Intrinsically safe isolator
Salwico NS-ISOLATOR
Part no. N1770
‘System: Salwico fire alarm systems
CS4000, NSAC-1, CS3000*, C300 series, Servomaster
Description Data, isolator
NS-ISOLATOR is a Pepprl and Fuchs Type KFDO-CS- Port number 11765 (isolator)
Ex1.S1P isolator. which is part of the Salico Nominal voltage 4-35 VDC
conventional intrinsically safe fre detection system. Approval (EExia]
Cable terminals 25 mm
Ambient temperature 20°C to +60°C
‘The NS-ISOLATOR barrier is located in a non hazardous ‘Ambient bamadity 0 100% RH (when mounted
area (safe area) and forming the interface to IS detectors im the enclosure box)
and other IS line units. ‘Weight 100 g (isolator)
‘The NS-ISOLATOR does not aced a separate power Data, isolator
supply. It is powered directly from the fire alarm pane]
‘ia the Loop section cables. which means thet no extra Part nusiber 11766 (enclosuse)
cables are needed. Ingress protection IPS.
Cable glands 98 - 14mm
‘The NS-ISOLATOR does not need an earth connection, Material, Polystyrol
and thus routine inspection of earth cable and connections Colour Grey, Blue
4s climinated Weight 620 g (with the isolator
‘The box has knock-out holes on the sides for the three ‘mounted inside)
included cable glands. The glands must be mounted on
the short sides of the box as chown in this data sheet.
*Only with SPK-2 for NOSE based detectors.
Connection
‘Safe area | Hazardous area
NSAC-1, Addressable $4000, C3000
\
'
'
6200, 6303, 6308, C816, 654000 conventfpna, NSAG-1 conventional
Senate’ coment ey Pra en
Ee olrm sector faye te FFF) | 10 Kea (200, C202, 308, C218, €34000, NSAC-1)
CS HE f ecmnca one
PT Sa WESTIE
www lavastica.comIntrinsically safe isolator
Salwico NS-ISOLATOR
Dimensions (mm)
180.
a7 Xe
I] ses canoes,
Seay SOR ORE mpRaTeT NEE Gas est = NIONSSOTOR TIE
Paget?
www lavastica.com