Urea-1 VAM Chiller Performance

HW In HW Out
Qout
Qin
CW Out

Condenser Generator

CW In Conentrated
Solution
Diluted
Chilled water Out VAM m/c Solution

Refrigerant Pump
Evaporator Absorber

Chilled water In

Qout
Qin
CW In CW Out

1 TR = 3024 Kcal/Hr  COP = Qc/Qh


TR = ( m*C* DT ) /3024 Qc = cooling capacity
Qh = heat input
m : mass flow rate kg/hr
C : Specific heat Kcal/kg 'C
DT : temp difference
Date / Time
Parameter Unit Designed VAM-1 VAM-2
Chilled Water Inlet Temp °C 18
Chilled Water Outlet Temp °C 8
Chilled Water DT °C 10
Chilled Water Inlet Pressure kgf/cm2
Chilled Water Outlet Pressure kgf/cm2
Chilled Water ∆P kgf/cm2 0
Chilled Water Flow Rate m³/hr 63.37
CW Inlet Temp °C 35
CW Outlet Temp °C 39.79
CW DT °C 4.79
CW Inlet Pressure kgf/cm2
CW Outlet P ressure kgf/cm2
CW Flow m³/hr 322
HW Inlet Temp °C 100
HW Outlet Temp °C 75.32
HW DT °C 24.68
HW Inlet Pressure kgf/cm2
HW outlet Pressure kgf/cm2
HW Flow m³/hr 37
HP Generator Temp °C
LP generator Temp °C
HW pump motor Amp Amp
Chilled Water Pump motor Amp Amp
Capacity TR 210