Professional Documents
Culture Documents
Impact of Wind Power Plant On Electrical Power System - Comparison of Calculation Method and Measurements
Impact of Wind Power Plant On Electrical Power System - Comparison of Calculation Method and Measurements
Abstract— In the paper the assessment of impact of wind power measurement is presented on the example of the Kamiensk
plant connected to high voltage network on selected power Wind Power Plant.
quality indices is discussed. On the example of the Kamiensk
Wind Power Plant with the installed capacity of 30 MW, a
comparison of flicker indices and current and voltage harmonics
II. KAMIENSK WIND POWER PLANT DESCRIPTION
calculated on the basis of data provided by wind turbines Kamiensk Wind Power Plant (KWPP) with a total
manufacturer with their values measured during the power plant generation capacity of 30 MW is located in the dumping
operation has been performed. Some problems related to the ground of Belchatow Lignite Mine. The wind farm consist of
accuracy of the assessment methods are pointed out. 15 gearless, variable speed wind turbines E70-E4 type, 2 MW
nominal power each, manufactured by Enercon GmbH.
Keywords-wind power plant; power quality; flicker; harmonics Turbines, divided into two groups, are connected with 30 kV
underground cables to the outdoor 110/30 kV transformer
I. INTRODUCTION substation. The PCC in which power quality is assessed is the
The connection of wind power plants to electrical power HV buses of the substation. Figure 1 shows schematically the
system influence its operating conditions and may affect power electric grid of Kamiensk Wind Power Plant.
quality at the point of common coupling (PCC). In Poland,
before connecting a new power plant Distribution System
Operator (DSO) requires an interconnection analysis to be
provided concerning the impact of the plant on the Polish
Electrical Power System (PEPS). According to [7] such an
expertise is obligatory if the nominal power of power plant
exceeds 2 MW. Requirements for the analysis include:
verification of the network transmission capacity, calculation
of short-circuit power and assessment of the impact of wind
farm operation on power quality at the PCC. Wind power
plants of nominal power greater than 10 MW are usually
connected to 110 kV busbars of high voltage (HV) substation
(GPZ-FW).
Evaluation of wind farm impact on power quality,
regarding flicker and harmonics emission, is based on
information provided by wind turbines manufacturer in the Figure 1. KWPP electrical network
certifying document called "windtest”, which is a report from
the turbine tests carried out by independent certification body The wind turbine manufacturer guarantees that the output
(eg, [6]). The assessment method, described in [2], assumes power of turbines (or energy within a specified period of time)
that the connected farm is the only source of disturbances. It will not be less than it results from the Guaranteed Power
takes into account the location of PCC in the network and local Curve (GPC). In Figure 2 there are compared the measured
wind conditions. values of energy generated by all the turbines of KWPP in
successive months of the year 2010 with the amount of energy
It seems useful to verify the calculation method on the basis calculated on the basis of the GPC using measured wind speed
of tests performed after the wind farm commissioning. In the at the point of connection. The presented comparison shows
paper the comparison of power quality indices obtained that for almost every month the produced energy was higher
according to the standard [2] with the results of power quality than the estimated one. Only in January a different situation
The work was supported by The Minister of Science and Higher Education
of Poland (Grant No. NN511305938).
978-1-4673-0378-1/11/$26.00 ©2011 IEEE
occurred, because the turbines was shut off due to unfavorable Pst , Plt - short-term and long-term flicker severity
atmospheric conditions that caused icing of turbine blades. indices
10000
9000
E Psti , E Plti - permissible values of flicker severity indices
Measured
8000 Calculated (GPC) equal to 0.35 and 0.25, respectively.
7000
Energy [MWh]
6000
5000
4000
In accordance with [7, 8] the 0.99 percentile of flicker
3000 emission from a single turbine during the continuous
2000 operations can be estimated using the formula:
1000
0
01.2010
02.2010
03.2010
04.2010
05.2010
06.2010
07.2010
08.2010
09.2010
10.2010
11.2010
12.2010
Sn
Pst = Plt = c(ψ k , va ) (3)
S k"
Figure 2. Comparison of energy actually generated with energy estimated
on the basis of GPC for each month where:
Using the value of energy AKWPP generated by KWPP in c(ψ k , va ) - flicker emission index of the single wind turbine
each month the nominal power utilization rate can be for a given phase angle ȥk of the network
calculated according to the following formula [5, 6] (Fig. 3): impedance at PCC and average wind speed ȞĮ at
hub height,
AKWPP Sn - rated apparent power of the wind turbine,
WKWPP = (1)
15 ⋅ PNT ⋅ T
S k" - short-circuit power at the PCC.
where PNT – nominal power of individual wind turbine. For many wind turbines connected to the PCC the total
50
flicker emission can be estimated using the formula:
45
40
N wt
¦ [ci (ψ k , va ) ⋅ S n,i ]2
35
1
30 Pst = Plt = " (4)
W [%]
25 Sk i =1
20
15
10
where Nwt is a number of wind turbines.
5
0
The values of flicker index c(ψ k , va ) for the E-70-E4 type
01.2010
02.2010
03.2010
04.2010
05.2010
06.2010
07.2010
08.2010
09.2010
10.2010
11.2010
12.2010
for 2010
50°
2.0 70° 2 0.2 0.50 0.1312
85° 3 0.1 0.50
5 0.7 2.00 1.6069
1.0
7 0.4 2.00 0.5247
10 0.1 0.50 0.0328
0.0 11 0.7 1.00 1.6069
6.0 7.0 8.0 9.0 10.0 13 0.6 1.00 1.1806 1.3229 2,5
v [m/s] 14 0.1 0.25 0.0328
Figure 4. Function c(ȥk,ȞĮ) for the E70- E4 type turbine 15 0.2 1.00
16 0.1 0.25 0.0328
17 0.4 0.75 0.5247
TABLE II. FLICKER INDICES AT THE PCC ESTIMATED FOR THE KWPP 19 0.1 0.75 0.0328
CONTINUOUS OPERATION 23 0.1 0.50 0.0328
1750
[MVA]
2500.0 85.0° 1.2 0.003 0.35 0.25 1500
1250
B. Current and voltage harmonics
Z [Ω]
1000
Wind turbines with power electronic converters are the 750
sources of current harmonics. According to [2, 3] the value of 500
individual current harmonic originating from wind power plant
250
with many turbines can be determined by the formula:
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500
N wt § β f [Hz]
I h,i ·
I hΣ = β ¦ ¨¨ ¸¸ (5) Figure 5. Frequency characteristics of the network impedance at the PCC for
i =1 © ni ¹ normal operation conditions
Ih/In [%]
3.0 0.4
2.5 Pst L1
0.2
Pst L2
2.0 Pst L3
0.0
1.5 2 6 10 14 18 22 26 30 34 38 42 46 50
Pst
harmonic number h
1.0
0.5 Figure 8. Comparison of current harmonics injected into the 110 kV network
by KWPP
0.0
17-10-09 18-10-09 19-10-09 20-10-09 21-10-09 22-10-09 23-10-09 24-10-09
0:00 0:00 0:00 0:00 0:00 0:00 0:00 0:00
Frequency spectrum of the measured current is in
t [d-m-r g:m]
compliance with the one contained in the "windtest" certificate
[6] up to the order of 35. The estimated values of individual
Figure 6. Values of Pst index in the measurement period
harmonics are bigger than the measured values due to the fact
that the algebraic summation of currents from individual wind
turbines were used. Relatively high values of harmonics close
3.0 to the order of 40 appear in the measurements, which are not
2.5
Plt L1 present in the “windtest”. It can be stated that these harmonics
Plt L2
Plt L3 are introduced by power electronic converters interfacing wind
2.0 generators with the supplying network.
1.5 Measured total current distortion factor of the wind power
Plt