Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

¾ IR/PI Value of Stator Winding before Tan Delta

@ 5 KV 1 Min 10 min PI
IR Value IR value
R-YBE 5.71 GΩ 34.3 GΩ 6.0
Y-RBE 5.56 GΩ 30.0 GΩ 5.4
B-RYE 5.53 GΩ 29.0 GΩ 5.24

¾ Tan Delta Value:

STATOR WINDING
TEST PHASE Current Watts Loss PF Tip –Up CAP Tan δ
PHASE – TO – GROUND INSULATION
(kV) ENG GND (mA) (W) (%) (%) (nF) (%)
2.0 R YB 288.341 20.774 3.604 458.79 3.604
4.0 ↓ ↓ 577.915 74.970 3.244 459.74 3.244
6.0 866.858 159.920 3.075 -0.68 460.08 3.075
8.0 1157.478 275.169 2.971 460.52 2.971
9.5 1375.378 381.018 2.916 460.85 2.916

2.0 Y RB 288.227 18.873 3.273 458.27 3.273


4.0 ↓ ↓ 577.769 69.174 2.993 459.13 2.993
6.0 866.477 147.187 2.831 -0.60 459.41 2.831
8.0 1155.849 252.387 2.729 459.79 2.729
9.5 1372.240 348.054 2.670 460.04 2.670

2.0 B RY 288.166 18.440 3.199 458.11 3.199


4.0 ↓ ↓ 576.554 67.291 2.918 458.86 2.918
6.0 865.153 143.728 2.769 -0.58 459.06 2.769
8.0 1153.207 245.753 2.664 459.39 2.664
9.5 1371.338 340.201 2.611 459.61 2.611

¾ IR Value after Tan Delta:

@ 5 KV IR (1 Min)

R-YBE 5.80 GΩ
Y-RBE 6.02 GΩ
B-RYE 5.92 GΩ
¾ Factory Test Value: