0.101 0.0584
HTMP11AA004 6 2.5 12.4 30.5 0.131 0.0962 0.0554
HTMP13AA004 10 4 8.91 18.9 0.119 0.0920 0.0519
HTMP15AA004 16 6 5.83 12.5 0.114 0.0905 0.0505
HTMC17AA004 25 6 4.95 12.0 0.110 0.0875 0.0487
HTMC18AA004 35 10 3.74 7.24 0.102 0.0852 0.0465
HTMC19AA004 50 16 2.75 4.62 0.101 0.0837 0.0458
HTMC20AA004 70 25 1.77 2.76 0.0944 0.0824 0.0440
HTMP22AA004 95 25 1.62 2.86 0.0903 0.0797 0.0423
HTMP23AA004 120 35 1.20 2.08 0.0905 0.0788 0.0421
HTMP24AA004 150 50 0.976 1.548 0.0893 0.0796 0.0421
HTMP25AA004 185 70 0.763 1.089 0.0849 0.0801 0.0412
HTMP26AA004 240 95 0.586 0.790 0.0848 0.0786 0.0408
HTMP27AA004 300 120 0.452 0.628 0.0740 0.0780 0.0380
HTMP28AA004 400 120 0.423 0.611 0.0837 0.0777 0.0403
NOTE: The assumption is that the fault is returning via the earth conductor for unarmoured cables
For armoured cables , values are given for fault return via earth conductor only,armour only and
armour in parallel with the earth conductor.

Single Core XLPE/PVC 0.6/1kV - Copper Conductors

Product Code Conductor Stranding Earth size Zero Sequence Zero Sequence Reactance
size Resistance Trefoil Flat
mm2 No./mm mm2 Ω/km Ω/km
BZHX01AA001 10 348/0.2 4 17.3 0.108 0.123
BZHX02AA001 16 528/0.2 6 11.4 0.103 0.118
BZHX03AA001 25 816/0.2 6 10.9 0.0976 0.113
BZHX04AA001 35 1152/0.2 10 6.57 0.0932 0.108
BZHX05AA001 50 672/0.3 16 4.21 0.0903 0.106
BZHX06AA001 70 972/0.3 25 2.50 0.0871 0.102
BZHX07AA001 95 1296/0.3 25 2.43 0.0850 0.100
BZHE87AA001 120 630/0.5 35 1.89 0.0848 0.100
BZHE88AA001 150 763/0.5 50 1.41 0.0845 0.100
BZHE89AA001 185 962/0.5 70 0.994 0.0818 0.0971
BZHE90AA001 240 1211/0.5 95 0.742 0.0805 0.0957
BZHE91AA001 300 1525/0.5 120 0.573 0.0800 0.0952
BZHE92AA001 400 2016/0.5 120 0.553 0.0788 0.0940
NOTE: The assumption is that the fault is returning via the earth conductor