Professional Documents
Culture Documents
EE 19 Module 3
EE 19 Module 3
DIFINITIONS
OBJECTIVES
2. Able to compute magnetizing current in real transformer and use Matlab software to
3.1
resistances, there is voltage drops in the windings of the transformer. Following are being
considered:
∴ = − …vector difference
(ii) Similarly, induced e.m.f. at must be the same to the difference of and
∴ = − …vector difference
61
AMU - 2020
EE 19 - MODULE 3
Figure 26
The vector diagram for; (a) non-inductive, (b) for inductive and (c) for capacitive
3.2
Resistances can be transferred any of the two windings. This happens when we want to
make our calculations simple and easy. Also, it will be proved that in secondary will be
Figure 27
The copper loss in secondary is / . This loss is supplied by primary which takes
a current of . Hence if ′ denoted as the equivalent resistance in primary, then this will
= =
62
AMU - 2020
EE 19 - MODULE 3
In Figure 28, when secondary resistances has been transferred to primary and
∴ = + ′= + /
= + ′= +
Above equations is shown in Figure 29, where in secondary winding all resistances
Figure 28 Figure 29
divide by
(c) but if voltage are being shift from primary to secondary or secondary to
63
AMU - 2020
EE 19 - MODULE 3
3.3
In previous discussion, it is assumed that flux are being linked from primary and
secondary. But then in practice, transformers are impossible to see such conditions and it
is found that only completes the magnetic circuit by passing through the air rather the
core, this is shown in Figure 30. When m.m.f. produced leakage flux caused by primary,
ampere-turn exist between points and , and it will acts as leakage paths. Leakage flux
in primary is proportional to primary ampere turn itself because primary and secondary
Figure 30
Secondary m.m.f. exist at points and , and it is leakage flux . Leakage flux
in secondary is proportional secondary turn itself because secondary and primary turns do
During light loads and no load, ampere-turns in both winding are small and leakage
flux is negligible. During increased of load, the primary and secondary windings is carrying
Earlier, it is discussed that each winding produces leakage flux that is link in both
windings and this will create inductive coil in series with each windings. Also, this series
coil in both windings has the same voltage drops. In Figure 31 shows the inductive coil in
each windings and the internal e.m.f. in both windings are equal.
64
AMU - 2020
EE 19 - MODULE 3
Figure 31
= / and = /
The terms and are known as the reactances in both windings primary and
secondary respectively.
3.4
In Figure 32, the windings in both primary and secondary of a transformer with
Figure 32
= ( + )
= ( + )
Resistances and leakage reactance are the one who is responsible for some voltage
= + ( + )= +
65
AMU - 2020
EE 19 - MODULE 3
give .
= + ( + )= +
The vector diagrams for such a transformer for different kinds of loads is being
shown in the Figure 33. Vector diagram for resistive are being drawn to parallel with
current vector. Whereas, the vector diagram for reactive drops are perpendicular to the
Leakage reactance is also to resistance when transferring from winding to the other.
′= / and ′ =
and = + ′= + / and
= + ′= +
Figure 33
66
AMU - 2020
EE 19 - MODULE 3
equation;
= ( + )
and = ( + )
Example 3.1
winding resistance and leakage reactance is 0.1 Ω and 0.22Ω respectively. Secondary
winding resistance and leakage reactance is 0.035 Ω and 0.012 Ω respectively. Determine
the equivalent winding resistance and leakage reactance referred to (i) primary side and (ii)
secondary side.
Solution.
(i)
1
= + = + = 0.22 + 0.12/ = .
20
= + = 14.1 + 5.02 =
67
AMU - 2020
EE 19 - MODULE 3
(ii)
1
= + = + = 0.035 + × 0.1 = .
20
1
= + = + = 0.012 + × 0.22 = .
20
= + = 0.0325 + 0.01255 = .
(or = = × 15 = . )
Example 3.2
= 5.2 Ω and = 0.015 Ω.Calculate for the transformer (i) equivalent resistance referred
to primary side (ii) equivalent resistance referred to secondary side (iii) equivalent
reactances referred to primary side and secondary side (iv) equivalent impedance referred
to primary side and secondary side (v) Total Cu losses, using individual resistance in two
Solution.
.
= + = + = 0.015 + = .
68
AMU - 2020
EE 19 - MODULE 3
= + = 0.0176 + 0.028 = .
.
Also = = = . (check)
= = 227 × 0.0176 =
Example 3.3
distribution system to step down voltage. The low tension voltage is to be kept constant at
240 V.
(a) What load impedance connected to low-tension size will be loading the transformer
Solution.
′= / = 1.142/ = .
69
AMU - 2020
EE 19 - MODULE 3
= = (1/10) × 625/3 = .
Example 3.4
The full-load copper loss on the high voltage side of a 100 , 11000/317 ,
single phase transformer is 0.62 and for the low voltage side is 0.48 .
(i) Calculate , and in ohms (ii) the total reactance is 4 per cent, find , and
Solution.
,
= / = 0.00482 × = 5.8 Ω
× 9.1 ×
% reactance = × 100 or 4 = 11000 × 100, = 48.4 Ω
+ ′ = 48.4 Ω. Given / ′= / ′
317
∴ = 48.4 − 21.1 = 27.3 Ω, = 21.1 × = .
11000
Example 3.5
The secondary current is 200 with a terminal voltage of 500 and p.f. of 0.8
lagging. By the aid of vector diagram, determine the primary applied voltage, the primary
70
AMU - 2020
EE 19 - MODULE 3
Solution.
Use the vector diagram in Figure 35. Let us take as the reference vector.
∴ = 500∠0° = 500 + 0
= (0.06 + 0.25)
= +
Obviously, = 3.5°
= 10,520 + 640
= −8.21 + 6.16
Figure 35
71
AMU - 2020
EE 19 - MODULE 3
∴ = 1.25∠123.5°
= −0.69 + 1.04
=− +
= −11,462 − 1350
= 11,540∠186.7°
72
AMU - 2020
EE 19 - MODULE 3
3.5
shows the diagram of Figure 33 with omitted altogether since may be neglected and
In Figure 36, , , are known, hence will be found by the sum of and
voltages on the primary side can be transformed to secondary side. However, it should be
The lower side of the diagram has been shown separately in Figure 38 laid
Figure 36
39.
73
AMU - 2020
EE 19 - MODULE 3
Figure 37 Figure 38
3.6
secondary voltage on load is . The difference between the two is as shown in Figure
39.
With as the center and the radius draw an arc cutting produced at . The
parallel to .
Figure 39
74
AMU - 2020
EE 19 - MODULE 3
= = +
= cos + sin
where = = (approx)
For a lagging power factor, this will be the value of approximate voltage drops.
The different figures for unity and leading power factors are shown in Figure 40
Figure 40
cos ± sin
It may be noted that the approximate voltage drops referred to primary side is
cos ± sin
cos ± sin
% voltage drop in secondary is = × 100
100 × 100 ×
= cos ± sin
= cos ± sin
100 × 100 ×
where = = percent resistive drop =
75
AMU - 2020
EE 19 - MODULE 3
100 × 100 ×
= = percent resistive drop =
With reference to Figure 39, it is to be noted that exact voltage drop is and not
. If we add the quantity to , we will get the exact value of the voltage drop.
∴ = . Now, = − = −
( cos − sin )
∴ = cos − sin ∴ =
2
( cos − sin )
= + =( cos + sin ) +
2
( cos + sin )
=( cos + sin ) +
2
( cos ± sin )
= cos ± sin +
2
Percentage drop is
The lower sign will be used for leading and for the upped is for lagging power factor
76
AMU - 2020
EE 19 - MODULE 3
Example 3.6
A 230/460-V transformer has = 0.2 Ω and = 0.5 Ω and for the = 0.75 Ω
and = 1.8 Ω respectively. Determine the secondary voltage at 10 A and 0.8 p.f. lagging.
Solution.
Example 3.7
A transformer has a reactance drop of 5% and a resistance drop of 2.5%. Find the
lagging power factor at which the voltage regulation is at maximum and the value of this
regulation
Solution.
= cos + sin
where is the percentage resistive drop and is the percentage reactive drop.
77
AMU - 2020
EE 19 - MODULE 3
Maximum percentage regulation is 5.585 and occurs at the power factor of 0.45
(lag).
Example 3.8
Calculate the percent voltage drops for the transformer with a percent resistance of
2.5% and a percent reactance of 5% with a rating of 500 when it is delivering a load
Solution.
(% ) (% )
% = +
(% ) (% )
∴ % = +
3.8
equivalent circuit in which whose only function then is to transform the voltage given the
external resistance an reactance (Figure 41(b)). The no-load current is the total current
connected in parallel.
For the value of , this will be obtained from the difference of and
78
AMU - 2020
EE 19 - MODULE 3
Figure 41
/ = / =
To make transformer calculations simpler, this manual suggest to transfer all the
parameters such as voltage, current and impedances either to primary or secondary. In that
′= / , ′= / , ′= /
The same relationship is used for shifting an external load impedance to the
primary.
The secondary circuit is shown in Figure 42 (a) and its equivalent primary values
79
AMU - 2020
EE 19 - MODULE 3
Figure 42
Figure showing the exact equivalent circuit of the transformer but it also present
Figure 43 Figure 44
From Figure 43 it is found that total impedance between the input terminal is
( + )
= + ||( + )= +
+( + )
This is so because there are two parallel circuits, one having an impedance of
∴ = +
80
AMU - 2020
EE 19 - MODULE 3
Example 3.9
The secondary load impedance = 0.387 + 0.29. Solve the exact equivalent
Solution.
2300∠0°
= =
+ 0.286 + 0.73 + 41.4∠33°
2300∠0°
= = 54.8∠ − 33.7°
42∠33.7°
Now
81
AMU - 2020
EE 19 - MODULE 3
245∠11.3°
′= × = 54.8∠ − 33.7° ×
( + )+ 290∠15.6°
( ′+ ) 49∠37.3°
= × = 54.8∠ − 33.7° ×
(( ′ + ′) + 290∠15.6°
Secondary Cu loss = 46.2 × 0.319 = 680 ; Core loss = 9.26 × 240 = 20.6
2300 − 2240
= × 100 = . %
2240
Example 3.10
A transformer with a voltage rating in its primary winding of 600 V. Its secondary
voltage is 1080 V, with 720 V additional tap. A resistive load of 8 kW is connected across
1080 V output. While in 720 V, a purely inductive load of 10 kVA is connected. Calculate
the current primary and its power factor. Correlate your answer with the existing loads in
Solution.
8000
= = 7.41 . .
1080
82
AMU - 2020
EE 19 - MODULE 3
10000
= = 13.89 . .
720
These are reflected on to the primary sides with appropriate ratios of turns, with
corresponding power-factors.
1080
′ = 7.41 × = 13.34 . .
600
720
′ = 13.89 × = 16.67 . .
600
Hence,
= + = 21.35 , 0.625 . .
Figure 46
Correlation: Since losses and magnetizing current are ignored, the calculations
for primary current and its power-factor can also be made with data pertaining to the two
Thus, = + = 8 − 10
.
= (8 + 10 ) = 12.8
83
AMU - 2020
EE 19 - MODULE 3
The voltage rating of a transformer serves two functions. One is to protect the
winding insulation from breakdown due to an excessive voltage applied to it. This is not
the most serious limitation in practical transformers. The second function is related to the
(a)
84
AMU - 2020
EE 19 - MODULE 3
(b)
Figure 47.2 The magnetization current caused by the flux in the transformer core.
( )= sin
1
( )= ( )
1
= sin
( )=− cos
If the applied voltage v(t) is increased by 10 percent, the resulting maximum flux
in the core also increases by 10 percent. Above a certain point on the magnetization curve,
85
AMU - 2020
EE 19 - MODULE 3
larger than 10 percent. This concept is illustrated in Figure 48. As the voltage increases,
the high-magnetization currents soon become unacceptable. The maximum applied voltage
(and therefore the rated voltage) is set by the maximum acceptable magnetization current
in the core.
Notice that voltage and frequency are related in a reciprocal fashion if the maximum
also be reduced by one-sixth or the peak flux in the core will be too high. This reduction in
applied voltage with frequency is called derating. Similarly, a 50-Hz transformer may be
operated at a 20 percent higher voltage on 60 Hz if this action does not cause insulation
problems.
86
AMU - 2020
EE 19 - MODULE 3
Figure 48
Example 3.11
A l-kVA, 2301115-V, 60-Hz single-phase transformer has 850 turns on the primary
winding and 425 turns on the secondary winding. The magnetization curve for this
87
AMU - 2020
EE 19 - MODULE 3
(a) Calculate and plot the magnetization current of this transformer when it is run
at 230 V on a 60-Hz power source. What is the rms value of the magnetization
current?
(b) Calculate and plot the magnetization current of this transformer when it is run
at 230 V on a 50-Hz power source. What is the rms value of the magnetization cur-
rent? How does this current compare to the magnetization current at 60 Hz?
Figure 49
Solution.
88
AMU - 2020
EE 19 - MODULE 3
The best way to solve this problem is to calculate the flux as a function of time for
this core, and then use the magnetization curve to transform each flux value to a
corresponding magnetomotive force. The magnetizing current can then be determined from
the equation;
Assuming that the voltage applied to the core is ( ) = volts, the flux in
( )=− cos
called mag_curve_l.dat. This file can be used by MATLAB to translate these flux
values into corresponding mmf values, and above equation can be used to find the required
magnetization current values. Finally, the rms value of the magnetization current can be
1
=
(a) At 230 V on a 60-Hz power source, Figure 50 shows the simulated output using
Matlab.
89
AMU - 2020
EE 19 - MODULE 3
Figure 50 (a)
Figure 50 (b)
(b) At 230 V on a 50-Hz power source, Figure 51 shows the simulated output using
Matlab.
Figure 51 (a)
90
AMU - 2020
EE 19 - MODULE 3
Figure 51 (b)
91
AMU - 2020