Professional Documents
Culture Documents
MeasurementofRIV ICOLIM 2004 I e
MeasurementofRIV ICOLIM 2004 I e
Abstract
The paper points out some practical aspects and remarks, from authors’ experience regarding
the measurements of radio-frequency interference voltages due to insulator sets and other
equipment for high-voltage overhead transmission lines. A critical review of today’s
international standards concerning this type of tests is also included.
1. Introduction
2.1. Generalities
According to CISPR 18-2 Publication, [2], the measuring circuit has the lay-out shown in
Fig.1, in which: EUT is the equipment under test, Tr. – a high-voltage test transformer, D – an
a.c. voltage divider, Co. – a corona free connection, simulating the line conductor, Cc. – a
coaxial cable, terminated in its characteristic impedance Zc at each end (R1 = Rm = Zc).
The others constituent parts of the circuit, as well as their prescribed characteristics are
specified in Table 1.
The measuring set – usually a receiver with a quasi-peak detector – shall be consistent
with the specifications of CISPR 16-1 Publication.
The high-frequency disturbance currents ip , generated by corona and micro-gap
discharges at the EUT are divided in:
• a current im , through the measuring impedance;
• a current ie , to ground, through the capacitance Ce of the EUT and
• a current is , to the test voltage transformer, limited by the rejection filter F.
The characteristics of the circuit have been established so that the largest amount of the
disturbance current flows through the measuring impedance.
C1
or
L1
C2
is Co.
F L2
im
Zs
Cd or
ip ie
EUT
Tr. C3 Measuring
D R2 set
Ce
L3
R1 Cc. (Zc) Rm
(Um )
Test voltage
measurement
2
The results of ours experiments, on an 110 kV suspension insulator set – partially
exposed in Table 2 – point out a practically constant RIV level, for various measurement
frequencies, between 0.5 MHz and 2 MHz.
An important feature of the measuring circuit is that it must withstand the high
power-frequency test voltage. Usually, this shall be 1.1⋅ Un / 3 , for equipment tested with
respect to earth (Un – the nominal system voltage), [2], but the test procedure implies a
maximum applied voltage about 10 % higher. The impedance ZS – the coupling capacitor C3
or the L2 – C2 series circuit, in fig.1 – shall withstand this voltage!
2.2. Remarks on the impedance Zs
The impedance Z s may be a coupling capacitor (C3) or a series circuit (L2 – C2), tuned to
the measurement frequency. Both variants shall meet the requirement (2), (3) and (4), stated
in Table 1, [2].
The coupling capacitor is the most used solution, since it allows changes of the
measurement frequency, in relative large interval, during the test, to avoid the frequencies
with unacceptable background noise levels. To meet, simultaneously, both the requirements
(2) and (4), from Table 1, this capacitor must have a relative large capacitance,
C3 2.92 nF, (6)
for a measurement frequency of 0.5 MHz, respectively
C3 1.46 nF, (7)
for a measurement frequency of 1 MHz.
At the same time, the coupling capacitor shall be capable of withstanding, with a low
partial discharges level, a relative high power-frequency voltage, e.g. about 270 kV, when
testing an EUT with a nominal voltage of 400 kV. Such a capacitor being a relative expensive
equipment, we investigated the possibility to use coupling capacitors with capacitances
something smaller than the above-established values. Even the CISPR18-2 Publication, [2]
hints that a capacitance C3 at least five times greater than the capacitance to earth of the
EUT and its high – voltage connection may be sufficiently, respectively – for the usual
applications – a value of 1 nF should be satisfactory.
Ours experiments, carried out in the high-voltage laboratory of the “Politehnica”
University of Bucharest, on a clean and dry suspension insulator set, for a nominal system
voltage of 110 kV, with the results displayed in Table 2 pointed out that for a relative large
range of the capacitance of the coupling capacitor, between 1.85 nF and 7.40 nF and for both
measurement frequencies, all RIV levels are comprised in an interval of
66 ± 1 dB/ V/300 . The small differences may be due to the instability of the corona
discharges, small variations of the applied voltage and atmospheric conditions during the test
etc.
It should be observed that, at the reference measurement frequency of 0.5 MHz, only the
capacitances C33 and C34 meet the requirements of CISPR 18 - 2 Publication.
Table 2 – RIV level versus coupling capacitor capacitance – 110 kV suspension insulator set
C3, (nF) RIV, (dB/ V/300 ) (1), (2)
fm = 0.520 MHz fm = 1.060 MHz
C31=1.85 66.0 66.4
C32=2.50 66.0 65.1
C33=3.70 65.9 65.7
C34=7.40 66.6 66.1
(1)
Test voltage: 79 kV
(2)
Calibration of the test circuit, acc. [2, § 1.3.12] for each measurement
3
In consequence, it may consider that:
Since the radio noise generated by high-voltage equipment depends mainly on the
distribution of the electric field at the surface of the equipment, the relevant standards
regarding insulator sets, [3], [4], [5] impose more or less restrictive mounting arrangements.
4
In some cases, e.g. by the tests of long insulator sets it is difficult – in laboratory
conditions – to fulfill exactly all these requirements. For this reason, we investigated the
extent in which reasonable deviations from the standardized mounting arrangements would
modify the measured RIV level.
The experiments has been carried out on an 110 kV suspension insulator set, in a
mounting arrangement sketched in Fig. 2, with the variants given in Table 3. Two metallic
structure, 100 mm by 100 mm mesh, “T” and “P” simulated, respectively, the tower and the
influence of the adjacent phase of the line, according to EN 61284 Standard, [4]. All
dimensions, excepting the distances to ground h = 5.20 m and h = 6.00 m agree with this very
restrictive standard. For more information, was measured the electric field in a point A,
situated on the vertical of string, at 1 m under the “line”.
1.4 m
1.65 m
4m
T P Φ 25 mm
1m
Fig.2 – Mounting arrangements for the RIV measurement on an 110 kV insulator set.
Table 3: RIV level and electrical field strength at 1 m below the line (EA) for an 110 kV suspension
insulator set, in various mounting arrangements.
Mounting “T” structure “P” structure h, (m) EA RIV
arrangement (simulating the (simulating the (kV/m) (dB/ V/300 )
tower) adjacent phase)
6.00 12.5 63.0
M1 No No 5.20 13.3 64.8
4.40 13.6 64.0
M2 No Yes 4.40 14.3 64.3
M3 Yes Yes 4.40 14.2 64.4
Notes:
• Test voltage: 78 kV
• Measuring frequency: 520 kHz
5
4. Conclusions
The requirements imposed by CISPR 18-2 Publication, regarding the RIV measurement
circuit are:
• too restrictive, with regard to the capacitance of the coupling capacitor;
• unrealistic, in some measure, with regard to the L2 – C2 series circuit.
At the same time, the requirements imposed by EN 61284 Standard, regarding the
mounting arrangement for RIV tests are also too restrictive and in some cases difficult to fulfill
exactly, in laboratory conditions.
The acquired results may conduct to improvements of these standards, in order to
facilitate the tests and to reduce their cost.
5. Bibliography