Project: ETAP Page: 1

Location: 18.0.0C Date: 16-09-2018


Contract: SN: -
Engineer: Revision: Base
Study Case: SC
Filename: Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase Fault Currents

Swing V-Control Load Total

Number of Buses: 3 2 39 44

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total

Number of Branches: 6 0 0 34 0 1 41

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 3 0 0 14 8 25

System Frequency: 50.00

Unit System: Metric

Project Filename:

Output Filename:
Project: - ETAP Page: 2
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable / Busway Resistance: Yes Individual


Project: - ETAP Page: 3
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 SWNG 6.600 6.600 1 100.00 0.00


Bus3 Gen. 6.600 6.600 1 100.00 0.00
Bus4 Gen. 6.600 6.600 1 100.00 0.00
Bus5 Load 6.600 6.600 1 100.00 0.00
Bus6 Load 0.415 0.415 1 100.00 0.00
Bus7 Load 0.415 0.415 1 100.00 0.00
Bus9 Load 6.600 6.600 1 100.00 0.00
Bus10 Load 0.415 0.415 1 100.00 0.00
Bus11 Load 0.415 0.415 1 100.00 0.00
Bus13 Load 6.600 6.600 1 100.00 0.00
Bus14 Load 0.415 0.415 1 100.00 0.00
Bus16 Load 0.415 0.415 1 100.00 0.00
Bus17 Load 0.415 0.415 1 100.00 0.00
Bus18 Load 6.600 6.600 1 100.00 0.00
Bus19 Load 6.600 6.600 1 100.00 0.00
Bus20 Load 0.415 0.415 1 100.00 0.00
Bus21 Load 6.600 6.600 1 100.00 0.00
Bus22 Load 0.415 0.415 1 100.00 0.00
Bus23 Load 0.415 0.415 1 100.00 0.00
Bus24 Load 0.415 0.415 1 100.00 0.00
Bus28 SWNG 6.600 6.600 2 100.00 0.00
Bus29 Load 6.600 6.600 2 100.00 0.00
Bus32 SWNG 6.600 6.600 3 100.00 0.00
Bus33 Load 6.600 6.600 3 100.00 0.00
Bus42 Load 6.600 6.600 1 100.00 0.00
Bus43 Load 6.600 6.600 1 100.00 0.00
Bus46 Load 6.600 6.600 1 100.00 0.00
Bus47 Load 6.600 6.600 1 100.00 0.00
EM-1001 Load 0.415 0.415 1 100.00 0.00
GOD Load 6.600 6.600 1 100.00 0.00
HSWG-1001 Load 6.600 6.600 1 100.00 0.00
LSWG-1001_A Load 0.415 0.415 1 100.00 0.00
LSWG-1001_B Load 0.415 0.415 1 100.00 0.00
LSWG-1001_C Load 0.415 0.415 1 100.00 0.00
LSWG-1002_A Load 0.415 0.415 1 100.00 0.00
LSWG-1002_B Load 0.415 0.415 1 100.00 0.00
MCC-1001A Load 0.415 0.415 1 100.00 0.00
MCC-1001B Load 0.415 0.415 1 100.00 0.00
MCC-1001C Load 0.415 0.415 1 100.00 0.00
MDB-1001 Load 0.415 0.415 1 100.00 0.00
SMDB-01 Load 0.415 0.415 1 100.00 0.00
Project: - ETAP Page: 4
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

SMDB-02 Load 0.415 0.415 1 100.00 0.00


C-VFD-2219A~ Load 6.600 6.600 0 100.00 0.00
C-VFD-2219B~ Load 6.600 6.600 0 100.00 0.00

44 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Project: - ETAP Page: 5
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Line/Cable/Busway Input Data

ohms or siemens/1000 m per Conductor (Cable) or per Phase (Line/Busway)


Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (C) R X Y

C-AM-4103A 6.6NCUN3 70 290.0 0 1 75 0.32714 0.10200 0.0000000


C-AM-4103B 6.6NCUN3 70 280.0 0 1 75 0.32714 0.10200 0.0000000
C-CM-3411 1.0NCUN4 400 70.0 0 3 75 0.06104 0.07100 0.0001687
C-CM-3412 1.0NCUN4 400 70.0 0 3 75 0.06104 0.07100 0.0001687
C-CM-3413 1.0NCUN4 400 78.0 0 3 75 0.06104 0.07100 0.0001687
C-CM-3414 1.0NCUN4 400 86.0 0 3 75 0.06104 0.07100 0.0001687
C-EM-1001 1.0NCUN4 400 25.0 0 4 75 0.06104 0.07100 0.0001687
C-G-6501 6.6NCUS3 120 235.0 0 2 75 0.18694 0.09310 0.0000000
C-G-6502 6.6NCUS3 120 225.0 0 2 75 0.18694 0.09310 0.0000000
C-G-6503 6.6NCUS3 120 215.0 0 2 75 0.18694 0.09310 0.0000000
C-HSWG-1001-PC-001 6.6NCUN3 120 68.0 0 1 75 0.18694 0.09310 0.0000000
C-HSWG-1001-PC-002 6.6NCUN3 120 63.0 0 1 75 0.18694 0.09310 0.0000000
C-HSWG-1001-PC-003 6.6NCUN3 120 58.0 0 1 75 0.18694 0.09310 0.0000000
C-HSWG-1001-PC-0004 6.6NCUN3 120 53.0 0 1 75 0.18694 0.09310 0.0000000
C-HSWG-1001-PC-005 6.6NCUN3 120 48.0 0 1 75 0.18694 0.09310 0.0000000
C-MCC-1001A 1.0NCUN4 400 30.0 0 4 75 0.06104 0.07100 0.0001687
C-MCC-1001B 1.0NCUN4 400 35.0 0 4 75 0.06104 0.07100 0.0001687
C-MCC-1001C 1.0NCUN4 400 40.0 0 4 75 0.06104 0.07100 0.0001687
C-MDB-1001 1.0NCUN4 400 25.0 0 4 75 0.06104 0.07100 0.0001687
C-PM-2219A 6.6NCUN3 70 190.0 0 1 75 0.32714 0.10200 0.0000000
C-PM-2219B 6.6NCUN3 70 185.0 0 1 75 0.32714 0.10200 0.0000000
C-PM-3203A 6.6NCUN3 70 240.0 0 1 75 0.32714 0.10200 0.0000000
C-PM-3203B 6.6NCUN3 70 235.0 0 1 75 0.32714 0.10200 0.0000000
C-SMDB-01 1.0NCUN4 400 45.0 0 1 75 0.06104 0.07100 0.0001687
C-SMDB-02 1.0NCUN4 400 50.0 0 1 75 0.06104 0.07100 0.0001687
C-VFD-2219A 6.6NCUN3 70 20.0 0 1 75 0.32714 0.10200 0.0000000
C-VFD-2219B 6.6NCUN3 70 20.0 0 1 75 0.32714 0.10200 0.0000000
C-XFMR-1001A-PC-001 1.0NCUN4 400 34.0 0 5 75 0.06104 0.07100 0.0001687
C-XFMR-1001B-PC-001 1.0NCUN4 400 31.0 0 5 75 0.06104 0.07100 0.0001687
C-XFMR-1001C-PC-001 1.0NCUN4 400 28.0 0 5 75 0.06104 0.07100 0.0001687
C-XFMR-1002A-PC-001 1.0NCUN4 400 43.0 0 5 75 0.06104 0.07100 0.0001687
C-XFMR-1002B-PC-001 1.0NCUN4 400 38.0 0 5 75 0.06104 0.07100 0.0001687
C-XFMR-1003-PC-001 6.6NCUN3 70 250.0 0 1 75 0.32714 0.10200 0.0000000
OHL-6.6kV 6.6NCUN3 70 50.0 0 1 75 0.32714 0.10200 0.0000000

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: - ETAP Page: 6
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted


ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

XFMR-1001A 1.750 6.600 0.415 6.25 6.00 0 0 0 0 0 6.2500

XFMR-1001B 1.750 6.600 0.415 6.25 6.00 0 0 0 0 0 6.2500

XFMR-1001C 1.750 6.600 0.415 6.25 6.00 0 0 0 0 0 6.2500

XFMR-1002A 1.750 6.600 0.415 6.25 6.00 0 0 0 0 0 6.2500

XFMR-1002B 1.750 6.600 0.415 6.25 6.00 0 0 0 0 0 6.2500

XFMR-1003 1.000 6.600 0.415 5.00 3.50 0 0 0 0 0 5.0000


Project: - ETAP Page: 7
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

XFMR-1001A 2W XFMR Bus5 Bus6 56.48 338.87 343.54

XFMR-1001B 2W XFMR Bus9 Bus10 56.48 338.87 343.54

XFMR-1001C 2W XFMR Bus13 Bus14 56.48 338.87 343.54

XFMR-1002A 2W XFMR Bus19 Bus20 56.48 338.87 343.54

XFMR-1002B 2W XFMR Bus21 Bus22 56.48 338.87 343.54

XFMR-1003 2W XFMR Bus18 Bus23 133.18 466.11 484.77

C-AM-4103A Cable HSWG-1001 Bus47 21.78 6.79 22.81

C-AM-4103B Cable HSWG-1001 Bus46 21.03 6.56 22.03

C-CM-3411 Cable LSWG-1002_A Bus7 82.70 96.19 126.86

C-CM-3412 Cable LSWG-1002_A Bus11 82.70 96.19 126.86

C-CM-3413 Cable LSWG-1002_B Bus16 92.15 107.19 141.35

C-CM-3414 Cable LSWG-1002_B Bus17 101.60 118.18 155.85

C-EM-1001 Cable LSWG-1001_C EM-1001 22.15 25.77 33.98

C-G-6501 Cable Bus1 HSWG-1001 5.04 2.51 5.63

C-G-6502 Cable Bus3 HSWG-1001 4.83 2.40 5.39

C-G-6503 Cable Bus4 HSWG-1001 4.61 2.30 5.15

C-HSWG-1001-PC-001 Cable HSWG-1001 Bus5 2.92 1.45 3.26

C-HSWG-1001-PC-002 Cable HSWG-1001 Bus9 2.70 1.35 3.02

C-HSWG-1001-PC-003 Cable HSWG-1001 Bus13 2.49 1.24 2.78

C-HSWG-1001-PC-0004 Cable HSWG-1001 Bus19 2.27 1.13 2.54

C-HSWG-1001-PC-005 Cable HSWG-1001 Bus21 2.06 1.03 2.30

C-MCC-1001A Cable LSWG-1001_A MCC-1001A 26.58 30.92 40.77

C-MCC-1001B Cable LSWG-1001_B MCC-1001B 31.01 36.07 47.57

C-MCC-1001C Cable LSWG-1001_C MCC-1001C 35.44 41.23 54.37

C-MDB-1001 Cable Bus23 Bus24 22.15 25.77 33.98

C-PM-2219A Cable Bus28 Bus29 14.27 4.45 14.95

C-PM-2219B Cable Bus32 Bus33 13.89 4.33 14.55

C-PM-3203A Cable HSWG-1001 Bus42 18.02 5.62 18.88

C-PM-3203B Cable HSWG-1001 Bus43 17.65 5.50 18.49

C-SMDB-01 Cable MDB-1001 SMDB-01 159.49 185.51 244.65

C-SMDB-02 Cable MDB-1001 SMDB-02 177.21 206.13 271.83

C-VFD-2219A Cable HSWG-1001 C-VFD-2219A~ 1.50 0.47 1.57

C-VFD-2219B Cable HSWG-1001 C-VFD-2219B~ 1.50 0.47 1.57

C-XFMR-1001A-PC-001 Cable Bus6 LSWG-1001_A 24.10 28.03 36.97

C-XFMR-1001B-PC-001 Cable Bus10 LSWG-1001_B 21.97 25.56 33.71

C-XFMR-1001C-PC-001 Cable Bus14 LSWG-1001_C 19.85 23.09 30.45

C-XFMR-1002A-PC-001 Cable Bus20 LSWG-1002_A 30.48 35.45 46.76


Project: - ETAP Page: 8
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y

C-XFMR-1002B-PC-001 Cable Bus22 LSWG-1002_B 26.94 31.33 41.32

C-XFMR-1003-PC-001 Cable HSWG-1001 GOD 18.78 5.85 19.67

OHL-6.6kV Cable GOD Bus18 3.76 1.17 3.93

2SW1 Tie Switch MDB-1001 Bus24


Project: - ETAP Page: 9
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Synchronous Generator Input Data

% Impedance in Machine Base


Synchronous Generator Connected Bus Rating Xd"
Excitation
ID Type ID MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Type

G-6501 Steam Turbo Bus1 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%

G-6502 Steam Turbo Bus3 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%

G-6503 Steam Turbo Bus4 4.350 6.600 1500 85.00 0.932 17.70 0.0 0.05 143.70 Turbine 130%

Total Connected Synchronous Generators ( = 3 ) : 13.050 MVA


Project: - ETAP Page: 10
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Induction Machine Input Data

% Impedance
Induction Machine Connected Bus Rating (Motor Base)

ID Type Qty ID HP/kW kVA kV Amp PF R X" R/X" MW/PP

PM-2219A Motor 1 Bus29 350.00 407.97 6.600 35.69 92.06 2.96 15.10 0.20 0.18
PM-2219B Motor 1 Bus33 350.00 407.97 6.600 35.69 92.06 2.96 15.10 0.20 0.18
PM-3203A Motor 1 Bus42 220.00 257.63 6.600 22.54 91.87 3.36 15.01 0.22 0.11
PM-3203B Motor 1 Bus43 220.00 257.63 6.600 22.54 91.87 3.36 15.01 0.22 0.11
AM-4103B Motor 1 Bus46 300.00 350.26 6.600 30.64 91.99 3.09 15.07 0.20 0.15
AM-4103A Motor 1 Bus47 300.00 350.26 6.600 30.64 91.99 3.09 15.07 0.20 0.15
CM-3411_1 Motor 1 Bus7 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3411_2 Motor 1 Bus7 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3412_1 Motor 1 Bus11 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3412_2 Motor 1 Bus11 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3413_1 Motor 1 Bus16 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3413_2 Motor 1 Bus16 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09
CM-3414_1 Motor 1 Bus17 318.00 371.03 0.415 516.18 92.02 3.29 16.34 0.20 0.16
CM-3414_2 Motor 1 Bus17 172.00 201.95 0.415 280.95 91.76 3.90 16.20 0.24 0.09

Total Connected Induction Machines ( = 14 ): 4323.6 kVA


Project: - ETAP Page: 11
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Lumped Load Input Data


Motor Loads
Lumped Load
% Impedance
Lumped Load Connected Bus Rating % Load Loading Machine Base
ID ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" MW/PP

AUX-CM-3411 Bus7 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02

AUX-CM-3412 Bus11 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02

AUX-CM-3413 Bus16 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02

AUX-CM-3414 Bus17 66.3 0.415 92.24 85.00 30 70 16.9 10.5 6.46 15.37 0.42 0.02

Lump-EM-1001 EM-1001 1242.0 0.415 1727.88 85.00 30 70 231.2 143.3 6.46 15.37 0.42 0.32

Lump-MCC-1001A MCC-1001A 842.0 0.415 1171.40 85.00 30 70 122.4 75.8 6.46 15.37 0.42 0.21

Lump-MCC-1001B MCC-1001B 579.0 0.415 805.51 85.00 30 70 124.0 76.9 6.46 15.37 0.42 0.15

Lump-MCC-1001C MCC-1001C 321.0 0.415 446.58 85.00 30 70 49.9 30.9 6.46 15.37 0.42 0.08

Total Connected Lumped Loads ( = 8 ): 3249.2 kVA


Project: - ETAP Page: 12
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

VFD Input Data

AC Rating
% Impedance
kVA kV FLA Input Output Bypass Equipment Base
ID Output Input Output Input Output % EFF % PF Hz % Imax Switch R X

VFD-PM-2219A 400.00 6.600 6.600 34.99 34.99 100.00 87.50 60.00 150.0 No 66.67 0.00

VFD-PM-2219B 400.00 6.600 6.600 34.99 34.99 100.00 87.50 60.00 150.0 No 66.67 0.00
Project: - ETAP Page: 13
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

SHORT-CIRCUIT REPORT

3-Phase fault at bus: EM-1001

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 69.138 kA Method C
Steady State = 27.174 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

EM-1001 Total 0.00 7.952 -31.729 4.0 32.711

LSWG-1001_C EM-1001 7.20 6.687 -28.719 4.3 29.487

Lump-EM-1001 EM-1001 105.00 1.265 -3.011 2.4 3.266

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 32.190 39.001 22.021

0.02 31.797 33.633 10.959

0.03 31.416 31.866 5.334

0.04 31.049 31.158 2.596

0.05 30.700 30.729 1.338

0.06 30.532 30.539 0.659

0.07 30.369 30.370 0.324

0.08 30.209 30.210 0.160

0.09 30.054 30.054 0.079

0.10 29.904 29.904 0.041

0.15 29.611 29.611 0.001

0.20 29.333 29.333 0.000

0.25 29.073 29.073 0.000

0.30 29.073 29.073 0.000


Project: - ETAP Page: 14
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: GOD

Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 17.558 kA Method C
Steady State = 6.147 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

GOD Total 0.00 2.271 -8.163 3.6 8.473

HSWG-1001 GOD 19.05 2.271 -8.163 3.6 8.473

Bus18 GOD 0.00 0.000 0.000 999.9 0.000

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 7.755 9.470 5.435

0.02 7.447 7.939 2.751

0.03 7.129 7.250 1.318

0.04 6.804 6.833 0.632

0.05 6.474 6.484 0.355

0.06 6.337 6.340 0.176

0.07 6.201 6.202 0.087

0.08 6.065 6.065 0.043

0.09 5.928 5.929 0.021

0.10 5.793 5.793 0.012

0.15 5.558 5.558 0.000

0.20 5.324 5.324 0.000

0.25 5.094 5.094 0.000

0.30 5.094 5.094 0.000


Project: - ETAP Page: 15
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: HSWG-1001

Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 22.758 kA Method C
Steady State = 2.208 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

HSWG-1001 Total 0.00 1.033 -9.175 8.9 9.233

Bus47 HSWG-1001 0.57 0.045 -0.214 4.8 0.219

Bus46 HSWG-1001 0.55 0.045 -0.214 4.8 0.219

Bus1 HSWG-1001 1.50 0.150 -2.326 15.5 2.331

Bus3 HSWG-1001 1.44 0.149 -2.327 15.6 2.332

Bus4 HSWG-1001 1.37 0.148 -2.328 15.7 2.333

Bus5 HSWG-1001 0.05 0.052 -0.127 2.4 0.137

Bus9 HSWG-1001 0.03 0.037 -0.089 2.4 0.096

Bus13 HSWG-1001 0.08 0.091 -0.226 2.5 0.244

Bus19 HSWG-1001 0.15 0.122 -0.506 4.1 0.520

Bus21 HSWG-1001 0.14 0.123 -0.504 4.1 0.519

Bus42 HSWG-1001 0.35 0.036 -0.157 4.4 0.161

Bus43 HSWG-1001 0.34 0.036 -0.157 4.4 0.161

C-VFD-2219A~ HSWG-1001 0.00 0.000 0.000 999.9 0.000

C-VFD-2219B~ HSWG-1001 0.00 0.000 0.000 999.9 0.000

GOD HSWG-1001 0.00 0.000 0.000 999.9 0.000

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 8.317 12.806 9.738

0.02 7.923 11.147 7.842

0.03 7.518 9.667 6.077

0.04 7.105 8.524 4.709

0.05 6.688 7.830 4.073

0.06 6.513 7.268 3.226

0.07 6.338 6.834 2.555

0.08 6.164 6.488 2.024

0.09 5.990 6.201 1.604

0.10 5.816 5.989 1.429


Project: - ETAP Page: 16
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

(Cont.)

3-Phase fault at bus: HSWG-1001

Nominal kV = 6.600
Voltage c Factor = 1.10 (User-Defined)
Peak Value = 22.758 kA Method C
Steady State = 2.208 kA rms

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.15 5.521 5.541 0.473

0.20 5.228 5.230 0.156

0.25 4.939 4.939 0.052

0.30 4.939 4.939 0.017


Project: - ETAP Page: 17
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: LSWG-1001_A

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 70.853 kA Method C
Steady State = 28.421 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LSWG-1001_A Total 0.00 6.801 -31.689 4.7 32.410

MCC-1001A LSWG-1001_A 0.65 0.856 -2.028 2.4 2.201

Bus6 LSWG-1001_A 8.04 5.945 -29.661 5.0 30.251

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 32.093 40.203 24.215

0.02 31.880 34.535 13.277

0.03 31.674 32.470 7.146

0.04 31.476 31.710 3.846

0.05 31.287 31.363 2.175

0.06 31.196 31.219 1.182

0.07 31.108 31.115 0.643

0.08 31.022 31.024 0.349

0.09 30.938 30.939 0.190

0.10 30.857 30.857 0.109

0.15 30.700 30.700 0.005

0.20 30.551 30.551 0.000

0.25 30.412 30.412 0.000

0.30 30.412 30.412 0.000


Project: - ETAP Page: 18
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: LSWG-1001_B

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 70.325 kA Method C
Steady State = 28.585 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LSWG-1001_B Total 0.00 6.476 -31.290 4.8 31.953

MCC-1001B LSWG-1001_B 0.52 0.589 -1.396 2.4 1.515

Bus10 LSWG-1001_B 7.38 5.886 -29.894 5.1 30.468

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 31.673 39.937 24.326

0.02 31.529 34.313 13.540

0.03 31.389 32.252 7.412

0.04 31.255 31.517 4.057

0.05 31.127 31.214 2.324

0.06 31.065 31.092 1.284

0.07 31.005 31.013 0.709

0.08 30.947 30.949 0.392

0.09 30.890 30.891 0.216

0.10 30.835 30.836 0.126

0.15 30.731 30.731 0.007

0.20 30.633 30.633 0.000

0.25 30.541 30.541 0.000

0.30 30.541 30.541 0.000


Project: - ETAP Page: 19
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: LSWG-1001_C

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 75.582 kA Method C
Steady State = 28.751 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LSWG-1001_C Total 0.00 7.342 -33.769 4.6 34.558

EM-1001 LSWG-1001_C 0.79 1.263 -2.986 2.4 3.242

MCC-1001C LSWG-1001_C 0.33 0.327 -0.776 2.4 0.842

Bus14 LSWG-1001_C 6.69 5.752 -30.008 5.2 30.554

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 34.018 42.813 25.995

0.02 33.622 36.621 14.515

0.03 33.237 34.166 7.911

0.04 32.868 33.150 4.311

0.05 32.517 32.612 2.497

0.06 32.348 32.377 1.377

0.07 32.183 32.192 0.760

0.08 32.022 32.025 0.419

0.09 31.867 31.867 0.231

0.10 31.715 31.716 0.136

0.15 31.421 31.421 0.007

0.20 31.142 31.142 0.000

0.25 30.882 30.882 0.000

0.30 30.882 30.882 0.000


Project: - ETAP Page: 20
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: LSWG-1002_A

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 85.753 kA Method C
Steady State = 27.983 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LSWG-1002_A Total 0.00 8.353 -38.563 4.6 39.457

Bus7 LSWG-1002_A 4.55 1.180 -4.852 4.1 4.993

Bus11 LSWG-1002_A 4.55 1.180 -4.852 4.1 4.993

Bus20 LSWG-1002_A 9.91 5.993 -28.860 4.8 29.475

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 37.438 47.212 28.763

0.02 36.513 39.539 15.169

0.03 35.617 36.484 7.909

0.04 34.756 35.000 4.124

0.05 33.938 34.011 2.223

0.06 33.541 33.561 1.167

0.07 33.153 33.159 0.612

0.08 32.777 32.778 0.321

0.09 32.411 32.411 0.169

0.10 32.056 32.056 0.092

0.15 31.389 31.389 0.004

0.20 30.759 30.759 0.000

0.25 30.168 30.168 0.000

0.30 30.168 30.168 0.000


Project: - ETAP Page: 21
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: LSWG-1002_B

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 86.594 kA Method C
Steady State = 28.246 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

LSWG-1002_B Total 0.00 8.262 -38.814 4.7 39.684

Bus16 LSWG-1002_B 5.05 1.186 -4.828 4.1 4.971

Bus17 LSWG-1002_B 5.54 1.191 -4.804 4.0 4.949

Bus22 LSWG-1002_B 8.84 5.885 -29.183 5.0 29.771

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 37.696 47.750 29.310

0.02 36.785 39.993 15.694

0.03 35.901 36.848 8.299

0.04 35.053 35.326 4.389

0.05 34.246 34.330 2.407

0.06 33.854 33.878 1.282

0.07 33.472 33.479 0.683

0.08 33.100 33.102 0.364

0.09 32.739 32.740 0.194

0.10 32.389 32.389 0.107

0.15 31.730 31.730 0.005

0.20 31.107 31.107 0.000

0.25 30.524 30.524 0.000

0.30 30.524 30.524 0.000


Project: - ETAP Page: 22
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: MCC-1001A

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 63.796 kA Method C
Steady State = 26.581 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MCC-1001A Total 0.00 7.450 -29.415 3.9 30.344

LSWG-1001_A MCC-1001A 8.25 6.593 -27.374 4.2 28.156

Lump-MCC-1001A MCC-1001A 105.00 0.858 -2.041 2.4 2.214

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 30.020 36.057 19.973

0.02 29.803 31.316 9.618

0.03 29.592 29.941 4.553

0.04 29.390 29.469 2.156

0.05 29.198 29.218 1.070

0.06 29.105 29.110 0.511

0.07 29.015 29.016 0.244

0.08 28.927 28.928 0.117

0.09 28.842 28.842 0.056

0.10 28.759 28.759 0.028

0.15 28.599 28.599 0.001

0.20 28.448 28.448 0.000

0.25 28.306 28.306 0.000

0.30 28.306 28.306 0.000


Project: - ETAP Page: 23
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: MCC-1001B

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 62.051 kA Method C
Steady State = 26.438 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MCC-1001B Total 0.00 7.234 -28.623 4.0 29.523

LSWG-1001_B MCC-1001B 9.58 6.645 -27.219 4.1 28.018

Lump-MCC-1001B MCC-1001B 105.00 0.590 -1.404 2.4 1.522

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 29.238 35.080 19.385

0.02 29.090 30.536 9.285

0.03 28.948 29.277 4.378

0.04 28.811 28.885 2.065

0.05 28.682 28.700 1.017

0.06 28.619 28.623 0.484

0.07 28.558 28.559 0.230

0.08 28.498 28.499 0.110

0.09 28.441 28.441 0.052

0.10 28.385 28.385 0.026

0.15 28.279 28.279 0.001

0.20 28.179 28.179 0.000

0.25 28.085 28.085 0.000

0.30 28.085 28.085 0.000


Project: - ETAP Page: 24
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: MCC-1001C

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 64.537 kA Method C
Steady State = 26.297 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MCC-1001C Total 0.00 8.236 -30.069 3.7 31.177

LSWG-1001_C MCC-1001C 11.86 7.909 -29.291 3.7 30.340

Lump-MCC-1001C MCC-1001C 105.00 0.327 -0.778 2.4 0.844

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 30.715 36.432 19.592

0.02 30.386 31.729 9.131

0.03 30.066 30.352 4.156

0.04 29.758 29.818 1.891

0.05 29.463 29.477 0.914

0.06 29.321 29.324 0.421

0.07 29.182 29.182 0.194

0.08 29.046 29.046 0.089

0.09 28.914 28.914 0.041

0.10 28.786 28.786 0.020

0.15 28.534 28.534 0.000

0.20 28.296 28.296 0.000

0.25 28.072 28.072 0.000

0.30 28.072 28.072 0.000


Project: - ETAP Page: 25
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: MDB-1001

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 45.953 kA Method C
Steady State = 22.033 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

MDB-1001 Total 0.00 6.940 -22.063 3.2 23.129

SMDB-01 MDB-1001 0.00 0.000 0.000 999.9 0.000

SMDB-02 MDB-1001 0.00 0.000 0.000 999.9 0.000

Bus23 Bus24 5.65 6.940 -22.063 3.2 23.129

Bus24 MDB-1001 0.00 6.940 -22.063 3.2 23.129

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 23.129 26.235 12.382

0.02 23.129 23.622 4.801

0.03 23.129 23.202 1.840

0.04 23.129 23.140 0.705

0.05 23.129 23.131 0.280

0.06 23.129 23.129 0.108

0.07 23.129 23.129 0.042

0.08 23.129 23.129 0.016

0.09 23.129 23.129 0.006

0.10 23.129 23.129 0.002

0.15 23.129 23.129 0.000

0.20 23.129 23.129 0.000

0.25 23.129 23.129 0.000

0.30 23.129 23.129 0.000


Project: - ETAP Page: 26
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: SMDB-01

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 30.724 kA Method C
Steady State = 16.383 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

SMDB-01 Total 0.00 6.864 -15.498 2.3 16.950

MDB-1001 SMDB-01 29.81 6.864 -15.498 2.3 16.950

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 16.950 18.000 6.057

0.02 16.950 17.022 1.566

0.03 16.950 16.955 0.400

0.04 16.950 16.950 0.102

0.05 16.950 16.950 0.027

0.06 16.950 16.950 0.007

0.07 16.950 16.950 0.002

0.08 16.950 16.950 0.000

0.09 16.950 16.950 0.000

0.10 16.950 16.950 0.000

0.15 16.950 16.950 0.000

0.20 16.950 16.950 0.000

0.25 16.950 16.950 0.000

0.30 16.950 16.950 0.000


Project: - ETAP Page: 27
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase fault at bus: SMDB-02

Nominal kV = 0.415
Voltage c Factor = 1.05 (User-Defined)
Peak Value = 29.631 kA Method C
Steady State = 15.921 kA rms

Contribution Voltage & Initial Symmetrical Current (rms)


From Bus To Bus %V kA kA X/R kA
ID ID From Bus Real Imaginary Ratio Magnitude

SMDB-02 Total 0.00 6.796 -14.983 2.2 16.452

MDB-1001 SMDB-02 32.15 6.796 -14.983 2.2 16.452

Breaking and DC Fault Current (kA)


Based on Total Bus Fault Current

TD (S) Ib sym Ib asym Idc

0.01 16.452 17.407 5.685

0.02 16.452 16.514 1.421

0.03 16.452 16.456 0.351

0.04 16.452 16.453 0.087

0.05 16.452 16.452 0.022

0.06 16.452 16.452 0.006

0.07 16.452 16.452 0.001

0.08 16.452 16.452 0.000

0.09 16.452 16.452 0.000

0.10 16.452 16.452 0.000

0.15 16.452 16.452 0.000

0.20 16.452 16.452 0.000

0.25 16.452 16.452 0.000

0.30 16.452 16.452 0.000


Project: - ETAP Page: 28
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
EM-1001 0.415 EM-1001 SwtchGear 105.000 32.711 69.138 27.174
0.415 EM-1001 CB CB 143.000 65.000 66.372 29.487 62.324 29.172 29.565 4.808
GOD 6.600 GOD Bus 8.473 17.558 6.147
HSWG-1001 6.600 HSWG-1001 SwtchGear 63.000 9.233 22.758 2.208
6.600 G-6501 CB CB 63.000 25.000 25.617 5.590 6.906 17.021 4.370 4.592 1.412
6.600 G-6502 CB CB 63.000 25.000 25.617 5.590 6.905 17.020 4.369 4.592 1.412
6.600 G-6503 CB CB 63.000 25.000 25.617 5.590 6.904 17.018 4.369 4.592 1.412
6.600 XFMR-1001A FUSE Fuse 50.000 66.539 9.101 22.433 8.203 12.627 9.599
6.600 XFMR-1001B FUSE Fuse 50.000 66.539 9.141 22.531 8.241 12.683 9.641
6.600 XFMR-1001C FUSE Fuse 50.000 66.539 8.998 22.179 8.110 12.484 9.490
6.600 XFMR-1002A FUSE Fuse 50.000 66.539 8.717 21.486 7.879 12.108 9.194
6.600 XFMR-1002B FUSE Fuse 50.000 66.539 8.719 21.489 7.880 12.110 9.195
6.600 XFMR-1003 FUSE Fuse 50.000 66.539 9.233 22.758 8.317 12.806 9.738
6.600 PM-2219A FUSE Fuse 50.000 66.539 9.233 22.758 8.317 12.806 9.738
6.600 PM-2219B FUSE Fuse 50.000 66.539 9.233 22.758 8.317 12.806 9.738
6.600 PM-3203A FUSE Fuse 50.000 66.539 9.073 22.364 8.193 12.598 9.569
6.600 PM-3203B FUSE Fuse 50.000 66.539 9.073 22.364 8.193 12.598 9.569
6.600 AM-4103A FUSE Fuse 50.000 66.539 9.016 22.222 8.142 12.518 9.509
6.600 AM-4103B FUSE Fuse 50.000 66.539 9.016 22.222 8.141 12.518 9.509
LSWG-1001_A 0.415 LSWG-1001_A SwtchGear 143.000 32.410 70.853 28.421
0.415 LSWG-1001 CB_A CB 143.000 65.000 66.372 30.251 66.133 30.251 30.978 6.670
0.415 MCC-1001A MAIN CB CB 143.000 65.000 66.372 30.251 66.133 30.251 30.978 6.670
LSWG-1001_B 0.415 LSWG-1001_B SwtchGear 143.000 31.953 70.325 28.585
0.415 LSWG-1001 CB_B CB 143.000 65.000 66.372 30.468 67.057 30.468 31.277 7.067
0.415 MCC-1001B MAIN CB CB 143.000 65.000 66.372 30.468 67.057 30.468 31.277 7.067
LSWG-1001_C 0.415 LSWG-1001_C SwtchGear 143.000 34.558 75.582 28.751
0.415 LSWG-1001 CB_C CB 143.000 65.000 66.372 30.554 66.824 30.554 31.344 6.994
0.415 MCC-1001C MAIN CB CB 143.000 65.000 66.372 33.731 73.773 32.776 33.673 7.721
0.415 EM-1001 MAIN CB CB 143.000 65.000 66.372 31.378 68.626 31.014 31.835 7.183
LSWG-1002_A 0.415 LSWG-1002_A SwtchGear 143.000 39.457 85.753 27.983
0.415 LSWG-1002 CB_A CB 143.000 65.000 66.372 29.475 64.060 29.475 30.062 5.908
0.415 CM-3411 CB CB 143.000 65.000 66.372 34.466 74.906 32.546 33.271 6.909
0.415 CM-3412 CB CB 143.000 65.000 66.372 34.466 74.906 32.546 33.271 6.909
LSWG-1002_B 0.415 LSWG-1002_B SwtchGear 143.000 39.684 86.594 28.246
0.415 LSWG-1002 CB_B CB 143.000 65.000 66.372 29.771 64.962 29.771 30.415 6.226
Project: - ETAP Page: 29
Location: - 18.0.0C Date: 16-09-2018
Contract: SN: -
Engineer: - Revision: Base
Study Case: SC
Filename: - Config.: Normal

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
LSWG-1002_B 0.415 CM-3413 CB CB 143.000 65.000 66.372 34.716 75.753 32.834 33.627 7.260
0.415 CM-3414 CB CB 143.000 65.000 66.372 34.738 75.801 32.838 33.632 7.265
MCC-1001A 0.415 MCC-1001A SwtchGear 105.000 30.344 63.796 26.581
0.415 MCC-1001A CB CB 143.000 65.000 66.372 28.156 59.197 28.156 28.472 4.225
MCC-1001B 0.415 MCC-1001B SwtchGear 105.000 29.523 62.051 26.438
0.415 MCC-1001B CB CB 143.000 65.000 66.372 28.018 58.889 28.018 28.325 4.155
MCC-1001C 0.415 MCC-1001C SwtchGear 105.000 31.177 64.537 26.297
0.415 MCC-1001C CB CB 143.000 65.000 66.372 30.340 62.805 29.601 29.876 4.044
MDB-1001 0.415 MDB-1001 SwtchGear 105.000 23.129 45.953 22.033
0.415 SMDB-01 CB CB 105.000 50.000 50.383 23.129 45.953 23.129 23.202 1.840
0.415 SMDB-02 CB CB 105.000 50.000 50.383 23.129 45.953 23.129 23.202 1.840
SMDB-01 0.415 SMDB-01 Bus 16.950 30.724 16.383
SMDB-02 0.415 SMDB-02 Bus 16.452 29.631 15.921

ip is calculated using method C


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Maximum through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)