Roof Load Calculation: Preliminary Data Building Dimension
Roof Load Calculation: Preliminary Data Building Dimension
1 Preliminary Data
1.1 Building Dimension
Height of the Building (including the truss structure) 6.5 m
Width Of the Building (W) 21.42 m
Length of the Building (l) 15.32 m
Pitch Height 1 m
Angle 8.3 degree
Longest span of Purlin 7.40 m
Spacing of Purlin 0.99 m
1.2 Material Property
Stress of the Steel Section 250 Mpa
2 Load Calcualtion
2.1 DL Loads
Weight of Roofing Materials 200 N/m2
Tiles/Water proofing N/m2
Purlins @ 0.99 m c/c N/m2
Other accessories 50 N/m2
Total DL 250 N/m2
Load per m in Purlin, Spacing of Purlin is 0.99 m 0.25 KN/m
900(cpe4)
E G
0 cpe1
0 00 Cpe3
F H
3 Design of Purlins:
3.1 Considering wind and DL combination.
Longest span of Purlin 7.4 m
Spacing of Purlin 0.99 m
The Critical load combination would be (DL+WL) uplift -1.45 kN/m2
Load per m in Purlin, Spacing of Purlin is 0.99 m -1.47 KN/m
Maximum Moment = -10059887.2 kN/m
Section Modulus Required, Zreq = 27504.8 mm3
yield stress of steel = 250 Mpa
3.2 Considering DL and IL combination.
Longest span of Purlin 7.4 m
Spacing of Purlin 0.99 m
The Critical load combination would be (DL+IL) 1.034 kN/m2
Load per m in Purlin, Spacing of Purlin is 0.99 m 1.04444444444 kN/m
Maximum Moment = 7149222.22222 Nmm
Section Modulus Required, Zreq = 25997.172 mm3
Thus, Choose SHS 1.5" (THK. 3.60 mm) yield stress of steel = 250 Mpa
0.914634
9.756098