QUESTION
How can WinCC flexible display values of SENTRON PAC3200 / PAC4200 via Ethernet?
RESPONSE
Measured values of SENTRON PAC3200 und PAC4200 can be transmitted via Ethernet and
displayed in WinCC flexible.
The maximum number of items for WinCC flexible runtime amounts to 8 pcs PAC3200 / PAC4200 and
for a HMI Panel max. 6 pcs. PAC3200 / PAC4200.
Modbus Modbus
TCP TCP
max. max.
8 pcs. 6 pcs.
PAC3200 PAC3200
PAC PAC4200
PAC PAC4200
3200 3200
This procedure is also applicable for connecting several PAC3200 / PAC4200 Power Monitoring
Devices to WinCC flexible
Detailed instructions
o
3. Provide new screens with tags
q
5. Generate new process tag
General
Name: name of the tag
Connection: insert communication connection from step no. 2
Data typ: Float
Properties
Area: %MW
Address: Modbus TCP Offset from the Sentron PAC3200 / PAC4200 manual
(example Address 1 = Offset 1 Voltage UL1-N)
Example for an unsigned long format, typical for operating hour counter
Example for a Bit format, typical for Limit Violation
7. Generate project
t u
9. Runtime