Professional Documents
Culture Documents
Frequency Converter (FC) Rating: Load Characteristics
Frequency Converter (FC) Rating: Load Characteristics
Load characteristics
Before the frequency converter size can be determined, a distinction
must be made between the two most widely used load characteristics.
Figure 1 shows the four most typical motor loads and their
characteristics.
Figure
1 – Typical motor load characteristics
When the speed of centrifugal pumps and fans increases, the power
requirement increases by the speed cubed (P = n 3). The normal working
range of centrifugal pumps and fans is the speed range of 50 to 90%.
The load ratio increases by the speed squared, i.e. approx. 30 to 80%.
Figure 2
– Constant and square load torque
For both torque characteristics the same load characteristics were entered for a
centrifugal pump.
In Figure 3, the total working range of the pump (0-100%) lies within the
rated values of the motor. Since the normal working range of the pump
is 30-80%, a frequency converter with a lower output can be chosen.
If the load torque is constant, the motor must be able to generate more
than the load torque as the excess torque is used for acceleration.
An overload torque of 60% generated by the frequency converter for a
short time is enough for acceleration and high starting torque, for
example in connection with conveyor belts.
The overload torque also guarantees that the system is able to cope
with sudden increases of load. A frequency converter that does not allow
any overload torque has to be selected such that the acceleration torque
(TB) lies within the rated torque.
Fi
gure 5 – Overload torque is used for acceleration
Figure 8 – Selection of
a frequency converter according to shaft output power