Point of ● Run CPU ○ DI120~150

TCD - 106 SD7D ON Error Application


Detection ○ Speed CPU ● DI180~420

[Meaning] SD7D does not operate at the bottom floor. [Actions to take]
※ To prevent any possible clash accidents caused by forced reduction
function not working at bottom floor on account of any ON errors such 1. Check wiring network for LIMIT S/W
as SD7D deposition, etc. - Check for bad connection of MIC and signal voltage

[Diagram] << S/W SKELETON >> 2. Check the operation of input buffer
ERR_EEPROM_FHT_SUMERR_NVRAM_FHT_SUM Err_Digital_Floor FAST_RUN_COMMAND
- Verify if voltage changes from 48V to 0V at the operation of SD7D.
- Check the address value from NVRAM READ MODE of Ann.
(Refer to H/W SKELETON)
(Normally, 0xFF should be changed into x00 at the operation of
POWER_READY_T ZONE_135MM LDC IS_CDS D1 IS_SD7D(ADDR:0x500D))
S - For 180 or more m/min, refer to H/W SKELETON drawing (3X02228
I/O C.[2])
D1 *Logical_Current_Floor =1 Equ_Sds_Tot_No & SDS7 BIT OR(SD7D) tmp_TXSDSR
check_off_history(XSD7D) = TRUE
3. Check any bend of LIMIT S/W CAM
tmp_TXSDR = TXSDSR tmp_TXSDR & SD7D - Visually check LIMIT S/W CAM for any bend
TCD 106 - Verify if roller does not deviate from the CAM when cage is
fluctuated right and left within car.
tmp_TXSDR
tmp_TXSDR
TXSDSR

<< H/W SKELETON >>


P48C ABOVE 180m/min OR BELOW 105m/min GD48
LSU-06 RCA-12 RCA-12
Y6-03

LSU-05 SD1U Y6-02 INB-05 DOR-230 IS_SD1U


INB-05 5005
ABOVE 180m/min OR BELOW 105m/min
LSU-08 RCA-14 RCA-14

LSU-07 SD2U Y6-03 INB-06 DOR-230 IS_SD2U


INB-06 5010

SD3U Y6-04 INB-07 DOR-230 IS_SD3U


INB-07 5011
ABOVE 180m/min OR BELOW 105m/min
LSD-06 RCA-13 RCA-13

LSD-05 SD1D Y6-05 INB-08 DOR-230 IS_SD1D


INB-08 5007
ABOVE 180m/min OR BELOW 105m/min
LSD-08 RCA-15 RCA-15

LSD-07 SD2D Y6-06 INB-09 DOR-230 IS_SD2D


INB-09 5008