Professional Documents
Culture Documents
Fire Alarm: 7. Noti Cation
Fire Alarm: 7. Noti Cation
17. Fire alarm
7. Noti cation
07-May-2018 | V1.1
Electrical Design Criteria
Visual
Visual signal appliances shall be synchronized.
Lights used for re alarm signalling only or to signal the intent for complete evacuation shall be clear or nominal white and shall
not exceed 1,000cd.
Combination devices
Combination smoke detectors and visible noti cation appliances or combination smoke alarms and visible noti cation appliances
shall be installed in accordance with Authority Having Jurisdiction (AHJ) and NFPA for the sleeping, inpatient areas etc.
Annunciation zoning
For the purpose of alarm annunciation, each oor of the building shall be considered as a separate zone.
For the purposes of alarm annunciation, if a oor of the building is subdivided into multiple zones by re or smoke barriers and the
re plan for the protected premises allows relocation of occupants from the zone of origin to another zone on the same oor, each
zone on the oor shall be annunciated separately.