All hold items shall Location of Fire


be replaced with station building shall
relevant information be updated as per
prior to the next plot plan.
I I
issue of the
drawing.

C2 column can be
optimized to
500x500. Bolt edge
H distance seems H
large. See
comments on
327106-BJ81-C-
RCC-0007 dwg also.

All hold items shall


be replaced with
relevant information
prior to the next
issue of the
drawing.

G G

All reinforcing bars shall be of high yield


type II deformed bars conforming to BS
4449 with a characteristic strength of 460
N/mm2. Concrete shall be of grade C35 and
blinding concrete shall be of grade C20.
Minimum lap & anchorage shall be provide
as per BS 8110. All exposed edges of
concrete shall have 25x25 chamfer.

F F

E E
REFERENCE DOCUMENTS:
DRAWING NO DRAWING TITLE

List the quantities


as per construction
sequence

D D

Add a column for


ECW MTO

C C
00 11-JUL-2018 ISSUED FOR REVIEW TPS RR TSM RAP
PA 09-JUL-2018 ISSUED FOR IDC TPS RR TSM RAP
REV DATE DESCRIPTION DWN PRP CHK APP
INFORMATION IN THIS DOCUMENT IS PROPERTY OF FLOREXX, BEING PROHIBITED OUTSIDE OF THEIR PURPOSE

COMPANY:

PROJECT MANAGEMENT CONSULTANT:


RAMBOLL OIL & GAS MIDDLE EAST
B
ABU DHABI B
CONTRACTOR:
SNC-LAVALIN
UAE
COMPANY PROJECT NO: CONTRACTOR PROJECT NO:
327101 614030
PROJECT TITLE:
100 KBPD TOPPING REFINERY, EBED
CONTRACTOR DRAWING NO:
614030-BJ81-42D1-0006
DRAWING TITLE:
ECW-FIRE STATION AND CLINIC BLDG
A A

The drawing / document is reviewed considering Contractor SNCL has ensured total integration between Design basis- Specification-Calculation-Analytical
model-drawings. Any anomalies SHALL Be rectified by SNCL without time and Cost impact to Company (Florexx) SCALE: COMPANY DRAWING NO SHEET REV

1:50 327101-BJ81-C-RCC-0006 00