HD 000 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

15.

2 deg C
6.2 deg C
15.2 deg C
6.2 deg C
Marafeq's comments:
1) This drawing shows incorrect secondary side temperatures as
5.5°C and 14.4°C. As per Marafeq's ETS guide line the
recommended secondary side chilled water supply and return
temperatures shall be 6.2°C and 15.2°C. Update the ETS
schematic drawing accordingly.

You might also like