Professional Documents
Culture Documents
Riello SDU 4000 10000VA
Riello SDU 4000 10000VA
Riello SDU 4000 10000VA
SDU
6
ONLINE ToweRack
1:1 4 kVA
5-10 kVA/kW
3:1 8-10 kVA/kW
HIGHLIGHTS
Sentinel Dual is the best solution for (VFI): the load is powered continuously by
• Power factor powering mission critical applications the inverter which supplies a sinusoidal
and electro-medical devices requiring voltage, filtered and stabilised in terms of
1 kW = kVA* maximum power reliability. voltage, form and frequency. In addition,
Flexibility of installation and use (digital the input and output filters significantly
• Parallelable up to 3 display, user-replaceable battery set), increase the load’s immunity to mains
units as well as the many communication disturbances and lightning strikes.
options available, makes the Sentinel Dual Technology and performance: selectable
• Simplified Installation suitable for many different applications ECO Mode and SMART ACTIVE Mode
from IT to security. Up to 3 Sentinel functions. Diagnostics: Standard digital
• Operating mode Dual can be operated in parallel in either display, RS232 and USB interfaces with
selection capacity or N+1 redundant configuration PowerShield3 software downloadable,
offering increased reliability for critical communications slot for connectivity
• High quality output system. The Sentinel Dual can be installed accessories.
90°
90°
rotated (using the key supplied); to the batteries) using a low ripple OTHER FEATURES
• Low noise (<45 dBA): can be installed current discharge (LCRD) system; • Selectable output voltage (220/230/240 V);
in any environment thanks to its high • Batteries are user replaceable without • Dual input supplies configuration (SDU
frequency switching inverter and PWM switching off equipment and without 10000 DI and SDU 10000 DI ER);
load-dependent digitally controlled fan; interruption to the load (Hot Swap); • Auto-restart when mains power is
• E xternal bypass option for maintenance • Unlimited extendible runtime using restored (programmable via software);
with interruption-free switching; matching Battery cabinets; • Bypass on: when the machine is
• Operation guaranteed up to 40 °C (the • The batteries do not cut in during mains switched off, it automatically goes into
components are designed for high failures of <20 msec. (high hold up time) bypass and battery charge mode;
temperatures and are thus subject to or when the input supply is between • Minimum load switch-off;
less stress at normal temperatures); 184 V to 276 V. • Low battery warning;
• Built-in IEC output sockets with thermal • Start up delay;
protection. EMERGENCY FUNCTION • Total microprocessor and DSP control;
This configuration ensures the operation • Automatic bypass without interruption;
OPERATING MODE SELECTION of those emergency systems that require • Use of custom power modules;
Functions can be programmed via software continuous, reliable and long-lasting • Status, measurements and alarms
or manually via the front display panel. power supply in the event of a mains available on standard backlit display;
• ON LINE: efficiency up to 95%; power failure, such as emergency lighting, • UPS digital updating (flash memory
• ECO Mode: to increase efficiency (up to fire detection/extinguishing systems and upgradeable);
to 98%), allows for the selection of LINE alarms. When the mains power supply • Output sockets protected with
INTERACTIVE technology (VI) to power fails, the inverter begins powering the resettable thermal switch;
low priority loads from the mains supply; loads with a progressive start up (Soft • Back-feed protection standard: to
• SMART ACTIVE: the UPS automatically Start) in order to prevent overload. prevent energy from being fed back to
decides upon the operating mode (VI or the network;
VFI) based on the quality of the mains BATTERY OPTIMISATION • Manual switching to bypass.
power supply; The wide input voltage range and a high
• STANDBY OFF: the UPS can be selected hold-up time minimise battery usage and ADVANCED
to function only when the mains power increase efficiency and battery life; for COMMUNICATIONS
supply fails (emergency only mode); smaller power breaks, energy is drawn • Advanced multi-platform
• Frequency Converter operation (50 or 60 Hz). from a group of appropriately-sized communications for all operating
capacitors. systems and network environments:
HIGH QUALITY OUTPUT PowerShield3 monitoring and shutdown
VOLTAGE RUNTIME EXPANDABILITY software for Windows operating
• Even with non-linear loads (IT loads with Optional battery extension packs can be systems 10, 8, 7, Hyper-V, 2019, 2016,
a crest factor of up to 3:1); connected to increase UPS runtime. In 2012, and previous versions, Mac OS X,
• High short circuit current on bypass; addition the Sentinel Dual range includes Linux, VMWare ESXi, Citrix XenServer and
• High overload capacity: 150% by inverter ER versions with no internal batteries and other Unix operating systems;
(even with mains failure); more powerful battery chargers for longer • Plug and play function;
• Filtered, stabilised and reliable voltage runtimes. • USB port;
(double conversion ON LINE technology • RS232 serial port;
(VFI compliant with EN62040-3), ENERGYSHARE • Slot for installation of communications
with filters for the suppression of 10 A configurable IEC output sockets allow boards.
atmospheric disturbances; for runtime optimisation by programming
• Power factor correction: UPS input the switching off of low priority loads on UNITY POWER FACTOR*
power factor close to 1 and sinusoidal mains failure; alternatively, emergency • More power delivered;
current uptake. loads that are normally not powered when • More real output power (W).
mains is present can be activated.
HIGH BATTERY RELIABILITY 2-YEAR WARRANTY
• Automatic and manual battery test;
• Reduced ripple component (detrimental
OPTIONS
BATTERY CABINET
3U
3U
3U
Dimensions [mm] BB BB
448
1320
448
1320
448
19 0 19 0
19 0 19 ” 0 4 ” 64
” 64 ” 64 6
0 0
64
0 64
0 64 1 64
13
1
13
1 13
1 40 31 815 40 8
0 0
DETAILS
COMMUNICATIONS SLOT
SERIAL PORT SERIAL PORT
USB PORT USB PORT
SLOT FOR
USB PORT COMMUNICATION REPO
REPO CONNECTOR
CARDS CONNECTOR
SERIAL PORT
REMOTE CONTROL
TERMINAL BOARD PARALLEL CARD PARALLEL CARD
(OPTION) (OPTION)
OUTPUT
IEC 10 A
SOCKETS OUTPUT SOCKETS
ENERGYSHARE
WITH CIRCUIT OUTPUT CABLE
BREAKER ACCESS
INPUT CABLE
IEC 16 A OUTPUT ACCESS
INPUT / OUTPUT SOCKET WITH
TERMINAL STRIP CIRCUIT BREAKER
COMMUNICATIONS
SLOT MAIN LINE INPUT
CABLE ACCESS
SERIAL PORT
PARALLEL CARD
USB PORT
(OPTION) BYPASS CABLE ACCESS
REPO CONNECTOR (ONLI FOR DI VERSION)
* DI = DUAL INPUT
OUTPUT CABLE ACCESS
ER =EXTENDED RECHARGE
SDU 5000 SDU 6000 SDU
SDU SDU SDU SDU SDU
MODELS SDU 4000 SDU 5000 SDU 6000 SDU 8000 10000 DI
6000 ER 10000 10000 DI 8000 TM 10000 TM
PDIST PDIST ER
INPUT
Dual Input no yes no
380 / 400 / 415
(3W+N+PE)
Rated voltage [V] 220 / 230 / 240
220 / 230 / 240
(1W+N+PE)
400 ±20%
The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document.
Voltage tolerance [V] 230 ±20%
230 ±20%
Minimum voltage [V] 184 318 / 184
Rated frequency [Hz] 50 / 60 ±5
Power factor >0.98
Current distortion ≤5%
BYPASS
Voltage tolerance [V] 180 / 264 (selectable in ECO Mode or SMART ACTIVE Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
Overload Times <110% continuous, 130% for 1 h, 150% for 10 min., over 150% for 3 sec.
OUTPUT
Nominal power [VA] 4000 5000 6000 6000 8000 10000 10000 10000 8000 10000
Active power [W] 3600 5000 6000 6000 8000 10000 10000 10000 8000 10000
Rated voltage [V] 220 / 230 / 240 selectable
Voltage distortion <1% with linear load / <3% with non-linear load
Frequency [Hz] 50 / 60 selectable
Static variation 1.5%
Dynamic variation ≤5% in 20 msec.
Waveform Sinusoidal
Crest factor [lpeak/irms] 3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 h
OVERALL SPECIFICATIONS
Net weight [kg] 38 45 46 20 19+53 20+62 21 19+53 20+62
Gross weight [kg] 43 53 54 28 83 93 25 83 93
131x640x448 tower 2x (131x640x448) tower - 2x (19”x640x3U) rack
Dimensions (WxDxH) [mm]
19”x640x3U rack ER version (131x640x448) tower - (19”x640x3U) rack
Packaging dimensions 2x (780x555x270) + H 15
780x555x(270+15)
(WxDxH) [mm] ER version (780x555x(270+15)
Efficiency up to 95% ON LINE Mode, 98% ECO Mode
Protections Overcurrent - short circuit - overvoltage - undervoltage - temperature - excessive low battery
DATSDUA1Y20AREN
Parallel Operation no Optional Parallel Card
Communications USB / RS232 / slot for communications interface / REPO + Input contact
Input Connection Terminal block
Terminal
block + 2 Terminal block + 2 IEC 320 C19
Output sockets IEC 320 PDIST: Terminal block + 8 IEC 320 Terminal block + 2 IEC 320 C13 + 3 IEC 320 C19
C13 + 1 IEC C13 + 2 IEC 320 C19
320 C19
European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive
Standards Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant
Classification in accordance with IEC 62040-3 (Voltage frequency Indioendent) VFI - SS - 111
Ambient temperature
0 °C - +40 °C
for the UPS
Recommended temperature
+20 °C - +25 °C
for battery life
Range of relative humidity 5-95% non-condensing
Colour Black RAL 9005
Noise level at 1 m
<48
(ECO Mode) [dBA]
Standard equipment
USB cable; handles kit
provided
RPS SpA - Riello Power Solutions - Member of the Riello Elettronica Group
Viale Europa, 7 - 37045 Legnago (Verona) - ITALY - Tel: +39 0442 635811
www.riello-ups.com