12 16A, T-N-C Switch for breaker control (2C + 2T) S11/S31 KAYCEE 1
13 Electronic on delay timer with 2 C/O contact, 240V AC T11/T31 EAPL/L&T 1
14 16A DP MCB, 10KA 1F1/3F1 L&T 1
15 6A DP MCB, 10KA F3, 1F2/3F2- L&T 6
1F6/3F6
16 2.5sq. mm. control terminal X12, X13 ELMEX 8+2
17 Disconnecting type Terminals, 2 BA size, stud type X11/X31 ELMEX 5
LINE PT 2 1 6A TPN MCB, 10KA F1 L&T 1
2 6A TPN MCB, 10KA F2 L&T 1
3 0-500V AC Digital Voltmeter, 96 Sq mm, Cl : 1.0, PT sec. : 110V AC, V SCHNEIDER 1
Aux. supply 240V AC
4 16A, 3 position (RY-YB-BR) With -off Voltmeter selector switch VSS KAYCEE 1
5 Digital Frequency Meter, 96 Sq mm , Cl:1.0, Aux-supply 240V AC Hz SCHNEIDER 1
6 415V : 110V AC 3Phase Fixed type Potential Transformer, PT INDUSREE 1
16.66 VA PER PH.
BUS-COUPLER 1 1 1000A 4P EDO ACB, 50KA with Micro-processor based release for O/C, S/C 2Q L&T 1
& E/F protection, Sp. Chgd. Motor : 240V AC, Closing Coil : 240V AC, St.
Coil : 240V AC, U/V Coil : 240V AC, trip signaling common micro switch,
Spring charge limit sw, Frame earthing contact, Service & test position limit
switch, Automatic safety shutters with 4 NO + 4 NC Aux-Contact
90KW DOL 4 1 250A TP MCCB, 50KA with magnatic type release for S/C Protection. 1Q1/2Q1/3Q1/ L&T 1
STARTER for Extended Door drive kit & spreader 4Q1
main pump- 2 185A TP Air Break Contactor (AC-3) with 5 NO + 1 NC contact, C11/C21/C31/ L&T 1
1,2,3 & spare 240V AC C41
3 200/5A Bar Primary type C.T, Class: 1.0, 10VA (Tape Wound) CT 1-3 KAPPA 3
4 200/5A Bar Primary type C.T, Class: 5P10, 10VA (Tape Wound) CT 5-7 KAPPA 3
5 200/5A Bar Primary type C.T, Class: 1.0, 10VA (Tape Wound) for CT 4 KAPPA 1
remote Ammeter
6 Microprocessor based motor protection relay inbuilt earth fault, auxiliary MPR SCHNEIDER 1
supply : 240V AC, 2 C/O output contact, (AREVA)
CT Secondary : 5A with RS 485 Port
7 0-200A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V A SCHNEIDER 1
AC
8 16A, 3 position (R-Y-B) With -off Ammeter selector switch ASS KAYCEE 1
9 16A, 2 Pole 2 Way without off L/R selector switch S12/S22/S32/S42 KAYCEE 1
10 Flush mounting type high speed tripping relay, 240V AC, 86P1/86P2/ AREVA 1
Contact: 3 NO +1 NC HR, 1/4N Vert. Case 86P3 & 86PS VAJH-13
11 On (R) / Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. h4,h5 & h6 L&T 3
12 Start (G) / Stop (R) Push Button with Spring return type actuator b1 & b2 L&T 2
with 1 NO / 1 NC Contact
13 Aux-Contactor with 2 NO + 2 NC contact, 240V AC K11/K21/K31/K41, L&T 2
K12/K22/K32/
K42
14 6A DP MCB, 10KA F11/F21/F31/F41& L&T 2
F12/F22/F32/F42
15 2.5sq. mm. control terminal X11/X21/X31/X41, ELMEX 11+10+3
X12/X22/X32/X42,
X13/X23/X34/X44
250A MCCB 2 1 250A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA with Q1 L&T 1
FEEDER for Thermo-magnetic release for O/C & S/C protection with spreader with
APFC 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC