FLUSARC 36kV - 630A - 25ka Maintenance Manual PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

FLUSARC Maintenance

FLUSARC 36 kV - 630 A - 25 kA
Medium Voltage Distribution

Maintenance Instructions
NHA8934901 Rev.01
11/2016

NHA8934901 rev 01-FLUSARC-36_(EN) 1


FLUSARC Maintenance

Information maintenance
All range of Flusarc-36 is maintenance free on active parts. ( presurized seeled tank)

Operating conditions
Normal operating conditions:
Normal service conditions following §2.1.1 CEI 62271-1
[-25°C ; +40°C]
Device installed in environment category 3C1 or 3C2 (IEC 60721-3-3)
Not standard / Severe operating conditions:
If one point of the normal operating conditions is not respected
[-25°C ; +40°C]
For wind farms device

Levels of maintenance
Maintenance level (who can carry out the corrective maintenance operation)
Level 1/2: Customer Level 4: Schneider Service Center (advanced)
Level 3: Local LAU / =S=service center (basic) Level 5: Factory return

Preventive maintenance
Normal operating conditions Harsh operating conditions
Level
Preventive maintenance Corrective operation Year 1 Year 2 Year 3 Year 4 Year 5 Year 6 Year 1 Year 2 Year 3 Year 4 Year 5 Year 6

- Re-tighten connectors if needed.


- Check that the LV
- Clean the connections if needed with a lvl 1/2
connections aren’t loose and
clean and dry cloth ■ ■ ■ ■ ■ ■ ■ ■ ■
that they don’t show any
traces of rust or oxidation - Change the damaged parts lvl 3/4

- Verify that on the cables’ - Clean the terminals if needed with a clean
lvl1/2
terminals there aren’t any cloth
■ ■ ■ ■ ■ ■ ■ ■ ■
- In case of damage, contact SE
damages
- Make sure that the - if damages are detected on the tank,
apparatus doesn’t show any check the SF6 pressure
lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
deformations, piles of dust, -Clean the external components wih a
dirt, or damages clean and dry cloth
- If grease is missing or corroded ==>
degrease and grease the mobile parts of
the operating mechanism.
- If red rust is detected on mobile parts of
- Check mechanical
operations indicated in the
the origin of the corrosion 2- follow up the lvl 4/5
instructions manual
damage 3- contact SE if the problem
”installation - operation - ■ ■ ■ ■ ■ ■ ■ ■ ■
increases
maintenance”. Check the
- If operating coils are damaged or sticked
positioning of the status
by rust, it has to be changed (see spare
indicators (Open/Closed),
part policy)
- If broken or damage parts are detected,
contact Schneider Electric.
- Check the chain. If needed, degrease and
lvl 3/4
grease it
- Operate the mechanism manualy (1 or 2
- Verify that the geared motor
operations) and test again the controled
of the CB unit (if present)
geared motorization lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
automatically loads the
- Check that the micrsowitches move in
spring.
accordance of the main switch position.
- If there is red rust on the motor, it has to be
changed (see spare parts policy)

2 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC
FLUSARC Maintenance
Maintenance

Normal operating conditions Harsh operating conditions


Level
Preventive maintenance Corrective operation Year 1 Year 2 Year 3 Year 4 Year 5 Year 6 Year 1 Year 2 Year 3 Year 4 Year 5 Year 6

- Check the chain. If needed, degrease and


lvl 3/4
grease it
- Check that the line control - Operate the mechanism manualy (1 or 2
geared motor (if present) operations) and test again the controled
automatically provides to geared motorization lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
open and to close the - Check that the micrsowitches move in
disconnector. accordance of the main switch position.
- If there is red rust on the motor, it has to be
changed (see spare parts policy)
- Check that the Voltage indicator LED´s
lvl 1/2
are in the same state
- Voltage indicator checking ■ ■ ■ ■ ■ ■ ■ ■ ■
- Check the integrity of the wires connected
lvl 3/4
to the bushings
- [0,3 bar ; P (SF6) ; 0,2 bars] (at 20°C R.T
& sea level) : Normal pressure
- [0,2 bar ; P (SF6) ; 0,1 bars] (at 20°C R.T
& sea level) : Open the circuit breaker,
- Check the SF6 pressure
disconnectors and earthing lines and
(manometer, pressure lvl 1/2 ■ ■ ■ ■ ■ ■ ■ ■ ■
contact SE for intervention
switch)
- [0,1 bar ; P (SF6) ; 0 bars] (at 20°C R.T &
sea level) : Do not operate the RMU. Open
the upstream and downstream lines and
contact SE for intervention
- Check the interlocks’
correct operation, by
executing a putting into - If damaged/missing components, see
lvl 3/4 ■ ■ ■
service operation and a spare part policy
putting out of service
operation
- Check the fault detection relay settings
- Operate the op. mechanism manualy (1
- Check that the operating
or 2 times) and control once again the
times of the opening and
opening and closing times.
closing controls of the CB
- If grease is missing or corroded, degrease lvl 3/4 ■ ■ ■
unit circuit-breaker are
and grease the mobile parts of the
comprehended within the
operating mechanism
correct values
- If parts are damaged, need SE
intervention
- Re-tighten connectors if needed.
- Clean the connectors
. if needed with a lvl 1/2
- Check that the caps are ■ ■ ■ ■ ■ ■ ■ ■ ■
clean and dry cloth
installed properly in the
.
upper bushing on - Change the damaged parts lvl 3/4
extensible compact
- Clean the terminals if needed with a clean
version (if they are lvl 1/2
cloth
needed) ■ ■ ■ ■ ■ ■ ■ ■ ■
- In case of damage, contact SE

NHA8934901 rev rev


NHA8934901 01-FLUSARC-36_(EN)
01-FLUSARC-36_(EN) 3 23
FLUSARC Maintenance
Maintenance

Phase concordance verification

CAUTION
Operation performed under voltage.

The principle of the phase concordance unit is that it allows a check of the phase
concordance between 2 energized functional input units on the same substation.

Phase concordance testing must be carried out each time a cable is connected to
a functional unit. It is a way of making sure that all three cables are each connec-
ted to the corresponding phase of the substation.

Ø2 mm test probe made of stainless steel. Minimum length: 10 mm. Ø4 mm rigid


socket accepting spring-loaded Ø4 mm with rigid insulating sleeve (banana plug).

General safety rules:

P.P.E. Personal Protective Equipment required during cells interventions.


All the operations described below must be performed in compliance with
applicable safety standards, under the responsibility of a competent authority.

Only undertake the work after having read and understood all the explanations
given in this document.

If you have any difficulty complying with these rules, please contact Schneider
Electric.

The contractor must be certified and authorized to manipulate and perform work
on the unit.

4 NHA8934901 rev 01-FLUSARC-36_(EN) NHA8934901 rev 01-FLUSARC-36_(EN) 3


FLUSARC Maintenance
Maintenance

1 - Choice of phase concordance unit:

Functional unit 1 Functional unit 2 Phase concordance unit Compatibility result Corrective actions
VPIS ELEN VPIS ELEN
Comparateur VPIS - V2 (VPI62421) Use a phase concordance
OK
unit VPIS ELEN.
VPIS ELEN VPIS-V2
OK Use the adaptator kit + voltmeter.

VPIS-V2 VPIS-V2
OK

VPIS ELEN VPIS ELEN Comparateur VPIS ELEN (AA.01.00.35)


OK

VPIS ELEN VPIS-V2


OK Use the adaptator kit + voltmeter.

VPIS-V2 VPIS-V2
OK Use a phase concordance unit V2.

Adaptator kit + voltmeter (EM558437)


VPIS ELEN VPIS-V2
OK

2 - Check before phase concordance test:


Cas 1 Cas 2 Cas 3

Test Result Actions


The 3 indicator lights of each The 2 functional units are energised, the VPIS units are operating and
Checking of the VPIS are on. the check can continue.
VPIS units of The 3 indicator lights of the VPIS
functional unit 1 The functional unit is not energised or the VPIS is defective.
are off.
and 2.
1 or 2 indicator lights unlit. 1 or 2 phases are not energised or the VPIS is defective.

Checking of
the phase You can test.
concordance
units

4NHA8934901 rev 01-FLUSARC-36_(EN) NHA8934901 rev 01-FLUSARC-36_(EN)5


FLUSARC Maintenance

3 - Rules of choosing phase concordance unit:

CAUTION
Voltmeter is not supplied by Schneider Electric.

Balanced phases: the phase concordance unit light (1) is unlit.


(Except Case 3: refer to point 5).

Unbalanced phases: the phase concordance unit light (1) is lit.


(Except Case 3: refer to point 5).

Cas 1 Cas 2 Cas 3


VPIS-V2 VPIS-V2 ELEN

VPIS-V2 ELEN ELEN

V2 (VPI62421) ELEN (AA.01.00.35)

Adaptator kit + voltmeter

4 - Phase concordance unit test


(with V2 and ELEN):

The 3 indicator lights of the 2 VPIS are lit and the phase concordance unit
is correct, meaning that phase concordance test can be performed.

GLOSSARY phase concordance unit LED lit (unbalanced phases)

LED unlit

6 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Maintenance

Functional unit1
Functional unit2

Change the Change the Reverse the MV Reverse the MV Reverse the MV
Conclusion
position of each position of each cables connected cables connected cables connected
regarding Connection is
MV cable on MV cable on to L1 and L3 on to L2 and L3 on to L1 and L2 on
phase satisfactory.
one of the 2 one of the 2 one of the 2 one of the 2 one of the 2
concordance.
functional units. functional units. funcional units. funcional units. funcional units.

5 - Voltmeter adapter kit:

Description:

The voltmeter adapter kit is used to test phase matching between VPIS V2 and
VPIS ELEN. This kit is only used to check phase matching: it is therefore not used
to measure or deduce the voltage present on the medium-voltage network.

Connecting the adapters:

■ The two test clips have to be connected to the earth of each cubicle to be tested.

■ Connect the two adapters to the two main plugs on the voltmeter.

NHA8934901 rev 01-FLUSARC-36_(EN) 7


FLUSARC Maintenance

6 - Setting the voltmeter and connecting to the voltage


presence boxes:

■ Choose V AC (or V ~ according to the devices)

■ Connect each of the adapters to output L1 on the two voltage presence indicators
to be tested.

■ IMPORTANT: this phase matching check can only be performed: If the medium-
voltage network supply is on.
If the voltage presence indicator lights are on.

■ The mismatch threshold is 3 V AC:


Measured voltage less than 3 V AC match
Measured voltage greater than 3 V AC mismatch

■ IMPORTANT: all the combinations shown in the matrix below must


be tested to ascertain whether the adapters and the voltmeter are
operating correctly.

VPIS A
L1 L2 L3
L1 <3 VCA / VAC >3 VCA / VAC >3 VCA / VAC
VPIS A L2 >3 VCA / VAC <3 VCA / VAC >3 VCA / VAC
L3 >3 VCA / VAC >3 VCA / VAC <3 VCA / VAC

8 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Maintenance

Greasing procedure

The greasing process is needed to avoid the corrosion of bearings or mechanical


contact areas and the Blockage / decrease of performances, due to lack of
lubricant or lubricant degradation in time.

WARNING
Degreasing and greasing operations must be performed by using
only the products indicated in the following box.

WARNING
Degreasing of the concerned components is mandatory before any
lubrication.

WARNING
The proper greasing product must be chosen according to the service
conditions indicated in the following box.

DEGREASING DEGREASING

PARTS TO BE GREASED STD & HARSH SERVICE CONDITIONS STANDARD SERVICE CONDITIONS HARSH SERVICE CONDITIONS

TRANSFER RODS ABSOL 64 MECHANICAL GREASE 28 MECHANICAL GREASE GLY 801

MOTORIZATION GEARS + CHAIN ABSOL 64 MECHANICAL GREASE 28 MECHANICAL GREASE GLY 801
CB FUNCTION
LATCHING BEARINGS ABSOL 64 VASELINE OIL “REF 11” S.K.D. 16

CAM BEARINGS ABSOL 64 VASELINE OIL “REF 11” S.K.D. 16

GEARS + CHAIN ABSOL 64 MECHANICAL GREASE 28 MECHANICAL GREASE GLY 801


C FUNCTION
BEARINGS ABSOL 64 VASELINE OIL “REF 11” S.K.D. 16

NHA8934901 rev 01-FLUSARC-36_(EN) 9


FLUSARC Maintenance

Maintenance on trip mechanism side

1 – Fuses box:

Maintenance only if the mechanism is evident blocked.

■ Open the fuse box.

■ Grease the indicated parts without disassembling them.

■ If dust is on plastic mechanism, clean it with dry and clean cloth.

■ Grease the part number 1 if it is necessary.

■ NO grease the part number 2

2 – Mechanism box:

Maintenance only if the mechanism is evident blocked.

■ Remove the mechanism cover.

10 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Maintenance

■ Verify if the mechanism is free to move. If not please, contact Schneider Electric.

■ Verify the correct position on lever of micro-switch.

■ Degrease and grease this parts if necessary.

NHA8934901 rev 01-FLUSARC-36_(EN) 11


FLUSARC Maintenance

Replacement of the three fuses

Intervention Busbar C ables Load Break Switch Earthing switch


Normal de-energized de-energized open closed
Possible energized de-energized open closed
Locking out the Functional Unit
All locking out operations must be performed according to the particular rules for the
network concerned.
Tools required:
■ leather gloves
■ compartment key
■ small, flatheaded screwdriver
■ fuse holder cover lever.
Parts required:
■ 3 fuses with the same reference (verify values in accordance with the transformer
power)

DANGER
Before proceeding to carry out the operations for removing/installing the parts
composing the FLUSARC switchgear, be sure that the voltage was cut out to the
primary circuit and to the auxiliary one.

See the corresponding chapter in the Installation Manual for the


characteristics of the fuses.

Replacement of a fuse

NOTICE
For an apparently single phase fault, it is imperative that all 3 fuses be replaced..

CAUTION
The body of a fuse can become very hot following a short circuit. Take standard
precautions (leather gloves) before starting work.

NOTICE
Whenever changing or fitting a fuse, close the compartment immediately
afterwards to avoid letting dust and humidity enter.

Transformer protection operating


SPL9107

mechanism restore

■ Turn the lever counter clockwise, up to reach the end of stroke.


The mimic diagram indicator will remain in the open line position .

12 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Maintenance

■ Turn the lever clockwise, up to reach the end of stroke. The mimic diagram
SPL9110

indicator will turn from the open earth position .

■ Extract the operating lever.

■ Ensure that the function’s earthing switch is closed.


SPL9200

■ Act on the interlock of the door, by shifting it rightwards.

■ After unlocking the fuse compartment door handle by the key, rotate the handle
SPL9201

itself counter clockwise.

■ Fully open the fuses compartment door, in order to restore the correct position of
SPL9202

the rod placed on the fuses compartment door.

NHA8934901 rev 01-FLUSARC-36_(EN) 13


FLUSARC Maintenance

■ Apply the lever to the fuseholder cover and screw into the two holes predisposed
KJA74KK

on the cover the two finned screws.

■ Turn the lever counter clockwise for a fourth of a revolution.


KJA75KK

■ Extract the cover with the fuse.


KJA76KK

■ Remove the fuse from the cover.


KJA7700

Insert the new fuse from the striker side on the cover, by paying attention that the
KJA78KK

fuse base gets into the spring acting as an interlock.

14 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Maintenance

Interlock Interlock ■ The figure shows the correct positioning of the cover interlock.
KJA6000

No Yes

Cover

■ From the fuse opposite side, insert the centering disc.


KJA7900

■ Insert the cover with the fuse.


KJA76aKK

■ Turn the lever clockwise and lock the cover.


KJA75aKK

NHA8934901 rev 01-FLUSARC-36_(EN) 15


FLUSARC Maintenance

■ Unscrew the wing screws and remove the lever from the cover.
KJA74KK

■ Close the fuse compartment door by rotating the handle clockwise and
SPL9203

successively locking it by the key.

16 NHA8934901 rev 01-FLUSARC-36_(EN)


FLUSARC Notes

NHA8934901
NHA8934901 rev 01-FLUSARC-36_(EN)
01-FLUSARC-36_(EN) 31
17
FLUSARC Maintenance

Schneider Electric Industries SAS


35, rue Joseph Monier
92500 Rueil Malmaison - France
Tél. : +33 (0)1 41 29 70 00
www.schneider-electric.com

in this publication.

© 2016 Schneider Electric. All rights reserved

NHA8934901 - REV. 01 - 05/2016

18 NHA8934901 rev 01-FLUSARC-36_(EN)

You might also like