Exercises Problem 6 Fans and Blowers

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

Module 5: Activity No.

4
Fans and Blowers Exercises Problems

Name: Gamboa, Ariel C.


Student No. 20151157958
Problem:
A sewerage aeration blower rotating at 3500 rpm is designed to deliver 567 cu.m/min of
air from 20 deg C and 1 atm to a discharge of 158 kPaa with an adiabatic efficiency of
65%. During summer the atmospheric temperature rises to 43 deg C but the barometric
pressure does not change. It is desired to vary the blower speed to maintain the same
discharge pressure. Determine the discharge volume of standard air with the new
head? Ans. 9.1 cu.m/s

Given:
N 1=3500 rpm

m3
Q 1=567
min
T 1=20 ℃

Ps =1 atm

Pd =158 kP aa

n ad=65 %

T 2=43 ℃

Required:
Q2

Solution:
Q1 N 1
=
Q2 N 2
h1 P 1
=
h2 P 2
P 1 p1
=
P 2 p2
m P
Note : PV =mRT then, p= =
V RT
P1
h1 p1 R T 1 T 2
= = =
h2 p2 P2 T1
RT2

h1 T 2
=
h2 T 1
h1 43 ℃+ 273
=
h2 20℃ +273
h1
=1.08
h2
2
h1 N 1
=( )
h2 N 2
2
3500 rpm
1.08= ( N2 )
N 2=3367.88 rpm

Q1 N 1
=
Q2 N 2

m3
567
min 3500rpm
=
Q2 3367.88rpm

m3
(
Q2= 545.6
min )( min
60 s )

m3
Q 2=9.1
s