Point of Detection Application

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Difference between Run CPU and Speed CUP SPEC Data / Point of ○ Run CPU ● DI2, DI4,5

TCD - 066 Application


Difference between Run CPU and Speed CPU characteristic SPEC data Detection ● Speed CPU ● DS4

[Meaning] In case the data of operation & speed CPU are abnormal, or ROM sum [Actions to take]
value of DPC-XXX has changed.
1. Error data check
[Diagram] - DI4 : ‘A53E’ ⇒ address 9909
- DS4: ‘A53E’ ⇒ address 010E.

2. In case bit0 was set ($01)


Start DI2 : check if the data of address 0205 (GD2_Low) is 0x64.
And address 0206 (GD2_High) is 0x00.
If data value is extremely small, set the data of address
Motor speed > 120% of 0205 to be 0x64.(DI2)
standard?
No
2-1. In case of DI-4,5 , inquire the standard data to factory
2-2. Compare the SPEC data as actions to take of TCD 54
Yes 123% RPM > 1930RPM(GD)? No
123%RPM > 300 RPM(GL) 3. In case bit1 was set($02) - Take action as 2-2 above.

Yes 4. In case Bit2 was set


SPEC data is not exist? Non defined SPEC data is written in 0200 to 020F.
Clarity_data No Record data of address 0000~000F by ‘A51E’ for inquiry.
bit 0 set Yes
ROM sum data of DPC-XXX
No 5. In case Bit2 was set
PCB has changed? ROM sum has changed, replace INV ROM of DPC -310
Clarity_data PCB.
bit 1 set Yes ( Whenever ROM replacement, do SPEC writing by ‘A52E’,
and turn off and on main power when TCD66 has occurred.)
Clarity_data
bit 2 set

Clarity_data
bit 3 set

End