3000TC0705

01/2008
Trip Curve LaVergne, TN, USA

IEC-RI-10PU(1)
Rapid Inverse
3000TC

100
1 T

3000TC0705-IEC-RI-DE50869b
t d ( I ) = ----------------------------------------------------- × ------------------
– 1 3.1706
0.339 – 0.236 ⎛ ----⎞
I
⎝ I s⎠

where:
td = Operate time (sec)
T = time setting (sec) at I/Is = 10
10 12.5

NOTES: Operating Time in Seconds 5


1. (1) The following minimum operate thresholds (I / Is)
apply:
2.5
SIT, VIT, LTI, EIT, UIT @ I / Is=1.2
RI, IAC-SIT, IAC-VIT, IAC-EIT @ I / Is=1.0
SIT-A, VIT-B, LTI-B, EIT-C, IEEE MI, IEEE VI, IEEE 1.2
EI @ I/ Is=1.1 1
2. When the monitored value is more than 20 times the 0.8
set point, the tripping time is limited to the value
corresponding to 20 times the set point.
0.4
3. If the monitored value exceeds the measurement
capacity of Sepam™ (40 IN for the phase current
channels, 20 INr for the residual current channels), the 0.2
tripping time is limited to the value corresponding to
the largest measurable value (40 IN or 20 INr). 0.1 0.1

0.01
1 10 100
Current I / Is