Professional Documents
Culture Documents
Field Service Report Trinidad
Field Service Report Trinidad
Autopista Panamericana
This report is to present analysis and evaluation of steam and condensate system from boiler house up to
consumers using data field carried.
Boiler house
Sterilizers
Milk reconstitution
Additional recommendation
Participants:
Oxygen is the main cause of corrosion in hotwell tanks, feedlines, feedpumps and boilers. If carbon dioxide is
also present then the pH will be low, the water will tend to be acidic, and the rate of corrosion will be
increased. Typically the corrosion is of the pitting type where, although the metal loss may not be great, deep
penetration and perforation can occur in a short period. One common practice is use a pressurized dearator.
There are 3 main observations that make difficult the correct operation
A) Orifice plate: Although the theory suggests that 22.4* kg steam / air mixture per ton of deaerator
capacity is required, in practice this is impossible to monitor or regulate successfully. It’s suggested to use
a orifice plate to control the maximum flow. Now there is no orifice plate and the suppose flow now is
definite for:
Loss = 2.8 x 6L, where L is the visible plume length in meters (DETR Energy Consume Guide
No.67 “Steam Distribution Cost”)
*Steam and Condensate Loop by Spirax Sarco and GI-203.16 by Nestlé.
It’s recommended install an orifice plate calibrated to blow dissolved gas and steam specified for the
actual flow. The average steam flow is 3000 kg/h, with actual 10% blow down, tan 3.3 ton/h water
consumes, it must leak:
Orifice specification:
1.1
We estimate 30 liter of high temperature water (100°C), it means around (30 liter/h x 8104h/year) 160m3/year.
Its recommended change the actual siphon for a new one, with the dimensions recommended on standard.
C) Control valve: the control valve is old fashioned pneumatic /pneumatic controller, positioner and valve
and other pre valve self-action. Both of than has problem with wear and calibration. Some steam are
loose because of this, but it’s immeasurable.
Normal operation:
Mechanical pump: 23 liters / min = ~ 1380 liters/h
Estimate makeup water = (actual flow – recovery condensate) + blowdown
Estimate makeup water = (3000 – 1380) + 300 (10% blowdown) = 1920 liters/h
*this steam flow is necessary according condensate recovery. It’s imperative check the sparge pipe to
make sure it is under original dimensions, for this application the steam injector are recommended.
Valve 2:
Control valve, electro pneumatic, 4/20mA, equal percentage CV calculated = 8.0 – CV selected = 16
Spira-trol I/P positioner – Ø1 1/2” TRIM 1
(Must complete control loop: Pressure transmitter 4/20mA installed on head dearator – 0 to2.0 bar and PID
controller)
Savings
$ lost = 1,167 x U$ 8
Freedom from scale - If hardness is present in the feedwater and not controlled chemically, then scaling
of the heat transfer surfaces will occur, reducing heat transfer and efficiency - making frequent cleaning of
the boiler necessary. In extreme cases, local hot spots can occur, leading to mechanical damage or even
tube failure.
Freedom from corrosion and chemical attack - If the water contains dissolved gases, particularly oxygen,
corrosion of the boiler surfaces, piping and other equipment is likely to occur.
If the pH value of the water is too low, the acidic solution will attack metal surfaces. If the pH value is too
high, and the water is alkaline, other problems such as foaming may occur.
Caustic embrittlement or caustic cracking must also be prevented in order to avoid metal failure. Cracking
and embrittlement are caused by too high a concentration of sodium hydroxide. Older riveted boilers are
more susceptible to this kind of attack; however, care is still necessary on modern welded boilers at the
tube ends.
As the dissolved solids become more and more concentrated, the steam bubbles tend to become more
stable, failing to burst as they reach the water surface of the boiler. There comes a point (depending on
boiler pressure, size, and steam load) where a substantial part of the steam space in the boiler becomes
filled with bubbles and foam is carried over into the steam main.
This is obviously undesirable not only because the steam is excessively wet as
it leaves the boiler, but it contains boiler water with a high level of dissolved
and perhaps suspended solids. These solids will contaminate control valves,
heat exchangers and steam traps.
The actual dissolved solids concentration at which foaming may start will vary from boiler to boiler.
Conventional shell boilers are normally operated with the TDS in the range of 2 000 ppm for very small
boilers, and up to 3 500 ppm for larger boilers, provided the:
Boiler is operating near to its design pressure.
Steam load conditions are not too severe.
Other boiler water conditions are correctly controlled.
Blowing down the boiler to maintain these TDS levels should help to ensure that reasonably clean and dry
steam is delivered to the plant.
The table below provides some broad guidelines on the maximum permissible levels of boiler water TDS in
certain types of boiler. Above these levels, problems may occur.
Note: the figures are offered as a broad guide only. The boilermaker should
be consulted for specify recommendations.
Actual condition:
There is manual TDS control, provisory up to maintenance control valve. But any
way the control is about 900 µs/cm. It means (900 x 0.7) 630 PPM. These over
flow blowdown represent lost water and energy.
= 150 Kg/h
Savings
Steritube B7 has direct steam mixing with water and this hot water does undirected
heat with the product. This energy came from steam condensation and it’s
overflowed to drain.
Returning this condensate to boiler house it represents energy (80°C) and water
safes. The average flow is 6 liter/min, and the savings are:
Savings
Proposal
The steam heat water to B8, and there are modulating valve controlling
temperature. After the system is stable, the steam flow rate reduces in corporation
with startup. In these moment the residual pressure inside steam loop is low, and
the condensate don’t have enough energy to go true the line because the
backpressure. This phenomenon is called “stall point”.
The adopted solution was bypass to the drain. Recovering this condensate saves
energy and water.
Savings
Proposal
Substitution the steam trap for steam pump trap, which work as a
trap meanwhile there is pressure inside enough to trap the
condensate.
When the pressure below, starts works as a pump, using steam as power source (3 kg steam / m3)
1.5 Flash steam from condensate recovery pump
The estimate actual condensate recovery is 1380 Kg/h and the average steam pressure is 4.0
kgf/cm2(g). With this ΔP the saturate steam flashes.
Proposal
The elbow drain must also remain open (without valve or plug)
to prevent any water accumulation at the base of the elbow
and water hammering.
The lower steam line should be used only to trap the
condensate. The current installation would lead to more
maintenance of the equipment because of erosion caused by
the settling of water.
“Without continual growth and progress, such words as improvement and success have no meaning”
Benjamin Franklin
Andres.bozo@spiraxsarco.com Fortunato.sasaki@mx.spiraxsarco.com