Load Calculation 5.5 m

Dead Load

Self weight of the sunshade members can be calculated by Staad.

Weight of Aluminium sheeting 0.7mm thick = 0.023 kN/m2


Assume the weight of the nuts & sag rods = 0.027 kN/m2
Self weight of the purlin = 0.03707 kN/m2 Purlin member = Z Purlin
Total Dead load per sq. m = 0.08707 kN/m2

Dead Load on End Rafter = 1.4 x 0.09 = 0.12 kN/m


Dead Load on Middle Rafter = 1.4 x 0.09 = 0.12 kN/m

Assumed Steel Column size = UB 203x102x23

Flange width bf = 101.8 mm

Depth of the Section d= 203.2 mm

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 1 of 7


Customer Proj No
Project Title Calc No
Calculation Title Phase/CTR
Elec File Location

Note: Yo
Project File Location Page of Workshe
Rev Date By Checked Rev Date By Checked Rev Date By Checked
- - - - - - - -

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 2 of 7


Customer Proj No
Project Title Calc No
Calculation Title Phase/CTR
Elec File Location

Note: Yo
Project File Location Page of Workshe
Rev Date By Checked Rev Date By Checked Rev Date By Checked
- - - - - - - -

Live Load

Live load on sheet for a pitch angle >5° = 0.75 kN/m2 (BS 6399 part 3 - Cl 4.3.2)

LL on End Rafters = 0.75 x 1.4 = 1.05 kN/m2


LL on Middle Rafters = 0.75 x 1.4 = 1.05 kN/m2

Wind Load

Prevailing wind direction: South-East direction


Mean hourly wind speed: 26 m/s @10m height
Gust duration factor: 1.7 ( for 3 second gust duration)
Topography category: 2

The design wind speed at any height Z above the ground , Vz (m/s) is derived from the formula below:

Vz = F V10 (Z/10)1/ϒ S3

F : 1.7
V10 : 26 m/s
Z : Height above the grade
1/ϒ : 0.09 ( Local factor)
S3 : 1.0 For Permanent structure
0.77 For temporary structure

Reference Elevation Design Wind speed Vz Pressure qs=0.613Vz2 ………………...Cl 2.1 -BS 6399-2
in m in m/s in kN/m 2

2 38.2 0.894
5 41.5 1.056
10 44.2 1.198
15 45.9 1.289
20 47.1 1.358
25 48.0 1.415
30 48.8 1.462
Shed Ht = 3.50 m 40.2 0.989

Co-efficient for the Open structure wind load on column: ( for non side sheeting area)

Wind on Column flange = 0.201 kN/m

Wind on Coulmn web = 0.402 kN/m

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 3 of 7


Customer Proj No
Project Title Calc No
Calculation Title Phase/CTR
Elec File Location

Note: Yo
Project File Location Page of Workshe
Rev Date By Checked Rev Date By Checked Rev Date By Checked
- - - - - - - -

Wind Pressure co-efficients


Roof Angl= ### º h1 = 2.40 m w = 5.5 m l = 2.8 m Table 14- BS 6399-2
h2 = 3.50 m
Solidity ratio h1/h2 = 0.6857 Net Pressure coefficient Cp
1. 2
1.2

Wind loads are as follows


a) Wind load on end rafters

Grid A
6 1.6
1.6 6

Wind Load on Rafter:

Wind load Span = 2.80 0 = 1.40 m


+
2

Net Pressure Coefficient = 1.2

Design Wind Pressure = 0.989 kN/m2

Wind Load on Rafter = 1.2 x 1.40 x 0.989 = 1.66 kN/m

Grid B
6 1.6
1.6 6

Wind Load on Rafter:

Wind load Span = 0.00 2.80 = 1.40 m


+
2 2

Net Pressure Coefficient = 1.200

Design Wind Pressure = 0.989 kN/m2

Wind Load on Rafter = 1.2 x 1.40 x 0.989 = 1.66 kN/m

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 4 of 7


Customer Proj No
Project Title Calc No
Calculation Title Phase/CTR
Elec File Location

Note: Yo
Project File Location Page of Workshe
Rev Date By Checked Rev Date By Checked Rev Date By Checked
- - - - - - - -

WL
Live Load = 0.75 x 1.50 = 1.13 kN/m
Dead load = 0.11 x 1.5 = 0.1584 kN/m
Max WL = 1.20 x 0.99 x 1.50 = 1.78 kN/m
Total Load for Delfection = -0.54 kN/m WL-(DL+LL)Cos15, where Cos 1 0 = 0.97
q
Total Load for Delfection = 1.28 kN/m ( DL+LL )

Refer METSEC Catalogue for spacing of 1.50 m & span of 2.8 m DL+LL (DL+LL)cosq
Z purlin used = 202Z20 wt. of purlin = 5.56 kg/m 0.06 kN/m I= 4E+06 mm4

Allowable Load = 15 kN/m (From Metsec Load tables P.55)


Actual Load =( 0.16 + 1.13 )x 2.80 = 3.59 kN < Allowable. SAFE
Allowable Uplift = 24.4 kN/m (with one anti sag rod)
Max Uplift = 1.78 kN/m < Allowable. SAFE
All. Deflection = 11.2 mm Non continuous system
Max. Actual Deflctn = 1.2 mm < Allowable. SAFE

Side Rail Design

Spacing of purlin = 0.50 m Max. Span of the Purlin = 2.80 m


Live Load = 0 x 0.50 = 0.00 kN/m
Dead load = 0.13 x 0.5 = 0.0635 kN/m y
Total Load for Delfection = 0.09 kN/m

Refer METSEC Cat. for spacing of 0.50 m & span of 2.8 m x x


Z purlin used = 172Z15 wt. of purlin = 3.85 kg/m 0.04 kN/m y
Iyy= 442000 mm4 Ixx= 2E+06 mm4
Allowable Load = 6.65 kN/m (From Metsec Load tables page 69 )

Actual Load in 'x' = ( Wind load on cladding) = 0.20 kN/m < Allowable. SAFE

Actual Load in 'y' = ( Due to vertical load) = 0.09 kN/m < Allowable. SAFE

All. Deflection = 11.2 mm Non continuous system

Max. Actual Deflctn in ' x' direction = 0.4 mm < Allowable. SAFE

Max. Actual Deflctn in ' y' direction = 0.8 mm < Allowable. SAFE

Load on Column due to Side Runner


Grid Total Load kN/m
Grid A 0.12
Grid B 0.12
Grid C 0.00
Grid D 0.00

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 5 of 7


Customer Proj No
Project Title Calc No
Calculation Title Phase/CTR
Elec File Location

Note: Yo
Project File Location Page of Workshe
Rev Date By Checked Rev Date By Checked Rev Date By Checked
- - - - - - - -

APPENDIX -1 RBB-11-100232-CS-8102-00001-0001 Page 6 of 7


Wind Load on Eqp. Wind Load on Eqp. CG Moment At Moment At Couple force Couple force
Sl. No. Equipment No. / ID CG ( Wind X) ( Wind Z) base ( Mz) base ( Mx) due to Mz due to Mx
1 24 VDC DB 1.14 3.79 1.19 3.98 1.19 13.26
2 415 VAC DB 0.69 2.08 0.68 2.03 1.13 10.15
3 WHCP 2.31 3.34 2.31 3.34 2.47 5.18
4 IPS/ICSS Panel 1.51 2.27 1.59 2.39 2.65 5.96
5 Telecom Panel 0.78 0.78 0.47 0.47 1.17 1.17
6 Local Control Panel 0.05 0.06 0.01 0.01 0.07 0.11