TECHNICAL SPECIFICATION | LINE POST INSULATOR

LINE POST INSULATOR


PRODUCT PARTS & TECHNICAL DRAWING

CPN-021-755
Composite Polimer Composite Line Post Insulator TIE - TOP HEAD
*Outdoor Composite Polimer
C = composite polymer
P = Line Post
N = insulator
012 = 12.5 KN, SCL, STL
755 = creepage distance

249
295

Silicon Rubber

Galvanized Steel

Bottom Fitting
*Galvanized Steel

NO SPESIFIKASI STANDARDS CPN-012-755

1 System voltage, kV 20

2 Rated voltage, kV 24

3 Specified Cantilever Load (SCL), bending, KN IEC 61952 12.5

4 Mechanical Design Cantilever Load (MDCL), KN 6.5

5 Specified Tensile Load (STL), KN 12.5

6 Routine Test Load, KN 6.5

7 Arching distance, mm IEC 60815-1,3 276

8 Minimum creepage distance, mm 755

9 Wet power frequency withstand voltage, kV IEC 61952 65

10 Dry Lightning impulse withstand voltage, kV 150

11 Insulator fittings IEC 60720 tie-top head

Material : shed, shank IEC 60815-1,3 295


12 Insulator profiles
Installation heigth, mm 295

Weight, kgs 2.65