6.

2 deg C
15.2 deg C
15.2 deg C
Marafeq's comments:
6.2 deg C 1)This drawing shows incorrect secondary side temperatures as
5.5°C and 14.4°C. As per Marafeq's ETS guide line the
recommended secondary side chilled water supply and return
temperatures shall be 6.2°C and 15.2°C. Update the PHE's,
FCU's and AHU's unit's schedule accordingly.
15.2 6.2
6.2 deg C
15.2 deg C