Professional Documents
Culture Documents
KraftPowercon - Rectifier - 77-107.0222 GB Rev.I1 (IM-EN) PDF
KraftPowercon - Rectifier - 77-107.0222 GB Rev.I1 (IM-EN) PDF
FlexKraft
77-107.0222 GB Rev.I1
KraftPowercon Sweden AB. P.O.Box 2102. SE-445 02 SURTE. Sweden Tel: +46 31 97 97 00. Fax: +46 31 97 97 97
User Guide Page 1(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
1 Safety Instruction
SAFETY INSTRUCTION
This product is only intended for use as a constant DC-power supply for industrial
processes, the product may only be used for other purposes after approval from
KraftPowercon. The product must not be used for charging batteries or welding.
The User Guide must be read before installation, use in production or work on the
production.
The equipment is only intended for professional use and must not be used in home or
office environments.
User Guide Page 2(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Table of Contents
This description applies to software version FLX-01 VER. 02.90 and higher.
Slight differences can exist between the program versions.
When upgrading to firmware version 2.5x from 2.xx no special action is needed.
NOTE!
If upgrading from version 01.xx to version 02.xx, please make a note of the settings
of the CFG and SET menus, as it may be necessary to re-enter these settings after
upgrading the software.
1.2 Standards
The following European standards or technical specifications apply:
Electrical safety:
EN 50178 Electronic equipment for use in power installations
EMC Immunity:
EN 61000-6-2 Electromagnetic compatibility -
Immunity for industrial equipment
EMC Emissions:
EN 61000-6-4 Electromagnetic compatibility -
Generic immunity standard
- Part 2: Industrial environment
This means that a device installed correctly does not disturb other CE marked equipment
via conducted or radiated RF effects.
User Guide Page 5(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
2 General
FlexKraft is a modular designed rectifier for galvanic processes. The rectifier consists of
one control module and one to ten identical power modules. If more current or power is
needed from an existing rectifier, power modules can be added, up to a maximum of 10.
FlexKraft has built in EMC filter according to the EMC directive.
1
5 A B 1 Roof
6 7 2 2 Control module
3 3 Power module
4 Base
8 5 Display with keys
6 Power connection
7 Control cable connection
Labels with information for
connecting
4 8 DC bus bars
Figure 2. : FlexKraft with four power modules and control module on top (standard configuration).
Figure 3. FlexKraft , two and four rectifiers configured as stack, rectifier with control module moved,
and bench-top model.
User Guide Page 6(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Example.
3 Basic Control
This chapter deals with control from the local display. The rectifier will, in most cases,
probably be remotely controlled from an external control system. The local display unit is
useful for service and troubleshooting.
3.1.1 Keypad
FlexKraft has the following keys on its membrane keypad:
In REMOTE mode, some or all control functions cannot be operated from the display unit
and are instead controlled by serial communication or by external analogue control signals.
If the rectifier is not in REMOTE mode it can only be operated from the display unit.
When SLAVE MODE is active, the keypad is disabled and no operating parameters can be
changed, see section 3.1.19. The keypad is activated using a password-protected menu.
Background lighting comes on when a key is pressed and remains on for 60 seconds after
the last key is pressed.
User Guide Page 9(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
The system is reset if the OFF key is held down for 5 seconds. The buzzer sounds to
indicate that reset has occurred.
If the rectifier is fitted with the optional CONTACTOR, the contactor opens at the alarm. If
the sound indication is set to “ON” in the CFG/USR menu, see the Technical Description
77-107.0223 Chapter Operating instructions , the buzzer goes on at the alarm. The buzzer
is turned off by pressing any button.
To reset from fault mode: switch the rectifier off using the keypad or serial
communication. Alternatively, send the ALARM RESET command using the DIG IN digital
input.
Message Explanation
“HIGH TEMP! P-M” Excess temperature in a power module. Too high temperature on
the output causes over temperature in the power module. (The
output from the affected power module is cut as long as the temperature
remains too high. The “power good” LED is off on the power module that has
sent the high temperature signal.)- The rectifier remains running with the
remaining power modules, the output current is decreased
accordingly.
“HIGH TEMP C-M” Excess temperature in the control module. The rectifier runs.
The output current is unaffected.
“REGULATIONERR” Regulator control error in a power module. (The rectifier runs. The
“powergood” LED is off on the power module that has sent the warning
signal).Tthe output current is decreased accordingly.
If all modules have “Power Good” LED off, check main supply,
out of range or one phase missing
User Guide Page 10(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
“MODULE FAILED!” Reverse current in a power module. (The rectifier stops. The
“powergood” LED is off on the power module that has sent the alarm signal)
“SHORT CKT!” The output voltage has been below the under voltage set value
for a longer period of time than set time value.
In the case of an ALARM, the reason for the ALARM should be determined. See
chapter 8 in technical description 77-107.0223 Chapter Service and Maintenance
Message Explanation
“CHK USRCFG” Only applies with pole reversal option. Fault in
configuration of DIG IN or DIG OUT signals.
“ILLEGAL PARAMETER” Shows that a set value sent via serial communication is
out of range. If the set value is above range, it will be set
to maximum range value. If the set value is below range,
it will be set to minimum range value.
“INTERNAL FAULT 256” Shows an internal software problem. Restart the rectifier
(OFF) and check if the fault disappears. Please call
KraftPowercon and report when the fault occurred.
“MAX POWER” The output of the rectifier does not correspond to the
(ALARM LED flashes) set values of current and voltage due to power limitation.
The set values for current and voltage is within the
triangle 12-15V/300A.
Effektgräns
Power limit
15V
12V
Spänning/Voltage
I
Ström/Current 250A 300A
When an EOP for elapsed time limit or ampere hour limit is reached the “ALARM” LED
flashes, see “Setting the time limit” and “Setting the Ah limit” for information.
User Guide Page 11(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
If the current requirement increases, additional power modules can be added (up to a
maximum of 10). Contact the service department at KraftPowercon.
Several rectifiers can be connected in parallel to obtain higher output current, but
they must be equipped with the parallel configuration option. NOTE that if more than
one rectifier stack shall be connected in parallel then each stacks bus bar shall be
connected together with the other stacks DC outputs. Please see Figure 5 Three
rectifier stacks connected in parallel.
User Guide Page 12(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Please note that some functions require that options are installed.
In order to control the rectifier locally, set the Remote control option to “NO”
See Technical description 77-107.0223 Chapter “Set menu” for further information.
User Guide Page 14(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Shut down the rectifier by pressing the “OFF” key again to switch from “STANDBY” mode
to “OFF” mode.
Rectifier, stops due STATUS: HIGH TEMP HIGH TEMP HIGH TEMP
to. excess
temperature
00.00 V 000.0 A 00.00 V 00.00 V
000000 Ah 00000 S 000.0 A 000.0 A
DUTY SET BLOCK CFG DUTY SET BLOCK CFG
This can be done using the “BLOCK” key, from the main menu, from the SET menu,
or by remote control. In DUAL-2 mode the rectifiers can only be operated
independently from the SET menu, or by remote control.
Change the voltage during operation with the “VOLTAGE” arrow keys to increase or
decrease the values.
Change the current during operation with the “CURRENT” arrow keys to increase or
decrease the value.
NB! If the rectifier is in DUAL mode the set values for both sides are changed equally and
simultaneously if the arrow keys on the keypad are used. The set values can be set
individually in the SET menu.
If required, set the initial voltage and current values before starting using the SET menu.
Both methods can be used in STANDBY and RUN mode.
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
User Guide Page 17(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
Setting whether the rectifier should stop, use HOLD level or only light the ALARM LED
when the set limit has been reached (option: contact to remote system) is set using the
CFG/USER menu with the EOP MODE parameter.
NOTE that the settings also apply for the Ah limit. The CFG menu is password protected.
FIRMWARE FIRMWARE
FLX-01 VER xx.xx FLX-01 VER xx.xx
← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑
The number of ampere hours is set in the SET menu using AH-LIMIT A and AH-LIMIT
B.
User Guide Page 19(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
Setting whether the rectifier should; stop, use HOLD level or only light the ALARM LED
when the set limit has been reached (option: contact to remote system) is set using the
CFG/USER menu with the EOP MODE parameter.
NOTE that the settings also apply for the time limit. The CFG menu is password protected.
PARALLEL, SERIES DUAL, DUAL-2
FIRMWARE FIRMWARE
FLX-01 VER xx.xx FLX-01 VER xx.xx
← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑
See the Technical description 77-107.0223 Chapter Operating Instructions for further
setting options and programming functions.
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
Press ↓ to get START RAMP Press ↓ to get START RAMP Press ↓ to get START RAMP
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
The rectifier can be set to close a potential free contact when a preset number of Ah hours
have elapsed. The number of Ah hours between the start of each pulse is set using
parameter AUTODOS, and the closed time for the contacts is set by the parameter
PULSLENG in the CFG/USER menu. The menu is password protected.
AUTODOS has a range of 0-30,000 Ah, and sets the number of ampere hours between
dosing.
PULSELENG has a range of 0-999.9 s, and sets the length of time that the contacts
remains closed.
The DIG OUT 1 to DIG OUT 4 parameter determines which contacts are used.
Parameters are set in the CFG/USER menu.
FIRMWARE FIRMWARE
FLX-01 VER xx.xx FLX-01 VER xx.xx
← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
Programs are entered using the CFG/PROG menu. The menu is password protected.
Basic
functions:
Remote control via serial communication is selected with the parameter REMOTE in the
SET menu.
← → ↓ ↑ ← → ↓ ↑ ← → ↓ ↑
The parameters for remote control must to be set to give correct remote control
functionality.
If the rectifier is delivered with remote digital or analogue control box, the parameters are
factory set.
NOTE If the rectifier is set for analogue remote control of set values these values
take, in REMOTE mode, priority over set values via serial communication.
See the Technical description 77-107.0223 Chapter Programming for further information.
User Guide Page 25(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Default settings:
S.C. LEVEL 2,00V
S.C. DELAY 0sec = -OFF-
For SERIES and PARALLEL rectifiers the “A-side” parameters shall be used.
NB! The output voltage set value must be higher than the under voltage/short circuit
detection voltage. Otherwise the under voltage/short circuit detection is disabled
3.2 Calibration/Configuration
The rectifier is calibrated and configured at the factory before delivery.
The rectifier can be calibrated from the CFG/CAL menu. The calibration menu is password
protected.
The rectifier needs to be reconfigured if the DC output's connection changes from parallel
(0–15VDC) to series (0–30VDC) or vice versa.
See Technical description 77-107.0223 Chapter Operating Instructions for further
information
3.3 Password
Some menus and settings are password protected. KraftPowercon service can set a new
password should the old one be lost.
See the Technical description 77-107.0223 Chapter Operating Instructions for further
information.
4 Installation guide
4.1 Essential electrical knowledge
Installation of the rectifier may only be carried out by qualified personnel, i.e. trained
electricians that have sufficient experience to avoid the dangers that electricity can bring
about.
User Guide Page 26(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
CAUTION! The rectifier is heavy when equipped with many modules. Use
lifting equipment and secure the load when lifting. Serious
personal injury and material damage can result should the unit
be dropped.
Check that the equipment has not been damaged during transport.
Protect FlexKraft against harsh treatment, vibrations and harmful substances.
The equipment can be lifted with a lift truck or with a sling/rope (or the optional lifting
eyes).
If the rectifier is lifted with a lifting sling or rope, you must check that the distance between
the top of the rectifier and the lifting point is sufficient. Alternatively, a bar, that spreads the
lifting sling above the rectifier, can be used.
NOTE! Take care to ensure that the sling/rope cannot slip off or that hooks can slip out of
place during lifting.
NOTE! When lifting heavier equipment (>=5 modules) use timber studding (approx.
40 x 80 x 600 mm) for additional support and use a lifting yoke if possible.
It may be necessary to increase the dimensions shows depending on the lifting capacity of
the sling.
User Guide Page 27(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
4.3 Set up
4.3.1 General
The galvanic rectifier FlexKraft is designed and manufactured to withstand the
environment in a modern surface treatment facility. The component parts and modules of
the rectifier have been treated so that the effects from the surrounding environment are
minimal. The device is air-cooled, the fans should be checked regularly and replaced when
necessary.
The control module is mounted as standard on top of the stack, but can be mounted in
other positions. Should the control module need to be moved, contact the service
department at KraftPowercon Sweden AB.
The rectifier can be expanded with power modules when the current/output need
increases. Contact KraftPowercon Sweden AB.
4.3.3 Installation
The rectifier should be installed to facilitate service and maintenance.
The rectifier needs to be accessible at the rear to connect cables to the load and to
remove the power modules from the chassis when replacing modules. At the front a free
space of at least 1 m is needed to pull out the power modules, and for servicing.
It is recommended that clearance of at least 500 mm is provided at the rear of the rectifier
to provide access for load connections.
Rear side
Rectifier
Front side
When placing rectifiers side by side, make sure that there is at least a space of 15mm
between the rectifiers. The front panels is removed by loosing 4 screws and then sliding
the panel to the left.
The rectifier can be installed without the need to open the enclosure, only the cover plate
over the connection terminals needs to be opened.
The rectifier should be installed so it has free access to air from the front and that the air
outlets at the rear are not blocked.
NB! Check that the exhaust air can freely depart from the rectifier and not recirculate to
the air intake.
X X
See the Technical description 77-107.0223 Chapter Technical Data for information about
measurements and weights.
User Guide Page 30(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
The control system or separate controller is connected to the control module. Control is
connected depending on the rectifier´s equipment by one of the following options:
Serial communication via RS 485
Serial communication via RS 232
Analogue signals.
The power module halves can be connected in series for an output voltage of
0-30 VDC, or in parallel for an output voltage of 0-15 VDC.
The control module is mounted as standard on top of the stack, but can be mounted in
other positions. Should the control module need to be moved, contact the service
department at KraftPowercon Sweden AB.
User Guide Page 31(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
NB! The rectifier must be connected to protective earth. The rectifier must be
connected to a Y-connected transformer with earthed zero point.
(Voltage phase to zero point (earth) = voltage phase to phase/√3. This is the
normal connection of a power distribution net)
NB! Each rectifier must be fused separately. Only one rectifier should be
connected to the same fuse
NB! The rectifier has high leakage current to earth. (The leakage current due to EMC
components) Protective earth should always be connected in a reliable manner
so that the rectifier does not become live in the event of a fault.
NB! If earth fault breakers are fitted, there must be one for each rectifier. The type
of the earth fault breaker shall be B.
The maximum output current or output voltage can be limited in the configuration menu.
The rectifier should be connected to a 3-phase supply with voltage according to the rating
plate on the rectifier.
User Guide Page 32(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
The three phases are connected to the terminal A1:X1 on the control module and the
protective earth to the earth bolt next to the terminal A1:X1 on the control module. If
rectifiers are connected in parallel their chassis must kept at the same potential, as
described above.
The equipment is not phase sensitive. The primary currents for rectifiers with a different
number of power modules and the recommended cable cross section can be found in the
Technical description 77-107.0223. Chapter Technical Data Observe local regulations for
cables and cable sizes.
Power cable connection X1 is in the box to the left of the control module. Open the cover
plate and connect the cable. It is possible to connect the cable from either end of the box.
The busbar temperature is supervised and the rectifier stops when the temperature is over
limit. See chapter 3.1.6 Alarms / Warnings / Fault messages
Loads connected at the rear of the rectifier. The module outputs are connected in series
for an output voltage of 30V and connected in parallel for an output voltage of 15V. See
figure 7. Recommended cable cross section can be found in Technical description 77-
107.0223. Chapter Technical Data Observe local regulations.
For parallel connection the module halves are connected individually so that there are four
interconnected busbars, two positive and two negative. This means the bath can be fed
from “two directions” to give balanced current distribution.
This is the optimum method of connecting the bath. When only one feed is required, the
two positive busbars are interconnected, as well as the two negative busbars.
See Figure 9 below.
Figure 9. Connection of FlexKraft to galvanic bath with 4 cables: in PARALLEL mode from
“two directions”
User Guide Page 33(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
The rectifier can, in parallel mode, compensate for differences in cable length to the bath,
and tries to give the same output current from both sides. The maximum voltage difference
between sides is 0.5V, corresponding to approximately 10m of cable.
SIDA/SIDE SIDA/SIDE
B A
When the rectifier has several modules, the DC-connection cables are to be connected in
the middle of the busbar or distributed across the interconnecting busbars at the rear of
the rectifier. Connections must not be made at one end of the busbar. If connection of the
load takes place at one end of the interconnecting busbar in a rectifier with several power
User Guide Page 34(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
modules, the interconnected busbar will be overloaded. NB that if more than one rectifier
stack shall be connected in parallel then each stacks bus bar shall be connected together
with the other stacks DC outputs. Please see Figure 5 Three rectifier stacks connected in
parallel.
Side
B A
B A
- + + -
NB! If the output current and\or output voltage are increased from reduced values, the
installation must be assessed, and altered if necessary, to cope with the increases in
output.
NOTE: all the options can not be fitted at the same time.
See the rear of the control module to see which option/options are fitted at delivery.
On the outside of the cover-plate a label indicates the options that are fitted to the rectifier.
On the inside of the cover-plate a label gives information about terminals and signal
configuration that was set at the factory..
Typical labels
The rectifier is equipped with serial communication I/O for RS485, analogue/digital I/O for
analogue control box/PLC and interface for external emergency stop.
User Guide Page 36(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
1
Analogue/Digital I/O A10
Serial/parallell (Dualmode A-side)
RS 485 A4 1
Adress
(Dualmode B-side)
X2 Note: Switch for
X2 X3 1 A termination resistors is
1 A-meter (0-10V) 1 A-meter (0-10V) 2 B located on internal PCB
2 V-Meter (0-10V) 2 V-Meter (0-10V) 3 0
3 Signal ground 3 Signal ground Interface A12
Analogue I/O A10 6 Uset (0-10V) 6 Uset (0-10V) 3 Emergency stop circuit
X Digital 1 12 1 12
7 Power ground
8 ON/OFF
7 Power ground
8 BLOCK/RUN A
5
6
7 -
Interface A12 X2 9 BLOCK/RUN A+B 9 BLOCK/RUN B 8 -
X 1 12 10 +24VDC (200mA)
11 "ON" (24V)
10 +24VDC (200mA)
11 Dig OUT 3
See manual,chapter
9
10
-
-
Label on the outside of the coverplate Label on the inside of the coverplate.
Example:
The rectifier is equipped with the Inputs/outputs/signals:
following options:
Interface PCB A12 - - - - - - - - - - - - - - - - Emergency stop A12:X2:3 – A12:X2:4
Analogue/Digital I/O PCB A10 - - - - - - - - Configutated according to the table
Seriellt I/O PCB A4 - - - - - - - - - - - - - - - - RS485
Open the cover plate with knockouts for cable glands (4 screws).
Signal connections on terminal blocks inside the control module are made using pluggable
connectors (the female part of the connector is supplied with the rectifier), so that the cable
can be secured in the cable gland and the connector/connectors fitted with the cover plate
removed from the control module. To assemble, fit the connectors in the control module
and then secure the cover plate.
Labels for options.
Use a PROFIBUS approved cable. The cable must be terminated at both ends. This is
done on the rectifier that is last on the loop by switching two DIP switches located on the
circuit card that the fieldbus cable is connected to.
Terminering
NOTE! It is important from operating and EMC standpoints that the correct cable is used
(screened and twisted pair).
It is a standard RS-485 connection, observe the limitations that exist concerning the
maximal length, termination, maximum number of devices, etc.
Serial communications can cease to work if the cabling is not installed correctly.
User Guide Page 38(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
The cable for analogue control is connected to combinations of, PCB A9, A10, A11, A12 at
the rear of the control module, depending on options fitted.
NB! Analogue remote control boxes for DUAL are not equal.
MASTER SLAVE
The rectifiers must be kept at the same potential by connecting a cable between the
rectifier chassis. See section 4.4.1 Power supply.
NB that if more than one rectifier stack shall be connected in parallel then each stacks bus
bar shall be connected together with the other stacks DC outputs. Please see Figure 5
Three rectifier stacks connected in parallel
User Guide Page 40(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Inrush current, cable length and voltage drop affects the choice of cable area.
The conductor area should preferably be 1,5 or 2,5 mm2.
If rectifiers are connected in parallel the contacts for each rectifier must be isolated from
each other.
Check that the rectifier and control unit are connected according to the wiring diagram in
the appendices. When the rectifier is equipped with options, see the enclosed
description/descriptions.
Switch on the 3-phase mains supply. The rectifier should start in OFF mode.
The display should now show information. If the unit is set to REMOTE, switch to LOCAL.
Start the rectifier in STANDBY mode by pressing the “ON” key.
The display should come on and the rectifier should be in STANDBY mode.
Adjust the set point values for the current and voltage to Min.
Permit output current/voltage and switch the rectifier to RUN by pressing the “ON” key.
Switch off the rectifier by pressing the “OFF” key to switch to STANDBY mode; press
“OFF” again to switch to OFF mode.
If there is a load available, connect this and check that it can provide a suitable load.
The load can be checked from the data sheet, measured or by running the test and using
voltage and current values to determine whether or not the load is suitable. At 20-100% of
the nominal current the voltage should be 20-100% of the nominal voltage.
When no load is available, the outputs can be short circuited using a cable with an
appropriate cross section depending on the rectifier's rated current.
Switch on the 3-phase mains supply. The rectifier should start in OFF mode.
The display should now show information. If there is no information on the display, check
that there is mains power to the rectifier
Adjust the set point value for the voltage to approximately 50% of the rated voltage.
Adjust the set point value for the current to zero.
Permit output current/voltage and switch the rectifier to RUN by pressing the “ON” key.
Check that the current and voltage can be increased and decreased to values that the
rectifier's rating and connected load permit.
Check that the fans in the power modules are running if the output current >20% In.
Switch off the rectifier by pressing the “OFF” key to switch to STANDBY mode; press
“OFF” again to switch to OFF mode.
5 Warranty
KraftPowercon Sweden AB provides a warranty as stated in the order acknowledgement
or contract. The warranty covers defects in design, materials and manufacturing. Defects
that can be shown to have arisen as a consequence of incorrect use and/or maintenance
are not covered. If a fault develops during the warranty period, KraftPowercon Sweden AB
or local representative must be contacted before any work is undertaken on the rectifier.
KraftPowercon Sweden AB
P.O. Box 2102 Telephone: +46 31-979700
SE-445 02 SURTE Fax: +46 31-979797
Sweden E-mail: service@kraftpowercon.com
The 24 VDC
output is a source
for feeding
optocouplers and
switches for input
signals to the
rectifier.
Applies to all
PCB:s.
NOTE! +24VDC on the circuit board is the power supply for signals. See the relevant
option in Technical description 77-107.0223
User Guide Page 45(45) 77-107.0222 GB
FlexKraft 2015-12-08
Rev. I1
Appendix 1