Professional Documents
Culture Documents
FLUSARC 36kV - 630A - 25ka Maintenance Manual PDF
FLUSARC 36kV - 630A - 25ka Maintenance Manual PDF
FLUSARC 36kV - 630A - 25ka Maintenance Manual PDF
FLUSARC 36 kV - 630 A - 25 kA
Medium Voltage Distribution
Maintenance Instructions
NHA8934901 Rev.01
11/2016
Information maintenance
All range of Flusarc-36 is maintenance free on active parts. ( presurized seeled tank)
Operating conditions
Normal operating conditions:
Normal service conditions following §2.1.1 CEI 62271-1
[-25°C ; +40°C]
Device installed in environment category 3C1 or 3C2 (IEC 60721-3-3)
Not standard / Severe operating conditions:
If one point of the normal operating conditions is not respected
[-25°C ; +40°C]
For wind farms device
Levels of maintenance
Maintenance level (who can carry out the corrective maintenance operation)
Level 1/2: Customer Level 4: Schneider Service Center (advanced)
Level 3: Local LAU / =S=service center (basic) Level 5: Factory return
Preventive maintenance
Normal operating conditions Harsh operating conditions
Level
Preventive maintenance Corrective operation Year 1 Year 2 Year 3 Year 4 Year 5 Year 6 Year 1 Year 2 Year 3 Year 4 Year 5 Year 6
- Verify that on the cables’ - Clean the terminals if needed with a clean
lvl1/2
terminals there aren’t any cloth
■ ■ ■ ■ ■ ■ ■ ■ ■
- In case of damage, contact SE
damages
- Make sure that the - if damages are detected on the tank,
apparatus doesn’t show any check the SF6 pressure
lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
deformations, piles of dust, -Clean the external components wih a
dirt, or damages clean and dry cloth
- If grease is missing or corroded ==>
degrease and grease the mobile parts of
the operating mechanism.
- If red rust is detected on mobile parts of
- Check mechanical
operations indicated in the
the origin of the corrosion 2- follow up the lvl 4/5
instructions manual
damage 3- contact SE if the problem
”installation - operation - ■ ■ ■ ■ ■ ■ ■ ■ ■
increases
maintenance”. Check the
- If operating coils are damaged or sticked
positioning of the status
by rust, it has to be changed (see spare
indicators (Open/Closed),
part policy)
- If broken or damage parts are detected,
contact Schneider Electric.
- Check the chain. If needed, degrease and
lvl 3/4
grease it
- Operate the mechanism manualy (1 or 2
- Verify that the geared motor
operations) and test again the controled
of the CB unit (if present)
geared motorization lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
automatically loads the
- Check that the micrsowitches move in
spring.
accordance of the main switch position.
- If there is red rust on the motor, it has to be
changed (see spare parts policy)
CAUTION
Operation performed under voltage.
The principle of the phase concordance unit is that it allows a check of the phase
concordance between 2 energized functional input units on the same substation.
Phase concordance testing must be carried out each time a cable is connected to
a functional unit. It is a way of making sure that all three cables are each connec-
ted to the corresponding phase of the substation.
Only undertake the work after having read and understood all the explanations
given in this document.
If you have any difficulty complying with these rules, please contact Schneider
Electric.
The contractor must be certified and authorized to manipulate and perform work
on the unit.
Functional unit 1 Functional unit 2 Phase concordance unit Compatibility result Corrective actions
VPIS ELEN VPIS ELEN
Comparateur VPIS - V2 (VPI62421) Use a phase concordance
OK
unit VPIS ELEN.
VPIS ELEN VPIS-V2
OK Use the adaptator kit + voltmeter.
VPIS-V2 VPIS-V2
OK
VPIS-V2 VPIS-V2
OK Use a phase concordance unit V2.
Checking of
the phase You can test.
concordance
units
CAUTION
Voltmeter is not supplied by Schneider Electric.
The 3 indicator lights of the 2 VPIS are lit and the phase concordance unit
is correct, meaning that phase concordance test can be performed.
LED unlit
Functional unit1
Functional unit2
Change the Change the Reverse the MV Reverse the MV Reverse the MV
Conclusion
position of each position of each cables connected cables connected cables connected
regarding Connection is
MV cable on MV cable on to L1 and L3 on to L2 and L3 on to L1 and L2 on
phase satisfactory.
one of the 2 one of the 2 one of the 2 one of the 2 one of the 2
concordance.
functional units. functional units. funcional units. funcional units. funcional units.
Description:
The voltmeter adapter kit is used to test phase matching between VPIS V2 and
VPIS ELEN. This kit is only used to check phase matching: it is therefore not used
to measure or deduce the voltage present on the medium-voltage network.
■ The two test clips have to be connected to the earth of each cubicle to be tested.
■ Connect the two adapters to the two main plugs on the voltmeter.
■ Connect each of the adapters to output L1 on the two voltage presence indicators
to be tested.
■ IMPORTANT: this phase matching check can only be performed: If the medium-
voltage network supply is on.
If the voltage presence indicator lights are on.
VPIS A
L1 L2 L3
L1 <3 VCA / VAC >3 VCA / VAC >3 VCA / VAC
VPIS A L2 >3 VCA / VAC <3 VCA / VAC >3 VCA / VAC
L3 >3 VCA / VAC >3 VCA / VAC <3 VCA / VAC
Greasing procedure
WARNING
Degreasing and greasing operations must be performed by using
only the products indicated in the following box.
WARNING
Degreasing of the concerned components is mandatory before any
lubrication.
WARNING
The proper greasing product must be chosen according to the service
conditions indicated in the following box.
DEGREASING DEGREASING
PARTS TO BE GREASED STD & HARSH SERVICE CONDITIONS STANDARD SERVICE CONDITIONS HARSH SERVICE CONDITIONS
MOTORIZATION GEARS + CHAIN ABSOL 64 MECHANICAL GREASE 28 MECHANICAL GREASE GLY 801
CB FUNCTION
LATCHING BEARINGS ABSOL 64 VASELINE OIL “REF 11” S.K.D. 16
1 – Fuses box:
2 – Mechanism box:
■ Verify if the mechanism is free to move. If not please, contact Schneider Electric.
DANGER
Before proceeding to carry out the operations for removing/installing the parts
composing the FLUSARC switchgear, be sure that the voltage was cut out to the
primary circuit and to the auxiliary one.
Replacement of a fuse
NOTICE
For an apparently single phase fault, it is imperative that all 3 fuses be replaced..
CAUTION
The body of a fuse can become very hot following a short circuit. Take standard
precautions (leather gloves) before starting work.
NOTICE
Whenever changing or fitting a fuse, close the compartment immediately
afterwards to avoid letting dust and humidity enter.
mechanism restore
■ Turn the lever clockwise, up to reach the end of stroke. The mimic diagram
SPL9110
■ After unlocking the fuse compartment door handle by the key, rotate the handle
SPL9201
■ Fully open the fuses compartment door, in order to restore the correct position of
SPL9202
■ Apply the lever to the fuseholder cover and screw into the two holes predisposed
KJA74KK
Insert the new fuse from the striker side on the cover, by paying attention that the
KJA78KK
Interlock Interlock ■ The figure shows the correct positioning of the cover interlock.
KJA6000
No Yes
Cover
■ Unscrew the wing screws and remove the lever from the cover.
KJA74KK
■ Close the fuse compartment door by rotating the handle clockwise and
SPL9203
NHA8934901
NHA8934901 rev 01-FLUSARC-36_(EN)
01-FLUSARC-36_(EN) 31
17
FLUSARC Maintenance
in this publication.